Medium Voltage Soft Starters
SOLCON
SOLCON
Soft Starting
Limiting the Starting Current :
Long supply cables
Loaded transformers
Diesel generator supply
Limiting the Starting Torque :
Preventing Water Hammer
High inertia loads
Complicated mechanical systems
Reducing maintenance
SOLCON
D.O.L vs. Soft Start
D.O.L Soft-starter
Motor
Current
Motor
Torque
SOLCON
Soft Starter Advantages
Electronic soft starters provide:
Solid state, no moving parts, reduced maintenance
Reduction of starting current
Reduction of starting torque & mechanical shock
Smooth acceleration & deceleration
Closed current loop starting
Easy adjustments for all applications
Comprehensive motor protection package
Special features: “Pump Control”, Soft Stop, Dual Adjustments.
Communication for full setting, control and supervision
SOLCON
HRVS-DN Advantages
 Complete line 60-1800A, 1500-15000V
 Third generation, Microprocessor design
 Superior Starting & Stopping Characteristics: Torque Control, Current Control
and Pump Control
 Advanced Motor Protection package
 Easy commissioning and maintenance - field testing with a L.V. motor
 Patent pending - Wireless SCR firing control system
 Patent pending – Electronic Voltage measurement system
 Fiber optic control (also for mains voltage measurement)
 Meets “Partial Discharge Test Requirements”
 Friendly operation -Multi Languages LCD, English, German, French & Spanish
 Communication: MODBUS, PROFIBUS, TCP/IP, DEVICENET and others
 Chassis or cabinet type, various options are available
 Solcon is offering the most advanced M.V. soft Starter
SOLCON
Heavy Duty Design
 Starting & Operation conditions
 Max. Starting Current 400 % I n
 Max. Starting Time 30 sec.
 Max. Ambient Temp. 40°C
 Max. Number of Starts 4 starts / hour at max.
starting conditions
 Special cases: One starter for few motors.
SOLCON
Typical Applications
 Typical applications:
 Pumps
 Chillers
 Conveyors
 Compressors
 Fans and blowers
 Complicated mechanical drives and loads
 Marine applications
 Thrusters
 LNG Ships
 Pumps-ballast
 Hydraulic systems
SOLCON
Medium Voltage motor starting
 Range 50-1000A, 1500-13800V
 Standard configuration includes:
 - Soft starter
 - Line Contactor
 - Bypass Contactors
 - Cabinet IP30
 - L.V. Controls
 Options are available
L.V.
Compartmen
t
M.V.
Compartme
nt upper
door
M.V.
Compartment
lower door
Operating
Buttons
M.V.
Compartment
Main (central)
door
Status
indications
Operating
Panel
(behind glass)
Emergency stop
Motor Protection
Relay
(Optional)
Name plate
with soft
starter data
SOLCON
Options
In H.V compartment
- Line Switch (On / Off load)
- Main Fuses (opt. Striker pin)
- Incoming Section
- Space Heater, Thermostat, C/B
- Fan at top, air inlet at bottom, C/B
- Special Painting
In L.V compartment
- Motor Protection Relay (MPR 2000)
- Digital Panel Meter (DPM-10)
- Other control components
Line Connection
(in the back)
Ground
Bus
Line
Contactor
Soft Starter
Power
Section
Cabinet
Light
Bypass
Contactor
Electronic
Transformer
(Transmitter)
Motor
Connection
Door
Switch
Space
Heater
Customer Control Terminals
SOLCON
PERDIDAS ELECTRICAS
P = 3 x Vscrs x I
EXAMPLE
4.16KV, 200 A, 1200 KW, 1600 HP
P = 3 x (2x3) x 4IFLA
P = 14.4 KW
2starts x 20 seconds in one hour
Pav = 14400 x 40 /3600 = 160 W
11
11
By-pass
Contactor
Fault
x2
x1
Line
Contactor
LightN ~
230VAC
Off
On
Contactor
Line
On
By-pass
Contactor
x2
x1
x2x2
x1
2 Red
x2
x1
x2
x1
GreenGreen Red
Line contactor
RC1
92
A2
10
A1
A2
2
A1
C1
9
21
7
7
4
3
C2
FT
22
6
RC1
22
3
6
24
21
21
24
24
21
8
21
18
24
21
22
24
11
MPR
Trip
14
11
14
17
18
17
24
10
10
12
21 C1
11
6
5
6
5
16A
10A
ES2 (Customer)
1
~230VAC
2
1
Control
e2 2
3P
Acceleration
Immediate
End0f
Fault
2
2
A2
C2
A1
A2
10
A1
Remote
20
21
186
SoftStarter
321 4 5 12987 1011 151413 1617
19
TR1*
11
14
212019
RC1
Aux
TB2
TB1
Immediate By-pass DoorTrip
K1 C2 LS1FT/1
31
34
14
L
13 0
16
1NO
-Start
31
34 16
1NC
-Stop 15
15
Contactor Switch
Start
D.O.L.
3
1
B.P.
1
2
12
2
54
53
RS
K3RS
e1 e2
ES1
LS1
4
4
3
LR1 L1 L2 L3 L4
6
RC1
K1
FT
9
3P
22
10
A2
A1
10
A2
A1
FT/1FT FR
3P 3P
6
K2
-TB4-Internal Terminals-TB1,
-Customer Terminals-TB2,TB3
Remarks:
20
21
FR
RS
R
FT
3P
10
A2
A1
10
A2
10
A2
A1 A1
2 2 2
K2
x2
x1
White
2
A2
10
A1
RSL5K3K1
Space Heater
2
N~230V
~230VAC
60W
H
3
~230V
1
1 HS
HS
2x120 Pri.
24Vac Sec.
Module
Power
19/1
60W
H
SOLCON
Patent Pending SCR Firing
 Fully isolated HV from LV, “wireless” system (patent pending)
 Diagnostics with firing and fault indication LED’s
SOLCON
EPT (Electronic Potential Transformer)
EPT
Transmitter
&
Receiver
The EPT (Patent Pending)
* Measures 3 phase current
and turns it to a PWM
sign.
Transmits it to the receiver
which turns the PWM sign
to a sine wave.
* The connection between
the transmitter and the
receiver is by fiber optic
wires for maximum safety
and reliability.
SOLCON
Power Section
Power section with 12-18 thyristors 2300-6900V
∼3
L 1
L 2
L 3
SOLCON
SCR’s Firing System
The left SCR conducts during
the positive period of the sine wave,
when Vc is On and can be turned
Off when the current is at zero
crossing.
Vc
SOLCON
SCR’s Firing System
The other SCR is coupled in an
anti-parallel method and conducts
in the negative half cycle.
Vc
SOLCON
SCR’s Firing System
SCR firing controls the soft starter output voltage
U start
Zero Crossing
t soft start
Phase Control
SOLCON
Calculating Motor’s Torque
Motor torque with soft starter
M soft = ( U soft / U n) 2
