Short-circuit switching (making/breaking) capacity
Edvard
Short-circuit switching (making / breaking) capacity
Definition of switching capacity
The switching capacity is the r.m.s value of a current at a given power factor cos φ as well as a given rated
voltage at which a switchgear or a fuse can still shut-off under specified conditions in an operationally safe way.
Both the short-circuit making capacity as well as the short-circuit breaking capacity of circuit breakers must
be larger than or equal to the prospective short-circuit current at the place of installation.
If this is not the case, then a suitable backup protection (for example a fuse) should be provided to ensure the
required switching capacity of the device combination. Data regarding devices for backup protection are given in
the technical documentation.
Rated short-circuit making capacityIcm
The rated short-circuit making capacity Icm is a quantity that according to regulations must be in a certain ratio to
the rated ultimate short-circuit breaking capacity Icu and that has to be guaranteed by the device manufacturer.
This is not a variable that must be considered by the user, however it ensures that a circuit breaker is in the
position to connect onto a short-circuit – and to disconnect it subsequently.
Rated short-circuit breaking capacity ICU and ICS
IEC 60947-2 makes distinction between the rated ultimate short-circuit breaking capacity ICU and the rated
service short-circuit breaking capacity ICS:
Rated ultimate short-circuit breaking capacityICU
ICU is the maximum breaking capacity of a circuit breaker at an associated rated operational voltage and under
specified conditions.
ICU is expressed in kA and must be at least as large as the prospective short-circuit current at the site of
installation.
Circuit breakers that have switched-off at the level of the ultimate short-circuit breaking capacity, are reduced
serviceable afterwards and should at least be checked regarding functionality. There may be changes in the
overload trip characteristic and increased temperature rise due to the erosion of contact material.
Rated service short-circuit interrupting capacity ICS
ICS values are usually lower than the values for ICU. Circuit breakers that have been switching-off at the level of
the service short-circuit breaking capacity continue to be serviceable afterward.
In plants in which interruptions to operations must be kept as short as possible, product selection should be
carried out based on ICS.
Breaking capacity of fuses
The same applies to fuses as to circuit breakers with respect to the I CU: at the given rated operational
voltage, the rated breaking capacity must be at least as large as the prospective short-circuit current at the site of
installation.
Reference: Low-Voltage Switchgear and Controlgear – Allen Bradley
Source:
http://electrical-engineering-portal.com/short-circuit-switching-
making-breaking-capacity

More Related Content

What's hot

17th Edition Part 2 3
17th Edition  Part 2   317th Edition  Part 2   3
17th Edition Part 2 3Paul Holden
 
17th Edition Parts 53 To 56
17th  Edition Parts 53 To 5617th  Edition Parts 53 To 56
17th Edition Parts 53 To 56Paul Holden
 
17th Edition Part 4 3
17th  Edition  Part 4 317th  Edition  Part 4 3
17th Edition Part 4 3Paul Holden
 
Practical No-9: Introduction to protecting devices-Fuse-MCB-ELCB
Practical No-9: Introduction to protecting devices-Fuse-MCB-ELCBPractical No-9: Introduction to protecting devices-Fuse-MCB-ELCB
Practical No-9: Introduction to protecting devices-Fuse-MCB-ELCBGhansyam Rathod
 
Earth Leakage Circuit Breaker
Earth Leakage Circuit BreakerEarth Leakage Circuit Breaker
Earth Leakage Circuit Breakermilanpatel007
 
Richard Blakeley - Options for managing safety with elderly switchgear
Richard Blakeley - Options for managing safety with elderly switchgearRichard Blakeley - Options for managing safety with elderly switchgear
Richard Blakeley - Options for managing safety with elderly switchgearNSW Environment and Planning
 
Surge current protection using super conductors
Surge current protection using super conductorsSurge current protection using super conductors
Surge current protection using super conductorsVamshiKrishna947
 
MCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitMCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitNavin Patle
 
Surge protection devices in indusrial automation
Surge protection devices in indusrial automationSurge protection devices in indusrial automation
Surge protection devices in indusrial automationfairautomation
 
17th Edition Part 4 4
17th  Edition  Part 4 417th  Edition  Part 4 4
17th Edition Part 4 4Paul Holden
 
Power System Protection Presentation
Power System Protection PresentationPower System Protection Presentation
Power System Protection PresentationAdeen Syed
 
17th Edition Part 5 1
17th  Edition  Part 5 117th  Edition  Part 5 1
17th Edition Part 5 1Paul Holden
 
Presentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliancePresentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical applianceNishant Kumar
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_advertsKhalid Sithari
 
