SlideShare a Scribd company logo
1 of 26
Part 3
Special Systems
Referenced Publications
All these modules are based upon the NFPA 70 and
the NFPA 72 publications unless otherwise dictated.
Agenda
 Part 1 Fire Alarm System Fundamentals
 Part 2 Initiating Devices
Protected Premises Fire Alarm Systems
Part 3 Circuits & Pathways
Inspection Testing & Maintenance
Notification Appliances
Special Functions
Agenda
NFPA 72
 Chapter 21 Emergency Control Functions &
Interfaces
 Chapter 23 Protected Premises Fire Alarm
Systems
 Chapter 24 Emergency Communication
Systems
Chapter 26 Supervising Station Alarm Systems
Chapter 27 Public Emergency Alarm Reporting
Systems
Chapter 29 Single and Multiple-Station Alarms
and Household Fire Alarm
Chapters 22 / 25 / 28 Reserved
Supervising Station Alarm
Systems
Chapter 26
26.1 Application
26.2 General
26.3 Alarm System for Central Station Service
26.4 Proprietary Supervising Station Systems
26.5 Remote Supervising Station Alarm Systems
26.6 Communication Methods for Supervising
Station Alarm Systems
Supervising Station Alarm
Systems
26.1.1* Where a protected premises fire alarm system
has its signals sent to a supervising station, the entire
system shall become a supervising station alarm
system
26.2.3.2 Where the supervising station provides the
required testing and where service changes covered
by 26.2.3.1 occur, the supervising station shall test all
zones, points, and signals from each affected property
in accordance with the requirements of Chapter 14
26.2.4 Qualification of Supervising Station Operators.
Supervising station operators shall be qualified in
accordance with the requirements of 10.4.4
Supervising Station Alarm
Systems
26.3.3 Contract Requirements. The central station
service elements shall be provided under contract to a
subscriber by …
26.3.4.2 The documentation shall include, at a minimum,
the following information:
(1) Name of the prime contractor involved with the ongoing Code
compliance of the central station service
(2)* Full description of the alarm system as installed
(3) Issue and expiration dates of the documentation
(4) Name, address, and contact information of the organization
issuing the document
(5) Identification of the authority(ies) having jurisdiction for the
central station service installation
Supervising Station Alarm
Systems
26.3.5.1 The central station building or that portion of a
building occupied by a central station shall conform to
the construction, fire protection, restricted access,
emergency lighting, and power facilities requirements
of the latest edition of ANSI/UL 827
26.3.5.2 Subsidiary station buildings or those portions of
buildings occupied by subsidiary stations shall
conform to the construction, fire protection, restricted
access, emergency lighting, and power facilities
requirements of the latest edition of ANSI/UL 827
Supervising Station Alarm
Systems
26.3.5.2.2 The subsidiary facility shall be inspected at
least monthly by central station personnel for the
purpose of verifying the operation of all supervised
equipment, …
26.3.5.2.3 In the event of the failure of equipment at the
subsidiary station or the communications channel to
the central station, a backup shall be operational
within 90 seconds
26.3.6.1.3 Computer-aided alarm and supervisory signal–
processing hardware and software shall be listed for
the purpose
Supervising Station Alarm
Systems
26.3.6.1.6.1 The use of a universal emergency number,
such as the 911 public safety answering point, shall
not meet the intent of this Code for the principal
means of retransmission.
26.3.6.1.6.4 The retransmission signal and the time and
date of retransmission shall be recorded at the central
station
26.3.6.2.1 The central station shall have not less than two
qualified operators on duty at the central station at all
times
Supervising Station Alarm
Systems
26.3.6.2.2 Operation and supervision shall be the primary
functions of the operators, and no other interest or
activity shall take precedence over the protective
service
26.3.7.1.1 Alarm signals initiated by manual fire alarm
boxes, automatic fire detectors, waterflow from the
automatic sprinkler system, or actuation of other fire
suppression system(s) or equipment shall be treated
as fire alarms
Supervising Station Alarm
Systems
26.3.7.1.2 The central station shall perform the following
actions:
(1)* Immediately retransmit the alarm to the communications
center.
(2) Dispatch a runner or technician to the protected premises to
arrive within 2 hours after receipt of a signal if equipment
needs to be manually reset …
(3) Immediately notify the subscriber.
(4) Provide notice to the subscriber or authority having
jurisdiction, or both, if required.
Supervising Station Alarm
Systems
26.3.7.2.1 Upon failure to receive a guard’s tour
supervisory signal within a 15-minute maximum grace
period, the central station shall perform the following
actions:
(1) Communicate without unreasonable delay with personnel at
the protected premises
(2) Dispatch a runner to the protected premises to arrive within
30 minutes of the delinquency if communications cannot be
established
(3) Report all delinquencies to the subscriber or authority having
jurisdiction, or both, if required
Supervising Station Alarm
Systems
26.3.7.3* Supervisory Signals. Upon receipt of a
supervisory signal from a sprinkler system, other fire
suppression system(s), or other equipment, the central
station shall perform the following actions:
(1)* Communicate immediately with the persons designated by
the subscriber
(2) Dispatch a runner or maintenance person to arrive within 2
hours to investigate
Exception: …
(3) Notify the authority having jurisdiction when sprinkler systems
or … have been wholly or partially out of service for 8 hours
