Bulletin 310-D
Armstrong Steam Trap Testing
Guide for Energy Conservation
Knowledge Not Shared Is Energy Wasted
2
Steam Trap Testing Procedure
CAUTION: Valves in steam lines should be opened or
closed by authorized personnel only, following the correct
procedure for specific system conditions. Always isolate
steam trap from pressurized supply and return lines before
opening for inspection or repair. Isolate strainer from
pressurized system before opening to clean. Failure to
follow correct procedures can result in system damage and
possible bodily injury.
Tips On Listening –
1. Some flow noises are best picked up with high
frequency electronic listening devices, but these
devices are not sensitive to mechanical sounds.
2. Low frequency meters, stethoscopes or even screw
drivers can be used to detect mechanical sounds, for
example: bucket dance, or the bubbling through the
bucket vent.
3. Before purchasing a listening device, check it out on
known conditions to see that it serves your purpose.
4. When checking traps on a manifold, be sure to check
them all. A good trap can telegraph a bad trap’s signal.
Check to see at which trap the signal is the loudest.
That’s probably the faulty trap.
I. Inverted Bucket
A. Is trap cold?
1. Yes, then:
a. Is steam shut off ? Yes, then turn on steam to
check trap. If still cold shut off steam. (Allow
sufficient time for purging of initial air.)
b. Is there a plugged strainer up stream of trap?
Yes, then clean strainer.
c. If no plugged strainer, open trap.
d. Is it over-pressured, orifice too large for applied
differential? Yes, then replace mechanism with
one for right pressure.
3
e. Is bucket vent plugged? Yes, clean it.
f. Is inlet or outlet plugged or mechanism
jammed with dirt? Yes, then clean it.
g. Is bucket unhooked? (worn mechanism) Yes,
then replace mechanism.
2. No, then listen to it.
a. Is it discharging intermittently? Yes, then it
is OK.
b. Is it relatively quiet, so you can hear the steady
“bubbling” through the bucket vent? Yes, then it
is OK, light load.
c. Does bubbling sound increase and decrease in
a kind of “rolling” sound? Yes, then it is
handling air. Check trap in an hour. If it is still
handling air, replace the standard bucket with a
thermic bucket. If air problem persists, replace
inverted bucket trap with a float and
thermostatic trap.
d. Is it discharging steadily with no bucket sound?
Yes, then it is too small. Replace trap with
larger one.
e. Is it discharging steadily with bucket dancing
up and down? Yes, then it has lost its prime.
Close a valve upstream or downstream of trap
for a few minutes and then re-open. If trap
does not catch its prime, mechanism is worn
(replace), or guide assembly is misaligned
(align. See instructions.) Internal check valve
on tube and coupling may be necessary to
cure chronic prime loss.
3. If trap is capsule construction, non-repairable,
remove it from the line in case of any malfunction,
and apply compressed air or a water stream to its
outlet and then its inlet. If this does not correct the
problem replace the trap.
4
II. Float & Thermostatic Trap
A. Is trap cold?
1. Yes, then:
a. Is steam shut off? Yes, then turn on steam to
check trap. If still cold shut off steam. (Allow
sufficient time for purging of initial air.)
b. Is there a plugged strainer up stream of trap?
Yes, then clean strainer.
c. If no plugged strainer, open trap.
d. Is it over-pressured, orifice too large for applied
differential? Yes, then replace mechanism with
one for right pressure.
e. Has thermostatic element failed shut? (Open
trap at room temperature, thermostatic valve
should be open.) Yes, then replace.
f. Is float collapsed? Yes, then replace.
g. Is float mechanism free to move open and
shut? No, then clean or ease binding parts of
mechanism or replace mechanism.
h. Is trap inlet or outlet plugged? Yes, then
clean it.
2. No, then listen to it.
A float and thermostatic trap modulates to the
load, so it discharges constantly. There is always
flow if there is a condensate load. If the trap is
passing live steam, this not only adds to flow
noise, but it also raises the pitch of the sound
because of the higher velocity.
If a valve upstream or downstream of the trap is
closed for a few minutes there will be a back-up of
condensate. When the valve is reopened, the float
valve should move to wide open until the back-up
condensate is clear. If the mechanism is OK,
there should now be a reduction in noise. If the
mechanism is faulty, live steam will be passed at
this time, which can be detected by a higher pitch
in the flow noise.
5
Is live steam discharge suspected? Yes, then shut
off steam, allow trap to cool and open trap.
a. Has thermostatic element failed open?
(Remove element from trap and place in
boiling water. It should close. Mounting the
discharge connection of the element on the
