TELEHOUSE CENTER SITE TOUR
TELEHOUSE Global Data Centers Europe Pac Rim Americas Telehouse Europe (Carrier Neutral) KDDI NW+Colocation Telehouse Amer...
TELEHOUSE CENTER <ul><li>Major Features: </li></ul><ul><li>TELEHOUSE custom designed building. </li></ul><ul><li>162,000 s...
Teleport II Teleport I Leading Securities Firm’s Data Center TELEHOUSE Center 7 Teleport Drive, SI, NY 10004 Satellite Far...
Carrier Hotel Cable Head Garden City Shirley Customer Carrier POP USA JPN Asia C/US, J/US Cables Cable Head Europe Manasqu...
<ul><li>Major Features: </li></ul><ul><li>Established in 1985 by the Port Authority of NY/NJ as the first TELEPORT in the ...
Dedicated  Data Center <ul><li>“ WARM OR HOT” Site. </li></ul><ul><li>Work area for Technical & Admin Staff. </li></ul><ul...
FOYER LOBBY VIP RECP PRESENTATION EXEC EXEC S TH Office TELEHOUSE Center First Floor Diagram Loading dock/ Freight   Eleva...
TELEHOUSE Center Second Floor Diagram L U N C H F O Y E R R O O F S E L T E L E H O U S E C E N T E R S E C O N D F L O O ...
TELEHOUSE Center Third Floor Diagram Diaster Recovery Personnel Suites Room 3010   6,000 usf  Available 2 nd  Half ‘08 L O...
<ul><li>Security: </li></ul><ul><li>24x7 on-site TELEHOUSE Security </li></ul><ul><li>Key card access throughout. </li></u...
<ul><li>Loading Dock: </li></ul><ul><li>2 main docks, plus 1 sub-dock. </li></ul><ul><li>24x7 customer access, at no cost....
<ul><li>Customer Assistance Center (CAC): </li></ul><ul><li>Control center for all TELEHOUSE America sites. </li></ul><ul>...
<ul><li>Data Signal Room (DSR): </li></ul><ul><li>AboveNet, AT&T, Verizon/MCI, KDDI, OCG, Time Warner and others are avail...
<ul><li>Battery Room: </li></ul><ul><li>6 battery strings for back-up. </li></ul><ul><li>Capable of handle full center pow...
<ul><li>Generator Room: </li></ul><ul><li>4 diesel-powered generators 1,250 KVA each, 3 are operational with 1 in stand-by...
<ul><li>Switchgear Room  (Commercial Power) : </li></ul><ul><li>Contains transformers for commercial power with upgrade un...
Power Grid System TELEHOUSE GOETHALS SUB STATION GOWANUS (Brooklyn) COGEN – LINDEN(NJ) PSE&G – LINDEN(NJ) FRESH KILLS SUB ...
<ul><li>Chiller (A/C) Room: </li></ul><ul><li>Chillers originally supported high cooling requirement of mainframe data cen...
10 TELEHOUSE CENTER
<ul><li>Data Center & Colocation  Spaces: </li></ul><ul><li>Fire Protection: </li></ul><ul><ul><li>Halon in restricted are...
<ul><li>Colocation : </li></ul><ul><li>Shared colocation space </li></ul><ul><li>Open Space (A),  Site H & J.   </li></ul>...
Upcoming SlideShare
Loading in …5
×