(4) When service has been restored, provide notice
Supervising Station Alarm
Systems
26.3.7.4 Trouble Signals. Upon receipt of trouble signals
or other signals pertaining solely to matters of
equipment maintenance of the alarm systems, the
central station shall perform the following actions:
(1)* Communicate immediately with persons designated by the
subscriber
(2) Dispatch personnel to arrive within 4 hours to initiate
maintenance, if necessary
(3) When the interruption is more than 8 hours, provide notice to
the subscriber and the fire
26.3.7.5.1 All test signals received shall be recorded to
indicate date, time, and type
Supervising Station Alarm
Systems
26.3.8.1 Complete records of all signals received shall be
retained for at least 1 year.
26.3.8.2 Testing and maintenance records shall be
retained as required by 14.6.3
Supervising Station Alarm
Systems
26.4.2.1 Proprietary supervising stations shall be
operated by trained, competent personnel in constant
attendance who are responsible to the owner of the
protected property.
26.4.2.2 The protected property shall be either a
contiguous property or noncontiguous properties
under one ownership.
26.4.2.3 If a protected premises control unit is integral to
or co-located with the supervising station equipment
Supervising Station Alarm
Systems
26.4.3.1* The proprietary supervising station shall be
located in either of the following:
(1) Fire-resistive, detached building
(2) A fire-resistive room protected from the hazardous parts of the
building
26.4.3.4.1 The proprietary supervising station shall be
provided with an automatic emergency lighting system
26.4.3.5 If 25 or more protected buildings or premises are
connected to a subsidiary station, both of the following
shall be provided at the subsidiary station:
(1) Automatic means for receiving and recording signals under
emergency staffing conditions
(2) A telephone
Supervising Station Alarm
Systems
26.4.4.2.2 All signals required to be received by the
proprietary supervising station that show a change in
status shall be automatically and permanently
recorded, including time and date of occurrence
26.4.4.6.1 The proprietary supervising station shall have
at least two qualified operators on duty at all times.
One of the two operators shall be permitted to be a
runner
26.4.4.6.2 When the runner is not in attendance at the
proprietary supervising station, the runner shall
establish two-way communications with the station at
intervals not exceeding 15 minutes
Supervising Station Alarm
Systems
26.4.5.1.1 All communications and transmission channels
between the proprietary supervising station and the
protected premises control unit shall be operated
manually or automatically once every 24 hours to
verify operation
26.4.5.2.1 All operator controls at the proprietary
supervising station(s) designated by the authority
having jurisdiction shall be operated at each change
of shift
Supervising Station Alarm
Systems
26.4.5.3 Retransmission. Indication of a fire shall be
promptly retransmitted to the communications center
or other locations accepted by the authority having
jurisdiction, indicating the building or group of
buildings from which the alarm has been received
26.4.6.1 Complete records of all signals received shall be
retained for at least 1 year.
26.4.6.2 Testing and maintenance records shall be
retained as required by 14.6.3
Supervising Station Alarm
Systems
26.5.1.3 Remote supervising station physical facilities,
equipment, operating personnel, response,
retransmission, signals, reports, and testing shall
comply with the minimum requirements of Section
26.5
26.5.3.2* Trouble signals shall be permitted to be
received at an approved location that has personnel
on duty who are trained to recognize the type of signal
received and to take prescribed action. The location
shall be permitted to be other than that at which alarm
and supervisory signals are received
Supervising Station Alarm
Systems
26.5.4.5.1 The remote supervising station shall have not
less than two qualified operators on duty at the remote
supervising station at all times to ensure disposition of
signals in accordance with the requirements of 26.5.5.
26.5.4.5.2 Duties pertaining to other than operation of the
remote supervising station receiving and transmitting
equipment shall be permitted, subject to the approval
Supervising Station Alarm
Systems
26.5.5.2 Upon receipt of an alarm, a supervisory, or a
trouble signal by the remote supervising Station … the
operator on duty shall be responsible for notifying the
owner
26.5.5.3 All operator controls at the remote supervising
station shall be operated at the beginning of each shift
or change in personnel
26.5.6.2 Testing and maintenance records shall be
retained as required in 14.6.3
Supervising Station Alarm
Systems
26.5.6.3 Records shall be permitted to be created by
manual means.
26.6.2.2* Alternate Methods. Nothing in Chapter 26 shall
be interpreted as prohibiting the use of listed
equipment using alternate communications methods
that provide a level of reliability and supervision
consistent with the requirements of Chapter 10 and
the intended level of protection.
26.6.2.4.2 Radio receiving equipment shall be installed in
compliance with NFPA 70
Supervising Station Alarm
Systems
26.6.3.2.1.1* Public Switched Network. A DACT shall
be connected to the public switched telephone
network upstream of any private telephone system at
the protected premises
(A)* A system employing a DACT shall employ one
telephone line. In addition, one of the following:
(1) A second telephone line (number)
(2) A cellular telephone connection
(3) A one-way radio system
(4) A one-way private radio alarm system
(5) A private microwave radio system
(6) A two-way RF multiplex system
(7) A transmission means complying with 26.6.3.1

