Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 
www.ijera.com 49 | P a g e 
Impact of APFC Panel at LT Side of Transformer Bhogadi. Havya, K.Ravi Kumar (Associate Professor) Department of Electrical and Electronic Engineering, Vasavi College of Engineering, Hyderabad, Andhra Pradesh, India. Abstract The Development of automatic sensing technologies have significantly advanced in recent years in electrical systems.One of them is Automatic Power Factor Correction(APFC)Panels.It is very difficult to maintain consistent power factor by using fixed capacitors because they need to be operated manually which may result in over voltages,saturation of transformers etc. that may lead to the interruption in the power supply of the distribution system.APFC Panels automatically varies according to the load requirements on the L.T side i.e. distribution side which compensates the load requirements.Impact of automatic power factor correction panels (APFC) at L.T side of a transformer are discussed which are inductive in nature. 
Key words: APFC Panels, Power Factor, Inductive, Fixed capacitors, Power factor correction. 
I. INTRODUCTION 
Most of the electrical loads are inductive in nature resulting in severely lagging power factor. The most practical and economical solution to improve the power factor(PF) is to provide reactive compensation by installing power capacitors of suitable rating at strategic locations. But this has to be operated manually and which may result in the over voltages, damage of the electrical equipments saturation of transformers etc. PF correction is more important in electrical distribution systems. For accomplishing the same low voltage(LV) capacitors are being extensively used both as fixed capacitor banks and in Automatic Power Factor Correction (APFC) Panels. Application of APFC Panels is becoming more attractive due to their techno-commercial advantages like 
(1) Ability to maintain PF at the required high value (close to unity) and hence avoid the penalties imposed by electrical supply companies due to low PF 
(2) Avoid over compensation during low load conditions and 
(3) Improved efficiency of the system due to reduction in losses. 
Application of automatic power factor correction panels(APFC) in electrical distribution network is gaining importance due to the advantages of APFC Panels over fixed capacitor banks like ability to maintain the target power factor with varying load and hence improve efficiency of the system and consequently reduce distribution losses. At present, no comprehensive Indian standard is available for testing APFC Panels. Bureau of Indian Standards(BIS),the national standards body of India has extended financial support to CPRI to undertake a R&D project for development of a new standard for 
LV APFC Panels. CPRI in association with APFC Panel manufacturers and purchasers has formulated an Indian standard for “APFC panels for voltage rating upto and including 1000 volts”. The standard will help both manufacturers and utilities to setup uniformity in testing and also to install reliable APFC Panels for achieving the target power factor(PF),closer to unity and consequently improve the efficiency of the LV system by minimizing the losses in distribution systems. 
II. METHODOLOGY 
Present study has been conducted on APFC panels with contactor type of switching mechanism .Rating of the panels was 500kvar,440V,3- phase,delta connected.To improve the power factor using APFC panels , the following points has to be noted. (1) Please check if required kvar of capacitors are installed. (2) Check the type of capacitor installed is suitable for application or the capacitors are de-rated. (3) Check if the capacitors are permanently „ON‟. The capacitors are not switched off. (4) When the load is not working under such condition the average power factor is found to be lower side. (5) Check whether all the capacitors are operated in APFC depending upon the load operation. (6) Check whether the APFC installed in the installation is working or not. Check the CT connection is taken from the main incomer side of transformer, after the fix compensation of transformer. (7) Check if the load demand in the system is increased. (8) Check if power transformer compensation is provided. 
RESEARCH ARTICLE OPEN ACCESS
Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 
www.ijera.com 50 | P a g e 