* M start
Assuming M start = 1.8 * M n
Assuming U start =0.5 Un M=(0.50)2
M soft = (0.25) * 1.8 = 0.45 M start
Torque is reduced by the square of the voltage reduction
SOLCON
Block Diagram
EPT
Transmiter
(Tx)
Fiber
optic
Line
Contactor
ML2
L1
Feedback
Sensor
Firing
Trafo
.. / 24V
Fiber
optic
Molex
Plug
C/T
Control
Module
X 6
Power Supply
Firing Control
EPT
Receiver
(Rx)
L3
By-pass
Contactor
SOLCON
L.V. Compartment
Connecting Plug
HRVS-DN Control Module
SOLCON
Control Module
MMI, local or
door mounted
(IP30)
Control
Terminals
Fiber optic
connections
SOLCON
The Control Module
* Analogue board
Analogue output
related to motor’s
current
Insulation board
Communication
Board, RS 485
Power
Supply
Board
EEPROM Dip Switch
µP
Fiber optic
board Optional cards:
3 Auxiliary Relays
SOLCON
Dip Switch
1 Display Minimum Maximum
2 Tacho feedback Disabled Enabled
3 Mains / Generator Mains Generator
4 Always Off
5+6 Language selector English, French, German, Spanish
7 Extended range settings Disabled Enabled
8 Software lock Unlocked Locked
No. Function Off On
1 2 3 4 5 6 7 8 Off
(factory default)
SOLCON
Line, Bypass & Capacitor Contactors
Power factor correction
Capacitors - when used, must
be at Line side, on top of
starter.
L1 L2 L3
∼3
Bypass Contactor
(must be used)
Line Contactor
(must be used)
SOLCON
Control Wiring
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Stop
SoftStop
Start
Input#3(Ext.Fault-1)
Input#4(Ext.Fault-2)
Common-B
Aux.Contact
“Immediate”
L1
N
FaultContact
(Fault/FailSafe)
Aux.Contact
EndOfAccel.”
Input#1-Test/Reset
Common-A
Control CommandsControl
Supply
Input#2-D.Adjust/Reset
Ext. Faults
Note: Terminals 2, 19-20-21 differ from same in low voltage starter RVSDN
FiringTransformerControl
SOLCON
Control wiring - optional cards
25
26
27
Motor Insulation Alarm
23
24
22
Communication Board
(+) RS485
(-) RS485
N.C.
25
26
27
Digital Tacho Board
Encoder
(-)
(+)
Ground
(+) Analogue
(-) Analogue
Thermistor
Thermistor
28
29
30
31
32
Analogue I/O Board
Ground
SOLCON
Control Supply Voltage
L N Same voltage for Control Supply (1-3) and Control Commands (4-9)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Common
SoftStop
Test/Reset
D.Adjust/Reset
Start
Stop
Electronics
SOLCON
Control Supply Voltage
Different voltages for Control Commands (4-9)
can be AC or DC (must be specified)
NL Control Commands
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Common
SoftStop
Test/Reset
D.Adjust/Reset
Start
Stop
Electronics
SOLCON
Soft Start & Immediate Stop
Motor will soft start when C closes and
stop immediately when C opensL N
1 2 3 4 5 6 7 8 9
Common
SoftStop
Stop
Reset
D.Adjust/Reset
Start
C
SOLCON
Soft Start & Soft Stop
Motor will soft start when C closes
and soft stop when C opensL N
1 2 3 4 5 6 7 8 9
Common
SoftStop
Stop
Reset
D.Adjust/Reset
Start
C
SOLCON
Soft Start, Immediate & Soft Stop
L N
1 2 3 4 5 6 7 8 9
Common
SoftStop
Stop
Reset
D.Adjust/Reset
Start
C2
With Start, Stop push buttons
C1 - Start and Soft Stop
C 2 - Emergency Stop
C1
SOLCON
Start - Stop With Push Buttons
L N
1 2 3 4 5 6 7 8 9
Common
SoftStop
Stop
Reset
D.Adjust/Reset
Start
C1
C – Start button
C2 – Soft Stop button
C1 – Emergency Stop Button
CC2
SOLCON
Remote Resetting
Remote (hardwire) Resetting via terminal 7 or 8
when designated as Reset.
L
1 2 3 4 5 6 7 8 9
Common
SoftStop
Stop
Reset
Start
N
C2C1
Reset
SOLCON
Auxiliary Relays
FaultImmediate
End of
Acceleration
Relay ratings : 8A, 250V, 2000VA
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
SOLCON
“Immediate Relay”
L
1 2 3 4 5 6 7 8 9 10 11 12
Immediate / Shear pin
Relay
Programmable (I/O Parameters) as:
* Immediate - with On and Off delays
* Shear pin - Functions only upon Jam, with On delay
SOLCON
On / Off Time Delays
Off Delay
after soft
stop
On delay
after start
When start / soft Stop
are used
Off delay
after stop
When start / stop
are used
On delay
after start
(Returns upon Stop, Trip, voltage outage)
SOLCON
Example for “Immediate” Operation
Creating special Starting
Curves:
1. Designate “Imm. Relay” as
Immediate, set On Delay time
2. Designate Terminal 8 as “Dual
Adjust”, setting parameter.
3. Connect the N.O contact to the
Dual Adj. Terminal
4. New Current & Torque - are
being developed now
1 2 3 4 5 6 7 8 9 10 11 12
D.Adjust
Immediate
Relay
On delay
Voltage
Ramp-up
SOLCON
Fault Relay
Programmable (I/O Parameters) as:
* Fault - changes position upon fault, returns upon fault reset
* Fault Fail Safe - changes position upon Control Supply (1-3)
connection, returns upon fault.
1 2 3 4…12 13 14 15 16 17 18 19 20 21
Fault Relay
SOLCON
End of Acceleration Relay
L
4…...
End of
Acceleration
Applications
* Operating a valve
* Operating By-Pass contactor
On delay
after End of
Acceleration
13 14 15 16 17 18
(Returns upon Stop, Soft stop, Trip, voltage outage)
SOLCON
External Faults
External Fault inputs - connected between terminals 19 or 20 and 21,
(no need to use short wires as in low voltage starter)
1 2 3 4...9 13 14 15 16 17 18 19 20 21
Input#4
Input#3
Common
N
SOLCON
Parameter Setting
6 keys, Menu driven software, Default parameters
Medium Voltage Digital Reduced Voltage Starter HRVS-DN
Mode
StoreReset
Select
On
Start
Run
S.Stop
Stop
Test
D.Adjust
Fault
CURRENT LIMIT
400%
8 LEDs for
quick status
display
 Two lines - 16 characters each, Back light
 Selectable languages - English, German, French and Spanish
 Communication Setting (software program)
