Server Power and Performance Evaluation
in High-Temperature Environments
Overview and Background
Expanding the ambient-temperature operating range for IT equipment (ITE) can yield significant savings in capital
and operating expenses related to cooling infrastructure.
Existing standards and guidelines can provide an appropriate framework for evaluating performance, reliability,
and other factors while operating close to the prescribed limits of ambient temperature ranges. This paper describes
the results of a study in which under certain load conditions an Intel®
Xeon®
processor-based system designed
for a Class A2 environment1
as defined by the American Society of Heating, Refrigerating, and Air-Conditioning
Engineers (ASHRAE) can be adapted to a Class A4 environment1
or to a 3.1E environment as defined by the European
Telecommunications Standards Institute (ETSI).
The study, conducted by Microsoft and Intel, shows how a server can be characterized to determine its capability based
on ambient temperature and performance while ensuring that power and thermal constraints can be maintained. It
also summarizes other issues to be considered in the context of operation at the extremes of the environmental range
specified for a given system.
Creating server systems that operate at higher-than-usual ambient temperatures can help initiate a trend away from
conventional chiller-cooled data centers to free-air-cooled data centers. The further system design improvements
discussed here target the elimination of water used for adiabatic cooling by using only the surrounding outdoor
ambient air for cooling, thereby lowering facility complexity and total cost of ownership (TCO).
The results of this study are not necessarily relevant to all environments, and it also does not address reliability
issues associated with operating outside the Class A2 environment.
Intel Corporation: K. Govindaraju, Workloads/Performance Architect; Robin Steinbrecher, Platform Thermal Architect; Sandeep Ahuja, CPU Thermal
Architect; Eyran Eylon, Technology Development Manager; Jay Kyathsandra, Product Marketing
Microsoft Corporation: Dileep Bhandarkar, Chief Architect, Global Foundation Services; Kushagra Vaid, General Manager, Hardware Engineering;
Mark Shaw, Director, Hardware Engineering; Sriram Sankar, Hardware Engineer
WHITE PAPER
Intel®
Xeon®
Processors with Intel®
Node Manager
Microsoft Windows Server®
Data Center Cooling and Power Management
Server Design for High-
Temperature Operation
The use of free-air-cooled data centers
can result in exposure to a wider range
of inlet temperatures to the ITE, which
is typically designed based upon a
maximum inlet temperature of 35° C
(95° F). While Microsoft has shown
that free-air-cooled data centers work
well in certain climates, such as that
of Dublin, Ireland,2
few populated
places in the world stay below this
temperature year round. This white
paper demonstrates how a well-designed
server can support temperature
excursions to as high as 45° C (113°
F) based upon meeting target use
conditions for a specific application.
One approach to operating at
higher temperatures is to improve
an air-cooled server design through
the use of enhanced heat sinks and
increased airflow. While improving
design for higher efficiency is often
the right choice, sizing ITE for full
performance at 45° C may result in
lower overall efficiency by requiring
a larger data center footprint and
provisioning power that is only used
during the hottest portion of the year
due to the increase in airflow and
power requirements for the servers.
If the extreme temperatures occur for
only a few hours, it is reasonable to
advocate trading off a small amount
of performance at the hottest time
of the year to achieve efficiency
the remainder of the year. This
approach is also likely to maintain
the server purchase cost, by avoiding
the increased cost of server cooling
components that support continuous
operation at high temperatures.
While operation above 35° C in an
economized data center needs to
be supported, these temperature
excursions occur for only a few
hours during the year, even in high-
temperature climates, as shown in
Figure 1.2
0 5 10 15 20 25 30 35 40 45
4500
4000
3500
3000
2500
2000
1500
1000
500
0
NumberofHours
Ambient Temperature (°C)
Tropical Climate Humid Northern Desert
Climate Data - Average Hours at a Given Temperature
In many climates, the temperature
goes above 35° C for only a few hours
in an average year; desert climates
experience the most, at 67 hours
per year (0.8 percent of the time).
Systems that can operate at 45° C
are able to handle 50-year extremes
in temperature. Note that temperatures
in tropical climates are nearly always
between 22° C and 33° C.
Hours
over 35° C
2
5
67
Tropical
Humid
Northern
Desert
Hours
over 40° C
0
0
3
Average
Maximum
36° C
36° C
41° C
50 year
Extreme
37° C
41° C
43° C
Figure 1. Low incidence of temperature
excursions above 35° C.3
Table of Contents
Overview and Background .  .  .  .  .  .  .  .  .  .  . 1
Server Design for
High-Temperature Operation .  .  .  .  .  .  .  .  . 2
	 Performance Requirement Based
on a Specific Benchmark .  .  .  .  .  .  .  .  .  .  .  . 4
	Provisioning for Power
and Server Quantity .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4
	 Recipe to Support Usage Model .  .  .  .  .  .  . 5
Test Environment and Protocol .  .  .  .  .  .  . 6
Results  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6
Conclusion  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
Acknowledgements .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
2
Server Power and Performance Evaluation in High-Temperature Environments
To support this usage model, it is
necessary to understand the relevant
environmental classes to ensure
alignment with IT manufacturer
design targets and warranties. In
2011, ASHRAE defined two new
classes—A3 and A4,1
as shown in
Figure 2—to set expectations for
data centers operating with a high
degree of economization and the
ITE designed for them. The ranges
of both temperature and humidity
widened significantly, creating the
opportunity for reductions in both
capital and operating expenditure
depending upon climate.
ASHRAE provides guidance1
on
evaluating the reliability of ITE in an
individual data center based on the
time spent at various environmental
conditions. By evaluating a data
center’s time-weighted temperature
throughout the period of interest, one
can derive the expected multiplier
to the baseline failure rate of ITE in
the data center. However, ASHRAE
does not recommend operating
at high temperature, and the ITE
manufacturer’s warranty may not
support it either.
ETSI has set an environmental
standard that includes operation up
to 45° C for limited time periods,
illustrated by the data shown in
Figure 2. This standard applies to
telecommunications equipment, as
opposed to the focus of the ASHRAE
guidelines on ITE in general. The
ETSI standard does provide one
model for designing ITE but does
not define the performance required
under these conditions. In any case,
an ITE manufacturer may find it
valuable to align future equipment
with one of these environments to
enable wide-ranging acceptance of its
product, and the ETSI specification
provides a model with respect to time
spent in state.
0 5 10 15 20
20%
10%
25
0
5
10
15
20
25
90%
80%
70%
60%
50%
40%
30%
30 35 40 45
25
20
15
10
5
0
Dry Bulb Temperature - °C
W
etBulbTem
perature-°C
Realtive Humidity
DewPointTemperature-°C
These environmental envelopes pertain
to air entering the IT equipment.
Condition at SEA LEVEL
A3 A4
A2
A1
0 10 20 30 40
Values outside this field have a probability of occurence of less than
10% (see IEC 6072-3-0)
Exceptional climate limits
Normal climatic limits: Values outside these limits have a probability
of occurence of less than 1%
NOTE: Exceptional conditions may occur following the failure of the temperature controlling system.
This is described as 3.1E in the tables, but it should be noted that there is no separate class 3.1E.
50
50
40
30
20
10
0
-10
-20
60 70 80 90 100
25
20
1.5
1
Relative Air Humidity - %
AirTemperature-°C
AbsoluteHumidityg/m3
90%
9%
1%
Normal Conditions
Exceptional Conditions
Figure 2. American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) classes and the
European Telecommunications Standards Institute (ETSI) specification.
3
Server Power and Performance Evaluation in High-Temperature Environments
3
Performance Requirement Based
on a Specific Benchmark
Large-scale online services that
are both processor and memory
intensive typically operate in scale-
out commodity server deployments.
Such applications operate under
a particular performance service-
level agreement (SLA). However,
due to the scale-out nature of the
application, it is extremely rare that
all servers are tasked with peak
workloads at the same time, and as