More Related Content

What's hot

Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]
Jennifer Kleinhenz
 
Water meter secure start guide
Water meter secure start guideWater meter secure start guide
Water meter secure start guide
Domotica daVinci
 

What's hot (20)

Fire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basicsFire alarm 2_a_initiation basics
Fire alarm 2_a_initiation basics
 
Fire basics 1-1-fundamentals
Fire basics 1-1-fundamentalsFire basics 1-1-fundamentals
Fire basics 1-1-fundamentals
 
Demystifying Fault Isolators
Demystifying Fault IsolatorsDemystifying Fault Isolators
Demystifying Fault Isolators
 
Back to Basics
Back to BasicsBack to Basics
Back to Basics
 
Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]Fire alarm system_nec_september[1]
Fire alarm system_nec_september[1]
 
SenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbookSenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbook
 
SenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbookSenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbook
 
Electronic units and systems for armored vehicles
Electronic units and systems for armored vehiclesElectronic units and systems for armored vehicles
Electronic units and systems for armored vehicles
 
S123 b30u
S123 b30uS123 b30u
S123 b30u
 
Water meter secure start guide
Water meter secure start guideWater meter secure start guide
Water meter secure start guide
 
GSM BASED FIRE ALARM SYSTEM
GSM BASED FIRE ALARM SYSTEMGSM BASED FIRE ALARM SYSTEM
GSM BASED FIRE ALARM SYSTEM
 
SenseTek Alarmline lwm 1 datasheet
SenseTek Alarmline lwm 1 datasheetSenseTek Alarmline lwm 1 datasheet
SenseTek Alarmline lwm 1 datasheet
 
Light level and gas monitoring system
Light level and gas monitoring systemLight level and gas monitoring system
Light level and gas monitoring system
 
CINT alarm systems
CINT alarm systemsCINT alarm systems
CINT alarm systems
 
GSM Based SMS fire alert system
GSM Based SMS fire alert systemGSM Based SMS fire alert system
GSM Based SMS fire alert system
 
wiDom Multi Sensor Room Controller MSRC Manual EN
wiDom Multi Sensor Room Controller MSRC Manual ENwiDom Multi Sensor Room Controller MSRC Manual EN
wiDom Multi Sensor Room Controller MSRC Manual EN
 
