7545 104 final sections as proposed
1. Scale 1:25
0 1000 2000500 1500 2500
1.8m head height
For ground floor make up see notes on 7545/102
Existing foundations depth
to be checked on site for
possible underpinning.
15mm Glasrock Board
sealed at joints
Air vent to appliance
from outside
Support block
Concrete lintels
Collars
LOW LEVEL BOXING
SVP
LOWLEVELBOXING
SVP
UP
UP
UP
Hatch indicates
minimum 1800mm
head height
Existing insulation removed.
New 100mm mineral insulation to be
installed prior to screed being laid
to act as a barrier.
Outer brick leaf removed,
new 50x50mm treated softwood stud.
DPM to meet with existing
Ensure that existing brick leaf is taken
back to level below new floor and
cavity is back filled with concrete
prior to new floor being laid.
0
Scale 1:10
200 800400 600 1000
THIS DRAWING IS COPYRIGHT AND MUST
NOT BE REPRODUCED WITHOUT PRIOR
CONSENT. FIGURED DIMENSIONS TO BE
USED ONLY. DO NOT SCALE. SITE
DIMENSIONS TO BE CHECKED / VERIFIED
BEFORE WORK IS COMMENCED.
NOTES:
As proposed - Section A-A
As proposed - Section B-B
'A''A'
'B'
'B'
As proposed - Section A-A detail
(1:10 @ A1)
Domestic project - Weyhill
Two storey extension
Building control drawings