a consequence, not all servers are
equally stressed.
This presents an opportunity for
optimizing operational constraints
based on this usage. For such large-
scale online services, if one can
achieve significant benefit in terms of
data center cost efficiency (operations
and build out), one can trade off
performance SLA in preference for
optimal operation, achieving a better
overall performance and TCO.
The next section elaborates the
efficiency of data center builds based
on capacity sizing. To understand
the benefit of sizing by power and
expected load on the machine,
applications were benchmarked on
proposed server configurations. The
load versus power characteristics
obtained from such benchmark runs
can be used to optimally size the data
center.
Figure 3 shows a sample load
versus power curve for specific
points making up the SPECpower*
workload for the server under study.
As load is reduced, power decreases
until it reaches the server’s idle power
level. Reducing utilization would
impact power and in turn component
temperatures in the server. The rest
of this paper references SPECpower
in examining performance and
power trade-offs associated with the
methodology under consideration.
Provisioning for Power
and Server Quantity
To ensure optimal efficiency of the
data center solution, all available
power capacity must be utilized.
The industry metric for building
data centers is millions of U.S.
dollars per megawatt ($M/MW). If a
hypothetical data center utilizes only
50 percent of the total capacity, the
true cost is doubled (1/0.50). Cloud
service providers typically size IT loads
to match data center capacity by adding
servers until the capacity is reached.
The ITE is rated based on running
the worst-case application. This
aspect of sizing is very important,
because the actual worst-case power
is typically much lower than the
nameplate power of the equipment,
since it accounts for variations in
configurations and actual system
utilization and includes the power
supply’s efficiency at the actual
operating point. This factor enables a
very high utilization of a data center’s
capacity. It also requires that users
of the equipment evaluate power
consumption whenever changes
are made to hardware or software
running on the servers.
Table 1 lists the comparative data
for a hypothetical 1 MW data center
populated with a single type of
server, with the power consumption
profile shown in Figure 3. As shown
in Table 1, if the data center is sized
for servers at the full SPECpower
consumption value, 3,703 servers
could be installed. But if the
application can never go above 225
W at 70-percent utilization, the data
center could fit 4,444 servers. Overall
capacity of the solution is 20-percent
better than sizing at the maximum
SPECpower value of 270 watts.
Figure 3 shows the power levels at
nominal temperature. If the server
operates at 45° C at full performance,
the fans and the silicon consume
more power. This approach requires
that an even higher power level per
server be used when calculating
data center capacity. By using power
0 50 100 150 200 250
0 500 1,000 1,500 2,000
TargetLoad
Performance to Power Ratio
Average Active Power (W)
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
Idle
2,202
2,155
2,026
1,879
1,721
1,537
1,310
1,040
732
393
Figure 3. Load versus power curve for SPECpower*.
4
Server Power and Performance Evaluation in High-Temperature Environments
Table 1. Server capacity improvement as a function of server power consumption
Server Utilization Used
for Sizing Capacity
Server Power
Consumption
Servers per
Data Center
Server Capacity
Improvement
100% 270 W 3,703 0%
90% 250 W 4,000 8%
80% 240 W 4,166 13%
70% 225 W 4,444 20%
60% 210 W 4,761 29%
50% 195 W 5,128 38%
capping at higher temperatures, power
requirements per server can be reduced,
allowing more servers to be provisioned
into the data center, as long as the
reduced performance and reliability
at high temperature are acceptable.
The following sections quantify a
method for determining the magnitude
of the performance degradation.
Additional investigation is needed to
determine the impact on reliability.
Recipe to Support Usage Model
Microsoft’s future environmental
needs based on climate align well
with the ETSI specification where
operation above 35° C is limited, but
requires support up to 45° C at least
a few days per year. Consequently,
a 45° C capability was chosen as the
high temperature requirement for
this study. Evaluating performance
under Microsoft’s workload during
the excursion above 35° C enables
Microsoft to size the capability for
optimizing TCO based upon the
previously described metrics.
A server selected for use under this
usage model must still meet all
thermal specifications, potentially
resulting in increased requirements
for the ITE manufacturer. Full
evaluation of thermal capability for
determining the adequacy of the
thermal design is still necessary.
However, it also important to
consider the capability for supporting
the higher ambient temperature
without adding undue cost to the
server or consuming excessive
power based on the higher ambient-
temperature support.
By characterizing the workloads,
ITE manufacturers can tune thermal
management to ensure that server
design supports the model. Through
use of power-limiting mechanisms
such as processor P-states and
memory thermal throttling, ITE
manufacturers can characterize and
tune server thermal management,
including fan speed control, to deliver
the thermal characteristics required
to meet performance goals. In effect,
the server must be classified as capable
of operating in A4 conditions but may
not support typical performance design
points for such a server. In that respect,
it is denoted as a “workload-tuned”
server tolerant of operating over short
periods of time in an A4 environment.
When selecting a server to support
extreme temperature conditions,
its basic design and its components
must be carefully considered. Some
processor models are better suited
to extreme operation and can be
enabled with little or no performance
degradation under any load.
One potentially counterintuitive
aspect of system design is that a
higher number of DIMMs may be
easier to cool than a lower number
of DIMMs. This relationship exists
because a higher number of smaller-
capacity DIMMs is associated with
lower power levels per DIMM and
lower DRAM temperatures for an
equivalent workload. However,
a higher number of low-capacity
DIMMs are likely to consume
more total power than fewer high-
capacity DIMMs, further reducing
the overall server capacity. These
interrelationships demonstrate that
optimizing memory configurations
cannot be achieved using a simple
formula, and the process can benefit
from consulting ITE manufacturers.
Finding an optimal thermal design for
the server itself requires trade-offs that
include optimal heat sink design, as
well as board and system layout. A
server that is configured to eliminate
thermal shadowing will generally be
easier to cool—and consume less fan
power—than an equivalent server with
the same features and configuration that
has thermally shadowed components.
Tests have shown that hard-disk
drives (HDDs) have lower reliability
as temperatures increase.4
Placing
HDDs in locations that receive fresh
inlet air is generally recommended.
Still more opportunities exist at
the system level in terms of density
reduction using larger form factors
such as 1.5U compared with 1U. These
larger form factors enable larger heat
sinks and improved venting, thereby
improving operating capabilities at
increased ambient temperature.
5
Server Power and Performance Evaluation in High-Temperature Environments
Test Environment and Protocol
Testing was conducted on the server,
which was designed to support an
ASHRAE Class A2 environment,
as described in Table 2. An
environmentally-controlled chamber
was used to deliver the tested ambient
temperature as measured at the
server inlet, and thermocouples
were mounted in the server on key
components and at other relevant
locations.
The SPECpower workload used in
the investigation was modified so
that for each load point, tests were
executed for 20 minutes instead of
the default four-minute setting. This
modification allowed the components
to stabilize based on the ambient
temperature setting. Execution of
benchmarks, data collection, and
system inlet temperature control were
fully automated. Intel®
Data Center
Manager (Intel®
DCM)5
was used for
power capping.
To enable temperature stabilization,
all system fans were set to specific
speeds in unison and at fixed
conditions instead of allowing the
server management firmware to
automatically adjust fan speeds.
The server fans were pulse-width
modulation (PWM) controlled. The
fan speeds were roughly linear with
PWM duty cycle setting and tested
at 34 percent (the approximate
recommended setting based upon
