International Journal of Civil Engineering and Technology (IJCIET)
Volume 8, Issue 2, February 2017, pp. 72–88 Article ID: IJCIET_08_02_008
Available online at http://www.iaeme.com/IJCIET/issues.asp?JType=IJCIET&VType=8&IType=2
ISSN Print: 0976-6308 and ISSN Online: 0976-6316
© IAEME Publication Scopus Indexed
SEISMIC RESPONSE OF UNSYMMETRIC BUILDING
WITH OPTIMALLY PLACED FRICTION DAMPERS
S. S. Sanghai
Assistant Professor, Civil Engineering Department,
G. H. Raisoni College of Engineering, Nagpur, India
S. N. Khante
Associate Professor, Applied Mechanics Department,
Govt. College of Engineering, Amravati, India
ABSTRACT
Conventional methods of seismic rehabilitation with concrete shear walls or steel bracing
are not considered suitable for some buildings as upgrades with these methods would have
required expensive and time consuming foundation work. Supplemental damping in
conjunction with appropriate stiffness offers an innovative and attractive solution for the
seismic rehabilitation of such structures. This paper deals with the use of friction damper as a
passive dissipative device in order to seismic retrofit of existing structures and discusses the
optimal placement criteria. To fulfill this objective, six storey and ten storey L-shaped
buildings have been modeled with five different damper location formats in SAP2000 subjected
to El Centro and Utterkashi earthquake records. Non-Linear Modal Time History Method has
been used for the analysis and base shear, joint displacement, member forces and hysteresis
energy has been compared to find out most optimal damper location format.
Key words: friction damper, non-linear modal time history analysis, optimization, slip load
Cite this Article: S. S. Sanghai and S. N. Khante, Seismic Response of Unsymmetric Building
with Optimally Placed Friction Dampers. International Journal of Civil Engineering and
Technology, 8(2), 2017, pp. 72–88.
http://www.iaeme.com/IJCIET/issues.asp?JType=IJCIET&VType=8&IType=2
1. INTRODUCTION
Severe ground shaking induces lateral inertial forces on buildings, causing them to sway back and
forth with amplitude proportional to the energy fed in. If a major portion of this energy can be
consumed during building motion, the seismic response can be considerably improved. The manner in
which this energy is consumed in the structure determines the level of damage.
The use of bracing systems equipped with dissipative devices is relatively new technique for the
earthquake protection of buildings that has been considered in several recent experimental and
theoretical studies. In particular, the friction damping bracing system involving the device proposed by
Pall and Marsh (1982) has been carefully analyzed, since its simplicity of construction and high
dissipative capacity encourages application in practice. At present, the existing studies offer
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 73 editor@iaeme.com
sufficiently detailed information about the protection level, expressed in terms of energy absorption or
reduction of maximum horizontal displacement.
Friction damping devices dissipate energy by utilizing the mechanism of solid friction developed
at the sliding surface, which is a relatively inexpensive and effective method for stable energy
dissipation. As their hysteretic behaviors could be kept stable for cyclic loads and desirable slip loads
are easily obtained by regulating normal forces acting perpendicularly to a friction surface, in addition
to their simple energy dissipation mechanism and easy manufacturing, installation and maintenance
(Pall and Marsh 1982). Filatrault and Cherry (1990) have proposed the design procedure of friction
dampers that minimizes the sum of the displacement and dissipating energy by carrying out the
parametric studies such as the structural fundamental period, frequency components of excitation load
and the slip load of friction damper. Moreschi and Singh (2003) have determined the optimal slip load
and the bracing stiffness by using the optimization technique such as genetic algorithm. Pujari and
Bakre (2011) have studied the optimal placement of XPDs which provides more reduction in response
compared with other schemes of placement of XPD considered in the study. Furthermore, the optimal
placement of dampers is sensitive to the nature of excitation force, number of XPDs used and the
modeling of XPD. Khante and Sanghai (2012) have studied optimal placement of friction damper
using Non-Linear Time History Analysis on symmetric RCC framed building.
In this paper, a general framework for optimal placement of passive energy dissipation devices in
the form of friction dampers for seismic structural application has been formulated. The study has
been done for unsymmetrical RCC framed building.
2. BUILDING DESCRIPTION
The model of buildings are 6 storey and 10 storey reinforced concrete building having L shape in plan
as shown in Fig.1. The building has four frames at 3m c/c in X and Y direction with 3.2m storey
height and 1.2m plinth height as shown in Fig.1 and Fig.2. The beam and column are modeled as
frame element while slab is modeled as thin shell element. The sizes of members are given in Table
No.1. The friction dampers are placed along peripheral frames of building. The elevation of G+5
storey and G+9 storey structure with five different format of placement of dampers as shown in Fig. 2
and Fig. 3 respectively.
Table 1 Sizes of members
Storey G+5 G+9
Sizes of Beams 0.3m X 0.45m 0.3m X 0.45m
Sizes of Columns 0.3m X 0.45m 0.3 m X 0.5m
Thickness of Slab 125mm 125mm
Figure 1 Plan of building
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 74 editor@iaeme.com
(1) (2) (3) (4) (5)
Figure 2 Elevation of formats of G+5 building model
(1) (2) (3) (4) (5)
Figure 3 Elevation of formats of G+9 building model
3. PROPERTIES OF FRICTION DAMPER
The slip load of the friction damper is the principal variable. Fig.4 shows that, if slip load is very low
or very high, response is very high. This is because, if slip load is very low, friction damper will slip
for small vibrations leading to minimum hysteresis energy and if slip load is very high friction damper
will not slip and act as simple brace reducing hysteresis energy. The current slip load is decided by
trial and error method. The appropriate selection of slip load leads to optimum response of structure.
The friction dampers in single diagonal brace are modeled as damped braces having member stiffness
equal to brace stiffness and nonlinear axial yielding equal to the slip load. The properties of friction
damper used for modeling are given in Table No. 2.The link element named as Plastic (wen) is used to
model friction damper.
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 75 editor@iaeme.com
Table 2 Properties of friction damper
Storey G+5 G+9
Slip Load 300kN 500kN
Brace section ISMB200 ISMB200
Stiffness of element 149883.99 149883.99
Yielding Load 300kN 500kN
Post yield stiffness ratio 0.0001 0.0001
Yielding Exponent 10 10
Figure 4 Responses versus Slip Load (Avtar Pall, 2004)
4. METHOD OF ANALYSIS
For the analysis of all five formats, Non-Linear Time History method has been used in SAP2000. To
conduct time history analysis, the ground motion records used are El-Centro having peak ground
acceleration of 0.313g and Utterkashi having peak ground acceleration of 0.252g as shown in Fig. 5
and Fig.6.
Figure 5 El Centro ground motion record
Figure 6 Utterkashi ground motion record
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 76 editor@iaeme.com
5. OPTIMIZATION TECHNIQUE
In this study, the friction dampers have been induced as diagonal braces in these structures with few
fixed location formats. These location formats have been selected arbitrarily based on the previous
study as well as with a view to keep the number of dampers used to minimum. Dampers are located
between floor to floor diagonally as braces.
The unconstrained optimization problem is now formulated as:
Minimize ( ) = + (1)
where, f (x) is the objective function to be minimized, and x is the vector of design variables. In the