Zaah Teleport

950 views

Published on

Published in: Business, Technology
  • Be the first to comment

  • Be the first to like this

Zaah Teleport

  1. 1. TELEHOUSE CENTER SITE TOUR
  2. 2. TELEHOUSE Global Data Centers Europe Pac Rim Americas Telehouse Europe (Carrier Neutral) KDDI NW+Colocation Telehouse America (Carrier Neutral) London(3) Hamburg Frankfurt Paris(2) Seoul Beijing Hong Kong Shanghai Taipei Japan(27) Bangkok Singapore Sydney Sao Paulo New York(3) Los Angeles Munich Site (sf) IX London-E 170,000 LINX, LONAP London-W 90,000 LINX, Xchang London-M 14,000 - Paris-J 11,000 PARIX Paris-V 140,000 Free IX Frankfurt 40,000 - Hamburg 27,000 Xchange Munich 40,000 - Site (sf) IX NY-THC 162,000 NYIIX NY-25B 87,000 NYIIX NY-BFC 15,500 - LA 11,000 LAIIX Site (sf) IX Beijing * Resale (NAP) Shanghai * STIX Hong Kong 25,000 (HKIX) Taipei * TWIX Seoul 30,000 (KTIX,DIX) Bangkok * IIG Singapore * (STIX) Sydney * -
  3. 3. TELEHOUSE CENTER <ul><li>Major Features: </li></ul><ul><li>TELEHOUSE custom designed building. </li></ul><ul><li>162,000 square feet of space. </li></ul><ul><li>24x7 on-site TELEHOUSE security, </li></ul><ul><li>N+1 redundant power system, commercial power capacity: (10,000 KVA). </li></ul><ul><li>Utilities located in the behind the main data center space. </li></ul><ul><li>Multiple telecom providers available: </li></ul><ul><li>AboveNet, AT&T, Verizon/MCI, KDDI, </li></ul><ul><li>RCN (Con Edison), OCG, Time Warner, ISPNet, Digital Providers, Voxel. </li></ul><ul><li>Water, Smoke & Fire detection. </li></ul><ul><li>Redundant AC units </li></ul><ul><li>SAS 70 Type 2 Certified </li></ul>TELEHOUSE Center Front Entrance to TELEHOUSE Center
  4. 4. Teleport II Teleport I Leading Securities Firm’s Data Center TELEHOUSE Center 7 Teleport Drive, SI, NY 10004 Satellite Farm Ariel view of the Teleport South Ave Main Gate Entrance
  5. 5. Carrier Hotel Cable Head Garden City Shirley Customer Carrier POP USA JPN Asia C/US, J/US Cables Cable Head Europe Manasquan & Tuckerton, NJ TAT Cables TELEHOUSE Teleport AT&T MH MH South St. Victory Blvd. Physically Diverse Access TELEHOUSE CENTER Advantage 1. Network Diversity (1) Manhattan bypass route for Global network (2) 100% physically diverse access to TH Center 2. Low cost Gig-E local connectivity 3. Schedule - BMI/OCG (Jan.06), Con Edison (March,06) - AboveNet (2Q, 06) - TWC. TWT NJ NY Manhattan New Jersey Telehouse Telehouse Center Existing Fiber Ring Carrier Hotel Newark Airport Carrier Hotel Carrier Hotel Carrier Hotel
  6. 6. <ul><li>Major Features: </li></ul><ul><li>Established in 1985 by the Port Authority of NY/NJ as the first TELEPORT in the world. </li></ul><ul><li>100-acre office park. </li></ul><ul><li>12 miles downwind from Manhattan. </li></ul><ul><li>24x7 Front Gate Security provided by Port Authority of NY/NJ Security </li></ul><ul><li>requiring 2 picture IDs and access list; </li></ul><ul><li>National Guard presence as directed by </li></ul><ul><li>NY State Governor when Home Land </li></ul><ul><li>Security Threat escalates. </li></ul><ul><li>Redundant power feeds from both Con Edison (NY). </li></ul><ul><li>Redundant Voice/Data Carrier entrance </li></ul><ul><li>into the office park. </li></ul><ul><li>Fenced with Infrared Perimeter Security </li></ul>Front Entrance to the Teleport Teleport Security Gates
  7. 7. Dedicated Data Center <ul><li>“ WARM OR HOT” Site. </li></ul><ul><li>Work area for Technical & Admin Staff. </li></ul><ul><li>Data Backup & Security. </li></ul><ul><li>Dedicated Telecom Distribution closet per suite. </li></ul>
