More Related Content Similar to WWT Magnetic Flow Meter, EMI Signal Analysis (20) WWT Magnetic Flow Meter, EMI Signal Analysis1. Signal Test 5-Dec 6-Dec 7-Dec 8-Dec 10-Dec 11-Dec 12-Dec
Record Short Test 1 day 1 day 1 day 2 days 1 day 1 day
Holding Tank Transfer Totalizer (Optiflux) 19.4 391.6 734.7 1224.9 1531.1 1931.6 2295.4
Discharge Water Totalizer (Optiflux) 19.6 555.9 1059.9 1884.8 2396.5 3015.9 3429.2
Holding Tank Transfer Totalizer (PLC) 19 383 724 490 796 1197 1568
Discharge Tank Totalizer (PLC) 20 545 1068 845 1403 2109 2672
IWO Transfer Totalizer (Optiflux) 335.4 335.4
Do FM and PLC work ?
IWO Transfer Totalizer (PLC) 0 0 0
IWM Transfer Totalizer (Optiflux) 218915 21962.7
IWM Transfer Totalizer (PLC) Does PLC work ? 0 0 0 measurement
IWO1 Totalizer (Optiflux) 3253.4 3257.7 3261.1 of holding
transfer
IWO1 Totalizer (PLC) 23 28 32
IWO2 Totalizer (Optiflux) 3433.4 3434.1 3435.1
IWO2 Totalizer (PLC) 1 1 2 discharge record
by gravity flow
IWM Totalizer (Optiflux) 16649.2 16650.1 16652.1
IWM Totalizer (PLC) 7 8 10
IWG Totalizer (Optiflux) 11961 12276.9 12534.2
IWG Totalizer (PLC) 1518 1841 2108
Is deviation OK ?
Calculation
Volume transferred (Holding) 19.4 372.2 343.1 490.2 306.2 400.5 363.8
Volume transferred (Discharge) 19.6 536.3 504 824.9 511.7 619.4 413.3 Discharge-Holding Deviation
PLC recording (Holding) 19 364 341 490 306 401 371 (see schematic process flow)
PLC recording (Discharge) 20 525 523 845 558 706 563 80% 600
Totalizer Deviation (Optiflux) 1.0% 44.1% 46.9% 68.3% 67.1% 54.7% 13.6% 70%
500
Communication Error Rate (Holding Tank) 0.0% -2.2% -0.6% 0.0% 0.0% 0.2% 2.2% 60%
Communication Error Rate (Discharge) 5.3% -2.1% 3.8% 2.5% 9.2% 14.1% 36.3% 400
50%
PLC reset PLC reset
40% 300
short test shield connection finished
30%
200
Other Flow Meter Calc Is error rate OK ? 20%
100
Volume Transferred (IWO1) 4.3 3.4 10%
PLC Recording 5 4 0% 0
Communication Error Rate (IWO1) 25.0% 33.3% 5-Dec 6-Dec 7-Dec 8-Dec 9-Dec 10-Dec 11-Dec 12-Dec
Volume Transferred (IWO2) 0.7 1 Series1 Series2
PLC Recording 0 1
Discharge-Holding to PLC
Volume Transferred (IWM) 0.9 2 Communication Error Rate
PLC Recording 1 2 20 mA current loop - HART™
50.0% 600
Volume Transferred (IWG) 315.9 257.3
PLC Recording 323 267 40.0% 500
Communication Error Rate (IWG) 2.5% 3.9% 30.0% 400
20.0% 300
10.0% 200
0.0% 100
5-Dec 6-Dec 7-Dec 8-Dec 9-Dec 10-Dec 11-Dec 12-Dec
-10.0% 0
Series1 Series2 Series3