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSMFIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
FIRE DETECTION AND ELETRICAL POWER ON/OFF CONTROL IN HOME/INDUSTRY USING GSM
 
Manual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - PhilioManual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - Philio
 
Fire control panel - Cheetah xi features
Fire control panel - Cheetah xi featuresFire control panel - Cheetah xi features
Fire control panel - Cheetah xi features
 
Grid stds
Grid stdsGrid stds
Grid stds
 

Viewers also liked

01 Mid-term Assignment - Christmas Land Project_khawar_v3
01 Mid-term Assignment - Christmas Land Project_khawar_v301 Mid-term Assignment - Christmas Land Project_khawar_v3
01 Mid-term Assignment - Christmas Land Project_khawar_v3
Reza Khawar
 
Nathalie Nasser_Curriculum Vitae
Nathalie Nasser_Curriculum VitaeNathalie Nasser_Curriculum Vitae
Nathalie Nasser_Curriculum Vitae
Nathalie Nasser
 

Viewers also liked (20)

Board Comunicação Integrada
Board Comunicação IntegradaBoard Comunicação Integrada
Board Comunicação Integrada
 
Mediat2
Mediat2Mediat2
Mediat2
 
01 Mid-term Assignment - Christmas Land Project_khawar_v3
01 Mid-term Assignment - Christmas Land Project_khawar_v301 Mid-term Assignment - Christmas Land Project_khawar_v3
01 Mid-term Assignment - Christmas Land Project_khawar_v3
 
Using Animation in Education
Using Animation in EducationUsing Animation in Education
Using Animation in Education
 
Fis 2
Fis 2Fis 2
Fis 2
 
Cuaderno de trabajo: EXPERIENCIAS DE FE Y CUIDO EN LAS MIGRACIONES FORZADAS
Cuaderno de trabajo: EXPERIENCIAS DE FE Y CUIDO EN LAS MIGRACIONES FORZADASCuaderno de trabajo: EXPERIENCIAS DE FE Y CUIDO EN LAS MIGRACIONES FORZADAS
Cuaderno de trabajo: EXPERIENCIAS DE FE Y CUIDO EN LAS MIGRACIONES FORZADAS
 
Kiran H K 17-06-2016
Kiran H K 17-06-2016Kiran H K 17-06-2016
Kiran H K 17-06-2016
 
Vol6
Vol6Vol6
Vol6
 
Body language presentation
Body language presentationBody language presentation
Body language presentation
 
Pm0017 project quality management
Pm0017 project quality managementPm0017 project quality management
Pm0017 project quality management
 
Projektverzögerungen - Welche Verteidigungsstrategien gibt es gegen Verzugver...
Projektverzögerungen - Welche Verteidigungsstrategien gibt es gegen Verzugver...Projektverzögerungen - Welche Verteidigungsstrategien gibt es gegen Verzugver...
Projektverzögerungen - Welche Verteidigungsstrategien gibt es gegen Verzugver...
 
Mk0018 international marketing
Mk0018 international marketingMk0018 international marketing
Mk0018 international marketing
 
Under ground dams design
Under ground dams designUnder ground dams design
Under ground dams design
 
Construction companies in qatar
Construction companies in qatarConstruction companies in qatar
Construction companies in qatar
 
Luyen viet tieng thai
Luyen viet tieng thaiLuyen viet tieng thai
Luyen viet tieng thai
 
Mf0011 mergers & acquisitions
Mf0011 mergers & acquisitionsMf0011 mergers & acquisitions
Mf0011 mergers & acquisitions
 
Me4Map presentation at Universidad Carlos III of Madrid
Me4Map presentation at Universidad Carlos III of MadridMe4Map presentation at Universidad Carlos III of Madrid
Me4Map presentation at Universidad Carlos III of Madrid
 
A2 Media Studies Advanced Portfolio Production Diary
A2 Media Studies Advanced Portfolio Production DiaryA2 Media Studies Advanced Portfolio Production Diary
A2 Media Studies Advanced Portfolio Production Diary
 