Electrostatic discharge
Electrostatic discharge Electrostatic discharge
Electrostatic discharge AJAL A J
 

What's hot (20)

17th Edition Part 2 3
17th Edition  Part 2   317th Edition  Part 2   3
17th Edition Part 2 3
 
Surge supressor
Surge supressorSurge supressor
Surge supressor
 
17th Edition Parts 53 To 56
17th  Edition Parts 53 To 5617th  Edition Parts 53 To 56
17th Edition Parts 53 To 56
 
17th Edition Part 4 3
17th  Edition  Part 4 317th  Edition  Part 4 3
17th Edition Part 4 3
 
Practical No-9: Introduction to protecting devices-Fuse-MCB-ELCB
Practical No-9: Introduction to protecting devices-Fuse-MCB-ELCBPractical No-9: Introduction to protecting devices-Fuse-MCB-ELCB
Practical No-9: Introduction to protecting devices-Fuse-MCB-ELCB
 
Report on MCB
Report on MCBReport on MCB
Report on MCB
 
Earth Leakage Circuit Breaker
Earth Leakage Circuit BreakerEarth Leakage Circuit Breaker
Earth Leakage Circuit Breaker
 
Richard Blakeley - Options for managing safety with elderly switchgear
Richard Blakeley - Options for managing safety with elderly switchgearRichard Blakeley - Options for managing safety with elderly switchgear
Richard Blakeley - Options for managing safety with elderly switchgear
 
Surge current protection using super conductors
Surge current protection using super conductorsSurge current protection using super conductors
Surge current protection using super conductors
 
Fuji BC Series MCB
Fuji BC Series MCBFuji BC Series MCB
Fuji BC Series MCB
 
MCB And Earth Leakage Circuit
MCB And Earth Leakage CircuitMCB And Earth Leakage Circuit
MCB And Earth Leakage Circuit
 
Surge protection devices in indusrial automation
Surge protection devices in indusrial automationSurge protection devices in indusrial automation
Surge protection devices in indusrial automation
 
L.v tech presentation 2
L.v tech presentation 2L.v tech presentation 2
L.v tech presentation 2
 
17th Edition Part 4 4
17th  Edition  Part 4 417th  Edition  Part 4 4
17th Edition Part 4 4
 
Power System Protection Presentation
Power System Protection PresentationPower System Protection Presentation
Power System Protection Presentation
 
17th Edition Part 5 1
17th  Edition  Part 5 117th  Edition  Part 5 1
17th Edition Part 5 1
 
Value icu
Value icuValue icu
Value icu
 
Presentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliancePresentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliance
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts
 
Electrostatic discharge
Electrostatic discharge Electrostatic discharge
Electrostatic discharge
 

Similar to Shortcircuit switching making__breaking_capacity

Application data explusion links
Application data explusion linksApplication data explusion links
Application data explusion linksing_eliali4748
 
Tecnical aplicacion1 abb
Tecnical aplicacion1 abbTecnical aplicacion1 abb
Tecnical aplicacion1 abbisaac diaz said
 
01. hrc din fuses 3 na
01. hrc din fuses  3 na01. hrc din fuses  3 na
01. hrc din fuses 3 naangelochintu
 
01. hrc din fuses 3 na
01. hrc din fuses  3 na01. hrc din fuses  3 na
01. hrc din fuses 3 naangeloneha
 
Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardIJAPEJOURNAL
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"michaeljmack
 
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions FinalDo's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions FinalJim White
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 
Insulation coordination.
Insulation coordination.Insulation coordination.
Insulation coordination.Parth Patel
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordinationsarunkutti
 
a26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptxa26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptxTesloachKongGilo
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revisedBasudev patra
 
Your electrical safety specilist for all equipments Powered AC and DC
Your electrical safety specilist for all equipments   Powered AC and DCYour electrical safety specilist for all equipments   Powered AC and DC
Your electrical safety specilist for all equipments Powered AC and DCMahesh Chandra Manav
 
Smart – Optimizer ECOD
Smart – Optimizer ECODSmart – Optimizer ECOD
Smart – Optimizer ECODAndrew Dmitrev
 
Littelfuse Fuseology Basics
Littelfuse Fuseology BasicsLittelfuse Fuseology Basics
Littelfuse Fuseology BasicsLittelfuse
 
Surge Protect, a critical issue you could not fail to know while implementing...
Surge Protect, a critical issue you could not fail to know while implementing...Surge Protect, a critical issue you could not fail to know while implementing...
Surge Protect, a critical issue you could not fail to know while implementing...Victor Lee
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSatish Pydimarla
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices pptZuhairQadri
 

