VM1: innovation in power technology
Vacuum circuit-breaker with magnetic
actuator
Product presentation
October, 2009
VM1
Vacuum circuit-breaker with magnetic actuator
Die Summe von Vorteilen
 Keine Wartung
 Wenige Einzelteile
 Einfache mechanische Abläufe
 Sehr hohe Zuverlässigkeit
 Hoher Qualitätsstandard
 Sehr hohe Lebensdauer
Main Characteristics
• Maintenance-free
• Extremely high number of operating cycles
• Electronic controller with sensor technology
• Vacuum interrupters embedded in epoxy resin
• High quality standard
• Compatible with conventional circuit-breakers
• For universal applications worldwide
VM1
VM1
Rated voltage kV 12 17.5 24
Rated current A ...2500 ...2500 ...2500
Rated short-circuit kA ...31.5 ...31.5 ...25
breaking current
VM1
Emergency manual breaking
mechanism
Electronic controller
Magnetic actuator
Capacitor
Inductive sensors for position
detection
VM1
VM1
Main characteristics
 Maintenance-free
 Control of the position open/closed with inductive sensors
 Magnetic actuator with extremely high number of operating cycles
 up to 100,000 operating cycles for breaking capacity up to 25 kA and rated current
up to 1250 A
 up to 50,000 operating cycles with rated current > 1600 A and/or breaking capacity
> 31.5 kA
 Embedding technology to protect vacuum interrupters
 High quality standard
 Interchangeable with VD4
 Developed for universal applications worldwide
 Emergency mechanical opening operation
VM1
Functional diagram of electronic controller
VM1
-SO4 Undervoltage opening (only with
ED2.0 Full Option)
-SL1 Contact locking the CB closing
-SO3 Auxiliary and safety open (2^ open
command from remote)
-SO2 Open command from remote
-SC2 Close command from remote
DO7 CB Remote Open
DO6 Unit Not Ready
DO5 Unit Ready
DO2 CB closed
DO1 CB open
24 .. 48V AC / 24 .. 60 V DC
100 .. 240V AC / 110 .. 250 V DC
Auxiliary voltage supply
VM1
Power supply and
electronic controller Capacitor Inductive sensors
VM1
Magnetic actuator
VM1
Representation of magnetic flux density distribution
Magnetic latching in end-of-run
position
Armature position: 0 mm
Ampere-turns: 0
Magnetic latching and action of
the magnetic field of a coil
Armature position: 0 mm
Ampere-turns: 12500
Moving armature in opposing
position and magnetic end-of-run
latching
Armature position: 20 mm
Ampere-turns: 5000
VM1
Reduction of the magnetic flux density of Koerdym 280 as a function of the lifetime t at an ambient
temperature of 120° C
VM1
Basic version
 Closing pushbutton (SC1)
 Opening pushbutton (SO1)
 Mechanical operation counter
 Mechanical signalling device for circuit-breaker open/closed
 Emergency manual opening device
 Lever for manual emergency opening
 Lamp signalling “READY” for the operation (PRDY)
 Capacitors for storing energy for the operation
 Mobile connector for direct connection to the sockets of the
electronic module, to cable the auxiliary circuits
 ED2.0 standard version control module
VM1
ED2.0 control module standard version
 Signalling contacts without potential, fitted with relay, with the following
functions:
 N° 1 contact signalling circuit-breaker open (DO1)
 N° 1 contact signalling circuit-breaker closed (DC1)
 N° 1 contact signalling circuit-breaker ready for the operation
(capacitors charged and check of circuit-breaker state) (DR) *
 N° 1 contact signalling circuit-breaker not ready for the operation (DN,
normally closed)
 N° 1 transient contact with momentary closing during the opening
operation (DOR).
Remark: with the circuit-breaker not supplied (without auxiliary power supply) these
contacts are open, except the contact signalling circuit-breaker not ready for the
operation (DN).
*Not available in some versions.
VM1
ED2.0 control module standard version
 2 feeder power supply:
 Type 1: 24 ... 48 V AC / 24 ... 60 V DC
 Type 2: 100 ... 240 V AC / 110 ... 250 V DC
Binary inputs (logical inputs) for remote control:
 N° 1 input for closing control (-SC2)
 N° 1 input for opening control (-SO2)
 N° 1 input for additional opening control (-SO3)
 N° 1 input for circuit-breaker opening on direct command from the
protection release PR512 (-SO5)
 N° 1 input for lock on closing control (the same function of the locking
electromagnet in the mechanical actuator of the VD4 circuit-breaker)
(-SL1)
Binary inputs:
 24 ... 240 V AC (– 15% ... + 10%)
 24 ... 250 V DC (– 30% ... + 10%)
 (minimum duration of the impulse is 20 ms)
VM1
ED2.0 control module standard version
 Functions:
 Self-opening following determination of incorrect state of circuit-
breaker
 Self-opening following load threshold of the capacitors lower
than the minimum value required for the opening and closing
operation
 Anti-pumping relay function
 Trip-free function
 Monitoring of capacitor load with feeder turning itself off in the
case of exceeding the maximum load level
(these functions can be disabled by means of dip-switches)
VM1
ED2.0 control module full option version (on request)
 Signalling contacts without potential, fitted with relay, with the following
functions:
 N° 2 contacts signalling circuit-breaker open (DO1, DO2)
 N° 2 contacts signalling circuit-breaker closed (DC1, DC2)
 N° 1 contact signalling circuit-breaker ready for the operation
(capacitors charged and check of circuit-breaker state) (DR)
 N° 1 contact signalling circuit-breaker not ready for the
operation (DN, normally closed)
 N° 1 transient contact with momentary closing during the
opening operation (DOR)
Remark: difference respect to ED2.0 control module basic version
VM1
ED2.0 control module full option version (on request)
 Binary inputs (logical inputs) for remote control:
 N° 1 input for closing control (-SC2)
 N° 1 input for opening control (-SO2)
 N° 1input for additional opening control (-SO3)
 N° 1 input for circuit-breaker opening on direct command from
the protection release PR512 (-SO5)
 N° 1 input for lock on closing control (the same function of the
locking electromagnet in the mechanical actuator of the VD4
circuit-breaker) (-SL1)
 N° 1 input as undervoltage control for (-S04)
Remark: difference respect to ED2.0 control module basic version
VM1
ED2.0 control module full option version (on request)
 Functions:
 Self-opening following determination of incorrect state of circuit-
breaker
 Self-opening following load threshold of the capacitor lower than
the minimum value required for the opening and closing
operation
 Anti-pumping relay function
 Trip-free function
 Monitoring of capacitor load with feeder turning itself off in the
case of exceeding the maximum load level
 Undervoltage function with selection of the reference rated
voltage and with possibility of delaying the opening from 0 to 5 s
(-SO4)
 Watchdog of the electronic power circuit with feeder turning itself
off in the case of overtemperature and/or overcurrent
 Slow capacitor charging function (the power load passes from
100 watt to 40 watt, doubling the charging time)
 Monitoring continuity of the opening and closing coils
 Watchdog (DN)
 Additional safety opening command function
Remark: difference respect to ED2.0 control module basic version
VM1
Accessories available (on request)
 Signalling auxiliary contacts circuit-breaker open/closed
 Fixed circuit-breaker (-BB1; -BB2; -BB3; -BB8):
 Set of 5 make contacts plus 5 break contacts
 Set of 10 make contacts plus 10 break contacts
(alternatively)
 Withdrawable circuit-breaker (-BB1; -BB2)
 Set of 5 break contacts plus 5 make contacts
 Transmitted contacts of the withdrawable circuit-breaker installed in the
truck (-BT1; -BT2)
These contacts are either in addition or as an alternative to the position
contacts (for signalling circuit-breaker racked out) located in the unit; they
also carry out the function of the position contact (-BT3)
 Position contact of the withdrawable circuit-breaker (-BT3)
With binary input SL1 prevents remote CB closing during translation of the
truck; it is supplied when the transmitted contacts -BT1; -BT2 are not
required
 Motorised truck (-MT) (only for VM1 for UniGear panel)
VM1
Features of the control module ED2.0 (standard version)
 The closing coil can only be activated when VM1 is open
 The opening coil can only be activated when VM1 is closed
 Closing is disabled when an opening command is active at the same time
 De-activation of the opening or closing coil takes place when the relative limit position has been reached
 WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is not reached within 70
ms during a closing (or opening) operation, an opening operation is immediately started to guarantee
reaching a defined safe position in any case.
 Anti-pumping function ensures that only one closing-opening cycle is carried out when a closing command
followed by an opening command is active; active closing command must be cancelled and reset for the
next closing operation.
 Activation of the input for the closing command can be locked by means of an external locking signal.
 Input for the “lock on closing” command must be energised to be able to close the circuit-breaker (without
power it inhibits closing).
VM1
Features of the control module ED2.0 full version
 Undervoltage function
 controls VM1 opening if the voltage applied drops below the limit of tolerance (established by the
Standards)
 rated voltage value to be monitored is set in the factory in conformity with the order specifications
but it can be changed by dip-switches
 to prevent UVR intervention, when the voltage drops below the specified level (e.g. in the case of
motor starting), it is possible to set a trip time
 UVR function can be disabled
 Monitoring function of the actuator closing and opening coil; if a fault is detected, the luminous
“READY” signal on front of the circuit-breaker turns off and the “READY/NOT READY” signalling contacts
are activated.
 Additional safety opening command function; the second input of the control module for the opening
function is designed so that an opening command is carried out directly even in the case of a fault in the
microprocessor.
VM1
Features of the capacitor
 The energy stored is suitable for an O-C-O operating cycle without
recharging
 The energy stored is constantly monitored by measuring the voltage of the
capacitor
 “READY” indication signals:
 application of the power supply voltage
 “ready” status of VM1 for the next operation
 “READY” signal switched on means
 (VM1 in the open position) energy sufficient for one C-O
operating cycle
 (VM1 in the closed position) energy sufficient for one opening
operation; energy available is sufficient for one opening
operation within 60 s from interruption of the auxiliary power
supply (up to 120 s with 2 capacitors)
VM1
Lifetime t of aluminium electrolytic capacitors as a function of the ambient temperature T
VM1
Characteristic data
Switching energy for CO VM1: 150 J
VD4: 115 J
Capacitor voltage 80 V
Closing cycle
VM1 max. 100 J
without capacitor max. 2.3 kW for 54 ms
Making current max. 29 A for 44 ms
Breaking capacity
with capacitor max. 50 J
without capacitor max. 2.1 kW for 27 ms
Breaking current max. 27 A for 30 ms
Opening time 35 ... 45 ms
Arcing time 10 ...15 ms
Total interruption time 45 ... 60 ms
Closing time 50 ... 60 ms
© ABB Group
August 17, 2022 | Slide 26