  8. 8. FOYER LOBBY VIP RECP PRESENTATION EXEC EXEC S TH Office TELEHOUSE Center First Floor Diagram Loading dock/ Freight Elevator DSR Generators Batteries UPS 8 Commercial Power Colocation Space CAC 1 Security AC Chiller Room Main Entrance 7 Teleport Drive UPS Expansion TH Office TH Office 11 10 7 9 6 5 4 3 2
  9. 9. TELEHOUSE Center Second Floor Diagram L U N C H F O Y E R R O O F S E L T E L E H O U S E C E N T E R S E C O N D F L O O R C O N F . R M 2 1 0 ( 9 2 6 s f ) C O N F . R M 2 1 1 ( 8 5 8 s f ) C O N F 2 1 2 - A ( 3 0 5 s f ) C O N F 2 1 3 ( 6 6 0 s f ) 2 , 1 7 2 u s f 6 , 9 4 2 u s f 7 , 6 3 5 u s f 1 0 , 1 9 2 u s f 2 , 1 0 1 u s f J I H P K C O N F 2 1 2 - B ( 3 0 5 s f ) 2 0 0 2 2 0 0 3 2 0 0 7 2 0 1 1 2 0 1 3 M a r c h 2 0 0 4 A v a i l a b l e Diaster Recovery Personnel Suites Site J 3,500 usf Colocation Space Site H - 10,192 usf Colocation Space Room 2011 8,642 usf Available Room 2013 2,000usf Available
  10. 10. TELEHOUSE Center Third Floor Diagram Diaster Recovery Personnel Suites Room 3010 6,000 usf Available 2 nd Half ‘08 L O B B Y U T I L I T Y T E L E H O U S E C E N T E R T H I R D F L O O R 2 , 8 9 5 u s f M a r c h 2 0 0 4 R o o m 3 0 9 ( 5 7 4 s f ) C N F 3 1 0 ( 6 1 6 s f ) C N F 3 1 1 - A ( 6 0 0 s f ) 4 , 4 1 3 u s f C N F 3 1 1 - B ( 2 7 0 s f ) C N F 3 1 2 ( 2 5 7 s f ) E L N C N F 3 1 3 ( 2 0 9 s f ) 3 0 0 2 3 0 0 4 3 0 1 0 3 0 1 3 3 0 0 5 3 0 0 7 A v a i l a b l e A v a i l a b l e
  11. 11. <ul><li>Security: </li></ul><ul><li>24x7 on-site TELEHOUSE Security </li></ul><ul><li>Key card access throughout. </li></ul><ul><li>Closed circuit television video surveillance – internal & external. </li></ul><ul><li>Infrared perimeter & internal motion detectors. </li></ul><ul><li>Photo ID (2) required for access to site. </li></ul><ul><li>24x7 customer access (access lists). </li></ul>TELEHOUSE CENTER TELEHOUSE Center Security Desk 1
  12. 12. <ul><li>Loading Dock: </li></ul><ul><li>2 main docks, plus 1 sub-dock. </li></ul><ul><li>24x7 customer access, at no cost. </li></ul><ul><li>Docks are raised, eliminating need for ramps. </li></ul><ul><li>All work monitored by TELEHOUSE security personnel. </li></ul><ul><li>Large freight elevator near docks. </li></ul>TELEHOUSE CENTER TELEHOUSE Center Loading Dock 2
  13. 13. <ul><li>Customer Assistance Center (CAC): </li></ul><ul><li>Control center for all TELEHOUSE America sites. </li></ul><ul><li>24x7 Communications Technicians and Infrastructure Engineers on duty. </li></ul><ul><li>All customer data and activities are handled via TIMS (TELEHOUSE Information Management System) & accessed by you via the Internet. </li></ul><ul><li>Electric Power Quality and Battery monitors in place (7x24) </li></ul>TELEHOUSE CENTER TELEHOUSE Center CAC 3
  14. 14. <ul><li>Data Signal Room (DSR): </li></ul><ul><li>AboveNet, AT&T, Verizon/MCI, KDDI, OCG, Time Warner and others are available to provide telecom service. </li></ul><ul><li>All circuit installations monitored by TELEHOUSE. </li></ul><ul><li>Circuits are run from DSR to customer telecom closets throughout the site. </li></ul><ul><li>Redundant entrance for carriers (South & Victory Blvd) </li></ul>TELEHOUSE CENTER TELEHOUSE Center DSR 4