end of a tube permits blowing into the tube to
see if the valve is shut.)
b. Is foreign material in trap preventing free
operation of mechanism? Yes, then clean it.
c. Is mechanism binding open or is valve not
seating squarely on orifice? Yes, then ease
binding parts, align mechanism, or replace
mechanism.
III. Disc Trap
A. Is trap cold?
1. Yes, then:
a. Is steam shut off? Yes, then turn on steam to
check trap. (Allow sufficient time for purging of
initial air.) If still cold, shut off steam.
b. Is there a plugged strainer up stream of trap?
Yes, then clean strainer.
c. If no plugged strainer, open trap.
d. Is disc free to be lifted from seats? No, then
clean it so it is free.
e. Is it plugged with dirt at inlet or outlet? Yes,
then clean it.
2. No, then: Listen to it:
a. Is it discharging intermittently, about six (6)
time/min.? Yes, then it is OK.
b. Is it discharging intermittently, about twelve
(12) times/minute or discharging steadily? Yes,
then it is worn and wasting excessive steam
and should be replaced OR it is too small and
should be replaced by larger trap. (New trap of
6
III. Disc Trap (Cont.)
proper size will intermit about six (6) times/
minute.) Or there is excessive back pressure.
B. If a disc trap is connected into a return line, don’t
check visually by discharging it to atmosphere
through a test valve. This removes the back
pressure, which can cause problems if it exceeds
50% of the inlet pressure. The temperature of the
return line indicates its back pressure.
IV. Thermostatic Trap
A. Is trap cold?
1. Yes, then:
a. Is steam shut off? Yes, then turn on steam to
check trap. (Allow sufficient time for purging of
initial air.) If still cold, shut off steam.
b. I there a plugged strainer up stream of trap?
Yes, then clean the strainer.
c. If no plugged strainer, open trap.
d. Has thermostatic element failed shut? (Valve
should be open at room temperature.) Yes,
then replace it.
e. Is it plugged at inlet or outlet?
Yes, then clean it.
2. No, then listen to it.
a. Is it discharging intermittently? Yes, then it
is OK.
b. Is it discharging constantly? Yes, then spray
with water.
1.If it discharges more heavily briefly and shuts
off, it is OK.
2. If there is no change in sound—
a. Close a valve upstream or downstream
for a few minutes. A short time after
reopening, is there a sudden rise in pitch
of the flow noise?
7
1. Yes, then trap has failed open. Shut off
steam and allow to cool. Open it and
clean it if dirt is preventing proper
functioning. If no dirt, remove element
from trap and place in boiling water. It
should close. Mounting the discharge
connection of the element on the end
of a tube permits blowing into the tube
to see if the valve is shut.
2. No, then trap is too small. Replace
with larger trap or add another of same
size in parallel.
3. If trap is capsule construction, non-
repairable, remove it from the line in
case of malfunction, and apply
compressed air or a water stream to
its outlet and then its inlet. If this does
not correct the problem replace the
trap. (Element must not experience
more than 40 psi pressure when cold.)
V. Sub-Cooling Trap
A. Is trap cold?
1. Yes, then:
a. Is steam shut off? Yes, then turn on steam to
check trap. (Allow sufficient time for purging of
initial air.) If still cold, shut off steam.
b. Is there a plugged strainer up stream of trap?
Yes, then clean strainer.
c. If no plugged strainer, open trap.
d. Is valve on seat at room temperature? Yes,
then replace element.
e. Is it plugged with dirt at inlet or outlet? Yes,
then clean it.
2. No then:
a. Observe trap discharge to atmosphere. (This is
the best way to check this trap.) Is there live
steam? Yes, then replace trap.
Traps on Superheated Steam
Do not use thermostatic or float and thermostatic traps,
which employ balanced pressure bellows, where
superheated steam will contact the element.
Inverted bucket traps can be used successfully on
superheated steam. When functioning properly they will be
at the saturation temperature of the pressure involved. If
one fails open it will be at the superheat temperature. An
inverted bucket trap on superheated steam is one of the
few combinations that can be checked successfully by
temperature.
Testing Schedule
For maximum trap life and steam economy, a regular
schedule should be set up for trap testing and preventative
maintenance. Trap size, operating pressure and importance
determine how frequently traps should be checked.
Drip Tracer Coil Process
0 - 100 1 1 2 3
101 - 250 2 2 2 3
251 - 450 2 2 3 4
450 and above 3 3 4 12
Suggested Yearly Trap Testing Frequency
Operating
Pressure (psig)
Application
Armstrong Steam and Condensate Group
816 Maple Street, Three Rivers, Michigan 49093 - USA
Ph: (269) 273-1415 Fax: (269) 278-6555
www.armstronginternational.com
Bulletin No. 310-D 6/06 Printed in U.S.A.
© 2006 Armstrong International, Inc.

