1. LWM-1 Controller
Alarmline Analogue Linear Heat Detection
▍ Monitors Alarmline Analogue sensor cables
▍ Provides fixed temperature and rate of rise alarms
▍ Easy installation and configuration
▍ Adjustable to sensitivity classes A1, A2, B and C as
well as custom settings
▍ Volt free outputs for alarms and fault conditions
▍ VdS approval based on EN54-5: 2000*
*Restrictions on sensor cable length and sensor cable type
apply.
The LWM-1 Controller is an integral part of the
Alarmline Analogue Linear Heat Detection system. The
controller monitors the Alarmline Analogue sensor
cable and reports changes in temperature by
permanent supervision of the sensor cable resistance.
Configuration of the Alarmline Analogue Linear Heat
Detection system is provided through a number of
switch settings within the LWM-1 controller allowing
setting of alarm trip settings, system sensitivity etc.
Dual alarm functionality is provided with fixed
temperature alarm settings as well as rate of rise alarm
settings providing system flexibility.
Interfacing the LWM-1 controller to the main fire alarm
system is made simple by the provision of Volt Free
Changeover contacts for Alarm and Fault conditions.
Internal push buttons enable alarm and fault conditions
to be simulated confirming correct operation of the
system by operating the alarm and fault test switches
together an LED test will be perfomed. An additional
internal push button provides the ability to reset alarm
and fault conditions providing the conditions have been
cleared.
A monitored input is provided in the unit allowing a
remote reset facility. Connection of a key switch or volt
free switched output to the input allows the unit to be
reset without removing the cover. Unit can only be reset
once the alarm or fault condition has been removed.
The controller is provided in a compact ABS enclosure
rated IP65. A number of IP65 plastic cable glands are
provided pre-fitted to the unit.
LWM-1 has been approved by VdS to European
standard EN54-5: 2000. To comply with this approval the
maximum sensor cable length is limited to 300m,
although the maximum sensor cable length that can be
connected to the unit is 1,000m.
The LWM-1 controller is compatible with the following
Alarmline Analogue sensor cables:
K82017 Sensor cable - Standard blue
K82021 Sensor cable – Nylon coated
K82078 Sensor cable – Bronze braided*
K98166 Sensor cable – Stainless steel braid over Nylon
*Bronze braided sensor cable is not covered under the VdS
approval.
In conjunction with suitable safety barriers the LWM-1
can provide an intrinsically safe detection system for
hazardous areas
For any further information please contact your sales
representative
2. LWM-1 Controller
Alarmline Analogue Control Unit
SPECIFICATION
Supply Voltage 10-30 VDC
Current consumption
(At 24 VDC)
<150mA
Enclosure material ABS
Colour Light grey
Size (mm) 200W x 120H x 80D
Weight 0.5Kg
Operating temperature
range
-20
o
C to 50
o
C
Cable glands 1 x M12 cable gland
1 x M16 cable gland
1 x M20 cable gland
3 x M16 entry holes fitted
with blanking caps
Maximum sensor cable
length
1,000m (to comply to EN54-
5 limited to 300m)
Outputs 3 x volt free relay outputs
rated 2A @ 30VDC for:
Max Alarm
Diff Alarm
Fault
Inputs 1 x Monitored input
Internal pushbuttons 3 x Momentary push
buttons for:
Alarm test
Fault test
Reset
Display LEDs Power - Green
Alarm Diff - Red
Alarm Max. - Red
Fault - Amber
Ordering information
Part No. Description
53836-K248 LWM-1 control unit
Kidde Airsense operates a continuous programme of product development. The right is therefore reserved to modify any specification
without prior notice and Kidde Airsense should be contacted to ensure the current issue of all technical data sheets are used.
Abberdaan 162 │1046 AB │ Amsterdam
T: +31(0)20 6131611 │ F: +31(0)20 6132212
www.sensetek.nl info@sensetek.nl
Iss. 2 Ref no. LHD00001/0614