SOLCON
PAGE 0 PAGE 1 PAGE 2 PAGE 3 PAGE 9
?
Mode
Store
Select
I1 I2 I3
A
MAIN & PROTECT.
PARAMETERS
STARTER FLC
150 AMP.
MOTOR FLA
150 AMP.
START PARAMETERS
SOFT START CURVE
0 (STANDARD)
START TACHO GAIN
0 (MIN. GAIN)
PULSE TIME
0 SEC.
INITIAL VOLTAGE
30 %
CURRENT LIMIT
400 % OF FLA
ACC. TIME
10 SEC.
MAX. START TIME
30 SEC.
NUMBER OF STARTS
1
STARTS PERIOD
20 MIN.
START INHIBIT
15 MIN.
RUN CONTACT DEL.
5 SEC.
STORE ENABLE
START PARAMETERS
STOP PARAMETERS
SOFT STOP CURVE
0 (STANDARD)
STOP TACHO GAIN
0 (MIN. GAIN)
DEC. TIME
10 SEC.
FINAL TORQUE
0 (MIN.)
STORE ENABLE
STOP PARAMETERS
UNDERCURR.DELAY
10 SEC.
O/C - SHEAR PIN
850 % OF FLA
UNDERCURR. TRIP
0 % OF FLA
STATISTICAL DATA
LAST STRT PERIOD
NO DATA
LAST START MAX. I
NO DATA
TOTAL RUN TIME
0 HOURS
TOTAL # OF START
0
LAST TRIP
NO DATA
TRIP CURRENT
0 % OF FLA
TOTAL # OF TRIPS
0
Minimized Mode
O/C - DELAY
0.5 SEC
OVERLOAD DELAY
4 SEC - AT 5 FLA
1 2 3 4 5 6 7 8
SOFT START CURVE *
4 (TORQUE)
SOFT STOP CURVE *
4 (TORQUE)
* Window appears* Window appears
when previous windowwhen previous window
exceeded its maximumexceeded its maximum
range.range.
INITIAL CURRENT *
100-400 %
OPTION CARD
NOT INSTALLED
STORE ENABLE
MAIN PARAMETERS
UNBALANCE TRIP
20 % OF FLA
GND FAULT TRIP
20% OF FLA
UNDERVOLT. TRIP
75% Un
UNDERVOLT. DELAY
5 SEC.
OVERVOLT. TRIP
120% Un
OVERVOLT. DELAY
2 SEC.
OVERLOAD TRIP
115 % OF FLA
OVERLOAD DELAY
4 SEC - AT 5 FLA
UNBALANCE DELAY
5 SEC.
GND FAULT DELAY
5 SEC.
SOLCON
COMM. PARAMETERS
STORE ENABLE
COMM. PARAMETERS
Maximized Mode
PAGE 4 PAGE 5 PAGE 6 PAGE 7 PAGE 9
FUTURE
FUTURE
FUTURE
STORE ENABLE
DRIVE NUMBER
0
BAUD RATE
9600
PARITY CHECK
EVEN
SERIAL LINK NO
248 (OFF)
?
Mode
Store
Select
DUAL ADJUSTMENT
PARAMETERS
DA: INIT. VOLT.
30%
DA: CUR. LIMIT
400 % OF FLA
DA: ACC. TIME
10 SEC.
DA: DEC. TIME
10 SEC.
DA: MOTOR FLA
105 AMP.
D. ADJ: GENERATOR
PARAMETERS
FAULT PARAMETERS
TRIP AFTER BYPAS
ENABLE
UNDER CUR. RESET
OFF
I/O PROGRAMMING
PARAMETERS
PROG. INPUT #1
TEST
PROG. INPUT #2
DUAL ADJUSTMENT
FAULT RELAY TYPE
FAULT
ANALOG OUTPUT
NORMAL
STORE ENABLE
I/O PROG.PARAM.
IMM / S.PIN RELAY
IMMEDIATE
RELAY ON DELAY
0 SEC.
RELAY OFF DEL.
0 SEC.
STORE ENABLE
D.ADJ. PARAMETERS
UV & PL AUTO RST
NO
1 2 3 4 5 6 7 8
BY-PASS AUTO RST
NO
STORE ENABLE
FAULT PARAMETERS
BYPASS OPEN TRIP
ENABLE
SOLCON
Start & Stop Parameters
Fully Voltage Ramp, Current Ramp , Torque Ramp
Initial Voltage OR Initial Current
Acceleration Time (Ramp-up Time)
Current Limit
Deceleration Time (Ramp-down Time) - Soft Stop
Pump Control
Dual Adjustments
Diesel Generator Starting
Tacho. feedback
SOLCON
Initial Voltage
Initial Voltage - determines the Initial Voltage and Torque (the Torque
is reduced in the square proportion of the voltage reduction).
Adjustable : 10-50% (5% - 80%) Un, should be set for the motor to
start turning immediately after Start signal is initiated.
Initial Current : above maximum value of initial voltage, setting
change to Initial Current of 100%, for Current Ramp.
10%
Initial
Voltage
50%
Un
SOLCON
Acceleration Time
Acceleration Time - Determines the Voltage Ramp-up Time, from
Initial to Full Voltage.
Adjustable :1-30 (90) sec. Set to the shortest acceptable time.
Time
Voltage Ramp-up Time
Un
U start
30 sec2
SOLCON
Current Limit
Current Limit - Determines the maximum current during acceleration
process and the acceleration time to full speed.
Adjustable :100-400% (500%) I FLA, Set to the highest acceptable current.
Current
Limit
U start
t soft start
U C. L
U1
Un
I start
RPM
400%
100%
SOLCON
Current Limit / Start Time Ratio
Lower Current Limit => longer Start Time
Time
4 x In
5 10 15 20 25 30
In
3 x In
SOLCON
Deceleration Time “Soft Stop”
Deceleration Time - Determines the Voltage Ramp-down Time,
from Un to zero.
Adjustable: 1-30 (90) sec. Set to the shortest acceptable time.
Un
Speed
Deceleration Time
2 30 / 90 sec
SOLCON
High Acceleration Torque causes rapid increase in pump speed, fast
change in flow & consequently high Pressure in the pipe sys
This high pressure may result in damage to pipes, fittings, joints, etc.
Pump Starting - D.O.L
TimeTime
Torque
M start
Accel.
Torque
Motor
DOL
Voltage
Speed
Load
Speed
SOLCON
Pump Starting - Soft Starter (standard)
Standard soft starters drastically reduce the Starting Torque, however
Peak Torque still remains high, causing high Acceleration Torque and
rapid acceleration towards end of starting process.
Peak Torque & Acceleration Torque must be reduced to extend
Acceleration time
Time
Torque
M start
Accel.
Torque
Motor
DOL
With soft
starter
Voltage
Slow
Accel.
Speed
Load
Speed
Motor
soft starter
Time
SOLCON
Pump Control – Start Curves
Pump Control “Start Curves” - Three special voltage ramp-up curves
to reduce peak torque & extend Acceleration time.
Adjustable: 0-4 Curves, set as required, 5=Torque Curve
(6 = Virtual Current Curve is achieved when increasing Initial Voltage
above full range and adjusting Initial current to the required setting)
Time
Voltage
Area of
Pump Control
Start Curves
With soft starter
Speed
Time
2 3 4
DOL
0 5,6
Torque
3
Speed
D.O.L
2
1
0
4
5
1
SOLCON
Pump Stopping – D.O.L
 When motor starter (DOL) is
opened, abruptly stopping the
pump, speed and flow are
quickly reduced. This may
cause a Water Hammer
(mechanical shock and audible
noise with severe damage to
pipes, joints, fittings, valves,
etc. )DOL opens
Un
Speed
SOLCON
Pump Stopping - Soft Starter (standard)