More Related Content

Similar to Steam Trap Testing Guide for Energy Conservation

CHARGING OF REFRIGERANT.pptx
CHARGING OF REFRIGERANT.pptxCHARGING OF REFRIGERANT.pptx
CHARGING OF REFRIGERANT.pptxMARIOBULANADI1
 
2014-12_Handbook
2014-12_Handbook2014-12_Handbook
2014-12_HandbookHeidi Wise
 
Hydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingHydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingCMA/Flodyne/Hydradyne
 
Clean core samples using soxhelt.pdf
Clean core samples using soxhelt.pdfClean core samples using soxhelt.pdf
Clean core samples using soxhelt.pdflaithahmed13
 
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak DetectorHow to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak DetectorBuyobdtoolShop
 
Pentair #320 chlorinator manual
Pentair #320 chlorinator manualPentair #320 chlorinator manual
Pentair #320 chlorinator manualDavid Hackney
 
Non return valves 18 1-11
Non return valves 18 1-11Non return valves 18 1-11
Non return valves 18 1-11narasimha reddy
 
HPLC Problems, Probable Causes, and Remedies2020.pptx
HPLC Problems, Probable Causes, and Remedies2020.pptxHPLC Problems, Probable Causes, and Remedies2020.pptx
HPLC Problems, Probable Causes, and Remedies2020.pptxutpalanand7
 
Polymerization Experiment
Polymerization ExperimentPolymerization Experiment
Polymerization ExperimentDan Betts
 
Cm241 la wandasmith_u9_final_project
Cm241 la wandasmith_u9_final_projectCm241 la wandasmith_u9_final_project
Cm241 la wandasmith_u9_final_projectkeys2all
 
hplc trouble shooting - final.ppt
hplc trouble shooting - final.ppthplc trouble shooting - final.ppt
hplc trouble shooting - final.pptJgdishrathi
 
Replacing main water shut off valve
Replacing main water shut off valveReplacing main water shut off valve
Replacing main water shut off valvePlumbing 911
 
Plumbing care and repair
Plumbing care and repairPlumbing care and repair
Plumbing care and repairZulaiha Amaria
 
Anastasia machine reparing
Anastasia machine reparingAnastasia machine reparing
Anastasia machine reparingRABAH ABUABKER
 

Similar to Steam Trap Testing Guide for Energy Conservation (20)

CHARGING OF REFRIGERANT.pptx
CHARGING OF REFRIGERANT.pptxCHARGING OF REFRIGERANT.pptx
CHARGING OF REFRIGERANT.pptx
 
2014-12_Handbook
2014-12_Handbook2014-12_Handbook
2014-12_Handbook
 
Hydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingHydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and Troubleshooting
 