Ambar lópez etapas_administración
Ambar lópez etapas_administraciónAmbar lópez etapas_administración
Ambar lópez etapas_administración
 
Nathalie Nasser_Curriculum Vitae
Nathalie Nasser_Curriculum VitaeNathalie Nasser_Curriculum Vitae
Nathalie Nasser_Curriculum Vitae
 

Similar to Fire alarm 3-d-supervising_station_alarm_system

California Firecodes
California FirecodesCalifornia Firecodes
California Firecodes
malcolmfd
 
Codigos y perifericos rep 2001
Codigos y perifericos rep 2001Codigos y perifericos rep 2001
Codigos y perifericos rep 2001
Jesus Ciau
 

Similar to Fire alarm 3-d-supervising_station_alarm_system (20)

California Firecodes
California FirecodesCalifornia Firecodes
California Firecodes
 
Water Detection System for Air Conditional&Mechanical Ventilation Installation
Water Detection System for Air Conditional&Mechanical Ventilation InstallationWater Detection System for Air Conditional&Mechanical Ventilation Installation
Water Detection System for Air Conditional&Mechanical Ventilation Installation
 
Automated Fault Analysis - IVPower for Transmission System Operators and Dist...
Automated Fault Analysis - IVPower for Transmission System Operators and Dist...Automated Fault Analysis - IVPower for Transmission System Operators and Dist...
Automated Fault Analysis - IVPower for Transmission System Operators and Dist...
 
FireAlarmSystemOperationalBasics (1).pdf
FireAlarmSystemOperationalBasics (1).pdfFireAlarmSystemOperationalBasics (1).pdf
FireAlarmSystemOperationalBasics (1).pdf
 
FIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdf
 
Nfpa72 emergingcommsystemsorlando2010
Nfpa72 emergingcommsystemsorlando2010Nfpa72 emergingcommsystemsorlando2010
Nfpa72 emergingcommsystemsorlando2010
 
Fire alarm checklist
Fire alarm checklistFire alarm checklist
Fire alarm checklist
 
Material Requisition for 2" Autonomous Robotic Fire Suppression System for We...
Material Requisition for 2" Autonomous Robotic Fire Suppression System for We...Material Requisition for 2" Autonomous Robotic Fire Suppression System for We...
Material Requisition for 2" Autonomous Robotic Fire Suppression System for We...
 
Lecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdfLecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdf
 
Em latest
Em latestEm latest
Em latest
 
Cctv guide
Cctv guideCctv guide
Cctv guide
 
Navgard bnwas presentation
Navgard bnwas presentationNavgard bnwas presentation
Navgard bnwas presentation
 
Control room ( Advance Services )
Control room ( Advance Services ) Control room ( Advance Services )
Control room ( Advance Services )
 
Fire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, ApplicationsFire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, Applications
 
Fundamentals of Automation Technology 20EE43P C-20 Lab Manual SCADA.pdf
Fundamentals of Automation Technology 20EE43P C-20  Lab Manual SCADA.pdfFundamentals of Automation Technology 20EE43P C-20  Lab Manual SCADA.pdf
Fundamentals of Automation Technology 20EE43P C-20 Lab Manual SCADA.pdf
 
Safety rules 2014
Safety rules 2014Safety rules 2014
Safety rules 2014
 
System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279
 
Fire and Life Safety: Integration: Building Automation Systems and Fire/Life ...
Fire and Life Safety: Integration: Building Automation Systems and Fire/Life ...Fire and Life Safety: Integration: Building Automation Systems and Fire/Life ...
Fire and Life Safety: Integration: Building Automation Systems and Fire/Life ...
 