Similar to Shortcircuit switching making__breaking_capacity (20)

Application data explusion links
Application data explusion linksApplication data explusion links
Application data explusion links
 
Tecnical aplicacion1 abb
Tecnical aplicacion1 abbTecnical aplicacion1 abb
Tecnical aplicacion1 abb
 
Ocpd 07-23-13
Ocpd 07-23-13Ocpd 07-23-13
Ocpd 07-23-13
 
01. hrc din fuses 3 na
01. hrc din fuses  3 na01. hrc din fuses  3 na
01. hrc din fuses 3 na
 
01. hrc din fuses 3 na
01. hrc din fuses  3 na01. hrc din fuses  3 na
01. hrc din fuses 3 na
 
Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazard
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
 
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions FinalDo's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
 
Thông số kĩ thuật siemens fuse 001
Thông số kĩ thuật siemens fuse 001Thông số kĩ thuật siemens fuse 001
Thông số kĩ thuật siemens fuse 001
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
Insulation coordination.
Insulation coordination.Insulation coordination.
Insulation coordination.
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordination
 
a26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptxa26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptx
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised
 
Your electrical safety specilist for all equipments Powered AC and DC
Your electrical safety specilist for all equipments   Powered AC and DCYour electrical safety specilist for all equipments   Powered AC and DC
Your electrical safety specilist for all equipments Powered AC and DC
 
Smart – Optimizer ECOD
Smart – Optimizer ECODSmart – Optimizer ECOD
Smart – Optimizer ECOD
 
Littelfuse Fuseology Basics
Littelfuse Fuseology BasicsLittelfuse Fuseology Basics
Littelfuse Fuseology Basics
 
Surge Protect, a critical issue you could not fail to know while implementing...
Surge Protect, a critical issue you could not fail to know while implementing...Surge Protect, a critical issue you could not fail to know while implementing...
Surge Protect, a critical issue you could not fail to know while implementing...
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices ppt
 

Shortcircuit switching making__breaking_capacity

  • 1. electrical-engineering-portal.com http://electrical-engineering-portal.com/short-circuit-switching-making-breaking-capacity Short-circuit switching (making/breaking) capacity Edvard Short-circuit switching (making / breaking) capacity Definition of switching capacity The switching capacity is the r.m.s value of a current at a given power factor cos φ as well as a given rated voltage at which a switchgear or a fuse can still shut-off under specified conditions in an operationally safe way. Both the short-circuit making capacity as well as the short-circuit breaking capacity of circuit breakers must be larger than or equal to the prospective short-circuit current at the place of installation. If this is not the case, then a suitable backup protection (for example a fuse) should be provided to ensure the required switching capacity of the device combination. Data regarding devices for backup protection are given in the technical documentation. Rated short-circuit making capacityIcm The rated short-circuit making capacity Icm is a quantity that according to regulations must be in a certain ratio to the rated ultimate short-circuit breaking capacity Icu and that has to be guaranteed by the device manufacturer. This is not a variable that must be considered by the user, however it ensures that a circuit breaker is in the position to connect onto a short-circuit – and to disconnect it subsequently.
  • 2. Rated short-circuit breaking capacity ICU and ICS IEC 60947-2 makes distinction between the rated ultimate short-circuit breaking capacity ICU and the rated service short-circuit breaking capacity ICS: Rated ultimate short-circuit breaking capacityICU ICU is the maximum breaking capacity of a circuit breaker at an associated rated operational voltage and under specified conditions. ICU is expressed in kA and must be at least as large as the prospective short-circuit current at the site of installation. Circuit breakers that have switched-off at the level of the ultimate short-circuit breaking capacity, are reduced serviceable afterwards and should at least be checked regarding functionality. There may be changes in the overload trip characteristic and increased temperature rise due to the erosion of contact material. Rated service short-circuit interrupting capacity ICS ICS values are usually lower than the values for ICU. Circuit breakers that have been switching-off at the level of the service short-circuit breaking capacity continue to be serviceable afterward. In plants in which interruptions to operations must be kept as short as possible, product selection should be carried out based on ICS. Breaking capacity of fuses The same applies to fuses as to circuit breakers with respect to the I CU: at the given rated operational voltage, the rated breaking capacity must be at least as large as the prospective short-circuit current at the site of installation. Reference: Low-Voltage Switchgear and Controlgear – Allen Bradley Source: http://electrical-engineering-portal.com/short-circuit-switching- making-breaking-capacity