Water Heater booklet
Water Heater bookletWater Heater booklet
Water Heater booklet
 
Clean core samples using soxhelt.pdf
Clean core samples using soxhelt.pdfClean core samples using soxhelt.pdf
Clean core samples using soxhelt.pdf
 
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak DetectorHow to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
 
Pentair #320 chlorinator manual
Pentair #320 chlorinator manualPentair #320 chlorinator manual
Pentair #320 chlorinator manual
 
Non return valves 18 1-11
Non return valves 18 1-11Non return valves 18 1-11
Non return valves 18 1-11
 
Multi desaturator cell
Multi desaturator cellMulti desaturator cell
Multi desaturator cell
 
Catalyst unloading details
Catalyst unloading detailsCatalyst unloading details
Catalyst unloading details
 
Granbo ultrasonic cleaner gn3613-user manual
Granbo ultrasonic cleaner gn3613-user manualGranbo ultrasonic cleaner gn3613-user manual
Granbo ultrasonic cleaner gn3613-user manual
 
HPLC Problems, Probable Causes, and Remedies2020.pptx
HPLC Problems, Probable Causes, and Remedies2020.pptxHPLC Problems, Probable Causes, and Remedies2020.pptx
HPLC Problems, Probable Causes, and Remedies2020.pptx
 
Autoclave
AutoclaveAutoclave
Autoclave
 
Polymerization Experiment
Polymerization ExperimentPolymerization Experiment
Polymerization Experiment
 
Gc troubleshooting
Gc troubleshootingGc troubleshooting
Gc troubleshooting
 
Cm241 la wandasmith_u9_final_project
Cm241 la wandasmith_u9_final_projectCm241 la wandasmith_u9_final_project
Cm241 la wandasmith_u9_final_project
 
hplc trouble shooting - final.ppt
hplc trouble shooting - final.ppthplc trouble shooting - final.ppt
hplc trouble shooting - final.ppt
 
Replacing main water shut off valve
Replacing main water shut off valveReplacing main water shut off valve
Replacing main water shut off valve
 
Plumbing care and repair
Plumbing care and repairPlumbing care and repair
Plumbing care and repair
 
Anastasia machine reparing
Anastasia machine reparingAnastasia machine reparing
Anastasia machine reparing
 

More from Mead O'Brien, Inc.

Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...
Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...
Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...Mead O'Brien, Inc.
 
Industrial Boiler and Burner Limit Control Switches
Industrial Boiler and Burner Limit Control SwitchesIndustrial Boiler and Burner Limit Control Switches
Industrial Boiler and Burner Limit Control SwitchesMead O'Brien, Inc.
 
Metso Neles Flow Control Solutions: Valves, Actuation, and Automation
Metso Neles Flow Control Solutions: Valves, Actuation, and AutomationMetso Neles Flow Control Solutions: Valves, Actuation, and Automation
Metso Neles Flow Control Solutions: Valves, Actuation, and AutomationMead O'Brien, Inc.
 
How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...
How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...
How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...Mead O'Brien, Inc.
 
Steam Trapping and Steam Tracing Equipment
Steam Trapping and Steam Tracing EquipmentSteam Trapping and Steam Tracing Equipment
Steam Trapping and Steam Tracing EquipmentMead O'Brien, Inc.
 
Limitorque WG Series Installation, Operation, and Maintenance
Limitorque WG Series Installation, Operation, and MaintenanceLimitorque WG Series Installation, Operation, and Maintenance
Limitorque WG Series Installation, Operation, and MaintenanceMead O'Brien, Inc.
 
Metso Neles T5 Series Top Entry Rotary Ball Valves
Metso Neles T5 Series Top Entry Rotary Ball ValvesMetso Neles T5 Series Top Entry Rotary Ball Valves
Metso Neles T5 Series Top Entry Rotary Ball ValvesMead O'Brien, Inc.
 