2-03.pdf
2-03.pdf2-03.pdf
2-03.pdf
 
Codigos y perifericos rep 2001
Codigos y perifericos rep 2001Codigos y perifericos rep 2001
Codigos y perifericos rep 2001
 

More from grantlerc

More from grantlerc (20)

Fire alarm 2_f_manual supervisory
Fire alarm 2_f_manual supervisoryFire alarm 2_f_manual supervisory
Fire alarm 2_f_manual supervisory
 
Fire alarm 2_e_combination
Fire alarm 2_e_combinationFire alarm 2_e_combination
Fire alarm 2_e_combination
 
Fire alarm 2_d_radiant energy detectors
Fire alarm 2_d_radiant energy detectorsFire alarm 2_d_radiant energy detectors
Fire alarm 2_d_radiant energy detectors
 
Fire alarm 2_c_smoke detectors
Fire alarm 2_c_smoke detectorsFire alarm 2_c_smoke detectors
Fire alarm 2_c_smoke detectors
 
Fire alarm 2_b_heat detectors
Fire alarm 2_b_heat detectorsFire alarm 2_b_heat detectors
Fire alarm 2_b_heat detectors
 
Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11
 
Fiber optics 2-7
Fiber optics 2-7Fiber optics 2-7
Fiber optics 2-7
 
Fiber optics 2-6
Fiber optics 2-6Fiber optics 2-6
Fiber optics 2-6
 
Fiber optics 2-5
Fiber optics 2-5Fiber optics 2-5
Fiber optics 2-5
 
Fiber optics 2-4
Fiber optics 2-4Fiber optics 2-4
Fiber optics 2-4
 
Fiber optics 2-3
Fiber optics 2-3Fiber optics 2-3
Fiber optics 2-3
 
Fiber optics 2-2
Fiber optics 2-2Fiber optics 2-2
Fiber optics 2-2
 
Fiber optics 2-1
Fiber optics 2-1Fiber optics 2-1
Fiber optics 2-1
 
Burglar alarm basics-1
Burglar alarm basics-1Burglar alarm basics-1
Burglar alarm basics-1
 
Access control basics-9
Access control basics-9Access control basics-9
Access control basics-9
 
Access control basics-8
Access control basics-8Access control basics-8
Access control basics-8
 
Access control basics-6
Access control basics-6Access control basics-6
Access control basics-6
 
Access control basics-7
Access control basics-7Access control basics-7
Access control basics-7
 
Access control basics-5
Access control basics-5Access control basics-5
Access control basics-5
 
Access control basics-4
Access control basics-4Access control basics-4
Access control basics-4
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
Health
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
 

Recently uploaded (20)

Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Rums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdfRums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdf
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 