present case, the locations of a specified number of dampers in the structural system form the design
variables. The objective function for the minimization problem is considered to be a linear
combination of normalized maximum base shear Vb, and normalized maximum storey drift D. The
factors Vbu and Du denote the maximum base shear and maximum storey drift in the structure without
any supplemental dampers (Kokil and Shrikhande, 2007
6. RESULTS AND DISCUSSION
Using SAP2000 the analysis were carried out. The comparison of results has been done to find out
best optimal damper location format. The format (1) has no dampers and Format (5) has dampers at
each storey, hence these two formats can’t be called as optimal location formats. While in location
formats (2), (3) and (4) using same number of dampers different locations have been tried. Therefore
best location format will be out of Format (2), (3) and (4).
The modal time period and frequencies of mode shapes are most important factor to determine the
dynamic characteristics of structure. For modal analysis, Ritz vector method has been selected for
calculating time period and frequencies of mode shapes. Following table shows the modal time period
and frequencies of first mode shape for different formats of friction dampers.
Table 3 Values of time period and frequencies for G+5 storey
FOR EL CENTRO FOR UTTERKASHI
TIME PERIOD FREQUENCY TIME PERIOD FREQUENCY
FORMAT (1) 0.80 1.25 0.80 1.25
FORMAT (2) 0.58 1.72 0.58 1.72
FORMAT (3) 0.63 1.60 0.63 1.60
FORMAT (4) 0.52 1.91 0.52 1.91
FORMAT (5) 0.45 2.23 0.45 2.23
Table 4 Values of time period and frequencies for G+9 storey
According to the above values, the modal time period of damped structure is less when compared
with undamped structure. This is due to increase of stiffness of damped structure by addition of braces.
The envelopes of maximum values of acceleration, velocity and displacement in X direction of
undamped and damped building are shown in Fig. 6, Fig. 10 and Fig. 14 for G+5 storey and Fig. 8,
Fig. 12 and Fig. 16 for G+9 storey structures subjected to El Centro ground motion record while Fig.
FOR EL CENTRO FOR UTTERKASHI
TIME PERIOD FREQUENCY TIME PERIOD FREQUENCY
FORMAT (1) 1.70 0.59 1.7 0.59
FORMAT (2) 1.27 0.79 1.27 0.79
FORMAT (3) 1.31 0.76 1.31 0.76
FORMAT (4) 1.19 0.84 1.19 0.84
FORMAT (5) 1.05 0.95 1.05 0.95
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 77 editor@iaeme.com
7, Fig. 11 and Fig. 15 for G+5 storey and Fig. 9, Fig. 13 and Fig. 17 for G+9 storey structures
subjected to Utterkashi ground motion record.
Figure 6 Jt. acceleration in X-direction for G+5 storey
Figure 7 Jt. acceleration in X-direction for G+5 storey
Figure 8 Jt. acceleration in X-direction for G+9 storey
0
1
2
3
4
5
6
7
0 2 4 6 8 10
FLOOR
ACCELERATION (m/s2)
JT. ACCELERATION IN X-DIR FOR EL CENTRO
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
0
1
2
3
4
5
6
7
0 2 4 6 8
FLOOR
ACCELERATION (m/s2)
JT. ACCELERATION IN X-DIR FOR UTTERKASHI
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
0
2
4
6
8
10
12
0 1 2 3 4 5 6 7
FLOOR
ACCELERATION (m/s2)
JT. ACCELERATION IN X-DIR FOR EL CENTRO
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 78 editor@iaeme.com
Figure 9 Jt. acceleration in X-direction for G+9 storey
Figure 10 Jt. velocity in X-direction for G+5 storey
Figure 11 Jt. velocity in X-direction for G+5 storey
0
2
4
6
8
10
12
0 1 2 3 4 5
FLOOR
ACCLERATION (m/s2)
JT. ACCELERATION IN X-DIR FOR UTTERKASHI
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
0
1
2
3
4
5
6
7
0 0.2 0.4 0.6 0.8 1
FLOOR
VELOCITY (m/s)
JT. VELOCITY IN X-DIR FOR EL CENTRO
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
0
1
2
3
4
5
6
7
0 0.2 0.4 0.6 0.8
FLOOR
VELOCITY (m/s)
JT. VELOCITY IN X-DIR FOR UTTERKASHI
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 79 editor@iaeme.com
Figure 12 Jt. velocity in X-direction for G+9 storey
Figure 13 Jt. velocity in X-direction for G+9 storey
Figure 14 Jt. displacement in X-direction for G+5 storey
0
2
4
6
8
10
12
0 0.2 0.4 0.6 0.8 1
FLOOR
VELOCITY (m/s)
JT. VELOCITY IN X-DIR FOR EL CENTRO
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
0
2
4
6
8
10
12
0 0.1 0.2 0.3 0.4 0.5 0.6
FLOOR
VELOCITY (m/s)
JT. VELOCITY IN X-DIR FOR UTTERKASHI
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
0
1
2
3
4
5
6
7
0 20 40 60 80 100 120
FLOORS
DISPLACEMENT (mm)
JT. DISPLACEMENT IN X-DIR FOR EL CENTRO
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 80 editor@iaeme.com
Figure 15 Jt. Displacement in X-direction for G+5 storey
Figure 16 Jt. Displacement in X-direction for G+9 storey
Figure 17 Jt. Displacement in X-direction for G+9 storey
From above figures, it can be seen that joint velocity and displacement in damped building in X-
direction is reduced in comparison with undamped building. While joint acceleration reduces for G+5
storey and increses for G+9 storey structure. The maximum top storey reduction in joint acceleration is
for Format (5) and minimum increase for Format (3), in joint velocity is for Format (4) and for Format
0
1
2
3
4
5
6
7
0 20 40 60 80 100
FLOORS
DISPLACEMENT (mm)
JT. DISPLACEMENT IN X-DIR FOR UTTERKASHI
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
0
2
4
6
8
10
12
0 50 100 150 200
FLOORS
DISPLACEMENT (mm)
JT. DISPLACEMENT IN X-DIR FOR EL CENTRO
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
-2
0
2
4
6
8
10
12
0 20 40 60 80 100 120
FLOORS
DISPLCEMENTS (mm)
JT. DISPLACEMENT IN X-DIR FOR UTTERKASHI
FORMAT(1)
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
Linear (FORMAT (3))
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 81 editor@iaeme.com
(4) and in joint displacement is for Format (5) and for Format (4) respectively for G+5 storey and G+9
storey structure subjected to El Centro while the maximum top storey reduction in joint acceleration is
for Format (3) and for Format (4), in joint velocity is for Format (4) and for Format (3) and in joint
displacement is for Format (5) and for Format (4) respectively for G+5 storey and G+9 storey
structure subjected to Utterkashi. The reduction in acceleration, velocity and displacement of stories is
due to increase of stiffness of structure.
The maximum base shear in X-direction of undamped and damped building is shown in Fig.18 and
Fig.19.
Figure 18 Maximum Base shear in X-direction for G+5 storey
Figure 19 Maximum Base shear in X-direction for G+9 storey
Fig.18 and Fig.19 show that base shear is decreased in damped building as compared to undamped
building. The maximum reduction is 22.93% for G+5 storey and 5.78% for G+9 storey structure in
Format (4) subjected to El Centro ground motion record while 12.87% for G+5 storey and 14.19%
for G+9 storey structure in Format (4) subjected to Utterkashi ground motion record . This reduction is
due to addition of friction dampers which increases supplemental damping by 20-30%.
The maximum axial forces and maximum bending moment in members are plotted for different
formats as shown in Fig. 20 and Fig. 22 for G+5 storey and Fig. 21 and Fig. 23 for G+9 storey
structure.
0
500
1000
1500
2000
2500
FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
BASESHEAR(kN)
MAX. BASE SHEAR IN X-DIR
EL CENTRO
UTTERKASHI
0
500
1000
1500
2000
2500
3000
3500
FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
BASESHEAR(kN)
MAX. BASE SHEAR IN X-DIR
EL CENTRO
UTTERKASHI
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 82 editor@iaeme.com
Figure 20 Maximum axial forces for G+5 storey
Figure 21 Maximum axial forces for G+9 storey
Figure 22 Maximum bending moment for G+5 storey
0
200
400
600
800
1000
1200
1400
FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
AXIALFORCE(kN)
MAX. AXIAL FORCE
EL CENTRO
UTTERKASHI
0
500
1000
1500
2000
2500
3000
3500
FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
AXIALFORCE(kN)
MAX. AXIAL FORCE
EL CENTRO
UTTERKASHI
0
50
100
150
200
250
300
350
400
450
500
FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
BENDINGMOMENT()kN.m)
MAX.BENDING MOMENT
EL CENTRO
UTTERKASHI
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 83 editor@iaeme.com
Figure 23 Maximum bending moment for G+9 storey
On comparing the maximum axial forces and maximum bending moments in members, it is
