2. VM1
Vacuum circuit-breaker with magnetic actuator
Die Summe von Vorteilen
Keine Wartung
Wenige Einzelteile
Einfache mechanische Abläufe
Sehr hohe Zuverlässigkeit
Hoher Qualitätsstandard
Sehr hohe Lebensdauer
Main Characteristics
• Maintenance-free
• Extremely high number of operating cycles
• Electronic controller with sensor technology
• Vacuum interrupters embedded in epoxy resin
• High quality standard
• Compatible with conventional circuit-breakers
• For universal applications worldwide
3. VM1
VM1
Rated voltage kV 12 17.5 24
Rated current A ...2500 ...2500 ...2500
Rated short-circuit kA ...31.5 ...31.5 ...25
breaking current
6. VM1
Main characteristics
Maintenance-free
Control of the position open/closed with inductive sensors
Magnetic actuator with extremely high number of operating cycles
up to 100,000 operating cycles for breaking capacity up to 25 kA and rated current
up to 1250 A
up to 50,000 operating cycles with rated current > 1600 A and/or breaking capacity
> 31.5 kA
Embedding technology to protect vacuum interrupters
High quality standard
Interchangeable with VD4
Developed for universal applications worldwide
Emergency mechanical opening operation
8. VM1
-SO4 Undervoltage opening (only with
ED2.0 Full Option)
-SL1 Contact locking the CB closing
-SO3 Auxiliary and safety open (2^ open
command from remote)
-SO2 Open command from remote
-SC2 Close command from remote
DO7 CB Remote Open
DO6 Unit Not Ready
DO5 Unit Ready
DO2 CB closed
DO1 CB open
24 .. 48V AC / 24 .. 60 V DC
100 .. 240V AC / 110 .. 250 V DC
Auxiliary voltage supply
11. VM1
Representation of magnetic flux density distribution
Magnetic latching in end-of-run
position
Armature position: 0 mm
Ampere-turns: 0
Magnetic latching and action of
the magnetic field of a coil
Armature position: 0 mm
Ampere-turns: 12500
Moving armature in opposing
position and magnetic end-of-run
latching
Armature position: 20 mm
Ampere-turns: 5000
12. VM1
Reduction of the magnetic flux density of Koerdym 280 as a function of the lifetime t at an ambient
temperature of 120° C
13. VM1
Basic version
Closing pushbutton (SC1)
Opening pushbutton (SO1)
Mechanical operation counter
Mechanical signalling device for circuit-breaker open/closed
Emergency manual opening device
Lever for manual emergency opening
Lamp signalling “READY” for the operation (PRDY)
Capacitors for storing energy for the operation
Mobile connector for direct connection to the sockets of the
electronic module, to cable the auxiliary circuits
ED2.0 standard version control module
14. VM1
ED2.0 control module standard version
Signalling contacts without potential, fitted with relay, with the following
functions:
N° 1 contact signalling circuit-breaker open (DO1)
N° 1 contact signalling circuit-breaker closed (DC1)
N° 1 contact signalling circuit-breaker ready for the operation
(capacitors charged and check of circuit-breaker state) (DR) *
N° 1 contact signalling circuit-breaker not ready for the operation (DN,
normally closed)
N° 1 transient contact with momentary closing during the opening
operation (DOR).
Remark: with the circuit-breaker not supplied (without auxiliary power supply) these
contacts are open, except the contact signalling circuit-breaker not ready for the
operation (DN).
*Not available in some versions.
15. VM1
ED2.0 control module standard version
2 feeder power supply:
Type 1: 24 ... 48 V AC / 24 ... 60 V DC
Type 2: 100 ... 240 V AC / 110 ... 250 V DC
Binary inputs (logical inputs) for remote control:
N° 1 input for closing control (-SC2)
N° 1 input for opening control (-SO2)
N° 1 input for additional opening control (-SO3)
N° 1 input for circuit-breaker opening on direct command from the
protection release PR512 (-SO5)
N° 1 input for lock on closing control (the same function of the locking
electromagnet in the mechanical actuator of the VD4 circuit-breaker)
(-SL1)
Binary inputs:
24 ... 240 V AC (– 15% ... + 10%)
24 ... 250 V DC (– 30% ... + 10%)
(minimum duration of the impulse is 20 ms)
16. VM1
ED2.0 control module standard version
Functions:
Self-opening following determination of incorrect state of circuit-
breaker
Self-opening following load threshold of the capacitors lower
than the minimum value required for the opening and closing
operation
Anti-pumping relay function
Trip-free function
Monitoring of capacitor load with feeder turning itself off in the
case of exceeding the maximum load level
(these functions can be disabled by means of dip-switches)
17. VM1
ED2.0 control module full option version (on request)
Signalling contacts without potential, fitted with relay, with the following
functions:
N° 2 contacts signalling circuit-breaker open (DO1, DO2)
N° 2 contacts signalling circuit-breaker closed (DC1, DC2)
N° 1 contact signalling circuit-breaker ready for the operation
(capacitors charged and check of circuit-breaker state) (DR)
N° 1 contact signalling circuit-breaker not ready for the
operation (DN, normally closed)
N° 1 transient contact with momentary closing during the
opening operation (DOR)
Remark: difference respect to ED2.0 control module basic version
18. VM1
ED2.0 control module full option version (on request)
Binary inputs (logical inputs) for remote control:
N° 1 input for closing control (-SC2)
N° 1 input for opening control (-SO2)
N° 1input for additional opening control (-SO3)
N° 1 input for circuit-breaker opening on direct command from