Fire alarm 3-d-supervising_station_alarm_system

  • 2. Referenced Publications All these modules are based upon the NFPA 70 and the NFPA 72 publications unless otherwise dictated.
  • 3. Agenda  Part 1 Fire Alarm System Fundamentals  Part 2 Initiating Devices Protected Premises Fire Alarm Systems Part 3 Circuits & Pathways Inspection Testing & Maintenance Notification Appliances Special Functions
  • 4. Agenda NFPA 72  Chapter 21 Emergency Control Functions & Interfaces  Chapter 23 Protected Premises Fire Alarm Systems  Chapter 24 Emergency Communication Systems Chapter 26 Supervising Station Alarm Systems Chapter 27 Public Emergency Alarm Reporting Systems Chapter 29 Single and Multiple-Station Alarms and Household Fire Alarm Chapters 22 / 25 / 28 Reserved
  • 5. Supervising Station Alarm Systems Chapter 26 26.1 Application 26.2 General 26.3 Alarm System for Central Station Service 26.4 Proprietary Supervising Station Systems 26.5 Remote Supervising Station Alarm Systems 26.6 Communication Methods for Supervising Station Alarm Systems
  • 6. Supervising Station Alarm Systems 26.1.1* Where a protected premises fire alarm system has its signals sent to a supervising station, the entire system shall become a supervising station alarm system 26.2.3.2 Where the supervising station provides the required testing and where service changes covered by 26.2.3.1 occur, the supervising station shall test all zones, points, and signals from each affected property in accordance with the requirements of Chapter 14 26.2.4 Qualification of Supervising Station Operators. Supervising station operators shall be qualified in accordance with the requirements of 10.4.4
  • 7. Supervising Station Alarm Systems 26.3.3 Contract Requirements. The central station service elements shall be provided under contract to a subscriber by … 26.3.4.2 The documentation shall include, at a minimum, the following information: (1) Name of the prime contractor involved with the ongoing Code compliance of the central station service (2)* Full description of the alarm system as installed (3) Issue and expiration dates of the documentation (4) Name, address, and contact information of the organization issuing the document (5) Identification of the authority(ies) having jurisdiction for the central station service installation
  • 8. Supervising Station Alarm Systems 26.3.5.1 The central station building or that portion of a building occupied by a central station shall conform to the construction, fire protection, restricted access, emergency lighting, and power facilities requirements of the latest edition of ANSI/UL 827 26.3.5.2 Subsidiary station buildings or those portions of buildings occupied by subsidiary stations shall conform to the construction, fire protection, restricted access, emergency lighting, and power facilities requirements of the latest edition of ANSI/UL 827
  • 9. Supervising Station Alarm Systems 26.3.5.2.2 The subsidiary facility shall be inspected at least monthly by central station personnel for the purpose of verifying the operation of all supervised equipment, … 26.3.5.2.3 In the event of the failure of equipment at the subsidiary station or the communications channel to the central station, a backup shall be operational within 90 seconds 26.3.6.1.3 Computer-aided alarm and supervisory signal– processing hardware and software shall be listed for the purpose
  • 10. Supervising Station Alarm Systems 26.3.6.1.6.1 The use of a universal emergency number, such as the 911 public safety answering point, shall not meet the intent of this Code for the principal means of retransmission. 26.3.6.1.6.4 The retransmission signal and the time and date of retransmission shall be recorded at the central station 26.3.6.2.1 The central station shall have not less than two qualified operators on duty at the central station at all times
  • 11. Supervising Station Alarm Systems 26.3.6.2.2 Operation and supervision shall be the primary functions of the operators, and no other interest or activity shall take precedence over the protective service 26.3.7.1.1 Alarm signals initiated by manual fire alarm boxes, automatic fire detectors, waterflow from the automatic sprinkler system, or actuation of other fire suppression system(s) or equipment shall be treated as fire alarms
  • 12. Supervising Station Alarm Systems 26.3.7.1.2 The central station shall perform the following actions: (1)* Immediately retransmit the alarm to the communications center. (2) Dispatch a runner or technician to the protected premises to arrive within 2 hours after receipt of a signal if equipment needs to be manually reset … (3) Immediately notify the subscriber. (4) Provide notice to the subscriber or authority having jurisdiction, or both, if required.
  • 13. Supervising Station Alarm Systems 26.3.7.2.1 Upon failure to receive a guard’s tour supervisory signal within a 15-minute maximum grace period, the central station shall perform the following actions: (1) Communicate without unreasonable delay with personnel at the protected premises (2) Dispatch a runner to the protected premises to arrive within 30 minutes of the delinquency if communications cannot be established (3) Report all delinquencies to the subscriber or authority having jurisdiction, or both, if required
  • 14. Supervising Station Alarm Systems 26.3.7.3* Supervisory Signals. Upon receipt of a supervisory signal from a sprinkler system, other fire suppression system(s), or other equipment, the central station shall perform the following actions: (1)* Communicate immediately with the persons designated by the subscriber (2) Dispatch a runner or maintenance person to arrive within 2 hours to investigate Exception: … (3) Notify the authority having jurisdiction when sprinkler systems or … have been wholly or partially out of service for 8 hours (4) When service has been restored, provide notice