Central compensation: Consumer installations usually possess a varying reactive power requirement. Unregulated fixed compensation is not possible in such cases since an uneconomical under- compensation or a dangerous over-compensation can occur. One must therefore continuously adjust the capacitor power to the required reactive power requirement. One achieves this by means of automatic capacitorbanks which are directly assigned to a switchgear unit, distribution and sub-distribution or to a large load with fluctuating reactive power requirements. This is achieved in non-reactor protected systems by using special capacitor switching contactors.These are equipped with pre-charging resistors as a permanent component of the contactors.The capacitor is first connected to the network via these resistors by means of early closing contacts before the main contacts close. The inrush current is then only approx.5% of the non-attenuated value. Regulation, number of steps and control series : Most consumer installations are compensated using automatic capacitor banks due to the recognized benefits. The compensation power is designed with switched steps to match the employed capacitor power to the fluctuating load situation in the consumer‟s system. A reactive power controller detects the momentary reactive power requirement by means of voltage and current measurements in the feeder to the consumer‟s installation(distribution or sub- distribution).The capacitor power is adjusted by connection or dis-connection in such a manner that a target power factor programmed at the regulators is reached. To avoid the reconnection of capacitors that have not yet been discharged ,certain switching or lock-out times are specified or pre-selectable in the reactive power regulator which are to be taken into account when choosing discharge devices. The distribution of the total power among the switched regulator control taps[control outputs]is specified with the control series. It contains the number of steps and their power ratings as a factor of the power of the first step, which is defined as 1.The cross-sum of the control series gives the number of combination steps of the compensation system. For example, control series with four control steps of the same power: 1:1:1:1,the compensation system is regulated in 1+1+1+1=4 combination steps. In this manner ,it is possible to implement reactive power compensation systems, with which the number of steps is significantly higher than the number of control outputs at the reactive power controller. 
Reactive power compensation systems are normally provided with 6 to 20 combination steps. The graduation is too coarse with small number of stops, while more steps do not offer a significant improvement of power factor. Controllers with 8 control steps fulfill all practical requirements. Power factor controller relay: Power Factor Controller relay (Model RPM-14) is designed for automatic control of capacitor banks in 3 phase 4 wire LT distribution systems. The relay maintains the system power factor at a set value, under fluctuating load conditions, by connecting or disconnecting capacitor banks to the 415V bus. The relay employs state of the art micro controller design for measurement of reactive power compensation required, system power factor, voltage and current. A specially formulated optimization program for capacitor bank switching ensures accurate power factor control at the set point and hunt free operation.RPM-14 is designed to control up to 14 capacitor banks. 
Please refer wiring diagram shown below . There are 4 groups of connections as explained below: Fig.1 Wiring diagram of RPM-14 relay on APFC panel. 
(a) Auxiliary supply to RPM-14: Please connect R phase voltage of the capacitor bank panel to terminals 22 & 23 of the unit. Please note that it should be 240 V AC 50 Hz supply (Phase to neutral voltage). Phase is connected to terminal 22 and neutral is connected to the terminal 23 of the unit. RPM-14 uses this supply as the auxiliary supply for electronic circuit as well as measuring voltage for PF and KVAR computation. 
(b) CT input to RPM-14: The unit is suitable for connecting to CT secondary of either 1A or 5A
Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 
www.ijera.com 51 | P a g e 
rating. Please ensure that the CT is on R phase. 
CT secondary is to be connected as follows: 
1A rating – Terminals 17& 16 
5A rating – Terminals 18 & 16 
c) Supply to Capacitor Bank contactor coil supply : 
RPM-14 is meant for connecting up to 14 capacitor 
banks through external contactors. Consequently it 
provides 14 relay contact outputs. 
- One terminal of all 14 contactor coils is to be 