 When using a standard soft
starter, while pumping to a
higher elevation, motor
torque may quickly fall
below load torque (as torque
decreases at the square route
of voltage reduction). This
may cause abrupt stalling
instead of smoothly
decreasing speed to zero,
creating the Water Hammer
phenomenon.
Stalling point
Un
Speed“Soft stop”
SOLCON
Pump Control – Stop Curves
 Pump Control “Stop Curves” - enables selection between 3 special
voltage ramp-down curves preventing stall condition and eliminating
Water Hammer.
 Adjustable:0-4 Curve, Set as required (4 = Torque controlled curve)
Time
Voltage
Area of
Pump Control
Stop Curves
Time
With soft starter
Speed 2 3 4
DOL
0 51
Torque
3
Speed
D.O.L
2
1
0
4
5
SOLCON
Pump Control - Final Torque
 Before reaching end of deceleration, motor torque reaches a level
where the load torque is higher than motor's torque and motor stalls
while current continues flowing through the motor heating the
windings.
 Final Torque feature enables setting a point where current stops when
the motor stops rotating.
Time
Check Valve
closes and
motor stops
Voltage
Speed
Area of
Pump Control
Final Torque
Time
DOL
SOLCON
Starting from a Diesel-Generator
When starting from older D.G. sets (especially those equipped with low
cost Voltage Regulators) both voltage and frequency are unstable, causing
irregular thyristor firing. The HRVS-DN is equipped with a special
program overcoming the voltage and frequency instability.
Two options to operate Generator Mode:
 Use Basic Curve.
 set Dip Switch 3 to On and energize the Dual Adjustment Terminal.
When testing in Generator mode at low voltage, motor must be loaded.
When motor can operate from Mains and D.G (stand-by D.G) set
Dip Switch # 3 to On. However, Dual Adjustment Terminal should be
energized only when D.G. is running.
1 2 3 4 5 6 7 8
SOLCON
Dual Adjustment Parameters
 Generator Mode: Special starting mode (D.G. supply)
 Initial Voltage: 10 - 50% Un
 Current Limit: 100 - 400% Motor FLA setting
 Acceleration Time: 1 - 30 sec.
 Deceleration Time: 1 - 30 sec.
 Motor FLA: 50 - 100% Starter FLC setting
Note - Set Dip Switch # 3
to On for Generator Mode
and connect control voltage
to terminal 8.
Dual Adjust
Characteristic
Voltage
Time
Standard
Characteristic
SOLCON
Motor & Starter Protection - 1
 Too Many Start (No. of starts, Start period & Start Inhibit Time)
 Long Start Time (Stall)
 Over Current Shear pin (Jam)
 Electronic Overload with selectable curves
 Under Current
 Under / No voltage
 Over Voltage
 Phase Loss
 Phase Sequence
 Wrong Connections / Shorted SCR
 Continues on next page
SOLCON
Motor & Starter Protection - 2
 Heatsink Over-temp.
 External Fault 1 & 2
 Unbalance Current
 Ground Fault Current
 Power On & no Start
 Bypass Open - It is possible to disable.
 It is possible to disable most of the protections after by-pass is
closed.
SOLCON
Upon Fault
 The starter locks in a Fault Mode
 The starter records the Fault Data and updated Faults record.
 Fault LED lights
 LCD describes fault cause
 Fault Relay changes position
 Data is transferred through the communication
SOLCON
Resetting After Fault
Resetting after fault has been removed, provided Start signal does not exist.
 Local resetting – front panel key
 Remote resetting – hard wire (terminals 7 & 8)
 Remote resetting – through communication
 Auto resetting – for Under Voltage & Phase Loss
 Auto resetting – for Under Current
 Auto resetting – for Faults occur after by-pass is closed
SOLCON
Motor & Starter Protection
Start Run Soft Stop Stop
 Too Many Starts + - - -
 Long Start Time (Stall) + - - -
 O/C Shear pin + + + +
 Overload - + - -
 Under Current - + - -
 Under / No Voltage + + + -
 Over Voltage + + + -
 Phase Loss + + + -
 Phase Sequence + + + -
 Wrong Con/ Shorted SCR + - + -
 Continues on next page
SOLCON
Motor & Starter Protection
Start Run Soft Stop Stop
 Heatsink Over temp. + - + -
 External Fault 1 & 2 + + + +
 Unbalance Current + + + -
 Ground Fault Current. + + + -
 Power On & no Start - - - +
 By-pass Open - + - -
SOLCON
Max. C/L Adjustment, diff. Between LV & MV
 In low voltage Max Current Limit is 500% (Extended Setting)
 In Medium Voltage Max Current Limit setting is 400 * FLC / FLA
400* (FLC)
FLA
SOLCON
Too Many Starts
Note: 3 sec. Time delay after stop, before
restarting
Max. Number of Starts - preventing excessive starts during a short
period of time.
Adjustments:
 Permitted Number of Starts: Off, 1- 10
 Start period: 1- 60 min.
 Start Inhibit Time (after Too Many Starts): 1- 60 min.
SOLCON
Stalled Motor
Max. start time - Preventing Stall condition, trips the starter if current is
not reduced below Motor FLA within the adjusted time.
Adjustments: 1-30 (240) sec.
Max. Starting Time
Starting
current
2010 30
SOLCON
Jam Protection
Jam Protection - Trips the starter in less than 1 cycle when current
exceeds 850% IFLA.
Trip
850% IFLA
Applications
* Conveyors
* Agitators
* Complex Machinery
SOLCON
Shear-pin (“Immediate Relay” set to “Shear-pin”) - Stops (no trip) the
motor when current exceeds the set level, with an adjustable time delay.
Adjustments:
 Trip Current 200 - 850% Motor FLA (during starting 850%)
 Shear-pin Delay 0.5 - 5 sec (no delay at 850%)
Trip
850% IFLA
Electronic Shear-pin
Applications
* Shredders
* Complicated drive
systems
SOLCON
Overload
Overload - Trips the starter when current increases above the O/L Trip level after