observed that bending moment reduces for all models however axial force reduces for six storey
building and increases for ten storey building with inclusion of damper. The earthquake forces acting
on main structural member get redistributed due to addition of friction damper diagonally. This causes
reduction in axial force and bending moment. It is observed that, in some cases axial force increases,
because some dampers are observed to remain in non-slip mode. The reason behind it, is provision of
excessive dampers and sometimes lower input acceleration. Thus they behave as bracing member.
Because of this building becomes stiffer than other formats, hence axial force increases in this case.
The step by step increase in hysteresis energy for different formats of friction dampers are as
shown in Fig.24 and Fig.25 for G+5 storey and Fig.26 and Fig.27 for G+9 storey structure.
Figure 24 Hysteresis Energy for G+5 storey
0
50
100
150
200
250
300
350
400
450
500
FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
BENDINGMOMENT(kN.m)
MAX. BENDING MOMENT
EL CENTRO
UTTERKASHI
-20
0
20
40
60
80
100
120
140
160
180
0 1000 2000 3000 4000 5000
ENERGY(kN-m)
TIME STEPS
HYSTERESIS ENERGY FOR EL CENTRO
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 84 editor@iaeme.com
Figure 25 Hysteresis Energy for G+5 storey
Figure 26 Hysteresis Energy for G+9 storey
Figure 27 Hysteresis Energy for G+9 storey
From comparison of hysteresis energy, it can be seen that the maximum hysteresis energy is
observed for format (4) in all cases. The more value of hysteresis energy means more amount input
-50
0
50
100
150
200
250
0 1000 2000 3000 4000 5000
ENERGY(kN-m)
TIME STEPS
HYSTERESIS ENERGY FOR EL CENTRO
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
-5
0
5
10
15
20
25
0 500 1000 1500 2000
ENERGY(kN-m)
TIME STEPS
HYSTERESIS ENERGY FOR UTTERKASHI
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
-10
0
10
20
30
40
50
60
70
80
90
0 500 1000 1500 2000
ENERGY(kN-m)
TIME STEPS
HYSTERISIS ENERGY FOR UTTERKASHI
FORMAT(2)
FORMAT(3)
FORMAT(4)
FORMAT(5)
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 85 editor@iaeme.com
energy is dissipated by friction dampers. From the figures it is clear that, by using more numbers of
friction dampers does not always lead to more dissipation of input energy.
Figure 28 Different energy component comparison for G+5 storey
Figure 29 Different energy component comparison for G+5 storey
Figure 30 Different energy component comparison for G+9 storey
0
50
100
150
200
250
300
350
400
FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5)
ENERGY COMPONENT COMPARISON FOR EL CENTRO
Input
Energy
Kinetic
Energy
Potential
Energy
Modal
Damping
Energy
Link
Hystretic
Energy
0
20
40
60
80
100
120
140
160
180
FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5)
ENERGY COMPONENT COMPARISON FOR UTTERKASHI
Input Energy
Kinetic
Energy
Potential
Energy
Modal
Damping
Energy
Link
Hystretic
Energy
0
100
200
300
400
500
600
700
800
FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5)
ENERGY COMPONENT COMPARISON FOR EL CENTRO
Input
Energy
Kinetic
Energy
Potential
Energy
Modal
Damping
Energy
Link
Hysteretic
Energy
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 86 editor@iaeme.com
Figure 31 Different energy component comparison for G+9 storey
Fig. 28, Fig.29, Fig.30 and Fig.31 shows the different energy components for various location
formats considered. The input energy depends upon work done on structure by force and acceleration
and kinetic energy is function of mass and velocity while potential energy is function of elastic
constant and displacement of structure. As force, mass and elastic constants of structure are same for
all formats, energy components depend on acceleration, velocity and displacement of structure. In
Format (1), link hysteretic energy is zero because of absence of friction damper. So, all the input
energy has to be dissipated through modes so as to satisfy equation of motion. While in other formats,
percentage energy dissipated through modes reduces while energy dissipated through hysteretic
behaviour of friction damper increases. This reduction in percentage dissipation of input energy
through modes and increase in percentage dissipation through link hysteretic behaviour depends upon
location of friction damper. The percentage dissipation of input energy through hysteretic behavior is
maximum for Format (4) in G+5 storey and G+9 storey building models. The value of function used
for optimization is as shown in Fig.32 and Fig.33.
Figure 32 Objective Function Value for G+5 storey
0
50
100
150
200
250
FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5)
ENERGY COMPONENT COMPARISON FOR UTTERKASHI
Input
Energy
Kinetic
Energy
Potential
Energy
Modal
Damping
Energy
Link
Hysteretic
Energy
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5)
FUNCTION VALUE
EL CENTRO
UTTERKASHI
S. S. Sanghai and S. N. Khante
http://www.iaeme.com/IJCIET/index.asp 87 editor@iaeme.com
Figure 33 Objective Function Value for G+9 storey
Fig. 32 and Fig.33 shows that the value objective function is minimum for format (4) for both G+5
storey and G+9 storey structure. Also, the base shear, axial force, bending moment is minimum in
format (4). Hence, it can be said that with the given no. of dampers format (4) is optimum location
format.
7. CONCLUSION
The supplementary energy dissipation devices are known to be effective in reducing the earthquake
induced response of structural systems. Optimal placement of these protective systems is of practical
interest. The main objective of this study, therefore, has been to find the most optimal configuration of
friction damper which gives maximum utilization of damper and minimal damage to unsymmetrical
buildings when subjected to real earthquake ground motions. The results showed that the format (4) is
the optimal format because of well distributed stiffness while in other cases alternate stories are soft
and stiff. Hence it is clear that the damper placement influences significantly the structural response.
Also, the study investigates that use of larger number of dampers do not always lead to the best
benefit.
REFERENCES
[1] Pall, A. S., and Marsh C. (1982), ‘Response of Friction Damped Braced Frames’, Journal of the
Structural Division, American Society of Civil Engineers, 108(ST6).
[2] Filiatrault, A., and Cherry, S. (1990), ‘Seismic Design Spectra for Friction Damped Structures’,
Journal of Structural Engineering, American Society of Civil Engineers, 116, pp. 1334-1355.
[3] Moreschi, L.M., and Singh, M.P. (2003), ‘Design of Yielding and Friction Dampers for Optimal
Seismic Performance’, Earthquake Engineering Structural Dynamics, 32, pp. 1291-1311.
[4] Pujari, N. N., and Bakre, S. V. (2011), ‘Optimum placement of X-plate dampers for seismic
response control of multistoried buildings’ International Journal of Earth Science and Engineering,
4(6), pp. 481-485.
[5] Manveer Singh and Khushpreet Singh, An Efficient Analysis of Linear and Non- Linear Model
using Various Regression Level for Fluid Dampers. International Journal of Civil Engineering and
Technology, 7(5), 2016, pp.111–123.
[6] Khante, S. N., and Sanghai, S. S. (2012), ‘Optimal placement of friction dampers for seismic
response control of symmetric RCC framed building’, Proceeding of NCETETA-2012, pp. 209-213.
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5)
FUNCTION VALUE
EL CENTRO
UTTERKASHI
Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers
http://www.iaeme.com/IJCIET/index.asp 88 editor@iaeme.com
[7] Kokil, A.S., and Shrikhande, M. (2007), ‘Optimal Placement of Supplemental Dampers in Seismic
Design of Structures’, JSEE Fall, 9(3), pp. 125-135.
[8] Pouya Azarsa, Mahdi Hosseini, Seyed Amin Ahmadi and Prof. N.V. Ramana Rao, Enhanced
Seismic Resistance of Steel Buildings Using Viscous Fluid Dampers. International Journal of Civil
Engineering and Technology, 7(6), 2016, pp.90–105.
[9] Pall, A., and Pall, T. R. (2004), ‘Performance-based design using Pall friction dampers- an
economical design solution’, Proceeding of World Conference of Earthquake Engineering,
Vancouver, B.C.