connected to neutral of the contactor coil supply. 
- The other terminal of each of the contactor coil has 
to be connected to RPM-14 terminals 1 to 14 as 
shown in the wiring diagram. 
- The phase supply of contactor coil should be 
connected to terminal 15 of RPM-14. 
d) Alarm Circuit: RPM-14 provides a change over 
contact at terminals 19, 20, 21. This is an 8A rated 
contact and can be used for energizing a buzzer. 
Note: Please ensure that: 
a) The auxiliary supply is 240 V AC 
b) The CT is on the same phase as the auxiliary 
supply. 
c) Earth connection to the relay is provided properly. 
Fig.2: Power factor controller (RPM-14). 
Capacitor bank selection: 
The RPM-14 relay will continuously evaluate the 
required KVAR compensation and keep adding to the 
bus- thus bringing the plant PF close to the set value. 
Sometimes, in operation, RPM-14 may not find the 
closest match for the required KVAR and may stop 
adding. This may result in a PF much less than the set 
target. 
In order that RPM-14 brings the plant PF closest 
to target PF, the system should have right 
denomination of capacitor banks as required by the 
load conditions of the plant. To determine, the right 
denomination of bank sizes (14 in total), following 
approach may be followed: 
III. RESULTS 
The experiment has been done in the National 
Small Industries Corporation (NSIC) industry in the 
industrial area of ECIL located in Hyderabad. 
The details of the company without the impact of 
panel are: 
Rating of transformer: 1500 KVA 
Average power factor: 0.887 
Connection type: 3-phase 5-wire 
Average DPF: 0.851 
The details of the company with the impact of 
panel are: 
Rating of transformer: 1500KVA 
Average power factor: 0.987 
Average DPF: 0.948
Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 
www.ijera.com 52 | P a g e 
CT ratio: 2500/1A PT ratio: 1:1 
Table-1: Values with APFC panel 
Table-2: Values with out APFC panel WAVEFORMS: The corresponding waveforms of voltage, current, powers and power factor without the presence of the panel are shown below: VOLTAGE: 
TRANSFORMER 
S. No 
PARAMETER 
RMS 
MIN 
AVG 
MAX 
1. 
VOLTAGE 
R 
249.9 
251.46 
252.6 
Y 
243.8 
245.21 
245.8 
B 
248 
250.01 
251 
2. 
CURRENT 
R 
14.99 
17.09 
23.86 
Y 
34.8 
34.87 
45.91 
B 
23.31 
24.045 
33.28 
3. 
POWER ( KW ) 
MIN 
AVG 
MAX 
16.365 
17.399 
24.795 
4. 
POWER(KVAR) 
-7.248 
-6.602 
-1.405 
5. 
POWER(KVA) 
18.126 
18.865 
25.411 
6. 
POWER FACTOR 
0.882 
0.907 
0.976 
TRANSFORMER 
S. No 
PARAMETER 
RMS 
MIN 
AVG 
MAX 
1. 
VOLTAGE 
R 
245.30 
247.59 
248.90 
Y 
241.70 
242.35 
243.30 
B 
246.00 
246.856 
247.90 
2. 
CURRENT 
R 
30.19 
34.038 
42.50 
Y 
50.41 
50.73 
51.01 
B 
38.06 
38.87 
39.91 
3. 
POWER( KW ) 
MIN 
AVG 
MAX 
24.469 
25.589 
27.909 
4. 
POWER(KVAR) 
29.116 
30.324 
32.383 
5. 
POWER(KVA) 
15.582 
16.120 
16.948 
6. 
POWER FACTOR 
0.827 
0.837 
0.860
Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 
www.ijera.com 53 | P a g e 
CURRENT: 
POWER : 
POWER FACTOR : 
Similarly, the corresponding waveforms of voltage, current, powers and power factor with the impact of APFC panel are shown below: VOLTAGE:
Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 
www.ijera.com 54 | P a g e 
CURRENT: 
POWER: 
POWER FACTOR: 
IV. CONCLUSIONS 
The impact of contactor switched automatic power factor panels at low tension side of transformer has been studied at rapidly varying and scattered loads. Automatic switching operation of the panel was observed to be satisfactory, thereby, eliminating the need for manual intervention. The target power factor was also improved much better(0.88 to ~0.99) almost unity when compared to its absence, thus. reducing the effect of high power bills and heavy penalties from electricity boards. REFERENCES [1] ”Performance of insulation systems for low voltage APFC panels during temperature rise test at elevated ambient temperatures” V.Vaidhyanathan,T.BhavaniShankar,G.Govinda Rao,H.N.Nagamani,2012 IEEE 10TH [2] International Standard IEC 60831-1, Shunt power capacitors of the self healing type for ac systems having rated voltage up to and including 1000 V. [3] International Standard IEC 60831-2, Shunt power capacitors of the self-healing type for ac systems having a rated voltage up to and including 1000 V Part:2 Ageing test, Self- healing test and destruction test. [4] H. N. Nagamani et.al, "Experience of CPRI in performance evaluation of power capacitors of unit rating up to 1000 kvar", 7lhInternational Seminar on Capacitors(CAPACIT 2010), pp. IV 1-13, Jan 2010, Mumbai, India.