Foxboro IMT23 Transmitter Operation, Configuration, and Calibration
Foxboro IMT23 Transmitter Operation, Configuration, and CalibrationFoxboro IMT23 Transmitter Operation, Configuration, and Calibration
Foxboro IMT23 Transmitter Operation, Configuration, and CalibrationMead O'Brien, Inc.
 
Water Cooled Portable Air Conditioners
Water Cooled Portable Air ConditionersWater Cooled Portable Air Conditioners
Water Cooled Portable Air ConditionersMead O'Brien, Inc.
 
Limitorque QX Electronic Actuator User Instructions
Limitorque QX Electronic Actuator User InstructionsLimitorque QX Electronic Actuator User Instructions
Limitorque QX Electronic Actuator User InstructionsMead O'Brien, Inc.
 
Steam Conservation Guidelines for Condensate Drainage
Steam Conservation Guidelines for Condensate DrainageSteam Conservation Guidelines for Condensate Drainage
Steam Conservation Guidelines for Condensate DrainageMead O'Brien, Inc.
 
Neles NDX Intelligent Valve Positioner
Neles NDX Intelligent Valve PositionerNeles NDX Intelligent Valve Positioner
Neles NDX Intelligent Valve PositionerMead O'Brien, Inc.
 
Data Supplement for Kunkle Safety and Relief Products
Data Supplement for Kunkle Safety and Relief ProductsData Supplement for Kunkle Safety and Relief Products
Data Supplement for Kunkle Safety and Relief ProductsMead O'Brien, Inc.
 
Neles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing Trim
Neles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing TrimNeles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing Trim
Neles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing TrimMead O'Brien, Inc.
 
BIST (Built-in-Self-Test) Features for Electronic Valve Actuators
BIST (Built-in-Self-Test) Features for Electronic Valve ActuatorsBIST (Built-in-Self-Test) Features for Electronic Valve Actuators
BIST (Built-in-Self-Test) Features for Electronic Valve ActuatorsMead O'Brien, Inc.
 
Understanding & Solving Heat Transfer Equipment Stall
Understanding & Solving Heat Transfer Equipment StallUnderstanding & Solving Heat Transfer Equipment Stall
Understanding & Solving Heat Transfer Equipment StallMead O'Brien, Inc.
 
Automation in Industry: The People Make the Difference!
Automation in Industry: The People Make the Difference! Automation in Industry: The People Make the Difference!
Automation in Industry: The People Make the Difference! Mead O'Brien, Inc.
 

More from Mead O'Brien, Inc. (20)

Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...
Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...
Intrusive vs. Non-Intrusive Electric Actuators: Which option is right for you...
 
Industrial Boiler and Burner Limit Control Switches
Industrial Boiler and Burner Limit Control SwitchesIndustrial Boiler and Burner Limit Control Switches
Industrial Boiler and Burner Limit Control Switches
 
Metso Neles Flow Control Solutions: Valves, Actuation, and Automation
Metso Neles Flow Control Solutions: Valves, Actuation, and AutomationMetso Neles Flow Control Solutions: Valves, Actuation, and Automation
Metso Neles Flow Control Solutions: Valves, Actuation, and Automation
 
Ashcroft Corrosion Guide
Ashcroft Corrosion GuideAshcroft Corrosion Guide
Ashcroft Corrosion Guide
 
How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...
How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...
How Your Steam Trap Selection Affects Your Bottom Line Profits: Inverted Buck...
 
Steam Trapping and Steam Tracing Equipment
Steam Trapping and Steam Tracing EquipmentSteam Trapping and Steam Tracing Equipment
Steam Trapping and Steam Tracing Equipment
 
Limitorque WG Series Installation, Operation, and Maintenance
Limitorque WG Series Installation, Operation, and MaintenanceLimitorque WG Series Installation, Operation, and Maintenance
Limitorque WG Series Installation, Operation, and Maintenance
 
Metso Neles T5 Series Top Entry Rotary Ball Valves
Metso Neles T5 Series Top Entry Rotary Ball ValvesMetso Neles T5 Series Top Entry Rotary Ball Valves
Metso Neles T5 Series Top Entry Rotary Ball Valves
 