More Related Content

Similar to SL_VM1(EN)C_1VCP000238-1001.ppt

Advanced motion controls azbe25a20
Advanced motion controls azbe25a20Advanced motion controls azbe25a20
Advanced motion controls azbe25a20Electromate
 
Advanced motion controls azbe10a20
Advanced motion controls azbe10a20Advanced motion controls azbe10a20
Advanced motion controls azbe10a20Electromate
 
K49 Controller
K49 ControllerK49 Controller
K49 ControllerJoseph
 
K32 Controller
K32 ControllerK32 Controller
K32 ControllerJoseph
 
Elc Inverter Introduction
Elc Inverter IntroductionElc Inverter Introduction
Elc Inverter Introductionscottburge
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchIves Equipment
 
Safety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureSafety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureMiller Energy, Inc.
 
United Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterUnited Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterMiller Energy, Inc.
 
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC ConverterXLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converterdegarden
 
Giuliano bozzo moncada hrvs dn s 05-06
Giuliano bozzo moncada hrvs dn s 05-06Giuliano bozzo moncada hrvs dn s 05-06
Giuliano bozzo moncada hrvs dn s 05-06GiulianoBozmm
 
Giuliano bozzo-moncada-hrvs-dn s 05-06
Giuliano bozzo-moncada-hrvs-dn s 05-06Giuliano bozzo-moncada-hrvs-dn s 05-06
Giuliano bozzo-moncada-hrvs-dn s 05-06GiulianoBozmmdf
 
K31 Controller
K31 ControllerK31 Controller
K31 ControllerJoseph
 
Advanced motion controls azbh10a20
Advanced motion controls azbh10a20Advanced motion controls azbh10a20
Advanced motion controls azbh10a20Electromate
 
Fermator door operator_vvvf3
Fermator door operator_vvvf3Fermator door operator_vvvf3
Fermator door operator_vvvf3alconele
 
Advanced motion controls dq111se20a8bdc qd1
Advanced motion controls dq111se20a8bdc qd1Advanced motion controls dq111se20a8bdc qd1
Advanced motion controls dq111se20a8bdc qd1Electromate
 
Advanced motion controls 25a20dd
Advanced motion controls 25a20ddAdvanced motion controls 25a20dd
Advanced motion controls 25a20ddElectromate
 
K48 Controller
K48 ControllerK48 Controller
K48 ControllerJoseph
 

Similar to SL_VM1(EN)C_1VCP000238-1001.ppt (20)