More Related Content

What's hot

MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEIJERD Editor
 
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Dr. Sudhir Kumar Srivastava
 
Voltage Sag and Harmonics Mitigation using Distributed Power Flow Controller
Voltage Sag and Harmonics Mitigation using Distributed Power Flow ControllerVoltage Sag and Harmonics Mitigation using Distributed Power Flow Controller
Voltage Sag and Harmonics Mitigation using Distributed Power Flow ControllerIRJET Journal
 
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFCPOWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFCvivatechijri
 
Distributed power flow controller (naresh)
Distributed power flow controller (naresh)Distributed power flow controller (naresh)
Distributed power flow controller (naresh)Naresh Raye
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...IJPEDS-IAES
 
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...eSAT Journals
 
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...IJMTST Journal
 
Design and Performance Analysis of 400Hz Static Frequency Converter
Design and Performance Analysis of 400Hz Static Frequency ConverterDesign and Performance Analysis of 400Hz Static Frequency Converter
Design and Performance Analysis of 400Hz Static Frequency Converterijtsrd
 
Fuzzy inference system for integrated vvc
Fuzzy inference system for integrated vvcFuzzy inference system for integrated vvc
Fuzzy inference system for integrated vvcijaia
 
Application Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper PresentationApplication Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper Presentationguestac67362
 
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...IJITE
 
power factor controlling using intregarted device controller
power factor controlling using intregarted device controllerpower factor controlling using intregarted device controller
power factor controlling using intregarted device controllerusic123
 
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...
A DAPTIVE  S UPPLY  V OLTAGE  M ANAGEMENT  F OR  L OW  P OWER  L OGIC  C IRCU...A DAPTIVE  S UPPLY  V OLTAGE  M ANAGEMENT  F OR  L OW  P OWER  L OGIC  C IRCU...
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...VLSICS Design
 

What's hot (20)

MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACE
 
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
 
Voltage Sag and Harmonics Mitigation using Distributed Power Flow Controller
Voltage Sag and Harmonics Mitigation using Distributed Power Flow ControllerVoltage Sag and Harmonics Mitigation using Distributed Power Flow Controller
Voltage Sag and Harmonics Mitigation using Distributed Power Flow Controller
 
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFCPOWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
 
Distributed power flow controller (naresh)
Distributed power flow controller (naresh)Distributed power flow controller (naresh)
Distributed power flow controller (naresh)
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
 
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
 
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
Power Quality Improvement Fuzzy Logical Controlled Based on Cascaded Shunt Ac...
 
Design and Performance Analysis of 400Hz Static Frequency Converter
Design and Performance Analysis of 400Hz Static Frequency ConverterDesign and Performance Analysis of 400Hz Static Frequency Converter
Design and Performance Analysis of 400Hz Static Frequency Converter
 
Fuzzy inference system for integrated vvc
Fuzzy inference system for integrated vvcFuzzy inference system for integrated vvc
Fuzzy inference system for integrated vvc
 
Application Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper PresentationApplication Of Shuntactive Power Filter Paper Presentation
Application Of Shuntactive Power Filter Paper Presentation
 
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
 
20120140505014
2012014050501420120140505014
20120140505014
 
Bc4102392396
Bc4102392396Bc4102392396
Bc4102392396
 
Ppt
PptPpt
Ppt
 
power factor controlling using intregarted device controller
power factor controlling using intregarted device controllerpower factor controlling using intregarted device controller
power factor controlling using intregarted device controller
 
O43068690
O43068690O43068690
O43068690
 
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...
A DAPTIVE  S UPPLY  V OLTAGE  M ANAGEMENT  F OR  L OW  P OWER  L OGIC  C IRCU...A DAPTIVE  S UPPLY  V OLTAGE  M ANAGEMENT  F OR  L OW  P OWER  L OGIC  C IRCU...
A DAPTIVE S UPPLY V OLTAGE M ANAGEMENT F OR L OW P OWER L OGIC C IRCU...
 
Analysis and design of single phase voltage-frequency converter with optimize...
Analysis and design of single phase voltage-frequency converter with optimize...Analysis and design of single phase voltage-frequency converter with optimize...
Analysis and design of single phase voltage-frequency converter with optimize...
 

Viewers also liked

Privacy Preservation and Restoration of Data Using Unrealized Data Sets
Privacy Preservation and Restoration of Data Using Unrealized Data SetsPrivacy Preservation and Restoration of Data Using Unrealized Data Sets
Privacy Preservation and Restoration of Data Using Unrealized Data SetsIJERA Editor
 
Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...
Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...
Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...IJERA Editor
 
Real Time Implementation Of Face Recognition System
Real Time Implementation Of Face Recognition SystemReal Time Implementation Of Face Recognition System
Real Time Implementation Of Face Recognition SystemIJERA Editor
 
Measuring Robustness on Generalized Gaussian Distribution
Measuring Robustness on Generalized Gaussian DistributionMeasuring Robustness on Generalized Gaussian Distribution
Measuring Robustness on Generalized Gaussian DistributionIJERA Editor
 
Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...
Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...
Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...IJERA Editor
 