the inverse time curve delay.
Remember - Overload protection is functional only during RUN condition,
after Max Start Time. During Start time motor is protected by
Max Start Time.
Adjustments:
 Trip Current: 75-150% I FLA
 Trip Delay at 500% I FLA : 1-10 sec.
150%
10 sec
t
75% 500%
1 sec
I
115%
trip time at
500% FLA
O/L setting
SOLCON
Under Current
Under current - Trips the starter when current decreases below the U/C
Trip level after the selectable time delay. Under current auto reset
allows for restarting after a predefined period of time, to re-check the
under current status.
Adjustments:
 Trip Current: Off, 20-90% I FLA
 Trip Delay 1-40 sec.
Start
I FLA
20%
40 sec.
80%
20
90%
2
Applications
* Dry running pumps
* Broken belt / gear
* Closed air inlet (fan)
SOLCON
Under / No Voltage
Under Voltage - Trips the starter when voltage drops
below the U/V Trip level after the selectable time delay.
With programmable auto-reset.
Adjustments:
 Trip level 50-90% of Un (Line - Line)
 Trip Delay 1-10 sec.
 The starter will trip immediately, overriding the the time delay, in
case voltage drops to zero
SOLCON
Over Voltage
Over Voltage - Trips the starter when voltage increases above the O/V Trip
level after the selectable time delay.
Adjustments:
 Trip level 110-125% of Un (Line - Line)
 Trip Delay 1-10 sec.
SOLCON
Phase Loss & Phase Sequence
Phase Loss - Trips the starter when one or two phases are missing for
over 1 sec. With programmable auto-reset.
Phase Sequence - Trips the starter immediately when phase sequence
is wrong
Note - There is no setting to allow working with wrong phase sequence
SOLCON
S.SCR / Wrong Motor Connection
 Trips the starter if motor is not properly connected
to starters’ Load terminals, 1,2 or 3 wires.
 Trips if current waveforms are wrong
 Disabled when in curve 0.
 Disabled for Generator starting.
C
R
4160V
SOLCON
Heatsink Over-temp.
Heatsink Over Temperature
- Trips the starter if thermal sensors mounted on starter’s heatsink sense
temperatures above 85 Deg. C.
- Sensors are of the N/O type
- Sensors are located on the top Heatsinks.
- Sensors are not isolated from Medium Voltage Heatsinks.
- “Sensor hot “ information is transferred to control module via fiber
optic
SOLCON
External Fault
External Fault – Inputs from two N.O. contacts. The starter trips
2 sec. after the any of the contact closes.
RVS-DN
Applications
* Water level for pumps
* Oil level for compressors
SOLCON
Current Imbalance
Current Imbalance - Trips the motor when the unbalanced current
increases above the preset current, and for time period above the
preset delay.
Adjustments:
 Trip level 10-100% of I FLA
 Trip Delay 1-60 sec.
SOLCON
Ground Fault Current
Ground Fault - Trips the motor when Ground Current increases above
the preset current, and for more then time period delay.
Adjustments:
 Trip level 10-100% of I FLA
 Trip Delay 1-60 sec.
 Protection can be disabled with dip switch
SOLCON
Power on & No start
Power On and No Start -
This protection becomes operational upon mains voltage connection.
It trips the motor when mains is connected to the HRVS-DN for more
then 30 seconds without a Start signal.
Designed to prevent overheating of the voltage dividing resistors in
the power section.
SOLCON
By - Pass Open
By - Pass Open - Becomes operational when the by-pass contactor did
not close after EOA contact command the pilot ( interposing) relay to
close.
SOLCON
Main Parameters & Protection
 Starter FLC 20 - 800A
 Motor FLA 50 - 100% of starter FLC setting
 Under Current Trip Off, 20 - 90% of motor FLA setting
 Under Current Delay 1 - 40 sec.
 O/C Shear pin 200 - 850% of motor FLA setting
 O/C Shear pin Delay 0.5 - 5 sec.
 Overload Trip 75 - 150% of motor FLA setting
 Overload Delay 1 - 10 sec. (at 500% motor FLA)
 Unbalance Trip 10-100% of motor FLA
 Unbalance Delay 1-60sec.
 Ground Fault Trip 10-100% of motor FLA
 Ground Fault Delay 1-60sec.
Continues on next slide
SOLCON
Main Parameters - cont.
 Under-voltage Trip 50 - 90% of Un
 Under-voltage Delay 1 - 10 sec.
 Over-voltage Trip 110 - 125%of Un
 Over-voltage Delay 1 - 10 sec.
SOLCON
Start Parameters
 Soft start curve 11 selectable curves, including:
 Start Tacho Gain 5 levels of Tacho Gain
 Torque Control
 Pulse Time 0 - 2 sec.
 Initial Voltage/Current 10 - 50% (5-80%) Un, 100-400% In
 Current Limit 100 - 400% (600) Motor FLA setting
 Acceleration Time 1 - 30 (90) sec.
 Max Start Time 1 - 30 (250)sec.
 Number of Starts 1 - 10, Off
 Starts Period 1 - 60 min.
 Start Inhibit Period 1 - 60 min.
 Run Contact Delay 0 - 120 sec.
 3 sec. time delay before immediate restart
 Current limit 410..600%, only for RVS_FLC > Motor_FLA
SOLCON
Stop Parameters
 Soft stop curve 11 selectable curves, including:
 Stop Tacho Gain 5 levels of Tacho Gain
 Torque Control
 Deceleration Time 1 - 30 (90) sec.
 Final Torque 0 - 10
SOLCON
Dual Adjustment Parameters
 Generator Mode Special starting mode (D.G. supply)
 Initial Voltage 10 - 50% Un
 Current Limit 100 - 400% (600) Motor FLA setting
 Acceleration Time 1 - 30 sec.
 Deceleration Time 1 - 30 sec.
 Motor FLA 50 - 100% Starter FLC setting
Note - Set Dip Switch # 3
to On for Generator Mode
and connect control voltage
to terminal 8.
Dual Adjust
Characteristic
Voltage
Time
Standard
Characteristic
SOLCON
Fault Parameters
 U/V & Phase Loss Auto Reset Yes / No
 Under Current Auto Reset Yes / No