More Related Content

What's hot

Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...IDES Editor
 
IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...
IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...
IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...IRJET Journal
 
Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...
Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...
Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...IRJET Journal
 
IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...
IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...
IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...IRJET Journal
 
Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...
Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...
Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...IRJET Journal
 
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...IRJET Journal
 
IRJET- Seismic Performance of Building using Accordion Metallic Damper
IRJET-  	  Seismic Performance of Building using Accordion Metallic DamperIRJET-  	  Seismic Performance of Building using Accordion Metallic Damper
IRJET- Seismic Performance of Building using Accordion Metallic DamperIRJET Journal
 
Simplified macro-modelling approach for infill masonry wall in-plane and out-...
Simplified macro-modelling approach for infill masonry wall in-plane and out-...Simplified macro-modelling approach for infill masonry wall in-plane and out-...
Simplified macro-modelling approach for infill masonry wall in-plane and out-...openseesdays
 
IRJET- Comparative Analysis of Tall Structure with and without Base Isola...
IRJET-  	  Comparative Analysis of Tall Structure with and without Base Isola...IRJET-  	  Comparative Analysis of Tall Structure with and without Base Isola...
IRJET- Comparative Analysis of Tall Structure with and without Base Isola...IRJET Journal
 
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...IRJET Journal
 
Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...
Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...
Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...IRJET Journal
 
IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...
IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...
IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...IRJET Journal
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Usage of N2 Method for the Performance Evaluation of Plan Asymmetric Structures
Usage of N2 Method for the Performance Evaluation of Plan Asymmetric StructuresUsage of N2 Method for the Performance Evaluation of Plan Asymmetric Structures
Usage of N2 Method for the Performance Evaluation of Plan Asymmetric StructuresIRJET Journal
 
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratiosModal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratiosIRJET Journal
 
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...IRJET Journal
 

What's hot (19)

Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
Study of Structural Behaviour of Gravity Dam with Various Features of Gallery...
 
20320140507009
2032014050700920320140507009
20320140507009
 
IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...
IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...
IRJET-Study on Behaviour of Retrofitted RC Beam-Column Exterior Joints with G...
 
Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...
Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...
Analytical Study on Flexural Behaviour of RCC Slabs with Concealed Beams usin...
 
IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...
IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...
IRJET-Analysis and Seismic Response Reduction of Building using Base Isolatio...
 
Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...
Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...
Effect of Soil Structure Interaction on Buildings with Stiffness Irregularity...
 
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
 
IRJET- Seismic Performance of Building using Accordion Metallic Damper
IRJET-  	  Seismic Performance of Building using Accordion Metallic DamperIRJET-  	  Seismic Performance of Building using Accordion Metallic Damper
IRJET- Seismic Performance of Building using Accordion Metallic Damper
 
Simplified macro-modelling approach for infill masonry wall in-plane and out-...
Simplified macro-modelling approach for infill masonry wall in-plane and out-...Simplified macro-modelling approach for infill masonry wall in-plane and out-...
Simplified macro-modelling approach for infill masonry wall in-plane and out-...
 
IRJET- Comparative Analysis of Tall Structure with and without Base Isola...
IRJET-  	  Comparative Analysis of Tall Structure with and without Base Isola...IRJET-  	  Comparative Analysis of Tall Structure with and without Base Isola...
IRJET- Comparative Analysis of Tall Structure with and without Base Isola...
 
P01254123131
P01254123131P01254123131
P01254123131
 
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
 
Cu35540546
Cu35540546Cu35540546
Cu35540546
 
Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...
Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...
Effect of Soil Structure Interaction on Buildings with Mass Irregularity unde...
 
IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...
IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...
IRJET- Seismic Analysis of Vertically Irregular RC Framed Structure using X- ...
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Usage of N2 Method for the Performance Evaluation of Plan Asymmetric Structures
Usage of N2 Method for the Performance Evaluation of Plan Asymmetric StructuresUsage of N2 Method for the Performance Evaluation of Plan Asymmetric Structures
Usage of N2 Method for the Performance Evaluation of Plan Asymmetric Structures
 
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratiosModal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
Modal analysis of multistorey rectangular buildings with 1:2:2.5 plan ratios
 
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
 

Similar to Ijciet 08 02_008

IRJET- Earthquake Resistant Design of Multistorey Building
IRJET-  	  Earthquake Resistant Design of Multistorey BuildingIRJET-  	  Earthquake Resistant Design of Multistorey Building
IRJET- Earthquake Resistant Design of Multistorey BuildingIRJET Journal
 
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous Damper
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous DamperSeismic Analysis of Reinforced Concrete Building Using Fluid Viscous Damper
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous DamperIRJET Journal
 
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...Effect of Positioning and Configuration of Shear Walls on Seismic Performance...
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...IRJET Journal
 
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisPerformance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisIJMER
 
Analyzing Utility of Component Elements of Outrigger System
Analyzing Utility of Component Elements of Outrigger System Analyzing Utility of Component Elements of Outrigger System
Analyzing Utility of Component Elements of Outrigger System IRJET Journal
 
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...IRJET Journal
 
IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...
IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...
IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...IRJET Journal
 