  15. 15. <ul><li>Battery Room: </li></ul><ul><li>6 battery strings for back-up. </li></ul><ul><li>Capable of handle full center power load for up to 15 minutes. </li></ul><ul><li>Batteries designed to immediately provide power in case of commercial power loss, until generators start (8-12 seconds). </li></ul>TELEHOUSE Center Battery Room <ul><li>UPS Room: </li></ul><ul><li>4 rotary UPSs, 600 KVA each, 3 are operational with 1 in stand-by mode. </li></ul><ul><li>Additional UPS upgrade underway. </li></ul><ul><li>Even out power source to prevent spikes and brown-outs. </li></ul><ul><li>In the event of commercial power loss, UPSs continue to generate power since rotary components spin at such a high rate of speed. </li></ul>TELEHOUSE Center UPS Room 5 6
  16. 16. <ul><li>Generator Room: </li></ul><ul><li>4 diesel-powered generators 1,250 KVA each, 3 are operational with 1 in stand-by mode. Additional generator upgrade underway. </li></ul><ul><li>2-day on-site underground supply of fuel, at max power, with multiple vendors on call. </li></ul><ul><li>Each generator is kept warm with crankcase heaters to avoid cold starts. </li></ul><ul><li>Generator operation is tested monthly, and once per quarter on full power load </li></ul><ul><li>(Feb, June, Sept & Dec – 2006) </li></ul><ul><li>Member of NYISO & NERA </li></ul><ul><li>NY Independent System Operators </li></ul><ul><li>No. American Electric Reliability Assoc. </li></ul>TELEHOUSE CENTER TELEHOUSE Center Generator Room 7
  17. 17. <ul><li>Switchgear Room (Commercial Power) : </li></ul><ul><li>Contains transformers for commercial power with upgrade underway. </li></ul><ul><li>Main power grid has Con Edison (NY) and PSE&G (NJ) feeds . </li></ul><ul><li>Multiple feeds from local substations. </li></ul><ul><li>Power distributed to 3 system set-ups: </li></ul><ul><ul><li>Critical (customers, emergency, etc.) </li></ul></ul><ul><ul><li>Essential (office lighting, A/C, etc.) </li></ul></ul><ul><ul><li>Non-essential (corridor outlets, etc.) </li></ul></ul><ul><li>If outage occurs, power is directed to Critical and Essential systems first. </li></ul>TELEHOUSE CENTER TELEHOUSE Center Switchgear Room 8
  18. 18. Power Grid System TELEHOUSE GOETHALS SUB STATION GOWANUS (Brooklyn) COGEN – LINDEN(NJ) PSE&G – LINDEN(NJ) FRESH KILLS SUB STATION TELEPORT 345KV Greenpoint (Brooklyn) ARTHER KILL GENERATING PLANT
  19. 19. <ul><li>Chiller (A/C) Room: </li></ul><ul><li>Chillers originally supported high cooling requirement of mainframe data centers. Less cooling capacity needed for equipment today so Chillers have been adapted accordingly. </li></ul><ul><li>4 water chillers, 3 are operational with 1 in stand-by mode with upgrade underway. </li></ul><ul><li>2-day on-site underground supply of condenser water, in the event of municipal water loss. </li></ul>TELEHOUSE CENTER TELEHOUSE Center Chiller Room 9
  20. 20. 10 TELEHOUSE CENTER
  21. 21. <ul><li>Data Center & Colocation Spaces: </li></ul><ul><li>Fire Protection: </li></ul><ul><ul><li>Halon in restricted areas. </li></ul></ul><ul><ul><li>Pre-action sprinklers. </li></ul></ul><ul><ul><li>Ceiling smoke detectors measure heat & smoke particle density before releasing water. </li></ul></ul><ul><ul><li>Centrally monitored by CAC. </li></ul></ul><ul><li>Raised Floor: </li></ul><ul><ul><li>2 feet of raised space. </li></ul></ul><ul><ul><li>Separate cable trays for communications and power cables to avoid interference. </li></ul></ul>TELEHOUSE CENTER TELEHOUSE Center Fire Suppression TELEHOUSE Center Raised Floor Halon Smoke Detector Pre-Action Sprinklers
  22. 22. <ul><li>Colocation : </li></ul><ul><li>Shared colocation space </li></ul><ul><li>Open Space (A), Site H & J. </li></ul><ul><li>Caged space available. </li></ul><ul><li>Access to space from main building corridor. </li></ul><ul><li>Equipment moved using maintenance corridor. </li></ul>10 TELEHOUSE Center Colocation 11

×