 By-Pass Open Trip Enable/Disable
 Trip After By-Pass Enable/Disable
 By-Pass Auto Reset Yes/No
 Disable By-Pass Open Trip - When by-pass is external to
Starter’s cabinet and CTs do not “see” current when by-pass is
closed.
SOLCON
I / O Programming
 Terminal 7 (Input # 1) Test (future), Reset
 Terminal 8 (Input # 2) Dual Adjustment, Reset
 Fault Relay Fault, Fault - fail safe
 Immediate Relay function Immediate / Shear pin
 Immediate Relay On-delay Imm. 0 - 60 sec. / Shear pin 0 - 5
sec.
 Immediate Relay Off-delay Imm. 0 - 5 sec. / Shear pin 0 - 5 sec.
 Analogue Output Normal, Inverted
SOLCON
Communication Parameters
MODBUS RTU (Optional)
 Drive number 0 - 999
 Baud rate 1200 - 9600
 Parity check Even / Odd
 Serial link No. 1 - 247 & 248 =Off
RS 485 with MODBUS RTU protocol
can control and supervise up to 32
starters through a twisted pair.
Other Optional protocols available
(Profibus, Modbus TCP/IP...)
SOLCON
Statistical Data
 Last start Period
 Last start max. current
 Total run time
 Total number of starts
 last trip
 Trip current
 Total number of trips
 Previous Trips (1-9)
SOLCON
Multi-Start Application
1100 mm
1100 mm
2500 mm
LC0
LC1
MOTOR
1
MOTOR
2
LC2
MOTOR
3
LC3
BP2 BP3BP1
Prot Prot Prot
MPS 3000 MPS 3000 MPS 3000
Prot
1100 mm 1100 mm 1100 mm
MOTOR
4
Prot
MPs 3000
1100 mm
BP4
LC4
INCOMING
MPS 3000
SOLCON
About Solcon
 Established in 1977
 Privately owned (approved investor)
 60 employees
 Export oriented (approx. 80% export)
 ISO 9002
 Other approvals CE, UL, cUL, Lloyd’s
 Main office - in Herzlia (near Tel-Aviv)
 Manufacturing - 3000 sq.m plant in Yokneam (near Haifa)
SOLCON
Soft Starter History
 1978 – Start manufacturing of L.V. soft starters, type RVS
 1981 – Introduction of digital soft starters, type RVS-D
 1985 – Developed the HRVS-D with digital control for PCC
Patriot (a Magnetek company).
 1999 – PCC / Motortronics Agreement
 2000 – Introduction of the “Third Generation” soft starter, with
two patents (pending) for:
Wireless SCR Control
Electronic Potential Transformer
 Offering today the most comprehensive line of soft starter
SOLCON
Contact Persons
 Ami Shahaf – Managing Director
 Dr. Yoram Waltuch – Engineering Director
 Jacob Gabai – Production Director
 Hanan Schwartz – Controller
 Eli Wildawski – Marketing Manager
 Ofir Goren – Sales Manager
 Izzi Eicher – Area Manager
SOLCON
Other Subjects
11 & 13.8 KV soft starters
DNV, ABS (Marine)
UL / CSA requirements
SOLCON
Product Lines
 Electronic Soft Starters
 Protection Relays
 Digital Control Systems
SOLCON
Marketing M.V. Soft Starters
 Agreements with major international companies
 Sales through Solcon Distributors
 Unique activities in Mexico
 Special activities in the marine market in Korea
SOLCON
Notes
 When Ordering:
 Specify low voltage level for testing.
 Specify Motor FLA
 Consult factory for multi - motor starting.
 Consult factory for long starts.
 Consult factory for long conveyer starting.
SOLCON
Testing with L.V. Motor
Low Voltage Test Harness
Firing Test without Mains
SOLCON
Ratings & Dimensions (mm)
Volts FLC KW Chassis (mm) Enclosed (mm)
60 190
110 350
2300 200 650 660 x 1000 x 460
320 1000
400 1300
600 1960 800 x 1200 x 570
800 2620
60 275 900 x 2300 x 1000
110 510
3300 200 940 660 x 1000 x 460
320 1500
400 1880
600 2820 800 x 1200 x 570
800 3760
SOLCON
Ratings & Dimensions (mm)
Volts FLC KW Chassis (mm) Enclosed (mm)
60 350
110 650
4160 200 1180 660 x 1000 x 460
320 1900 900 x 2300 x 1000
400 2370
600 3560 800 x 1200 x 570
800 4750
70 650
140 1310 660 x 1000 x 460
6600 250 2350 1100 x 2300 x 1100
300 2820
400 3770 800 x 1200 x 570
600 4720
Select starter according to motors nominal current
and starting conditions.
SOLCON
Ratings & Dimensions (mm)
Volts FLC KW Chassis (mm) Enclosed (mm)
140 2200
11000 250 4000
400 6400 1500 x 2300 x 1500
500 8000
600 10000
800 13000
100 2000
200 4000
13800 300 6000 1500 x 2300 x 1500
400 8000
500 10000
600 12000
800 16000
1000 20000
Select starter according to motors nominal current
and starting conditions.
SOLCON
IP00 Assembly
HRVS-DN
Soft-Starter
Control Panel
HRVS-DN
Soft-Starter
Power
Module
I 1
I 2
I 3
EPT-Rx
Receiver
EPT - Tx
Transmitter
13
11
{
{
{
CT
3
4
8
9
13
14
13
11
Electric Wire Harness (6 wires)
HRVS-DN IP00 Wiring and connections between:
Power Module, EPT Receiver , Control module and Transformer
1 3 5 7 8 9
Fiber Optic Harness (6 fibers)
Fiber-Optic
Inputs
24VAC 115/230VAC
24V Gnd
1 2 3
Auxiliary Relay (Not Supplied)
1
2
3
1
6
11
(R)
(S)
(T)
115V / 230V
Cooper Wire Area -
At least 4 mm2
1
1
1
Fiber-Optic
links (2 fibers)
15 10 5
11 6 1
White Male
Connector White Female
Connector
Fuse
inside
Receptacle
Segregated Low
Voltage Compartment
Segregated High
Voltage Compartment
CT
CT
SOLCON
Firing Boards Assembly
Six Red LED’s
Six Green LED’s
SOLCON
Soft Starters components
Control Module Power Section
Transformer to 24VAC Electronic P/T - Receiver
SOLCON
Power Section Connections
Power Section Harness
EPT Rx
Two F/O and
Three wires
Plug at the back of
Control Module
F/O Plugs at the Top
of Control Module
SOLCON
Electronic P/T
Two fiber optic
Transmitter
Receiver
SOLCON
24VAC connection
Transformer to 24VAC
SOLCON
Firing Power supply
VAC Supply
from Trans.
L.V. Fuse
SOLCON
Fiber Optic Board
SOLCON
Fiber Optic Board
L3
Ground Fault 1&2
0 - Normal
1 - Cancel G/F Protection
Current Gain
L1
1- off – x 5 Gain
On - Normal
2- off - x 13.4 Gain
On - Normal
L2