  • 15. Supervising Station Alarm Systems 26.3.7.4 Trouble Signals. Upon receipt of trouble signals or other signals pertaining solely to matters of equipment maintenance of the alarm systems, the central station shall perform the following actions: (1)* Communicate immediately with persons designated by the subscriber (2) Dispatch personnel to arrive within 4 hours to initiate maintenance, if necessary (3) When the interruption is more than 8 hours, provide notice to the subscriber and the fire 26.3.7.5.1 All test signals received shall be recorded to indicate date, time, and type
  • 16. Supervising Station Alarm Systems 26.3.8.1 Complete records of all signals received shall be retained for at least 1 year. 26.3.8.2 Testing and maintenance records shall be retained as required by 14.6.3
  • 17. Supervising Station Alarm Systems 26.4.2.1 Proprietary supervising stations shall be operated by trained, competent personnel in constant attendance who are responsible to the owner of the protected property. 26.4.2.2 The protected property shall be either a contiguous property or noncontiguous properties under one ownership. 26.4.2.3 If a protected premises control unit is integral to or co-located with the supervising station equipment
  • 18. Supervising Station Alarm Systems 26.4.3.1* The proprietary supervising station shall be located in either of the following: (1) Fire-resistive, detached building (2) A fire-resistive room protected from the hazardous parts of the building 26.4.3.4.1 The proprietary supervising station shall be provided with an automatic emergency lighting system 26.4.3.5 If 25 or more protected buildings or premises are connected to a subsidiary station, both of the following shall be provided at the subsidiary station: (1) Automatic means for receiving and recording signals under emergency staffing conditions (2) A telephone
  • 19. Supervising Station Alarm Systems 26.4.4.2.2 All signals required to be received by the proprietary supervising station that show a change in status shall be automatically and permanently recorded, including time and date of occurrence 26.4.4.6.1 The proprietary supervising station shall have at least two qualified operators on duty at all times. One of the two operators shall be permitted to be a runner 26.4.4.6.2 When the runner is not in attendance at the proprietary supervising station, the runner shall establish two-way communications with the station at intervals not exceeding 15 minutes
  • 20. Supervising Station Alarm Systems 26.4.5.1.1 All communications and transmission channels between the proprietary supervising station and the protected premises control unit shall be operated manually or automatically once every 24 hours to verify operation 26.4.5.2.1 All operator controls at the proprietary supervising station(s) designated by the authority having jurisdiction shall be operated at each change of shift
  • 21. Supervising Station Alarm Systems 26.4.5.3 Retransmission. Indication of a fire shall be promptly retransmitted to the communications center or other locations accepted by the authority having jurisdiction, indicating the building or group of buildings from which the alarm has been received 26.4.6.1 Complete records of all signals received shall be retained for at least 1 year. 26.4.6.2 Testing and maintenance records shall be retained as required by 14.6.3
  • 22. Supervising Station Alarm Systems 26.5.1.3 Remote supervising station physical facilities, equipment, operating personnel, response, retransmission, signals, reports, and testing shall comply with the minimum requirements of Section 26.5 26.5.3.2* Trouble signals shall be permitted to be received at an approved location that has personnel on duty who are trained to recognize the type of signal received and to take prescribed action. The location shall be permitted to be other than that at which alarm and supervisory signals are received
  • 23. Supervising Station Alarm Systems 26.5.4.5.1 The remote supervising station shall have not less than two qualified operators on duty at the remote supervising station at all times to ensure disposition of signals in accordance with the requirements of 26.5.5. 26.5.4.5.2 Duties pertaining to other than operation of the remote supervising station receiving and transmitting equipment shall be permitted, subject to the approval
  • 24. Supervising Station Alarm Systems 26.5.5.2 Upon receipt of an alarm, a supervisory, or a trouble signal by the remote supervising Station … the operator on duty shall be responsible for notifying the owner 26.5.5.3 All operator controls at the remote supervising station shall be operated at the beginning of each shift or change in personnel 26.5.6.2 Testing and maintenance records shall be retained as required in 14.6.3
  • 25. Supervising Station Alarm Systems 26.5.6.3 Records shall be permitted to be created by manual means. 26.6.2.2* Alternate Methods. Nothing in Chapter 26 shall be interpreted as prohibiting the use of listed equipment using alternate communications methods that provide a level of reliability and supervision consistent with the requirements of Chapter 10 and the intended level of protection. 26.6.2.4.2 Radio receiving equipment shall be installed in compliance with NFPA 70
  • 26. Supervising Station Alarm Systems 26.6.3.2.1.1* Public Switched Network. A DACT shall be connected to the public switched telephone network upstream of any private telephone system at the protected premises (A)* A system employing a DACT shall employ one telephone line. In addition, one of the following: (1) A second telephone line (number) (2) A cellular telephone connection (3) A one-way radio system (4) A one-way private radio alarm system (5) A private microwave radio system (6) A two-way RF multiplex system (7) A transmission means complying with 26.6.3.1