a TDP workload under worst-case
ASHRAE Class A2 conditions for the
tested configuration), 41 percent (+20
percent of baseline), and 48 percent
(+40 percent of baseline). Intel DCM
was used to define the power capping
limit of the server in order to study its
performance behavior.
Table 2. Test server configuration.
Component Description
Processors
Two Intel®
Xeon®
processors L5640, 60W @ 2.53 GHz, 6.4 GT/s
Intel®
QuickPath Interconnect
Chipset Intel®
5500 Chipset
Memory Configuration DRx8 (32 GB total)
Drives Four 300-GB drives
60 65 70 75 80 85 90 95 100
Performance(ssj_ops)
SystemPower(W)
Performance, Power vs. Processor P State Setting @PWM=34%, 50°C
Processor P State Setting (% of P1)
600,000
550,000
500,000
450,000
400,000
350,000
300,000
275
270
265
260
255
250
245
Performance
Power
Figure 4. Performance characterization.
Results
Power and performance
characteristics were established using
the acquired data as shown in Figure
4 for a single ambient temperature
and fan speed combination. With
these characteristics and those
under other fan speeds and ambient
temperature combinations, power
and performance capability can
be determined under any defined
processor utilization setting.
Microsoft’s performance
requirements can then be mapped
within the performance, power, and
ambient temperature capability of the
server. Figure 5 shows an example
of this approach, based on staying
within a power cap of 285 W.
As ambient temperature increases
above 35° C, performance as
measured by relative SPECpower
performance drops to 90 percent of
6
Server Power and Performance Evaluation in High-Temperature Environments
20° C 25° C 30° C 35° C 40° C 45° C 50° C 55° C
RelativeSPECpowerPerfomance
Power,Watts
Performance and Power Over Temperature
120%
100%
80%
60%
40%
20%
0%
280 W 282 W 282 W 284 W
90%90%90%
100%100%100%
285 W 281 W 300 W
250 W
200 W
150 W
100 W
50 W
0 W
Relative Performance Power Consumption
Maximum power is set for 285 W at 35° C.
Above 35° C, the fans are set up one notch and
the processor is capped at 82% of maximum
frequency, resulting in a 10% drop in perfomance.
Figure 5. Performance within a power envelope versus system inlet temperature.
peak capability to match the power
capability of the data center as
equated to a single server. A power
management capability such as that
available from Intel®
Intelligent Node
Manager can provide that power
capping capability. For the specific
system under test, only at 50° C
could any component temperature
be exceeded. However, that one
component was the processor itself,
which reduces P-state based on
thermal limits thereby ensuring
continuous performance within
the boundaries of Microsoft’s
requirements. Because systems
are rarely operated at or above 90
percent of peak capability, server
power capping is below the rated
maximum and would not drop
the processor frequency or impact
application performance.
The testing described in this paper
used an ASHRAE Class A2 server.
The equipment manufacturer
must evaluate and approve server
operations outside the intended
range; otherwise, the data center
operator must assume the added risk.
The characteristics of the specific
server tested were well understood,
and as a consequence even non-
monitored components were known
to be within the specification based
on the evaluated cases. The usage
condition for the processor also
fell within the allowable excursion
specification. Locations likely to
experience longer term excursions,
such as those in the deserts of the
southwestern United States, may
be outside the 360-hour processor
excursion specification and may
not be supportable because of the
potential impact on long-term
reliability.
7
Server Power and Performance Evaluation in High-Temperature Environments
Conclusion
A methodology utilizing power
capping technology was defined to
allow an ASHRAE Class A2 server
to meet real-world application
performance requirements in an
ASHRAE Class A4 environment over
short intervals of time. More servers
can be deployed into the data center
under this methodology, improving
TCO. Power capping ensures that
thermal specifications are met, and
power capacity limits are not broken.
A free-air-cooled data center
that supports higher temperature
excursions can help reduce data
center capital costs by elimination of
the need for adiabatic or mechanical
cooling. A small reduction in
performance capability during high
ambient temperature excursions
will be experienced. The capacity
increases and the amount of
performance degradation can be
modeled in advance by reviewing
climate data and adjusting the knobs
to align with the business needs of
the data center user. Operationally,
potential performance degradation
can be anticipated and addressed
accordingly by watching day-to-day
weather reports.
Data center operators that have not
yet begun to consider the topics
covered in this paper may put
their competitiveness at risk. The
alternative described here shows
a possible avenue for improving
efficiency and reducing the use
of water and refrigerants in data
centers, while balancing power and
performance. The reliability aspects
of high temperature operation needs
further investigation to complete
the analysis.
Acknowledgements
The authors wish to thank the
Intel Data Center Group for
contributions and assistance.
Server Power and Performance Evaluation in High-Temperature Environments
	1
	See the ASHRAE white paper describing environmental classes at www.tc99.ashraetcs.org.
	2
	Microsoft’s Dublin Data Center Grows with Enhanced Efficiency and Sustainability
http://www.globalfoundationservices.com/posts/2012/march/5/microsofts-dublin-data-center-grows-with-enhanced-efficiency-and-sustainability.aspx.
	3
	ASHRAE Technical FAQ ID 40 Question Where can I get bin weather data for my area? www.ashrae.org/File%20Library/docLib/Public/20100427_tc_0407faq_40.pdf.
	4
	Sriram Sankar, Mark Shaw, Kushagra Vaid “Impact of Temperature on Hard Disk Drive Reliability in Large Datacenters” at DSN 2011, International Conference on Dependable Systems and Networks.
	5
	More information on Intel®
Data Center Manager can be found at www.datacentermanager.intel.com.
		INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL®
PRODUCTS. NO LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE, TO ANY INTELLECTUAL PROPERTY RIGHTS IS GRANTED BY THIS
DOCUMENT. EXCEPT AS PROVIDED IN INTEL’S TERMS AND CONDITIONS OF SALE FOR SUCH PRODUCTS, INTEL ASSUMES NO LIABILITY WHATSOEVER, AND INTEL DISCLAIMS ANY EXPRESS OR IMPLIED WARRANTY, RELATING TO
SALE AND/OR USE OF INTEL PRODUCTS INCLUDING LIABILITY OR WARRANTIES RELATING TO FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, OR INFRINGEMENT OF ANY PATENT, COPYRIGHT OR OTHER INTELLECTUAL
PROPERTY RIGHT. UNLESS OTHERWISE AGREED IN WRITING BY INTEL, THE INTEL PRODUCTS ARE NOT DESIGNED NOR INTENDED FOR ANY APPLICATION IN WHICH THE FAILURE OF THE INTEL PRODUCT COULD CREATE A SITUATION
WHERE PERSONAL INJURY OR DEATH MAY OCCUR.
		Intel may make changes to specifications and product descriptions at any time, without notice. Designers must not rely on the absence or characteristics of any features or instructions marked “reserved” or “undefined.” Intel reserves these
for future definition and shall have no responsibility whatsoever for conflicts or incompatibilities arising from future changes to them. The information here is subject to change without notice. Do not finalize a design with this information.
The products described in this document may contain design defects or errors known as errata which may cause the product to deviate from published specifications. Current characterized errata are available on request. Contact your local
Intel sales office or your distributor to obtain the latest specifications and before placing your product order. Copies of documents which have an order number and are referenced in this document, or other Intel literature, may be obtained by
calling 1-800-548-4725, or by visiting Intel’s Web Site http://www.intel.com/.
		Software and workloads used in performance tests may have been optimized for performance only on Intel microprocessors. Performance tests, such as SYSmark and MobileMark, are measured using specific computer systems,
components, software, operations and functions. Any change to any of those factors may cause the results to vary. You should consult other information and performance tests to assist you in fully evaluating your contemplated purchases,
including the performance of that product when combined with other products. For more information go to www.intel.com/performance.
		*Other names and brands may be claimed as the property of others.
		Copyright © 2012 Intel Corporation. All rights reserved. Intel, the Intel logo, and Xeon are trademarks of Intel Corporation in the U.S. and other countries
		0512/JK/MESH/PDF	 326605-002US