Advanced motion controls azbe25a20
Advanced motion controls azbe25a20Advanced motion controls azbe25a20
Advanced motion controls azbe25a20
 
Advanced motion controls azbe10a20
Advanced motion controls azbe10a20Advanced motion controls azbe10a20
Advanced motion controls azbe10a20
 
K49 Controller
K49 ControllerK49 Controller
K49 Controller
 
K32 Controller
K32 ControllerK32 Controller
K32 Controller
 
Elc Inverter Introduction
Elc Inverter IntroductionElc Inverter Introduction
Elc Inverter Introduction
 
lm3914.pdf
lm3914.pdflm3914.pdf
lm3914.pdf
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature Switch
 
Safety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureSafety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and Pressure
 
United Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterUnited Electric One Series Safety Transmitter
United Electric One Series Safety Transmitter
 
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC ConverterXLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
XLSEMI XL140 2A 380KHz 18V Buck DC to DC Converter
 
Giuliano bozzo moncada hrvs dn s 05-06
Giuliano bozzo moncada hrvs dn s 05-06Giuliano bozzo moncada hrvs dn s 05-06
Giuliano bozzo moncada hrvs dn s 05-06
 
Giuliano bozzo-moncada-hrvs-dn s 05-06
Giuliano bozzo-moncada-hrvs-dn s 05-06Giuliano bozzo-moncada-hrvs-dn s 05-06
Giuliano bozzo-moncada-hrvs-dn s 05-06
 
K31 Controller
K31 ControllerK31 Controller
K31 Controller
 
Compact Inverter WJ200 series
Compact Inverter WJ200 seriesCompact Inverter WJ200 series
Compact Inverter WJ200 series
 
Advanced motion controls azbh10a20
Advanced motion controls azbh10a20Advanced motion controls azbh10a20
Advanced motion controls azbh10a20
 
Fermator door operator_vvvf3
Fermator door operator_vvvf3Fermator door operator_vvvf3
Fermator door operator_vvvf3
 
Advanced motion controls dq111se20a8bdc qd1
Advanced motion controls dq111se20a8bdc qd1Advanced motion controls dq111se20a8bdc qd1
Advanced motion controls dq111se20a8bdc qd1
 
Advanced motion controls 25a20dd
Advanced motion controls 25a20ddAdvanced motion controls 25a20dd
Advanced motion controls 25a20dd
 
14269179.pdf
14269179.pdf14269179.pdf
14269179.pdf
 
K48 Controller
K48 ControllerK48 Controller
K48 Controller
 

Recently uploaded

Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 

Recently uploaded (20)

Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 

SL_VM1(EN)C_1VCP000238-1001.ppt

  • 1. 1VCP000238 – Rev. C, en – Presentation – 2010.01 © ABB Group August 17, 2022 | Slide 1 VM1: innovation in power technology Vacuum circuit-breaker with magnetic actuator Product presentation October, 2009
  • 2. VM1 Vacuum circuit-breaker with magnetic actuator Die Summe von Vorteilen  Keine Wartung  Wenige Einzelteile  Einfache mechanische Abläufe  Sehr hohe Zuverlässigkeit  Hoher Qualitätsstandard  Sehr hohe Lebensdauer Main Characteristics • Maintenance-free • Extremely high number of operating cycles • Electronic controller with sensor technology • Vacuum interrupters embedded in epoxy resin • High quality standard • Compatible with conventional circuit-breakers • For universal applications worldwide
  • 3. VM1 VM1 Rated voltage kV 12 17.5 24 Rated current A ...2500 ...2500 ...2500 Rated short-circuit kA ...31.5 ...31.5 ...25 breaking current
  • 4. VM1 Emergency manual breaking mechanism Electronic controller Magnetic actuator Capacitor Inductive sensors for position detection
  • 5. VM1
  • 6. VM1 Main characteristics  Maintenance-free  Control of the position open/closed with inductive sensors  Magnetic actuator with extremely high number of operating cycles  up to 100,000 operating cycles for breaking capacity up to 25 kA and rated current up to 1250 A  up to 50,000 operating cycles with rated current > 1600 A and/or breaking capacity > 31.5 kA  Embedding technology to protect vacuum interrupters  High quality standard  Interchangeable with VD4  Developed for universal applications worldwide  Emergency mechanical opening operation
  • 7. VM1 Functional diagram of electronic controller
  • 8. VM1 -SO4 Undervoltage opening (only with ED2.0 Full Option) -SL1 Contact locking the CB closing -SO3 Auxiliary and safety open (2^ open command from remote) -SO2 Open command from remote -SC2 Close command from remote DO7 CB Remote Open DO6 Unit Not Ready DO5 Unit Ready DO2 CB closed DO1 CB open 24 .. 48V AC / 24 .. 60 V DC 100 .. 240V AC / 110 .. 250 V DC Auxiliary voltage supply
  • 9. VM1 Power supply and electronic controller Capacitor Inductive sensors
  • 11. VM1 Representation of magnetic flux density distribution Magnetic latching in end-of-run position Armature position: 0 mm Ampere-turns: 0 Magnetic latching and action of the magnetic field of a coil Armature position: 0 mm Ampere-turns: 12500 Moving armature in opposing position and magnetic end-of-run latching Armature position: 20 mm Ampere-turns: 5000
  • 12. VM1 Reduction of the magnetic flux density of Koerdym 280 as a function of the lifetime t at an ambient temperature of 120° C
  • 13. VM1 Basic version  Closing pushbutton (SC1)  Opening pushbutton (SO1)  Mechanical operation counter  Mechanical signalling device for circuit-breaker open/closed  Emergency manual opening device  Lever for manual emergency opening  Lamp signalling “READY” for the operation (PRDY)  Capacitors for storing energy for the operation  Mobile connector for direct connection to the sockets of the electronic module, to cable the auxiliary circuits  ED2.0 standard version control module
  • 14. VM1 ED2.0 control module standard version  Signalling contacts without potential, fitted with relay, with the following functions:  N° 1 contact signalling circuit-breaker open (DO1)  N° 1 contact signalling circuit-breaker closed (DC1)  N° 1 contact signalling circuit-breaker ready for the operation (capacitors charged and check of circuit-breaker state) (DR) *  N° 1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)  N° 1 transient contact with momentary closing during the opening operation (DOR). Remark: with the circuit-breaker not supplied (without auxiliary power supply) these contacts are open, except the contact signalling circuit-breaker not ready for the operation (DN). *Not available in some versions.
  • 15. VM1 ED2.0 control module standard version  2 feeder power supply:  Type 1: 24 ... 48 V AC / 24 ... 60 V DC  Type 2: 100 ... 240 V AC / 110 ... 250 V DC Binary inputs (logical inputs) for remote control:  N° 1 input for closing control (-SC2)  N° 1 input for opening control (-SO2)  N° 1 input for additional opening control (-SO3)  N° 1 input for circuit-breaker opening on direct command from the protection release PR512 (-SO5)  N° 1 input for lock on closing control (the same function of the locking electromagnet in the mechanical actuator of the VD4 circuit-breaker) (-SL1) Binary inputs:  24 ... 240 V AC (– 15% ... + 10%)  24 ... 250 V DC (– 30% ... + 10%)  (minimum duration of the impulse is 20 ms)
  • 16. VM1 ED2.0 control module standard version  Functions:  Self-opening following determination of incorrect state of circuit- breaker  Self-opening following load threshold of the capacitors lower than the minimum value required for the opening and closing operation  Anti-pumping relay function  Trip-free function  Monitoring of capacitor load with feeder turning itself off in the case of exceeding the maximum load level (these functions can be disabled by means of dip-switches)
  • 17. VM1 ED2.0 control module full option version (on request)  Signalling contacts without potential, fitted with relay, with the following functions:  N° 2 contacts signalling circuit-breaker open (DO1, DO2)  N° 2 contacts signalling circuit-breaker closed (DC1, DC2)  N° 1 contact signalling circuit-breaker ready for the operation (capacitors charged and check of circuit-breaker state) (DR)  N° 1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)  N° 1 transient contact with momentary closing during the opening operation (DOR) Remark: difference respect to ED2.0 control module basic version