the protection release PR512 (-SO5)
N° 1 input for lock on closing control (the same function of the
locking electromagnet in the mechanical actuator of the VD4
circuit-breaker) (-SL1)
N° 1 input as undervoltage control for (-S04)
Remark: difference respect to ED2.0 control module basic version
19. VM1
ED2.0 control module full option version (on request)
Functions:
Self-opening following determination of incorrect state of circuit-
breaker
Self-opening following load threshold of the capacitor lower than
the minimum value required for the opening and closing
operation
Anti-pumping relay function
Trip-free function
Monitoring of capacitor load with feeder turning itself off in the
case of exceeding the maximum load level
Undervoltage function with selection of the reference rated
voltage and with possibility of delaying the opening from 0 to 5 s
(-SO4)
Watchdog of the electronic power circuit with feeder turning itself
off in the case of overtemperature and/or overcurrent
Slow capacitor charging function (the power load passes from
100 watt to 40 watt, doubling the charging time)
Monitoring continuity of the opening and closing coils
Watchdog (DN)
Additional safety opening command function
Remark: difference respect to ED2.0 control module basic version
20. VM1
Accessories available (on request)
Signalling auxiliary contacts circuit-breaker open/closed
Fixed circuit-breaker (-BB1; -BB2; -BB3; -BB8):
Set of 5 make contacts plus 5 break contacts
Set of 10 make contacts plus 10 break contacts
(alternatively)
Withdrawable circuit-breaker (-BB1; -BB2)
Set of 5 break contacts plus 5 make contacts
Transmitted contacts of the withdrawable circuit-breaker installed in the
truck (-BT1; -BT2)
These contacts are either in addition or as an alternative to the position
contacts (for signalling circuit-breaker racked out) located in the unit; they
also carry out the function of the position contact (-BT3)
Position contact of the withdrawable circuit-breaker (-BT3)
With binary input SL1 prevents remote CB closing during translation of the
truck; it is supplied when the transmitted contacts -BT1; -BT2 are not
required
Motorised truck (-MT) (only for VM1 for UniGear panel)
21. VM1
Features of the control module ED2.0 (standard version)
The closing coil can only be activated when VM1 is open
The opening coil can only be activated when VM1 is closed
Closing is disabled when an opening command is active at the same time
De-activation of the opening or closing coil takes place when the relative limit position has been reached
WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is not reached within 70
ms during a closing (or opening) operation, an opening operation is immediately started to guarantee
reaching a defined safe position in any case.
Anti-pumping function ensures that only one closing-opening cycle is carried out when a closing command
followed by an opening command is active; active closing command must be cancelled and reset for the
next closing operation.
Activation of the input for the closing command can be locked by means of an external locking signal.
Input for the “lock on closing” command must be energised to be able to close the circuit-breaker (without
power it inhibits closing).
22. VM1
Features of the control module ED2.0 full version
Undervoltage function
controls VM1 opening if the voltage applied drops below the limit of tolerance (established by the
Standards)
rated voltage value to be monitored is set in the factory in conformity with the order specifications
but it can be changed by dip-switches
to prevent UVR intervention, when the voltage drops below the specified level (e.g. in the case of
motor starting), it is possible to set a trip time
UVR function can be disabled
Monitoring function of the actuator closing and opening coil; if a fault is detected, the luminous
“READY” signal on front of the circuit-breaker turns off and the “READY/NOT READY” signalling contacts
are activated.
Additional safety opening command function; the second input of the control module for the opening
function is designed so that an opening command is carried out directly even in the case of a fault in the
microprocessor.
23. VM1
Features of the capacitor
The energy stored is suitable for an O-C-O operating cycle without
recharging
The energy stored is constantly monitored by measuring the voltage of the
capacitor
“READY” indication signals:
application of the power supply voltage
“ready” status of VM1 for the next operation
“READY” signal switched on means
(VM1 in the open position) energy sufficient for one C-O
operating cycle
(VM1 in the closed position) energy sufficient for one opening
operation; energy available is sufficient for one opening
operation within 60 s from interruption of the auxiliary power
supply (up to 120 s with 2 capacitors)
24. VM1
Lifetime t of aluminium electrolytic capacitors as a function of the ambient temperature T
25. VM1
Characteristic data
Switching energy for CO VM1: 150 J
VD4: 115 J
Capacitor voltage 80 V
Closing cycle
VM1 max. 100 J
without capacitor max. 2.3 kW for 54 ms
Making current max. 29 A for 44 ms
Breaking capacity
with capacitor max. 50 J
without capacitor max. 2.1 kW for 27 ms
Breaking current max. 27 A for 30 ms
Opening time 35 ... 45 ms
Arcing time 10 ...15 ms
Total interruption time 45 ... 60 ms
Closing time 50 ... 60 ms