More Related Content

Similar to Data center-server-cooling-power-management-paper

LiquidCool Solutions - NREL test results!
LiquidCool Solutions - NREL test results! LiquidCool Solutions - NREL test results!
LiquidCool Solutions - NREL test results! Daren Klum
 
TEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEW
TEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEWTEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEW
TEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEWIAEME Publication
 
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationRobert Schmidt
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...SimScale
 
IRJET - Use of Peltier Effect in Medical Device
IRJET - Use of Peltier Effect in Medical DeviceIRJET - Use of Peltier Effect in Medical Device
IRJET - Use of Peltier Effect in Medical DeviceIRJET Journal
 
NER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_WhitepaperNER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_WhitepaperGreg Stover
 
IRJET- Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...
IRJET-  	  Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...IRJET-  	  Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...
IRJET- Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...IRJET Journal
 
Optimize power and cooling final
Optimize power and cooling finalOptimize power and cooling final
Optimize power and cooling finalViridity Software
 
Optimize power and cooling final 1
Optimize power and cooling final 1Optimize power and cooling final 1
Optimize power and cooling final 1Viridity Software
 
IRJET-V9I12214.Comparative Computational analysis of performance parameters f...
IRJET-V9I12214.Comparative Computational analysis of performance parameters f...IRJET-V9I12214.Comparative Computational analysis of performance parameters f...
IRJET-V9I12214.Comparative Computational analysis of performance parameters f...IRJET Journal
 
Environmental Sustainability - Green IT
Environmental Sustainability - Green ITEnvironmental Sustainability - Green IT
Environmental Sustainability - Green ITHKAIM
 
The Economics of Green HPC
The Economics of Green HPCThe Economics of Green HPC
The Economics of Green HPCIntel IT Center
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centresColt UK
 
OCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfOCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfbui thequan
 
High Efficiency Indirect Air Economizer Based Cooling for Data Centers
High Efficiency Indirect Air Economizer Based Cooling for Data CentersHigh Efficiency Indirect Air Economizer Based Cooling for Data Centers
High Efficiency Indirect Air Economizer Based Cooling for Data CentersSchneider Electric
 
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Upsite Technologies
 
ARM Based Climate Controlled Wearable Jacket
ARM Based Climate Controlled Wearable JacketARM Based Climate Controlled Wearable Jacket
ARM Based Climate Controlled Wearable JacketIJTET Journal
 
Design and Analysis of Air Conditioning System for An IT Office Building
Design and Analysis of Air Conditioning System for An IT Office  BuildingDesign and Analysis of Air Conditioning System for An IT Office  Building
Design and Analysis of Air Conditioning System for An IT Office Buildingvivatechijri
 

Similar to Data center-server-cooling-power-management-paper (20)

LiquidCool Solutions - NREL test results!
LiquidCool Solutions - NREL test results! LiquidCool Solutions - NREL test results!
LiquidCool Solutions - NREL test results!
 
TEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEW
TEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEWTEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEW
TEMPERATURE CONTROL AND DATA ACQUISITION METHOD FOR FACTORY USING LABVIEW
 
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
 
IRJET - Use of Peltier Effect in Medical Device
IRJET - Use of Peltier Effect in Medical DeviceIRJET - Use of Peltier Effect in Medical Device
IRJET - Use of Peltier Effect in Medical Device
 
NER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_WhitepaperNER Aurora Thermal_Monitoring_Whitepaper
NER Aurora Thermal_Monitoring_Whitepaper
 
IRJET- Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...
IRJET-  	  Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...IRJET-  	  Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...
IRJET- Experimental Analysis on Liquid-Cooled Minichannel Heatsink for Pe...
 
Optimize power and cooling final
Optimize power and cooling finalOptimize power and cooling final
Optimize power and cooling final
 
Optimize power and cooling final 1
Optimize power and cooling final 1Optimize power and cooling final 1
Optimize power and cooling final 1
 
Green computing
Green computingGreen computing
Green computing
 
Eco cooling
Eco cooling Eco cooling
Eco cooling
 
IRJET-V9I12214.Comparative Computational analysis of performance parameters f...
IRJET-V9I12214.Comparative Computational analysis of performance parameters f...IRJET-V9I12214.Comparative Computational analysis of performance parameters f...
IRJET-V9I12214.Comparative Computational analysis of performance parameters f...
 
Environmental Sustainability - Green IT
Environmental Sustainability - Green ITEnvironmental Sustainability - Green IT
Environmental Sustainability - Green IT
 
The Economics of Green HPC
The Economics of Green HPCThe Economics of Green HPC
The Economics of Green HPC
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centres
 
OCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfOCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdf
 
High Efficiency Indirect Air Economizer Based Cooling for Data Centers
High Efficiency Indirect Air Economizer Based Cooling for Data CentersHigh Efficiency Indirect Air Economizer Based Cooling for Data Centers
High Efficiency Indirect Air Economizer Based Cooling for Data Centers
 
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
Clarifying ASHRAE's Recommended Vs. Allowable Temperature Envelopes and How t...
 