Research on Privacy Protection in Big Data Environment
Research on Privacy Protection in Big Data EnvironmentResearch on Privacy Protection in Big Data Environment
Research on Privacy Protection in Big Data EnvironmentIJERA Editor
 
The behavior of hybrid reinforced concrete after heat resistance
The behavior of hybrid reinforced concrete after heat resistanceThe behavior of hybrid reinforced concrete after heat resistance
The behavior of hybrid reinforced concrete after heat resistanceIJERA Editor
 
Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...
Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...
Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...IJERA Editor
 
Boosting Solar Efficiency
Boosting Solar EfficiencyBoosting Solar Efficiency
Boosting Solar EfficiencyIJERA Editor
 
Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...
Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...
Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...IJERA Editor
 
Intrusion Detection System: Security Monitoring System
Intrusion Detection System: Security Monitoring SystemIntrusion Detection System: Security Monitoring System
Intrusion Detection System: Security Monitoring SystemIJERA Editor
 
Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...
Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...
Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...IJERA Editor
 
Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...
Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...
Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...IJERA Editor
 
Modeling and Analysis of Bracket Assembly in Aerospace Industry
Modeling and Analysis of Bracket Assembly in Aerospace IndustryModeling and Analysis of Bracket Assembly in Aerospace Industry
Modeling and Analysis of Bracket Assembly in Aerospace IndustryIJERA Editor
 

Viewers also liked (20)

Privacy Preservation and Restoration of Data Using Unrealized Data Sets
Privacy Preservation and Restoration of Data Using Unrealized Data SetsPrivacy Preservation and Restoration of Data Using Unrealized Data Sets
Privacy Preservation and Restoration of Data Using Unrealized Data Sets
 
Bn4301364368
Bn4301364368Bn4301364368
Bn4301364368
 
Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...
Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...
Optimization of Patrol Manpower Allocation Using Goal Programming Approach -A...
 
Real Time Implementation Of Face Recognition System
Real Time Implementation Of Face Recognition SystemReal Time Implementation Of Face Recognition System
Real Time Implementation Of Face Recognition System
 
Measuring Robustness on Generalized Gaussian Distribution
Measuring Robustness on Generalized Gaussian DistributionMeasuring Robustness on Generalized Gaussian Distribution
Measuring Robustness on Generalized Gaussian Distribution
 
Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...
Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...
Studying the Factors Affecting Mainteneance Strategies & Computerised Mainten...
 
Research on Privacy Protection in Big Data Environment
Research on Privacy Protection in Big Data EnvironmentResearch on Privacy Protection in Big Data Environment
Research on Privacy Protection in Big Data Environment
 
C44081316
C44081316C44081316
C44081316
 
The behavior of hybrid reinforced concrete after heat resistance
The behavior of hybrid reinforced concrete after heat resistanceThe behavior of hybrid reinforced concrete after heat resistance
The behavior of hybrid reinforced concrete after heat resistance
 
D044032430
D044032430D044032430
D044032430
 
Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...
Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...
Electrochemical Synthesis of MoO3 Nanoparticles Effect of Temperature Convert...
 
Ai044230235
Ai044230235Ai044230235
Ai044230235
 
Boosting Solar Efficiency
Boosting Solar EfficiencyBoosting Solar Efficiency
Boosting Solar Efficiency
 
Av4301248253
Av4301248253Av4301248253
Av4301248253
 
Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...
Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...
Building Development Practice in Flood Prone Area: Case of Ogbaru Council Are...
 
E44082429
E44082429E44082429
E44082429
 
Intrusion Detection System: Security Monitoring System
Intrusion Detection System: Security Monitoring SystemIntrusion Detection System: Security Monitoring System
Intrusion Detection System: Security Monitoring System
 
Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...
Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...
Preparation and Characterization of Lithium Ion Conducting Solid Polymer Elec...
 
Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...
Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...
Evaluation of Post-liquefaction Reconsolidation Settlement based on Standard ...
 