Foxboro IMT23 Transmitter Operation, Configuration, and Calibration
Foxboro IMT23 Transmitter Operation, Configuration, and CalibrationFoxboro IMT23 Transmitter Operation, Configuration, and Calibration
Foxboro IMT23 Transmitter Operation, Configuration, and Calibration
 
Water Cooled Portable Air Conditioners
Water Cooled Portable Air ConditionersWater Cooled Portable Air Conditioners
Water Cooled Portable Air Conditioners
 
VERIS Accelabar Flow Meter
VERIS Accelabar Flow MeterVERIS Accelabar Flow Meter
VERIS Accelabar Flow Meter
 
Limitorque QX Electronic Actuator User Instructions
Limitorque QX Electronic Actuator User InstructionsLimitorque QX Electronic Actuator User Instructions
Limitorque QX Electronic Actuator User Instructions
 
Steam Conservation Guidelines for Condensate Drainage
Steam Conservation Guidelines for Condensate DrainageSteam Conservation Guidelines for Condensate Drainage
Steam Conservation Guidelines for Condensate Drainage
 
Neles NDX Intelligent Valve Positioner
Neles NDX Intelligent Valve PositionerNeles NDX Intelligent Valve Positioner
Neles NDX Intelligent Valve Positioner
 
Data Supplement for Kunkle Safety and Relief Products
Data Supplement for Kunkle Safety and Relief ProductsData Supplement for Kunkle Safety and Relief Products
Data Supplement for Kunkle Safety and Relief Products
 
Hot Water for Industry
Hot Water for IndustryHot Water for Industry
Hot Water for Industry
 
Neles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing Trim
Neles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing TrimNeles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing Trim
Neles Triple Eccentric Disc Valve, Metal Seated with Flow Balancing Trim
 
BIST (Built-in-Self-Test) Features for Electronic Valve Actuators
BIST (Built-in-Self-Test) Features for Electronic Valve ActuatorsBIST (Built-in-Self-Test) Features for Electronic Valve Actuators
BIST (Built-in-Self-Test) Features for Electronic Valve Actuators
 
Understanding & Solving Heat Transfer Equipment Stall
Understanding & Solving Heat Transfer Equipment StallUnderstanding & Solving Heat Transfer Equipment Stall
Understanding & Solving Heat Transfer Equipment Stall
 
Automation in Industry: The People Make the Difference!
Automation in Industry: The People Make the Difference! Automation in Industry: The People Make the Difference!
Automation in Industry: The People Make the Difference!
 

Recently uploaded

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadhamedmustafa094
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaOmar Fathy
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086anil_gaur
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdfKamal Acharya
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projectssmsksolar
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesRAJNEESHKUMAR341697
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxSCMS School of Architecture
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...soginsider
 
Bridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptxBridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptxnuruddin69
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network DevicesChandrakantDivate1
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 

Recently uploaded (20)

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Bridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptxBridge Jacking Design Sample Calculation.pptx
Bridge Jacking Design Sample Calculation.pptx
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 