ARM Based Climate Controlled Wearable Jacket
ARM Based Climate Controlled Wearable JacketARM Based Climate Controlled Wearable Jacket
ARM Based Climate Controlled Wearable Jacket
 
Design and Analysis of Air Conditioning System for An IT Office Building
Design and Analysis of Air Conditioning System for An IT Office  BuildingDesign and Analysis of Air Conditioning System for An IT Office  Building
Design and Analysis of Air Conditioning System for An IT Office Building
 

More from Dileep Bhandarkar

Open Compute Summit Keynote 17 June 2011
Open Compute Summit Keynote 17 June 2011Open Compute Summit Keynote 17 June 2011
Open Compute Summit Keynote 17 June 2011Dileep Bhandarkar
 
Datacenter Dynamics Chicago 30 sept 2010
Datacenter Dynamics Chicago 30 sept 2010Datacenter Dynamics Chicago 30 sept 2010
Datacenter Dynamics Chicago 30 sept 2010Dileep Bhandarkar
 
Energy Efficiency Considerations in Large Datacenters
Energy Efficiency Considerations in Large DatacentersEnergy Efficiency Considerations in Large Datacenters
Energy Efficiency Considerations in Large DatacentersDileep Bhandarkar
 
Moscow conference keynote in 2012
Moscow conference keynote in 2012Moscow conference keynote in 2012
Moscow conference keynote in 2012Dileep Bhandarkar
 
New Delhi Cloud Summit 05 26-11
New Delhi Cloud Summit 05 26-11New Delhi Cloud Summit 05 26-11
New Delhi Cloud Summit 05 26-11Dileep Bhandarkar
 
Performance Characterization of the Pentium Pro Processor
Performance Characterization of the Pentium Pro ProcessorPerformance Characterization of the Pentium Pro Processor
Performance Characterization of the Pentium Pro ProcessorDileep Bhandarkar
 
Innovation lecture for hong kong
Innovation lecture for hong kongInnovation lecture for hong kong
Innovation lecture for hong kongDileep Bhandarkar
 
Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...
Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...
Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...Dileep Bhandarkar
 
Qualcomm centriq 2400 hot chips final submission corrected
Qualcomm centriq 2400 hot chips final submission correctedQualcomm centriq 2400 hot chips final submission corrected
Qualcomm centriq 2400 hot chips final submission correctedDileep Bhandarkar
 
Innovation lecture for shanghai final
Innovation lecture for shanghai finalInnovation lecture for shanghai final
Innovation lecture for shanghai finalDileep Bhandarkar
 
Linaro connect 2018 keynote final updated
Linaro connect 2018 keynote final updatedLinaro connect 2018 keynote final updated
Linaro connect 2018 keynote final updatedDileep Bhandarkar
 
Dileep Random Access Talk at salishan 2016
Dileep Random Access Talk at salishan 2016Dileep Random Access Talk at salishan 2016
Dileep Random Access Talk at salishan 2016Dileep Bhandarkar
 
Server design summit keynote handout
Server design summit keynote handoutServer design summit keynote handout
Server design summit keynote handoutDileep Bhandarkar
 

More from Dileep Bhandarkar (20)

Open Compute Summit Keynote 17 June 2011
Open Compute Summit Keynote 17 June 2011Open Compute Summit Keynote 17 June 2011
Open Compute Summit Keynote 17 June 2011
 
Datacenter Dynamics Chicago 30 sept 2010
Datacenter Dynamics Chicago 30 sept 2010Datacenter Dynamics Chicago 30 sept 2010
Datacenter Dynamics Chicago 30 sept 2010
 
Energy Efficiency Considerations in Large Datacenters
Energy Efficiency Considerations in Large DatacentersEnergy Efficiency Considerations in Large Datacenters
Energy Efficiency Considerations in Large Datacenters
 
Samsung cio-forum-2012
Samsung cio-forum-2012 Samsung cio-forum-2012
Samsung cio-forum-2012
 
Moscow conference keynote in 2012
Moscow conference keynote in 2012Moscow conference keynote in 2012
Moscow conference keynote in 2012
 
New Delhi Cloud Summit 05 26-11
New Delhi Cloud Summit 05 26-11New Delhi Cloud Summit 05 26-11
New Delhi Cloud Summit 05 26-11
 
Performance Characterization of the Pentium Pro Processor
Performance Characterization of the Pentium Pro ProcessorPerformance Characterization of the Pentium Pro Processor
Performance Characterization of the Pentium Pro Processor
 
Innovation lecture for hong kong
Innovation lecture for hong kongInnovation lecture for hong kong
Innovation lecture for hong kong
 
Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...
Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...
Performance from Architecture: Comparing a RISC and a CISC with Similar Hardw...
 
Qualcomm centriq 2400 hot chips final submission corrected
Qualcomm centriq 2400 hot chips final submission correctedQualcomm centriq 2400 hot chips final submission corrected
Qualcomm centriq 2400 hot chips final submission corrected
 
Innovation lecture for shanghai final
Innovation lecture for shanghai finalInnovation lecture for shanghai final
Innovation lecture for shanghai final
 
Semicon2018 dileepb
Semicon2018 dileepbSemicon2018 dileepb
Semicon2018 dileepb
 
Linaro connect 2018 keynote final updated
Linaro connect 2018 keynote final updatedLinaro connect 2018 keynote final updated
Linaro connect 2018 keynote final updated
 
Hipeac 2018 keynote Talk
Hipeac 2018 keynote TalkHipeac 2018 keynote Talk
Hipeac 2018 keynote Talk
 
Alpha memo july 1992
Alpha memo july 1992Alpha memo july 1992
Alpha memo july 1992
 
China AI Summit talk 2017
China AI Summit talk 2017China AI Summit talk 2017
China AI Summit talk 2017
 
Dileep Random Access Talk at salishan 2016
Dileep Random Access Talk at salishan 2016Dileep Random Access Talk at salishan 2016
Dileep Random Access Talk at salishan 2016
 
Risc vs cisc
Risc vs ciscRisc vs cisc
Risc vs cisc
 
Moscow conference keynote
Moscow conference keynoteMoscow conference keynote
Moscow conference keynote
 
Server design summit keynote handout
Server design summit keynote handoutServer design summit keynote handout
Server design summit keynote handout
 

Recently uploaded

DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfAlex Barbosa Coqueiro
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks..."LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...Fwdays
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
Search Engine Optimization SEO PDF for 2024.pdf
Search Engine Optimization SEO PDF for 2024.pdfSearch Engine Optimization SEO PDF for 2024.pdf
Search Engine Optimization SEO PDF for 2024.pdfRankYa
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embeddingZilliz
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piececharlottematthew16
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Scott Keck-Warren
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLScyllaDB
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machinePadma Pradeep
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxhariprasad279825
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 

Recently uploaded (20)

DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdf
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks..."LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
Search Engine Optimization SEO PDF for 2024.pdf
Search Engine Optimization SEO PDF for 2024.pdfSearch Engine Optimization SEO PDF for 2024.pdf
Search Engine Optimization SEO PDF for 2024.pdf
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
Transcript: New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embedding
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piece
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQL
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machine
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptx
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 