Modeling and Analysis of Bracket Assembly in Aerospace Industry
Modeling and Analysis of Bracket Assembly in Aerospace IndustryModeling and Analysis of Bracket Assembly in Aerospace Industry
Modeling and Analysis of Bracket Assembly in Aerospace Industry
 

Similar to Impact of APFC Panel at LT Side of Transformer

IRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonicIRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonicIRJET Journal
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor ImprovementIRJET Journal
 
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemPower Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemIRJET Journal
 
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...IAES-IJPEDS
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...Vikram Rawani
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...IRJET Journal
 
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET Journal
 
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...IJMTST Journal
 
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET Journal
 
MINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfMINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfDrSabhyataSoni
 
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...IJERD Editor
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
power quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcompower quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcom7867867869
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...ijiert bestjournal
 

Similar to Impact of APFC Panel at LT Side of Transformer (20)

IRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonicIRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonic
 
Apfc project 2016 17
Apfc project 2016 17Apfc project 2016 17
Apfc project 2016 17
 
Sme apfc panel catalogue
Sme apfc panel catalogueSme apfc panel catalogue
Sme apfc panel catalogue
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor Improvement
 
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemPower Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
 
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
 
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
 
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...
 
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
 
MINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfMINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdf
 
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
7PG2111 Solkor Relay
7PG2111 Solkor Relay7PG2111 Solkor Relay
7PG2111 Solkor Relay
 
B360614
B360614B360614
B360614
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
power quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcompower quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcom
 
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
POWER QUALITY IMPROVEMENT USING 5-LEVEL FLYING CAPACITOR MULTILEVEL CONVERTER...
 

Recently uploaded

DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage examplePragyanshuParadkar1
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixingviprabot1
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 

Recently uploaded (20)

DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage example
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixing
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