Steam Trap Testing Guide for Energy Conservation

  • 1. Bulletin 310-D Armstrong Steam Trap Testing Guide for Energy Conservation Knowledge Not Shared Is Energy Wasted
  • 2. 2 Steam Trap Testing Procedure CAUTION: Valves in steam lines should be opened or closed by authorized personnel only, following the correct procedure for specific system conditions. Always isolate steam trap from pressurized supply and return lines before opening for inspection or repair. Isolate strainer from pressurized system before opening to clean. Failure to follow correct procedures can result in system damage and possible bodily injury. Tips On Listening – 1. Some flow noises are best picked up with high frequency electronic listening devices, but these devices are not sensitive to mechanical sounds. 2. Low frequency meters, stethoscopes or even screw drivers can be used to detect mechanical sounds, for example: bucket dance, or the bubbling through the bucket vent. 3. Before purchasing a listening device, check it out on known conditions to see that it serves your purpose. 4. When checking traps on a manifold, be sure to check them all. A good trap can telegraph a bad trap’s signal. Check to see at which trap the signal is the loudest. That’s probably the faulty trap. I. Inverted Bucket A. Is trap cold? 1. Yes, then: a. Is steam shut off ? Yes, then turn on steam to check trap. If still cold shut off steam. (Allow sufficient time for purging of initial air.) b. Is there a plugged strainer up stream of trap? Yes, then clean strainer. c. If no plugged strainer, open trap. d. Is it over-pressured, orifice too large for applied differential? Yes, then replace mechanism with one for right pressure.
  • 3. 3 e. Is bucket vent plugged? Yes, clean it. f. Is inlet or outlet plugged or mechanism jammed with dirt? Yes, then clean it. g. Is bucket unhooked? (worn mechanism) Yes, then replace mechanism. 2. No, then listen to it. a. Is it discharging intermittently? Yes, then it is OK. b. Is it relatively quiet, so you can hear the steady “bubbling” through the bucket vent? Yes, then it is OK, light load. c. Does bubbling sound increase and decrease in a kind of “rolling” sound? Yes, then it is handling air. Check trap in an hour. If it is still handling air, replace the standard bucket with a thermic bucket. If air problem persists, replace inverted bucket trap with a float and thermostatic trap. d. Is it discharging steadily with no bucket sound? Yes, then it is too small. Replace trap with larger one. e. Is it discharging steadily with bucket dancing up and down? Yes, then it has lost its prime. Close a valve upstream or downstream of trap for a few minutes and then re-open. If trap does not catch its prime, mechanism is worn (replace), or guide assembly is misaligned (align. See instructions.) Internal check valve on tube and coupling may be necessary to cure chronic prime loss. 3. If trap is capsule construction, non-repairable, remove it from the line in case of any malfunction, and apply compressed air or a water stream to its outlet and then its inlet. If this does not correct the problem replace the trap.
  • 4. 4 II. Float & Thermostatic Trap A. Is trap cold? 1. Yes, then: a. Is steam shut off? Yes, then turn on steam to check trap. If still cold shut off steam. (Allow sufficient time for purging of initial air.) b. Is there a plugged strainer up stream of trap? Yes, then clean strainer. c. If no plugged strainer, open trap. d. Is it over-pressured, orifice too large for applied differential? Yes, then replace mechanism with one for right pressure. e. Has thermostatic element failed shut? (Open trap at room temperature, thermostatic valve should be open.) Yes, then replace. f. Is float collapsed? Yes, then replace. g. Is float mechanism free to move open and shut? No, then clean or ease binding parts of mechanism or replace mechanism. h. Is trap inlet or outlet plugged? Yes, then clean it. 2. No, then listen to it. A float and thermostatic trap modulates to the load, so it discharges constantly. There is always flow if there is a condensate load. If the trap is passing live steam, this not only adds to flow noise, but it also raises the pitch of the sound because of the higher velocity. If a valve upstream or downstream of the trap is closed for a few minutes there will be a back-up of condensate. When the valve is reopened, the float valve should move to wide open until the back-up condensate is clear. If the mechanism is OK, there should now be a reduction in noise. If the mechanism is faulty, live steam will be passed at this time, which can be detected by a higher pitch in the flow noise.