Dynamic Analysis of Soft Storey Frame with Isolators
Dynamic Analysis of Soft Storey Frame with IsolatorsDynamic Analysis of Soft Storey Frame with Isolators
Dynamic Analysis of Soft Storey Frame with IsolatorsIJMTST Journal
 
IRJET- Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...
IRJET-  	  Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...IRJET-  	  Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...
IRJET- Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...IRJET Journal
 
Push over analysis
Push over analysisPush over analysis
Push over analysisNupur Sharma
 
Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...
Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...
Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...IRJET Journal
 
IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...
IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...
IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...IRJET Journal
 
Seismic Response of Vertically Irregular Structure with Composite Columns
Seismic Response of Vertically Irregular Structure with Composite ColumnsSeismic Response of Vertically Irregular Structure with Composite Columns
Seismic Response of Vertically Irregular Structure with Composite ColumnsIRJET Journal
 
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...IRJET Journal
 
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...IRJET Journal
 
IRJET- Analysis of G+15 Building Different Seismic Zones of India
IRJET-  	  Analysis of G+15 Building Different Seismic Zones of IndiaIRJET-  	  Analysis of G+15 Building Different Seismic Zones of India
IRJET- Analysis of G+15 Building Different Seismic Zones of IndiaIRJET Journal
 
ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...
ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...
ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...IAEME Publication
 

Similar to Ijciet 08 02_008 (20)

IRJET- Earthquake Resistant Design of Multistorey Building
IRJET-  	  Earthquake Resistant Design of Multistorey BuildingIRJET-  	  Earthquake Resistant Design of Multistorey Building
IRJET- Earthquake Resistant Design of Multistorey Building
 
Final Ppt (18MTSE005 ).pptx
Final Ppt (18MTSE005 ).pptxFinal Ppt (18MTSE005 ).pptx
Final Ppt (18MTSE005 ).pptx
 
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous Damper
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous DamperSeismic Analysis of Reinforced Concrete Building Using Fluid Viscous Damper
Seismic Analysis of Reinforced Concrete Building Using Fluid Viscous Damper
 
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...Effect of Positioning and Configuration of Shear Walls on Seismic Performance...
Effect of Positioning and Configuration of Shear Walls on Seismic Performance...
 
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisPerformance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
 
Analyzing Utility of Component Elements of Outrigger System
Analyzing Utility of Component Elements of Outrigger System Analyzing Utility of Component Elements of Outrigger System
Analyzing Utility of Component Elements of Outrigger System
 
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
A COMPARATIVE STUDY ON DYNAMIC ANALYSIS OF MULTI- STORIED BUILDING (G+24) WIT...
 
IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...
IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...
IRJET- Performance Study of High Rise Building with Bracing and Diagrid Struc...
 
Dynamic Analysis of Soft Storey Frame with Isolators
Dynamic Analysis of Soft Storey Frame with IsolatorsDynamic Analysis of Soft Storey Frame with Isolators
Dynamic Analysis of Soft Storey Frame with Isolators
 
presentation]
presentation]presentation]
presentation]
 
IRJET- Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...
IRJET-  	  Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...IRJET-  	  Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...
IRJET- Effect of Pile Cap Thickness Variation on Load Carrying Capacity o...
 
Push over analysis
Push over analysisPush over analysis
Push over analysis
 
Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...
Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...
Comparison of Seismic Resistance of Moment Resisting RC Building using Shear ...
 
IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...
IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...
IRJET- Dynamic Analysis and Design of G+ 8 Storey RC Structure by Providing L...
 
Seismic Response of Vertically Irregular Structure with Composite Columns
Seismic Response of Vertically Irregular Structure with Composite ColumnsSeismic Response of Vertically Irregular Structure with Composite Columns
Seismic Response of Vertically Irregular Structure with Composite Columns
 
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
IRJET - Analysis of Flat Slab Structural System in Different Earthquake Zones...
 
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
IRJET- Comparative Seismic Evaluation of Response of RC Building with Shear W...
 
Ijciet 08 02_031
Ijciet 08 02_031Ijciet 08 02_031
Ijciet 08 02_031
 
IRJET- Analysis of G+15 Building Different Seismic Zones of India
IRJET-  	  Analysis of G+15 Building Different Seismic Zones of IndiaIRJET-  	  Analysis of G+15 Building Different Seismic Zones of India
IRJET- Analysis of G+15 Building Different Seismic Zones of India
 
ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...
ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...
ISEISMIC PERFORMANCE OF RC FRAMED BUILDINGS UNDER LINEAR DYNAMIC ANALYSISjcie...
 

More from IAEME Publication

IAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdfIAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdfIAEME Publication
 
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...IAEME Publication
 
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSA STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSIAEME Publication
 
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSBROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSIAEME Publication
 
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONSDETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONSIAEME Publication
 
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONSANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONSIAEME Publication
 
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINOVOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINOIAEME Publication
 
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...IAEME Publication
 
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMYVISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMYIAEME Publication
 
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...IAEME Publication
 
GANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEGANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEIAEME Publication
 
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...IAEME Publication
 
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...IAEME Publication
 
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...IAEME Publication
 
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...IAEME Publication
 
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...IAEME Publication
 
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...IAEME Publication
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...IAEME Publication
 
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...IAEME Publication
 
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENTA MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENTIAEME Publication
 

More from IAEME Publication (20)

IAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdfIAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdf
 
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
 
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSA STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
 
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSBROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
 
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONSDETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
 
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONSANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
 
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINOVOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
 
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
 
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMYVISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
 
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
 
GANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEGANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICE
 
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
 
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
 
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
 
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
 
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
 
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
 
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
 
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENTA MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
 

Recently uploaded

Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 

Recently uploaded (20)

Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 

Ijciet 08 02_008

  • 1. http://www.iaeme.com/IJCIET/index.asp 72 editor@iaeme.com International Journal of Civil Engineering and Technology (IJCIET) Volume 8, Issue 2, February 2017, pp. 72–88 Article ID: IJCIET_08_02_008 Available online at http://www.iaeme.com/IJCIET/issues.asp?JType=IJCIET&VType=8&IType=2 ISSN Print: 0976-6308 and ISSN Online: 0976-6316 © IAEME Publication Scopus Indexed SEISMIC RESPONSE OF UNSYMMETRIC BUILDING WITH OPTIMALLY PLACED FRICTION DAMPERS S. S. Sanghai Assistant Professor, Civil Engineering Department, G. H. Raisoni College of Engineering, Nagpur, India S. N. Khante Associate Professor, Applied Mechanics Department, Govt. College of Engineering, Amravati, India ABSTRACT Conventional methods of seismic rehabilitation with concrete shear walls or steel bracing are not considered suitable for some buildings as upgrades with these methods would have required expensive and time consuming foundation work. Supplemental damping in conjunction with appropriate stiffness offers an innovative and attractive solution for the seismic rehabilitation of such structures. This paper deals with the use of friction damper as a passive dissipative device in order to seismic retrofit of existing structures and discusses the optimal placement criteria. To fulfill this objective, six storey and ten storey L-shaped buildings have been modeled with five different damper location formats in SAP2000 subjected to El Centro and Utterkashi earthquake records. Non-Linear Modal Time History Method has been used for the analysis and base shear, joint displacement, member forces and hysteresis energy has been compared to find out most optimal damper location format. Key words: friction damper, non-linear modal time history analysis, optimization, slip load Cite this Article: S. S. Sanghai and S. N. Khante, Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers. International Journal of Civil Engineering and Technology, 8(2), 2017, pp. 72–88. http://www.iaeme.com/IJCIET/issues.asp?JType=IJCIET&VType=8&IType=2 1. INTRODUCTION Severe ground shaking induces lateral inertial forces on buildings, causing them to sway back and forth with amplitude proportional to the energy fed in. If a major portion of this energy can be consumed during building motion, the seismic response can be considerably improved. The manner in which this energy is consumed in the structure determines the level of damage. The use of bracing systems equipped with dissipative devices is relatively new technique for the earthquake protection of buildings that has been considered in several recent experimental and theoretical studies. In particular, the friction damping bracing system involving the device proposed by Pall and Marsh (1982) has been carefully analyzed, since its simplicity of construction and high dissipative capacity encourages application in practice. At present, the existing studies offer
  • 2. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 73 editor@iaeme.com sufficiently detailed information about the protection level, expressed in terms of energy absorption or reduction of maximum horizontal displacement. Friction damping devices dissipate energy by utilizing the mechanism of solid friction developed at the sliding surface, which is a relatively inexpensive and effective method for stable energy dissipation. As their hysteretic behaviors could be kept stable for cyclic loads and desirable slip loads are easily obtained by regulating normal forces acting perpendicularly to a friction surface, in addition to their simple energy dissipation mechanism and easy manufacturing, installation and maintenance (Pall and Marsh 1982). Filatrault and Cherry (1990) have proposed the design procedure of friction dampers that minimizes the sum of the displacement and dissipating energy by carrying out the parametric studies such as the structural fundamental period, frequency components of excitation load and the slip load of friction damper. Moreschi and Singh (2003) have determined the optimal slip load and the bracing stiffness by using the optimization technique such as genetic algorithm. Pujari and Bakre (2011) have studied the optimal placement of XPDs which provides more reduction in response compared with other schemes of placement of XPD considered in the study. Furthermore, the optimal placement of dampers is sensitive to the nature of excitation force, number of XPDs used and the modeling of XPD. Khante and Sanghai (2012) have studied optimal placement of friction damper using Non-Linear Time History Analysis on symmetric RCC framed building. In this paper, a general framework for optimal placement of passive energy dissipation devices in the form of friction dampers for seismic structural application has been formulated. The study has been done for unsymmetrical RCC framed building. 2. BUILDING DESCRIPTION The model of buildings are 6 storey and 10 storey reinforced concrete building having L shape in plan as shown in Fig.1. The building has four frames at 3m c/c in X and Y direction with 3.2m storey height and 1.2m plinth height as shown in Fig.1 and Fig.2. The beam and column are modeled as frame element while slab is modeled as thin shell element. The sizes of members are given in Table No.1. The friction dampers are placed along peripheral frames of building. The elevation of G+5 storey and G+9 storey structure with five different format of placement of dampers as shown in Fig. 2 and Fig. 3 respectively. Table 1 Sizes of members Storey G+5 G+9 Sizes of Beams 0.3m X 0.45m 0.3m X 0.45m Sizes of Columns 0.3m X 0.45m 0.3 m X 0.5m Thickness of Slab 125mm 125mm Figure 1 Plan of building
  • 3. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 74 editor@iaeme.com (1) (2) (3) (4) (5) Figure 2 Elevation of formats of G+5 building model (1) (2) (3) (4) (5) Figure 3 Elevation of formats of G+9 building model 3. PROPERTIES OF FRICTION DAMPER The slip load of the friction damper is the principal variable. Fig.4 shows that, if slip load is very low or very high, response is very high. This is because, if slip load is very low, friction damper will slip for small vibrations leading to minimum hysteresis energy and if slip load is very high friction damper will not slip and act as simple brace reducing hysteresis energy. The current slip load is decided by trial and error method. The appropriate selection of slip load leads to optimum response of structure. The friction dampers in single diagonal brace are modeled as damped braces having member stiffness equal to brace stiffness and nonlinear axial yielding equal to the slip load. The properties of friction damper used for modeling are given in Table No. 2.The link element named as Plastic (wen) is used to model friction damper.
  • 4. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 75 editor@iaeme.com Table 2 Properties of friction damper Storey G+5 G+9 Slip Load 300kN 500kN Brace section ISMB200 ISMB200 Stiffness of element 149883.99 149883.99 Yielding Load 300kN 500kN Post yield stiffness ratio 0.0001 0.0001 Yielding Exponent 10 10 Figure 4 Responses versus Slip Load (Avtar Pall, 2004) 4. METHOD OF ANALYSIS For the analysis of all five formats, Non-Linear Time History method has been used in SAP2000. To conduct time history analysis, the ground motion records used are El-Centro having peak ground acceleration of 0.313g and Utterkashi having peak ground acceleration of 0.252g as shown in Fig. 5 and Fig.6. Figure 5 El Centro ground motion record Figure 6 Utterkashi ground motion record