Impact of APFC Panel at LT Side of Transformer

  • 1. Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 www.ijera.com 49 | P a g e Impact of APFC Panel at LT Side of Transformer Bhogadi. Havya, K.Ravi Kumar (Associate Professor) Department of Electrical and Electronic Engineering, Vasavi College of Engineering, Hyderabad, Andhra Pradesh, India. Abstract The Development of automatic sensing technologies have significantly advanced in recent years in electrical systems.One of them is Automatic Power Factor Correction(APFC)Panels.It is very difficult to maintain consistent power factor by using fixed capacitors because they need to be operated manually which may result in over voltages,saturation of transformers etc. that may lead to the interruption in the power supply of the distribution system.APFC Panels automatically varies according to the load requirements on the L.T side i.e. distribution side which compensates the load requirements.Impact of automatic power factor correction panels (APFC) at L.T side of a transformer are discussed which are inductive in nature. Key words: APFC Panels, Power Factor, Inductive, Fixed capacitors, Power factor correction. I. INTRODUCTION Most of the electrical loads are inductive in nature resulting in severely lagging power factor. The most practical and economical solution to improve the power factor(PF) is to provide reactive compensation by installing power capacitors of suitable rating at strategic locations. But this has to be operated manually and which may result in the over voltages, damage of the electrical equipments saturation of transformers etc. PF correction is more important in electrical distribution systems. For accomplishing the same low voltage(LV) capacitors are being extensively used both as fixed capacitor banks and in Automatic Power Factor Correction (APFC) Panels. Application of APFC Panels is becoming more attractive due to their techno-commercial advantages like (1) Ability to maintain PF at the required high value (close to unity) and hence avoid the penalties imposed by electrical supply companies due to low PF (2) Avoid over compensation during low load conditions and (3) Improved efficiency of the system due to reduction in losses. Application of automatic power factor correction panels(APFC) in electrical distribution network is gaining importance due to the advantages of APFC Panels over fixed capacitor banks like ability to maintain the target power factor with varying load and hence improve efficiency of the system and consequently reduce distribution losses. At present, no comprehensive Indian standard is available for testing APFC Panels. Bureau of Indian Standards(BIS),the national standards body of India has extended financial support to CPRI to undertake a R&D project for development of a new standard for LV APFC Panels. CPRI in association with APFC Panel manufacturers and purchasers has formulated an Indian standard for “APFC panels for voltage rating upto and including 1000 volts”. The standard will help both manufacturers and utilities to setup uniformity in testing and also to install reliable APFC Panels for achieving the target power factor(PF),closer to unity and consequently improve the efficiency of the LV system by minimizing the losses in distribution systems. II. METHODOLOGY Present study has been conducted on APFC panels with contactor type of switching mechanism .Rating of the panels was 500kvar,440V,3- phase,delta connected.To improve the power factor using APFC panels , the following points has to be noted. (1) Please check if required kvar of capacitors are installed. (2) Check the type of capacitor installed is suitable for application or the capacitors are de-rated. (3) Check if the capacitors are permanently „ON‟. The capacitors are not switched off. (4) When the load is not working under such condition the average power factor is found to be lower side. (5) Check whether all the capacitors are operated in APFC depending upon the load operation. (6) Check whether the APFC installed in the installation is working or not. Check the CT connection is taken from the main incomer side of transformer, after the fix compensation of transformer. (7) Check if the load demand in the system is increased. (8) Check if power transformer compensation is provided. RESEARCH ARTICLE OPEN ACCESS
  • 2. Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 www.ijera.com 50 | P a g e Central compensation: Consumer installations usually possess a varying reactive power requirement. Unregulated fixed compensation is not possible in such cases since an uneconomical under- compensation or a dangerous over-compensation can occur. One must therefore continuously adjust the capacitor power to the required reactive power requirement. One achieves this by means of automatic capacitorbanks which are directly assigned to a switchgear unit, distribution and sub-distribution or to a large load with fluctuating reactive power requirements. This is achieved in non-reactor protected systems by using special capacitor switching contactors.These are equipped with pre-charging resistors as a permanent component of the contactors.The capacitor is first connected to the network via these resistors by means of early closing contacts before the main contacts close. The inrush current is then only approx.5% of the non-attenuated value. Regulation, number of steps and control series : Most consumer installations are compensated using automatic capacitor banks due to the recognized benefits. The compensation power is designed with switched steps to match the employed capacitor power to the fluctuating load situation in the consumer‟s system. A reactive power controller detects the momentary reactive power requirement by means of voltage and current measurements in the feeder to the consumer‟s installation(distribution or sub- distribution).The capacitor power is adjusted by connection or dis-connection in such a manner that a target power factor programmed at the regulators is reached. To avoid the reconnection of capacitors that have not yet been discharged ,certain switching or lock-out times are specified or pre-selectable in the reactive power regulator which are to be taken into account when choosing discharge devices. The distribution of the total power among the switched regulator control taps[control outputs]is specified with the control series. It contains the number of steps and their power ratings as a factor of the power of the first step, which is defined as 1.The cross-sum of the control series gives the number of combination steps of the compensation system. For example, control series with four control steps of the same power: 1:1:1:1,the compensation system is regulated in 1+1+1+1=4 combination