  • 5. 5 Is live steam discharge suspected? Yes, then shut off steam, allow trap to cool and open trap. a. Has thermostatic element failed open? (Remove element from trap and place in boiling water. It should close. Mounting the discharge connection of the element on the end of a tube permits blowing into the tube to see if the valve is shut.) b. Is foreign material in trap preventing free operation of mechanism? Yes, then clean it. c. Is mechanism binding open or is valve not seating squarely on orifice? Yes, then ease binding parts, align mechanism, or replace mechanism. III. Disc Trap A. Is trap cold? 1. Yes, then: a. Is steam shut off? Yes, then turn on steam to check trap. (Allow sufficient time for purging of initial air.) If still cold, shut off steam. b. Is there a plugged strainer up stream of trap? Yes, then clean strainer. c. If no plugged strainer, open trap. d. Is disc free to be lifted from seats? No, then clean it so it is free. e. Is it plugged with dirt at inlet or outlet? Yes, then clean it. 2. No, then: Listen to it: a. Is it discharging intermittently, about six (6) time/min.? Yes, then it is OK. b. Is it discharging intermittently, about twelve (12) times/minute or discharging steadily? Yes, then it is worn and wasting excessive steam and should be replaced OR it is too small and should be replaced by larger trap. (New trap of
  • 6. 6 III. Disc Trap (Cont.) proper size will intermit about six (6) times/ minute.) Or there is excessive back pressure. B. If a disc trap is connected into a return line, don’t check visually by discharging it to atmosphere through a test valve. This removes the back pressure, which can cause problems if it exceeds 50% of the inlet pressure. The temperature of the return line indicates its back pressure. IV. Thermostatic Trap A. Is trap cold? 1. Yes, then: a. Is steam shut off? Yes, then turn on steam to check trap. (Allow sufficient time for purging of initial air.) If still cold, shut off steam. b. I there a plugged strainer up stream of trap? Yes, then clean the strainer. c. If no plugged strainer, open trap. d. Has thermostatic element failed shut? (Valve should be open at room temperature.) Yes, then replace it. e. Is it plugged at inlet or outlet? Yes, then clean it. 2. No, then listen to it. a. Is it discharging intermittently? Yes, then it is OK. b. Is it discharging constantly? Yes, then spray with water. 1.If it discharges more heavily briefly and shuts off, it is OK. 2. If there is no change in sound— a. Close a valve upstream or downstream for a few minutes. A short time after reopening, is there a sudden rise in pitch of the flow noise?
  • 7. 7 1. Yes, then trap has failed open. Shut off steam and allow to cool. Open it and clean it if dirt is preventing proper functioning. If no dirt, remove element from trap and place in boiling water. It should close. Mounting the discharge connection of the element on the end of a tube permits blowing into the tube to see if the valve is shut. 2. No, then trap is too small. Replace with larger trap or add another of same size in parallel. 3. If trap is capsule construction, non- repairable, remove it from the line in case of malfunction, and apply compressed air or a water stream to its outlet and then its inlet. If this does not correct the problem replace the trap. (Element must not experience more than 40 psi pressure when cold.) V. Sub-Cooling Trap A. Is trap cold? 1. Yes, then: a. Is steam shut off? Yes, then turn on steam to check trap. (Allow sufficient time for purging of initial air.) If still cold, shut off steam. b. Is there a plugged strainer up stream of trap? Yes, then clean strainer. c. If no plugged strainer, open trap. d. Is valve on seat at room temperature? Yes, then replace element. e. Is it plugged with dirt at inlet or outlet? Yes, then clean it. 2. No then: a. Observe trap discharge to atmosphere. (This is the best way to check this trap.) Is there live steam? Yes, then replace trap.
  • 8. Traps on Superheated Steam Do not use thermostatic or float and thermostatic traps, which employ balanced pressure bellows, where superheated steam will contact the element. Inverted bucket traps can be used successfully on superheated steam. When functioning properly they will be at the saturation temperature of the pressure involved. If one fails open it will be at the superheat temperature. An inverted bucket trap on superheated steam is one of the few combinations that can be checked successfully by temperature. Testing Schedule For maximum trap life and steam economy, a regular schedule should be set up for trap testing and preventative maintenance. Trap size, operating pressure and importance determine how frequently traps should be checked. Drip Tracer Coil Process 0 - 100 1 1 2 3 101 - 250 2 2 2 3 251 - 450 2 2 3 4 450 and above 3 3 4 12 Suggested Yearly Trap Testing Frequency Operating Pressure (psig) Application Armstrong Steam and Condensate Group 816 Maple Street, Three Rivers, Michigan 49093 - USA Ph: (269) 273-1415 Fax: (269) 278-6555 www.armstronginternational.com Bulletin No. 310-D 6/06 Printed in U.S.A. © 2006 Armstrong International, Inc.