More Related Content

What's hot

Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Electromate
 
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...IndiaMART InterMESH Limited
 
F4 s c_instruction manual
F4 s c_instruction manualF4 s c_instruction manual
F4 s c_instruction manualToàn Huỳnh
 
Iai acon controller_specsheet
Iai acon controller_specsheetIai acon controller_specsheet
Iai acon controller_specsheetElectromate
 
LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013
LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013
LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013Steve Mappus
 
Advanced motion controls be25a20ac
Advanced motion controls be25a20acAdvanced motion controls be25a20ac
Advanced motion controls be25a20acElectromate
 
Advanced motion controls ab125a200
Advanced motion controls ab125a200Advanced motion controls ab125a200
Advanced motion controls ab125a200Electromate
 
Advanced motion controls b100a20
Advanced motion controls b100a20Advanced motion controls b100a20
Advanced motion controls b100a20Electromate
 
AVR_Course_Day8 motor drive and pwm techniques
AVR_Course_Day8 motor drive and pwm techniquesAVR_Course_Day8 motor drive and pwm techniques
AVR_Course_Day8 motor drive and pwm techniquesMohamed Ali
 
Advanced motion controls avb100c200
Advanced motion controls avb100c200Advanced motion controls avb100c200
Advanced motion controls avb100c200Electromate
 
Iai scon controller_specsheet
Iai scon controller_specsheetIai scon controller_specsheet
Iai scon controller_specsheetElectromate
 
An Introduction to LM3464 LED Driver with Dynamic Headroom Control
An Introduction to LM3464 LED Driver with Dynamic Headroom ControlAn Introduction to LM3464 LED Driver with Dynamic Headroom Control
An Introduction to LM3464 LED Driver with Dynamic Headroom ControlPremier Farnell
 
Advanced motion controls se10a20
Advanced motion controls se10a20Advanced motion controls se10a20
Advanced motion controls se10a20Electromate
 
Advanced motion controls se30a8
Advanced motion controls se30a8Advanced motion controls se30a8
Advanced motion controls se30a8Electromate
 

What's hot (19)

Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Advanced motion controls azbh20a8
Advanced motion controls azbh20a8
 
Omron ladder programming
Omron ladder programmingOmron ladder programming
Omron ladder programming
 
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
 
Lm2907
Lm2907Lm2907
Lm2907
 
Lm2907
Lm2907Lm2907
Lm2907
 
F4 s c_instruction manual
F4 s c_instruction manualF4 s c_instruction manual
F4 s c_instruction manual
 
Iai acon controller_specsheet
Iai acon controller_specsheetIai acon controller_specsheet
Iai acon controller_specsheet
 
LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013
LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013
LED Streetlight APEC Demo Performance_SMappus 03062013 AC 12 Mar 2013
 
Advanced motion controls be25a20ac
Advanced motion controls be25a20acAdvanced motion controls be25a20ac
Advanced motion controls be25a20ac
 
Advanced motion controls ab125a200
Advanced motion controls ab125a200Advanced motion controls ab125a200
Advanced motion controls ab125a200
 
Ucn5804 datasheet
Ucn5804 datasheetUcn5804 datasheet
Ucn5804 datasheet
 
Advanced motion controls b100a20
Advanced motion controls b100a20Advanced motion controls b100a20
Advanced motion controls b100a20
 
AVR_Course_Day8 motor drive and pwm techniques
AVR_Course_Day8 motor drive and pwm techniquesAVR_Course_Day8 motor drive and pwm techniques
AVR_Course_Day8 motor drive and pwm techniques
 
Advanced motion controls avb100c200
Advanced motion controls avb100c200Advanced motion controls avb100c200
Advanced motion controls avb100c200
 
Iai scon controller_specsheet
Iai scon controller_specsheetIai scon controller_specsheet
Iai scon controller_specsheet
 
An Introduction to LM3464 LED Driver with Dynamic Headroom Control
An Introduction to LM3464 LED Driver with Dynamic Headroom ControlAn Introduction to LM3464 LED Driver with Dynamic Headroom Control
An Introduction to LM3464 LED Driver with Dynamic Headroom Control
 
330cl
 330cl 330cl
330cl
 
Advanced motion controls se10a20
Advanced motion controls se10a20Advanced motion controls se10a20
Advanced motion controls se10a20
 
Advanced motion controls se30a8
Advanced motion controls se30a8Advanced motion controls se30a8
Advanced motion controls se30a8
 

Similar to Giuliano bozzo moncada hrvs dn s 05-06

Advanced motion controls b100a40ac
Advanced motion controls b100a40acAdvanced motion controls b100a40ac
Advanced motion controls b100a40acElectromate
 
Advanced motion controls b30a40ac
Advanced motion controls b30a40acAdvanced motion controls b30a40ac
Advanced motion controls b30a40acElectromate
 
Advanced motion controls ab100c200
Advanced motion controls ab100c200Advanced motion controls ab100c200
Advanced motion controls ab100c200Electromate
 
Advanced motion controls ab200a100
Advanced motion controls ab200a100Advanced motion controls ab200a100
Advanced motion controls ab200a100Electromate
 
Advanced motion controls ab250a060
Advanced motion controls ab250a060Advanced motion controls ab250a060
Advanced motion controls ab250a060Electromate
 
Advanced motion controls b60a40ac
Advanced motion controls b60a40acAdvanced motion controls b60a40ac
Advanced motion controls b60a40acElectromate
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40acElectromate
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40acElectromate
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40acElectromate
 
Advanced motion controls be25a20i
Advanced motion controls be25a20iAdvanced motion controls be25a20i
Advanced motion controls be25a20iElectromate
 
Advanced motion controls 25a20
Advanced motion controls 25a20Advanced motion controls 25a20
Advanced motion controls 25a20Electromate
 
Advanced motion controls s100a40
Advanced motion controls s100a40Advanced motion controls s100a40
Advanced motion controls s100a40Electromate
 
Advanced motion controls be30a8
Advanced motion controls be30a8Advanced motion controls be30a8
Advanced motion controls be30a8Electromate
 
Advanced motion controls 50a20
Advanced motion controls 50a20Advanced motion controls 50a20
Advanced motion controls 50a20Electromate
 
Advanced motion controls avb250a060
Advanced motion controls avb250a060Advanced motion controls avb250a060
Advanced motion controls avb250a060Electromate
 