  • 5. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 76 editor@iaeme.com 5. OPTIMIZATION TECHNIQUE In this study, the friction dampers have been induced as diagonal braces in these structures with few fixed location formats. These location formats have been selected arbitrarily based on the previous study as well as with a view to keep the number of dampers used to minimum. Dampers are located between floor to floor diagonally as braces. The unconstrained optimization problem is now formulated as: Minimize ( ) = + (1) where, f (x) is the objective function to be minimized, and x is the vector of design variables. In the present case, the locations of a specified number of dampers in the structural system form the design variables. The objective function for the minimization problem is considered to be a linear combination of normalized maximum base shear Vb, and normalized maximum storey drift D. The factors Vbu and Du denote the maximum base shear and maximum storey drift in the structure without any supplemental dampers (Kokil and Shrikhande, 2007 6. RESULTS AND DISCUSSION Using SAP2000 the analysis were carried out. The comparison of results has been done to find out best optimal damper location format. The format (1) has no dampers and Format (5) has dampers at each storey, hence these two formats can’t be called as optimal location formats. While in location formats (2), (3) and (4) using same number of dampers different locations have been tried. Therefore best location format will be out of Format (2), (3) and (4). The modal time period and frequencies of mode shapes are most important factor to determine the dynamic characteristics of structure. For modal analysis, Ritz vector method has been selected for calculating time period and frequencies of mode shapes. Following table shows the modal time period and frequencies of first mode shape for different formats of friction dampers. Table 3 Values of time period and frequencies for G+5 storey FOR EL CENTRO FOR UTTERKASHI TIME PERIOD FREQUENCY TIME PERIOD FREQUENCY FORMAT (1) 0.80 1.25 0.80 1.25 FORMAT (2) 0.58 1.72 0.58 1.72 FORMAT (3) 0.63 1.60 0.63 1.60 FORMAT (4) 0.52 1.91 0.52 1.91 FORMAT (5) 0.45 2.23 0.45 2.23 Table 4 Values of time period and frequencies for G+9 storey According to the above values, the modal time period of damped structure is less when compared with undamped structure. This is due to increase of stiffness of damped structure by addition of braces. The envelopes of maximum values of acceleration, velocity and displacement in X direction of undamped and damped building are shown in Fig. 6, Fig. 10 and Fig. 14 for G+5 storey and Fig. 8, Fig. 12 and Fig. 16 for G+9 storey structures subjected to El Centro ground motion record while Fig. FOR EL CENTRO FOR UTTERKASHI TIME PERIOD FREQUENCY TIME PERIOD FREQUENCY FORMAT (1) 1.70 0.59 1.7 0.59 FORMAT (2) 1.27 0.79 1.27 0.79 FORMAT (3) 1.31 0.76 1.31 0.76 FORMAT (4) 1.19 0.84 1.19 0.84 FORMAT (5) 1.05 0.95 1.05 0.95
  • 6. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 77 editor@iaeme.com 7, Fig. 11 and Fig. 15 for G+5 storey and Fig. 9, Fig. 13 and Fig. 17 for G+9 storey structures subjected to Utterkashi ground motion record. Figure 6 Jt. acceleration in X-direction for G+5 storey Figure 7 Jt. acceleration in X-direction for G+5 storey Figure 8 Jt. acceleration in X-direction for G+9 storey 0 1 2 3 4 5 6 7 0 2 4 6 8 10 FLOOR ACCELERATION (m/s2) JT. ACCELERATION IN X-DIR FOR EL CENTRO FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) 0 1 2 3 4 5 6 7 0 2 4 6 8 FLOOR ACCELERATION (m/s2) JT. ACCELERATION IN X-DIR FOR UTTERKASHI FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) 0 2 4 6 8 10 12 0 1 2 3 4 5 6 7 FLOOR ACCELERATION (m/s2) JT. ACCELERATION IN X-DIR FOR EL CENTRO FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
  • 7. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 78 editor@iaeme.com Figure 9 Jt. acceleration in X-direction for G+9 storey Figure 10 Jt. velocity in X-direction for G+5 storey Figure 11 Jt. velocity in X-direction for G+5 storey 0 2 4 6 8 10 12 0 1 2 3 4 5 FLOOR ACCLERATION (m/s2) JT. ACCELERATION IN X-DIR FOR UTTERKASHI FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) 0 1 2 3 4 5 6 7 0 0.2 0.4 0.6 0.8 1 FLOOR VELOCITY (m/s) JT. VELOCITY IN X-DIR FOR EL CENTRO FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) 0 1 2 3 4 5 6 7 0 0.2 0.4 0.6 0.8 FLOOR VELOCITY (m/s) JT. VELOCITY IN X-DIR FOR UTTERKASHI FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
  • 8. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 79 editor@iaeme.com Figure 12 Jt. velocity in X-direction for G+9 storey Figure 13 Jt. velocity in X-direction for G+9 storey Figure 14 Jt. displacement in X-direction for G+5 storey 0 2 4 6 8 10 12 0 0.2 0.4 0.6 0.8 1 FLOOR VELOCITY (m/s) JT. VELOCITY IN X-DIR FOR EL CENTRO FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) 0 2 4 6 8 10 12 0 0.1 0.2 0.3 0.4 0.5 0.6 FLOOR VELOCITY (m/s) JT. VELOCITY IN X-DIR FOR UTTERKASHI FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) 0 1 2 3 4 5 6 7 0 20 40 60 80 100 120 FLOORS DISPLACEMENT (mm) JT. DISPLACEMENT IN X-DIR FOR EL CENTRO FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
  • 9. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 80 editor@iaeme.com Figure 15 Jt. Displacement in X-direction for G+5 storey Figure 16 Jt. Displacement in X-direction for G+9 storey Figure 17 Jt. Displacement in X-direction for G+9 storey From above figures, it can be seen that joint velocity and displacement in damped building in X- direction is reduced in comparison with undamped building. While joint acceleration reduces for G+5 storey and increses for G+9 storey structure. The maximum top storey reduction in joint acceleration is for Format (5) and minimum increase for Format (3), in joint velocity is for Format (4) and for Format 0 1 2 3 4 5 6 7 0 20 40 60 80 100 FLOORS DISPLACEMENT (mm) JT. DISPLACEMENT IN X-DIR FOR UTTERKASHI FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) 0 2 4 6 8 10 12 0 50 100 150 200 FLOORS DISPLACEMENT (mm) JT. DISPLACEMENT IN X-DIR FOR EL CENTRO FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) -2 0 2 4 6 8 10 12 0 20 40 60 80 100 120 FLOORS DISPLCEMENTS (mm) JT. DISPLACEMENT IN X-DIR FOR UTTERKASHI FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) Linear (FORMAT (3))
  • 10. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 81 editor@iaeme.com (4) and in joint displacement is for Format (5) and for Format (4) respectively for G+5 storey and G+9 storey structure subjected to El Centro while the maximum top storey reduction in joint acceleration is for Format (3) and for Format (4), in joint velocity is for Format (4) and for Format (3) and in joint displacement is for Format (5) and for Format (4) respectively for G+5 storey and G+9 storey structure subjected to Utterkashi. The reduction in acceleration, velocity and displacement of stories is due to increase of stiffness of structure. The maximum base shear in X-direction of undamped and damped building is shown in Fig.18 and Fig.19. Figure 18 Maximum Base shear in X-direction for G+5 storey Figure 19 Maximum Base shear in X-direction for G+9 storey Fig.18 and Fig.19 show that base shear is decreased in damped building as compared to undamped building. The maximum reduction is 22.93% for G+5 storey and 5.78% for G+9 storey structure in Format (4) subjected to El Centro ground motion record while 12.87% for G+5 storey and 14.19% for G+9 storey structure in Format (4) subjected to Utterkashi ground motion record . This reduction is due to addition of friction dampers which increases supplemental damping by 20-30%. The maximum axial forces and maximum bending moment in members are plotted for different formats as shown in Fig. 20 and Fig. 22 for G+5 storey and Fig. 21 and Fig. 23 for G+9 storey structure. 0 500 1000 1500 2000 2500 FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) BASESHEAR(kN) MAX. BASE SHEAR IN X-DIR EL CENTRO UTTERKASHI 0 500 1000 1500 2000 2500 3000 3500 FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) BASESHEAR(kN) MAX. BASE SHEAR IN X-DIR EL CENTRO UTTERKASHI
  • 11. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 82 editor@iaeme.com Figure 20 Maximum axial forces for G+5 storey Figure 21 Maximum axial forces for G+9 storey Figure 22 Maximum bending moment for G+5 storey 0 200 400 600 800 1000 1200 1400 FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) AXIALFORCE(kN) MAX. AXIAL FORCE EL CENTRO UTTERKASHI 0 500 1000 1500 2000 2500 3000 3500 FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) AXIALFORCE(kN) MAX. AXIAL FORCE EL CENTRO UTTERKASHI 0 50 100 150 200 250 300 350 400 450 500 FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) BENDINGMOMENT()kN.m) MAX.BENDING MOMENT EL CENTRO UTTERKASHI