  • 18. VM1 ED2.0 control module full option version (on request)  Binary inputs (logical inputs) for remote control:  N° 1 input for closing control (-SC2)  N° 1 input for opening control (-SO2)  N° 1input for additional opening control (-SO3)  N° 1 input for circuit-breaker opening on direct command from the protection release PR512 (-SO5)  N° 1 input for lock on closing control (the same function of the locking electromagnet in the mechanical actuator of the VD4 circuit-breaker) (-SL1)  N° 1 input as undervoltage control for (-S04) Remark: difference respect to ED2.0 control module basic version
  • 19. VM1 ED2.0 control module full option version (on request)  Functions:  Self-opening following determination of incorrect state of circuit- breaker  Self-opening following load threshold of the capacitor lower than the minimum value required for the opening and closing operation  Anti-pumping relay function  Trip-free function  Monitoring of capacitor load with feeder turning itself off in the case of exceeding the maximum load level  Undervoltage function with selection of the reference rated voltage and with possibility of delaying the opening from 0 to 5 s (-SO4)  Watchdog of the electronic power circuit with feeder turning itself off in the case of overtemperature and/or overcurrent  Slow capacitor charging function (the power load passes from 100 watt to 40 watt, doubling the charging time)  Monitoring continuity of the opening and closing coils  Watchdog (DN)  Additional safety opening command function Remark: difference respect to ED2.0 control module basic version
  • 20. VM1 Accessories available (on request)  Signalling auxiliary contacts circuit-breaker open/closed  Fixed circuit-breaker (-BB1; -BB2; -BB3; -BB8):  Set of 5 make contacts plus 5 break contacts  Set of 10 make contacts plus 10 break contacts (alternatively)  Withdrawable circuit-breaker (-BB1; -BB2)  Set of 5 break contacts plus 5 make contacts  Transmitted contacts of the withdrawable circuit-breaker installed in the truck (-BT1; -BT2) These contacts are either in addition or as an alternative to the position contacts (for signalling circuit-breaker racked out) located in the unit; they also carry out the function of the position contact (-BT3)  Position contact of the withdrawable circuit-breaker (-BT3) With binary input SL1 prevents remote CB closing during translation of the truck; it is supplied when the transmitted contacts -BT1; -BT2 are not required  Motorised truck (-MT) (only for VM1 for UniGear panel)
  • 21. VM1 Features of the control module ED2.0 (standard version)  The closing coil can only be activated when VM1 is open  The opening coil can only be activated when VM1 is closed  Closing is disabled when an opening command is active at the same time  De-activation of the opening or closing coil takes place when the relative limit position has been reached  WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is not reached within 70 ms during a closing (or opening) operation, an opening operation is immediately started to guarantee reaching a defined safe position in any case.  Anti-pumping function ensures that only one closing-opening cycle is carried out when a closing command followed by an opening command is active; active closing command must be cancelled and reset for the next closing operation.  Activation of the input for the closing command can be locked by means of an external locking signal.  Input for the “lock on closing” command must be energised to be able to close the circuit-breaker (without power it inhibits closing).
  • 22. VM1 Features of the control module ED2.0 full version  Undervoltage function  controls VM1 opening if the voltage applied drops below the limit of tolerance (established by the Standards)  rated voltage value to be monitored is set in the factory in conformity with the order specifications but it can be changed by dip-switches  to prevent UVR intervention, when the voltage drops below the specified level (e.g. in the case of motor starting), it is possible to set a trip time  UVR function can be disabled  Monitoring function of the actuator closing and opening coil; if a fault is detected, the luminous “READY” signal on front of the circuit-breaker turns off and the “READY/NOT READY” signalling contacts are activated.  Additional safety opening command function; the second input of the control module for the opening function is designed so that an opening command is carried out directly even in the case of a fault in the microprocessor.
  • 23. VM1 Features of the capacitor  The energy stored is suitable for an O-C-O operating cycle without recharging  The energy stored is constantly monitored by measuring the voltage of the capacitor  “READY” indication signals:  application of the power supply voltage  “ready” status of VM1 for the next operation  “READY” signal switched on means  (VM1 in the open position) energy sufficient for one C-O operating cycle  (VM1 in the closed position) energy sufficient for one opening operation; energy available is sufficient for one opening operation within 60 s from interruption of the auxiliary power supply (up to 120 s with 2 capacitors)
  • 24. VM1 Lifetime t of aluminium electrolytic capacitors as a function of the ambient temperature T
  • 25. VM1 Characteristic data Switching energy for CO VM1: 150 J VD4: 115 J Capacitor voltage 80 V Closing cycle VM1 max. 100 J without capacitor max. 2.3 kW for 54 ms Making current max. 29 A for 44 ms Breaking capacity with capacitor max. 50 J without capacitor max. 2.1 kW for 27 ms Breaking current max. 27 A for 30 ms Opening time 35 ... 45 ms Arcing time 10 ...15 ms Total interruption time 45 ... 60 ms Closing time 50 ... 60 ms
  • 26. © ABB Group August 17, 2022 | Slide 26