Data center-server-cooling-power-management-paper

  • 1. Server Power and Performance Evaluation in High-Temperature Environments Overview and Background Expanding the ambient-temperature operating range for IT equipment (ITE) can yield significant savings in capital and operating expenses related to cooling infrastructure. Existing standards and guidelines can provide an appropriate framework for evaluating performance, reliability, and other factors while operating close to the prescribed limits of ambient temperature ranges. This paper describes the results of a study in which under certain load conditions an Intel® Xeon® processor-based system designed for a Class A2 environment1 as defined by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) can be adapted to a Class A4 environment1 or to a 3.1E environment as defined by the European Telecommunications Standards Institute (ETSI). The study, conducted by Microsoft and Intel, shows how a server can be characterized to determine its capability based on ambient temperature and performance while ensuring that power and thermal constraints can be maintained. It also summarizes other issues to be considered in the context of operation at the extremes of the environmental range specified for a given system. Creating server systems that operate at higher-than-usual ambient temperatures can help initiate a trend away from conventional chiller-cooled data centers to free-air-cooled data centers. The further system design improvements discussed here target the elimination of water used for adiabatic cooling by using only the surrounding outdoor ambient air for cooling, thereby lowering facility complexity and total cost of ownership (TCO). The results of this study are not necessarily relevant to all environments, and it also does not address reliability issues associated with operating outside the Class A2 environment. Intel Corporation: K. Govindaraju, Workloads/Performance Architect; Robin Steinbrecher, Platform Thermal Architect; Sandeep Ahuja, CPU Thermal Architect; Eyran Eylon, Technology Development Manager; Jay Kyathsandra, Product Marketing Microsoft Corporation: Dileep Bhandarkar, Chief Architect, Global Foundation Services; Kushagra Vaid, General Manager, Hardware Engineering; Mark Shaw, Director, Hardware Engineering; Sriram Sankar, Hardware Engineer WHITE PAPER Intel® Xeon® Processors with Intel® Node Manager Microsoft Windows Server® Data Center Cooling and Power Management
  • 2. Server Design for High- Temperature Operation The use of free-air-cooled data centers can result in exposure to a wider range of inlet temperatures to the ITE, which is typically designed based upon a maximum inlet temperature of 35° C (95° F). While Microsoft has shown that free-air-cooled data centers work well in certain climates, such as that of Dublin, Ireland,2 few populated places in the world stay below this temperature year round. This white paper demonstrates how a well-designed server can support temperature excursions to as high as 45° C (113° F) based upon meeting target use conditions for a specific application. One approach to operating at higher temperatures is to improve an air-cooled server design through the use of enhanced heat sinks and increased airflow. While improving design for higher efficiency is often the right choice, sizing ITE for full performance at 45° C may result in lower overall efficiency by requiring a larger data center footprint and provisioning power that is only used during the hottest portion of the year due to the increase in airflow and power requirements for the servers. If the extreme temperatures occur for only a few hours, it is reasonable to advocate trading off a small amount of performance at the hottest time of the year to achieve efficiency the remainder of the year. This approach is also likely to maintain the server purchase cost, by avoiding the increased cost of server cooling components that support continuous operation at high temperatures. While operation above 35° C in an economized data center needs to be supported, these temperature excursions occur for only a few hours during the year, even in high- temperature climates, as shown in Figure 1.2 0 5 10 15 20 25 30 35 40 45 4500 4000 3500 3000 2500 2000 1500 1000 500 0 NumberofHours Ambient Temperature (°C) Tropical Climate Humid Northern Desert Climate Data - Average Hours at a Given Temperature In many climates, the temperature goes above 35° C for only a few hours in an average year; desert climates experience the most, at 67 hours per year (0.8 percent of the time). Systems that can operate at 45° C are able to handle 50-year extremes in temperature. Note that temperatures in tropical climates are nearly always between 22° C and 33° C. Hours over 35° C 2 5 67 Tropical Humid Northern Desert Hours over 40° C 0 0 3 Average Maximum 36° C 36° C 41° C 50 year Extreme 37° C 41° C 43° C Figure 1. Low incidence of temperature excursions above 35° C.3 Table of Contents Overview and Background . . . . . . . . . . . 1 Server Design for High-Temperature Operation . . . . . . . . . 2 Performance Requirement Based on a Specific Benchmark . . . . . . . . . . . . 4 Provisioning for Power and Server Quantity . . . . . . . . . . . . . . . . 4 Recipe to Support Usage Model . . . . . . . 5 Test Environment and Protocol . . . . . . . 6 Results . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Conclusion . . . . . . . . . . . . . . . . . . . . . . . 8 Acknowledgements . . . . . . . . . . . . . . . . 8 2 Server Power and Performance Evaluation in High-Temperature Environments
  • 3. To support this usage model, it is necessary to understand the relevant environmental classes to ensure alignment with IT manufacturer design targets and warranties. In 2011, ASHRAE defined two new classes—A3 and A4,1 as shown in Figure 2—to set expectations for data centers operating with a high degree of economization and the ITE designed for them. The ranges of both temperature and humidity widened significantly, creating the opportunity for reductions in both capital and operating expenditure depending upon climate. ASHRAE provides guidance1 on evaluating the reliability of ITE in an individual data center based on the time spent at various environmental conditions. By evaluating a data center’s time-weighted temperature throughout the period of interest, one can derive the expected multiplier to the baseline failure rate of ITE in the data center. However, ASHRAE does not recommend operating at high temperature, and the ITE manufacturer’s warranty may not support it either. ETSI has set an environmental standard that includes operation up to 45° C for limited time periods, illustrated by the data shown in Figure 2. This standard applies to telecommunications equipment, as opposed to the focus of the ASHRAE guidelines on ITE in general. The ETSI standard does provide one model for designing ITE but does not define the performance required under these conditions. In any case, an ITE manufacturer may find it valuable to align future equipment with one of these environments to enable wide-ranging acceptance of its product, and the ETSI specification provides a model with respect to time spent in state. 0 5 10 15 20 20% 10% 25 0 5 10 15 20 25 90% 80% 70% 60% 50% 40% 30% 30 35 40 45 25 20 15 10 5 0 Dry Bulb Temperature - °C W etBulbTem perature-°C Realtive Humidity DewPointTemperature-°C These environmental envelopes pertain to air entering the IT equipment. Condition at SEA LEVEL A3 A4 A2 A1 0 10 20 30 40 Values outside this field have a probability of occurence of less than 10% (see IEC 6072-3-0) Exceptional climate limits Normal climatic limits: Values outside these limits have a probability of occurence of less than 1% NOTE: Exceptional conditions may occur following the failure of the temperature controlling system. This is described as 3.1E in the tables, but it should be noted that there is no separate class 3.1E. 50 50 40 30 20 10 0 -10 -20 60 70 80 90 100 25 20 1.5 1 Relative Air Humidity - % AirTemperature-°C AbsoluteHumidityg/m3 90% 9% 1% Normal Conditions Exceptional Conditions Figure 2. American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) classes and the European Telecommunications Standards Institute (ETSI) specification. 3 Server Power and Performance Evaluation in High-Temperature Environments 3