steps. In this manner ,it is possible to implement reactive power compensation systems, with which the number of steps is significantly higher than the number of control outputs at the reactive power controller. Reactive power compensation systems are normally provided with 6 to 20 combination steps. The graduation is too coarse with small number of stops, while more steps do not offer a significant improvement of power factor. Controllers with 8 control steps fulfill all practical requirements. Power factor controller relay: Power Factor Controller relay (Model RPM-14) is designed for automatic control of capacitor banks in 3 phase 4 wire LT distribution systems. The relay maintains the system power factor at a set value, under fluctuating load conditions, by connecting or disconnecting capacitor banks to the 415V bus. The relay employs state of the art micro controller design for measurement of reactive power compensation required, system power factor, voltage and current. A specially formulated optimization program for capacitor bank switching ensures accurate power factor control at the set point and hunt free operation.RPM-14 is designed to control up to 14 capacitor banks. Please refer wiring diagram shown below . There are 4 groups of connections as explained below: Fig.1 Wiring diagram of RPM-14 relay on APFC panel. (a) Auxiliary supply to RPM-14: Please connect R phase voltage of the capacitor bank panel to terminals 22 & 23 of the unit. Please note that it should be 240 V AC 50 Hz supply (Phase to neutral voltage). Phase is connected to terminal 22 and neutral is connected to the terminal 23 of the unit. RPM-14 uses this supply as the auxiliary supply for electronic circuit as well as measuring voltage for PF and KVAR computation. (b) CT input to RPM-14: The unit is suitable for connecting to CT secondary of either 1A or 5A
  • 3. Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 www.ijera.com 51 | P a g e rating. Please ensure that the CT is on R phase. CT secondary is to be connected as follows: 1A rating – Terminals 17& 16 5A rating – Terminals 18 & 16 c) Supply to Capacitor Bank contactor coil supply : RPM-14 is meant for connecting up to 14 capacitor banks through external contactors. Consequently it provides 14 relay contact outputs. - One terminal of all 14 contactor coils is to be connected to neutral of the contactor coil supply. - The other terminal of each of the contactor coil has to be connected to RPM-14 terminals 1 to 14 as shown in the wiring diagram. - The phase supply of contactor coil should be connected to terminal 15 of RPM-14. d) Alarm Circuit: RPM-14 provides a change over contact at terminals 19, 20, 21. This is an 8A rated contact and can be used for energizing a buzzer. Note: Please ensure that: a) The auxiliary supply is 240 V AC b) The CT is on the same phase as the auxiliary supply. c) Earth connection to the relay is provided properly. Fig.2: Power factor controller (RPM-14). Capacitor bank selection: The RPM-14 relay will continuously evaluate the required KVAR compensation and keep adding to the bus- thus bringing the plant PF close to the set value. Sometimes, in operation, RPM-14 may not find the closest match for the required KVAR and may stop adding. This may result in a PF much less than the set target. In order that RPM-14 brings the plant PF closest to target PF, the system should have right denomination of capacitor banks as required by the load conditions of the plant. To determine, the right denomination of bank sizes (14 in total), following approach may be followed: III. RESULTS The experiment has been done in the National Small Industries Corporation (NSIC) industry in the industrial area of ECIL located in Hyderabad. The details of the company without the impact of panel are: Rating of transformer: 1500 KVA Average power factor: 0.887 Connection type: 3-phase 5-wire Average DPF: 0.851 The details of the company with the impact of panel are: Rating of transformer: 1500KVA Average power factor: 0.987 Average DPF: 0.948
  • 4. Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 www.ijera.com 52 | P a g e CT ratio: 2500/1A PT ratio: 1:1 Table-1: Values with APFC panel Table-2: Values with out APFC panel WAVEFORMS: The corresponding waveforms of voltage, current, powers and power factor without the presence of the panel are shown below: VOLTAGE: TRANSFORMER S. No PARAMETER RMS MIN AVG MAX 1. VOLTAGE R 249.9 251.46 252.6 Y 243.8 245.21 245.8 B 248 250.01 251 2. CURRENT R 14.99 17.09 23.86 Y 34.8 34.87 45.91 B 23.31 24.045 33.28 3. POWER ( KW ) MIN AVG MAX 16.365 17.399 24.795 4. POWER(KVAR) -7.248 -6.602 -1.405 5. POWER(KVA) 18.126 18.865 25.411 6. POWER FACTOR 0.882 0.907 0.976 TRANSFORMER S. No PARAMETER RMS MIN AVG MAX 1. VOLTAGE R 245.30 247.59 248.90 Y 241.70 242.35 243.30 B 246.00 246.856 247.90 2. CURRENT R 30.19 34.038 42.50 Y 50.41 50.73 51.01 B 38.06 38.87 39.91 3. POWER( KW ) MIN AVG MAX 24.469 25.589 27.909 4. POWER(KVAR) 29.116 30.324 32.383 5. POWER(KVA) 15.582 16.120 16.948 6. POWER FACTOR 0.827 0.837 0.860
  • 5. Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 www.ijera.com 53 | P a g e CURRENT: POWER : POWER FACTOR : Similarly, the corresponding waveforms of voltage, current, powers and power factor with the impact of APFC panel are shown below: VOLTAGE:
  • 6. Bhogadi. Havya Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 7( Version 1), July 2014, pp.49-54 www.ijera.com 54 | P a g e CURRENT: POWER: POWER FACTOR: IV. CONCLUSIONS The impact of contactor switched automatic power factor panels at low tension side of transformer has been studied at rapidly varying and scattered loads. Automatic switching operation of the panel was observed to be satisfactory, thereby, eliminating the need for manual intervention. The target power factor was also improved much better(0.88 to ~0.99) almost unity when compared to its absence, thus. reducing the effect of high power bills and heavy penalties from electricity boards. REFERENCES [1] ”Performance of insulation systems for low voltage APFC panels during temperature rise test at elevated ambient temperatures” V.Vaidhyanathan,T.BhavaniShankar,G.Govinda Rao,H.N.Nagamani,2012 IEEE 10TH [2] International Standard IEC 60831-1, Shunt power capacitors of the self healing type for ac systems having rated voltage up to and including 1000 V. [3] International Standard IEC 60831-2, Shunt power capacitors of the self-healing type for ac systems having a rated voltage up to and including 1000 V Part:2 Ageing test, Self- healing test and destruction test. [4] H. N. Nagamani et.al, "Experience of CPRI in performance evaluation of power capacitors of unit rating up to 1000 kvar", 7lhInternational Seminar on Capacitors(CAPACIT 2010), pp. IV 1-13, Jan 2010, Mumbai, India.