  • 12. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 83 editor@iaeme.com Figure 23 Maximum bending moment for G+9 storey On comparing the maximum axial forces and maximum bending moments in members, it is observed that bending moment reduces for all models however axial force reduces for six storey building and increases for ten storey building with inclusion of damper. The earthquake forces acting on main structural member get redistributed due to addition of friction damper diagonally. This causes reduction in axial force and bending moment. It is observed that, in some cases axial force increases, because some dampers are observed to remain in non-slip mode. The reason behind it, is provision of excessive dampers and sometimes lower input acceleration. Thus they behave as bracing member. Because of this building becomes stiffer than other formats, hence axial force increases in this case. The step by step increase in hysteresis energy for different formats of friction dampers are as shown in Fig.24 and Fig.25 for G+5 storey and Fig.26 and Fig.27 for G+9 storey structure. Figure 24 Hysteresis Energy for G+5 storey 0 50 100 150 200 250 300 350 400 450 500 FORMAT(1) FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) BENDINGMOMENT(kN.m) MAX. BENDING MOMENT EL CENTRO UTTERKASHI -20 0 20 40 60 80 100 120 140 160 180 0 1000 2000 3000 4000 5000 ENERGY(kN-m) TIME STEPS HYSTERESIS ENERGY FOR EL CENTRO FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
  • 13. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 84 editor@iaeme.com Figure 25 Hysteresis Energy for G+5 storey Figure 26 Hysteresis Energy for G+9 storey Figure 27 Hysteresis Energy for G+9 storey From comparison of hysteresis energy, it can be seen that the maximum hysteresis energy is observed for format (4) in all cases. The more value of hysteresis energy means more amount input -50 0 50 100 150 200 250 0 1000 2000 3000 4000 5000 ENERGY(kN-m) TIME STEPS HYSTERESIS ENERGY FOR EL CENTRO FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) -5 0 5 10 15 20 25 0 500 1000 1500 2000 ENERGY(kN-m) TIME STEPS HYSTERESIS ENERGY FOR UTTERKASHI FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5) -10 0 10 20 30 40 50 60 70 80 90 0 500 1000 1500 2000 ENERGY(kN-m) TIME STEPS HYSTERISIS ENERGY FOR UTTERKASHI FORMAT(2) FORMAT(3) FORMAT(4) FORMAT(5)
  • 14. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 85 editor@iaeme.com energy is dissipated by friction dampers. From the figures it is clear that, by using more numbers of friction dampers does not always lead to more dissipation of input energy. Figure 28 Different energy component comparison for G+5 storey Figure 29 Different energy component comparison for G+5 storey Figure 30 Different energy component comparison for G+9 storey 0 50 100 150 200 250 300 350 400 FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5) ENERGY COMPONENT COMPARISON FOR EL CENTRO Input Energy Kinetic Energy Potential Energy Modal Damping Energy Link Hystretic Energy 0 20 40 60 80 100 120 140 160 180 FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5) ENERGY COMPONENT COMPARISON FOR UTTERKASHI Input Energy Kinetic Energy Potential Energy Modal Damping Energy Link Hystretic Energy 0 100 200 300 400 500 600 700 800 FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5) ENERGY COMPONENT COMPARISON FOR EL CENTRO Input Energy Kinetic Energy Potential Energy Modal Damping Energy Link Hysteretic Energy
  • 15. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 86 editor@iaeme.com Figure 31 Different energy component comparison for G+9 storey Fig. 28, Fig.29, Fig.30 and Fig.31 shows the different energy components for various location formats considered. The input energy depends upon work done on structure by force and acceleration and kinetic energy is function of mass and velocity while potential energy is function of elastic constant and displacement of structure. As force, mass and elastic constants of structure are same for all formats, energy components depend on acceleration, velocity and displacement of structure. In Format (1), link hysteretic energy is zero because of absence of friction damper. So, all the input energy has to be dissipated through modes so as to satisfy equation of motion. While in other formats, percentage energy dissipated through modes reduces while energy dissipated through hysteretic behaviour of friction damper increases. This reduction in percentage dissipation of input energy through modes and increase in percentage dissipation through link hysteretic behaviour depends upon location of friction damper. The percentage dissipation of input energy through hysteretic behavior is maximum for Format (4) in G+5 storey and G+9 storey building models. The value of function used for optimization is as shown in Fig.32 and Fig.33. Figure 32 Objective Function Value for G+5 storey 0 50 100 150 200 250 FORMAT (1) FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5) ENERGY COMPONENT COMPARISON FOR UTTERKASHI Input Energy Kinetic Energy Potential Energy Modal Damping Energy Link Hysteretic Energy 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5) FUNCTION VALUE EL CENTRO UTTERKASHI
  • 16. S. S. Sanghai and S. N. Khante http://www.iaeme.com/IJCIET/index.asp 87 editor@iaeme.com Figure 33 Objective Function Value for G+9 storey Fig. 32 and Fig.33 shows that the value objective function is minimum for format (4) for both G+5 storey and G+9 storey structure. Also, the base shear, axial force, bending moment is minimum in format (4). Hence, it can be said that with the given no. of dampers format (4) is optimum location format. 7. CONCLUSION The supplementary energy dissipation devices are known to be effective in reducing the earthquake induced response of structural systems. Optimal placement of these protective systems is of practical interest. The main objective of this study, therefore, has been to find the most optimal configuration of friction damper which gives maximum utilization of damper and minimal damage to unsymmetrical buildings when subjected to real earthquake ground motions. The results showed that the format (4) is the optimal format because of well distributed stiffness while in other cases alternate stories are soft and stiff. Hence it is clear that the damper placement influences significantly the structural response. Also, the study investigates that use of larger number of dampers do not always lead to the best benefit. REFERENCES [1] Pall, A. S., and Marsh C. (1982), ‘Response of Friction Damped Braced Frames’, Journal of the Structural Division, American Society of Civil Engineers, 108(ST6). [2] Filiatrault, A., and Cherry, S. (1990), ‘Seismic Design Spectra for Friction Damped Structures’, Journal of Structural Engineering, American Society of Civil Engineers, 116, pp. 1334-1355. [3] Moreschi, L.M., and Singh, M.P. (2003), ‘Design of Yielding and Friction Dampers for Optimal Seismic Performance’, Earthquake Engineering Structural Dynamics, 32, pp. 1291-1311. [4] Pujari, N. N., and Bakre, S. V. (2011), ‘Optimum placement of X-plate dampers for seismic response control of multistoried buildings’ International Journal of Earth Science and Engineering, 4(6), pp. 481-485. [5] Manveer Singh and Khushpreet Singh, An Efficient Analysis of Linear and Non- Linear Model using Various Regression Level for Fluid Dampers. International Journal of Civil Engineering and Technology, 7(5), 2016, pp.111–123. [6] Khante, S. N., and Sanghai, S. S. (2012), ‘Optimal placement of friction dampers for seismic response control of symmetric RCC framed building’, Proceeding of NCETETA-2012, pp. 209-213. 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 FORMAT (2) FORMAT (3) FORMAT (4) FORMAT (5) FUNCTION VALUE EL CENTRO UTTERKASHI
  • 17. Seismic Response of Unsymmetric Building with Optimally Placed Friction Dampers http://www.iaeme.com/IJCIET/index.asp 88 editor@iaeme.com [7] Kokil, A.S., and Shrikhande, M. (2007), ‘Optimal Placement of Supplemental Dampers in Seismic Design of Structures’, JSEE Fall, 9(3), pp. 125-135. [8] Pouya Azarsa, Mahdi Hosseini, Seyed Amin Ahmadi and Prof. N.V. Ramana Rao, Enhanced Seismic Resistance of Steel Buildings Using Viscous Fluid Dampers. International Journal of Civil Engineering and Technology, 7(6), 2016, pp.90–105. [9] Pall, A., and Pall, T. R. (2004), ‘Performance-based design using Pall friction dampers- an economical design solution’, Proceeding of World Conference of Earthquake Engineering, Vancouver, B.C.