  • 4. Performance Requirement Based on a Specific Benchmark Large-scale online services that are both processor and memory intensive typically operate in scale- out commodity server deployments. Such applications operate under a particular performance service- level agreement (SLA). However, due to the scale-out nature of the application, it is extremely rare that all servers are tasked with peak workloads at the same time, and as a consequence, not all servers are equally stressed. This presents an opportunity for optimizing operational constraints based on this usage. For such large- scale online services, if one can achieve significant benefit in terms of data center cost efficiency (operations and build out), one can trade off performance SLA in preference for optimal operation, achieving a better overall performance and TCO. The next section elaborates the efficiency of data center builds based on capacity sizing. To understand the benefit of sizing by power and expected load on the machine, applications were benchmarked on proposed server configurations. The load versus power characteristics obtained from such benchmark runs can be used to optimally size the data center. Figure 3 shows a sample load versus power curve for specific points making up the SPECpower* workload for the server under study. As load is reduced, power decreases until it reaches the server’s idle power level. Reducing utilization would impact power and in turn component temperatures in the server. The rest of this paper references SPECpower in examining performance and power trade-offs associated with the methodology under consideration. Provisioning for Power and Server Quantity To ensure optimal efficiency of the data center solution, all available power capacity must be utilized. The industry metric for building data centers is millions of U.S. dollars per megawatt ($M/MW). If a hypothetical data center utilizes only 50 percent of the total capacity, the true cost is doubled (1/0.50). Cloud service providers typically size IT loads to match data center capacity by adding servers until the capacity is reached. The ITE is rated based on running the worst-case application. This aspect of sizing is very important, because the actual worst-case power is typically much lower than the nameplate power of the equipment, since it accounts for variations in configurations and actual system utilization and includes the power supply’s efficiency at the actual operating point. This factor enables a very high utilization of a data center’s capacity. It also requires that users of the equipment evaluate power consumption whenever changes are made to hardware or software running on the servers. Table 1 lists the comparative data for a hypothetical 1 MW data center populated with a single type of server, with the power consumption profile shown in Figure 3. As shown in Table 1, if the data center is sized for servers at the full SPECpower consumption value, 3,703 servers could be installed. But if the application can never go above 225 W at 70-percent utilization, the data center could fit 4,444 servers. Overall capacity of the solution is 20-percent better than sizing at the maximum SPECpower value of 270 watts. Figure 3 shows the power levels at nominal temperature. If the server operates at 45° C at full performance, the fans and the silicon consume more power. This approach requires that an even higher power level per server be used when calculating data center capacity. By using power 0 50 100 150 200 250 0 500 1,000 1,500 2,000 TargetLoad Performance to Power Ratio Average Active Power (W) 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% Idle 2,202 2,155 2,026 1,879 1,721 1,537 1,310 1,040 732 393 Figure 3. Load versus power curve for SPECpower*. 4 Server Power and Performance Evaluation in High-Temperature Environments
  • 5. Table 1. Server capacity improvement as a function of server power consumption Server Utilization Used for Sizing Capacity Server Power Consumption Servers per Data Center Server Capacity Improvement 100% 270 W 3,703 0% 90% 250 W 4,000 8% 80% 240 W 4,166 13% 70% 225 W 4,444 20% 60% 210 W 4,761 29% 50% 195 W 5,128 38% capping at higher temperatures, power requirements per server can be reduced, allowing more servers to be provisioned into the data center, as long as the reduced performance and reliability at high temperature are acceptable. The following sections quantify a method for determining the magnitude of the performance degradation. Additional investigation is needed to determine the impact on reliability. Recipe to Support Usage Model Microsoft’s future environmental needs based on climate align well with the ETSI specification where operation above 35° C is limited, but requires support up to 45° C at least a few days per year. Consequently, a 45° C capability was chosen as the high temperature requirement for this study. Evaluating performance under Microsoft’s workload during the excursion above 35° C enables Microsoft to size the capability for optimizing TCO based upon the previously described metrics. A server selected for use under this usage model must still meet all thermal specifications, potentially resulting in increased requirements for the ITE manufacturer. Full evaluation of thermal capability for determining the adequacy of the thermal design is still necessary. However, it also important to consider the capability for supporting the higher ambient temperature without adding undue cost to the server or consuming excessive power based on the higher ambient- temperature support. By characterizing the workloads, ITE manufacturers can tune thermal management to ensure that server design supports the model. Through use of power-limiting mechanisms such as processor P-states and memory thermal throttling, ITE manufacturers can characterize and tune server thermal management, including fan speed control, to deliver the thermal characteristics required to meet performance goals. In effect, the server must be classified as capable of operating in A4 conditions but may not support typical performance design points for such a server. In that respect, it is denoted as a “workload-tuned” server tolerant of operating over short periods of time in an A4 environment. When selecting a server to support extreme temperature conditions, its basic design and its components must be carefully considered. Some processor models are better suited to extreme operation and can be enabled with little or no performance degradation under any load. One potentially counterintuitive aspect of system design is that a higher number of DIMMs may be easier to cool than a lower number of DIMMs. This relationship exists because a higher number of smaller- capacity DIMMs is associated with lower power levels per DIMM and lower DRAM temperatures for an equivalent workload. However, a higher number of low-capacity DIMMs are likely to consume more total power than fewer high- capacity DIMMs, further reducing the overall server capacity. These interrelationships demonstrate that optimizing memory configurations cannot be achieved using a simple formula, and the process can benefit from consulting ITE manufacturers. Finding an optimal thermal design for the server itself requires trade-offs that include optimal heat sink design, as well as board and system layout. A server that is configured to eliminate thermal shadowing will generally be easier to cool—and consume less fan power—than an equivalent server with the same features and configuration that has thermally shadowed components. Tests have shown that hard-disk drives (HDDs) have lower reliability as temperatures increase.4 Placing HDDs in locations that receive fresh inlet air is generally recommended. Still more opportunities exist at the system level in terms of density reduction using larger form factors such as 1.5U compared with 1U. These larger form factors enable larger heat sinks and improved venting, thereby improving operating capabilities at increased ambient temperature. 5 Server Power and Performance Evaluation in High-Temperature Environments
  • 6. Test Environment and Protocol Testing was conducted on the server, which was designed to support an ASHRAE Class A2 environment, as described in Table 2. An environmentally-controlled chamber was used to deliver the tested ambient temperature as measured at the server inlet, and thermocouples were mounted in the server on key components and at other relevant locations. The SPECpower workload used in the investigation was modified so that for each load point, tests were executed for 20 minutes instead of the default four-minute setting. This modification allowed the components to stabilize based on the ambient temperature setting. Execution of benchmarks, data collection, and system inlet temperature control were fully automated. Intel® Data Center Manager (Intel® DCM)5 was used for power capping. To enable temperature stabilization, all system fans were set to specific speeds in unison and at fixed conditions instead of allowing the server management firmware to automatically adjust fan speeds. The server fans were pulse-width modulation (PWM) controlled. The fan speeds were roughly linear with PWM duty cycle setting and tested at 34 percent (the approximate recommended setting based upon a TDP workload under worst-case ASHRAE Class A2 conditions for the tested configuration), 41 percent (+20 percent of baseline), and 48 percent (+40 percent of baseline). Intel DCM was used to define the power capping limit of the server in order to study its performance behavior. Table 2. Test server configuration. Component Description Processors Two Intel® Xeon® processors L5640, 60W @ 2.53 GHz, 6.4 GT/s Intel® QuickPath Interconnect Chipset Intel® 5500 Chipset Memory Configuration DRx8 (32 GB total) Drives Four 300-GB drives 60 65 70 75 80 85 90 95 100 Performance(ssj_ops) SystemPower(W) Performance, Power vs. Processor P State Setting @PWM=34%, 50°C Processor P State Setting (% of P1) 600,000 550,000 500,000 450,000 400,000 350,000 300,000 275 270 265 260 255 250 245 Performance Power Figure 4. Performance characterization. Results Power and performance characteristics were established using the acquired data as shown in Figure 4 for a single ambient temperature and fan speed combination. With these characteristics and those under other fan speeds and ambient temperature combinations, power and performance capability can be determined under any defined processor utilization setting. Microsoft’s performance requirements can then be mapped within the performance, power, and ambient temperature capability of the server. Figure 5 shows an example of this approach, based on staying within a power cap of 285 W. As ambient temperature increases above 35° C, performance as measured by relative SPECpower performance drops to 90 percent of 6 Server Power and Performance Evaluation in High-Temperature Environments
  • 7. 20° C 25° C 30° C 35° C 40° C 45° C 50° C 55° C RelativeSPECpowerPerfomance Power,Watts Performance and Power Over Temperature 120% 100% 80% 60% 40% 20% 0% 280 W 282 W 282 W 284 W 90%90%90% 100%100%100% 285 W 281 W 300 W 250 W 200 W 150 W 100 W 50 W 0 W Relative Performance Power Consumption Maximum power is set for 285 W at 35° C. Above 35° C, the fans are set up one notch and the processor is capped at 82% of maximum frequency, resulting in a 10% drop in perfomance. Figure 5. Performance within a power envelope versus system inlet temperature. peak capability to match the power capability of the data center as equated to a single server. A power management capability such as that available from Intel® Intelligent Node Manager can provide that power capping capability. For the specific system under test, only at 50° C could any component temperature be exceeded. However, that one component was the processor itself, which reduces P-state based on thermal limits thereby ensuring continuous performance within the boundaries of Microsoft’s requirements. Because systems are rarely operated at or above 90 percent of peak capability, server power capping is below the rated maximum and would not drop the processor frequency or impact application performance. The testing described in this paper used an ASHRAE Class A2 server. The equipment manufacturer must evaluate and approve server operations outside the intended range; otherwise, the data center operator must assume the added risk. The characteristics of the specific server tested were well understood, and as a consequence even non- monitored components were known to be within the specification based on the evaluated cases. The usage condition for the processor also fell within the allowable excursion specification. Locations likely to experience longer term excursions, such as those in the deserts of the southwestern United States, may be outside the 360-hour processor excursion specification and may not be supportable because of the potential impact on long-term reliability. 7 Server Power and Performance Evaluation in High-Temperature Environments
  • 8. Conclusion A methodology utilizing power capping technology was defined to allow an ASHRAE Class A2 server to meet real-world application performance requirements in an ASHRAE Class A4 environment over short intervals of time. More servers can be deployed into the data center under this methodology, improving TCO. Power capping ensures that thermal specifications are met, and power capacity limits are not broken. A free-air-cooled data center that supports higher temperature excursions can help reduce data center capital costs by elimination of the need for adiabatic or mechanical cooling. A small reduction in performance capability during high ambient temperature excursions will be experienced. The capacity increases and the amount of performance degradation can be modeled in advance by reviewing climate data and adjusting the knobs to align with the business needs of the data center user. Operationally, potential performance degradation can be anticipated and addressed accordingly by watching day-to-day weather reports. Data center operators that have not yet begun to consider the topics covered in this paper may put their competitiveness at risk. The alternative described here shows a possible avenue for improving efficiency and reducing the use of water and refrigerants in data centers, while balancing power and performance. The reliability aspects of high temperature operation needs further investigation to complete the analysis. Acknowledgements The authors wish to thank the Intel Data Center Group for contributions and assistance. Server Power and Performance Evaluation in High-Temperature Environments 1 See the ASHRAE white paper describing environmental classes at www.tc99.ashraetcs.org. 2 Microsoft’s Dublin Data Center Grows with Enhanced Efficiency and Sustainability http://www.globalfoundationservices.com/posts/2012/march/5/microsofts-dublin-data-center-grows-with-enhanced-efficiency-and-sustainability.aspx. 3 ASHRAE Technical FAQ ID 40 Question Where can I get bin weather data for my area? www.ashrae.org/File%20Library/docLib/Public/20100427_tc_0407faq_40.pdf. 4 Sriram Sankar, Mark Shaw, Kushagra Vaid “Impact of Temperature on Hard Disk Drive Reliability in Large Datacenters” at DSN 2011, International Conference on Dependable Systems and Networks. 5 More information on Intel® Data Center Manager can be found at www.datacentermanager.intel.com. INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL® PRODUCTS. NO LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE, TO ANY INTELLECTUAL PROPERTY RIGHTS IS GRANTED BY THIS DOCUMENT. EXCEPT AS PROVIDED IN INTEL’S TERMS AND CONDITIONS OF SALE FOR SUCH PRODUCTS, INTEL ASSUMES NO LIABILITY WHATSOEVER, AND INTEL DISCLAIMS ANY EXPRESS OR IMPLIED WARRANTY, RELATING TO SALE AND/OR USE OF INTEL PRODUCTS INCLUDING LIABILITY OR WARRANTIES RELATING TO FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, OR INFRINGEMENT OF ANY PATENT, COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT. UNLESS OTHERWISE AGREED IN WRITING BY INTEL, THE INTEL PRODUCTS ARE NOT DESIGNED NOR INTENDED FOR ANY APPLICATION IN WHICH THE FAILURE OF THE INTEL PRODUCT COULD CREATE A SITUATION WHERE PERSONAL INJURY OR DEATH MAY OCCUR. Intel may make changes to specifications and product descriptions at any time, without notice. Designers must not rely on the absence or characteristics of any features or instructions marked “reserved” or “undefined.” Intel reserves these for future definition and shall have no responsibility whatsoever for conflicts or incompatibilities arising from future changes to them. The information here is subject to change without notice. Do not finalize a design with this information. The products described in this document may contain design defects or errors known as errata which may cause the product to deviate from published specifications. Current characterized errata are available on request. Contact your local Intel sales office or your distributor to obtain the latest specifications and before placing your product order. Copies of documents which have an order number and are referenced in this document, or other Intel literature, may be obtained by calling 1-800-548-4725, or by visiting Intel’s Web Site http://www.intel.com/. Software and workloads used in performance tests may have been optimized for performance only on Intel microprocessors. Performance tests, such as SYSmark and MobileMark, are measured using specific computer systems, components, software, operations and functions. Any change to any of those factors may cause the results to vary. You should consult other information and performance tests to assist you in fully evaluating your contemplated purchases, including the performance of that product when combined with other products. For more information go to www.intel.com/performance. *Other names and brands may be claimed as the property of others. Copyright © 2012 Intel Corporation. All rights reserved. Intel, the Intel logo, and Xeon are trademarks of Intel Corporation in the U.S. and other countries 0512/JK/MESH/PDF 326605-002US