Advanced motion controls b40a40ac
Advanced motion controls b40a40acAdvanced motion controls b40a40ac
Advanced motion controls b40a40acElectromate
 
Mitsubishi lap trinh plc afdf afaf
Mitsubishi lap trinh plc afdf afafMitsubishi lap trinh plc afdf afaf
Mitsubishi lap trinh plc afdf afafphong279
 
Advanced motion controls b100a40
Advanced motion controls b100a40Advanced motion controls b100a40
Advanced motion controls b100a40Electromate
 
Advanced motion controls avb125a200
Advanced motion controls avb125a200Advanced motion controls avb125a200
Advanced motion controls avb125a200Electromate
 

Similar to Giuliano bozzo moncada hrvs dn s 05-06 (20)

Advanced motion controls b100a40ac
Advanced motion controls b100a40acAdvanced motion controls b100a40ac
Advanced motion controls b100a40ac
 
Advanced motion controls b30a40ac
Advanced motion controls b30a40acAdvanced motion controls b30a40ac
Advanced motion controls b30a40ac
 
Advanced motion controls ab100c200
Advanced motion controls ab100c200Advanced motion controls ab100c200
Advanced motion controls ab100c200
 
938 k eletrico w8k
938 k eletrico w8k938 k eletrico w8k
938 k eletrico w8k
 
Advanced motion controls ab200a100
Advanced motion controls ab200a100Advanced motion controls ab200a100
Advanced motion controls ab200a100
 
Advanced motion controls ab250a060
Advanced motion controls ab250a060Advanced motion controls ab250a060
Advanced motion controls ab250a060
 
Advanced motion controls b60a40ac
Advanced motion controls b60a40acAdvanced motion controls b60a40ac
Advanced motion controls b60a40ac
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40ac
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40ac
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40ac
 
Advanced motion controls be25a20i
Advanced motion controls be25a20iAdvanced motion controls be25a20i
Advanced motion controls be25a20i
 
Advanced motion controls 25a20
Advanced motion controls 25a20Advanced motion controls 25a20
Advanced motion controls 25a20
 
Advanced motion controls s100a40
Advanced motion controls s100a40Advanced motion controls s100a40
Advanced motion controls s100a40
 
Advanced motion controls be30a8
Advanced motion controls be30a8Advanced motion controls be30a8
Advanced motion controls be30a8
 
Advanced motion controls 50a20
Advanced motion controls 50a20Advanced motion controls 50a20
Advanced motion controls 50a20
 
Advanced motion controls avb250a060
Advanced motion controls avb250a060Advanced motion controls avb250a060
Advanced motion controls avb250a060
 
Advanced motion controls b40a40ac
Advanced motion controls b40a40acAdvanced motion controls b40a40ac
Advanced motion controls b40a40ac
 
Mitsubishi lap trinh plc afdf afaf
Mitsubishi lap trinh plc afdf afafMitsubishi lap trinh plc afdf afaf
Mitsubishi lap trinh plc afdf afaf
 
Advanced motion controls b100a40
Advanced motion controls b100a40Advanced motion controls b100a40
Advanced motion controls b100a40
 
Advanced motion controls avb125a200
Advanced motion controls avb125a200Advanced motion controls avb125a200
Advanced motion controls avb125a200
 

More from GiulianoBozmm

Giuliano bozzo moncada lider
Giuliano bozzo moncada liderGiuliano bozzo moncada lider
Giuliano bozzo moncada liderGiulianoBozmm
 
Giuliano bozzo moncada h istoria
Giuliano bozzo moncada h istoriaGiuliano bozzo moncada h istoria
Giuliano bozzo moncada h istoriaGiulianoBozmm
 
Giuliano bozzo moncada heridas por proyectil de arma de fuego
Giuliano bozzo moncada heridas por proyectil de arma de fuegoGiuliano bozzo moncada heridas por proyectil de arma de fuego
Giuliano bozzo moncada heridas por proyectil de arma de fuegoGiulianoBozmm
 
Giuliano bozzo moncada clase practica-dig silent
Giuliano bozzo moncada clase practica-dig silentGiuliano bozzo moncada clase practica-dig silent
Giuliano bozzo moncada clase practica-dig silentGiulianoBozmm
 
Giuliano bozzo moncada cinematica del trauma
Giuliano bozzo moncada cinematica del traumaGiuliano bozzo moncada cinematica del trauma
Giuliano bozzo moncada cinematica del traumaGiulianoBozmm
 
Giuliano bozzo moncada casa mirador san damian fichas tecnicas 28 09-09
Giuliano bozzo moncada casa mirador san damian  fichas tecnicas 28 09-09Giuliano bozzo moncada casa mirador san damian  fichas tecnicas 28 09-09
Giuliano bozzo moncada casa mirador san damian fichas tecnicas 28 09-09GiulianoBozmm
 
Giuliano bozzo moncada ril 11 m
Giuliano bozzo moncada  ril 11 mGiuliano bozzo moncada  ril 11 m
Giuliano bozzo moncada ril 11 mGiulianoBozmm
 
Giuliano bozzo moncada presentacion de tarifas de suministro electrico v2.0 ...
Giuliano bozzo moncada  presentacion de tarifas de suministro electrico v2.0 ...Giuliano bozzo moncada  presentacion de tarifas de suministro electrico v2.0 ...
Giuliano bozzo moncada presentacion de tarifas de suministro electrico v2.0 ...GiulianoBozmm
 
Giuliano bozzo moncada legalidad
Giuliano bozzo moncada  legalidadGiuliano bozzo moncada  legalidad
Giuliano bozzo moncada legalidadGiulianoBozmm
 
Giuliano Bozzo Moncada rrdon
Giuliano Bozzo Moncada rrdonGiuliano Bozzo Moncada rrdon
Giuliano Bozzo Moncada rrdonGiulianoBozmm
 
Giuliano Bozzo Moncada que es gerencia de proyectos
Giuliano Bozzo Moncada que es gerencia de proyectosGiuliano Bozzo Moncada que es gerencia de proyectos
Giuliano Bozzo Moncada que es gerencia de proyectosGiulianoBozmm
 
1089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-1
1089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-11089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-1
1089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-1GiulianoBozmm
 
manual de mantencion Giuliano Bozzo Moncada de equipos
 manual de mantencion Giuliano Bozzo Moncada de equipos manual de mantencion Giuliano Bozzo Moncada de equipos
manual de mantencion Giuliano Bozzo Moncada de equiposGiulianoBozmm
 

More from GiulianoBozmm (13)

Giuliano bozzo moncada lider
Giuliano bozzo moncada liderGiuliano bozzo moncada lider
Giuliano bozzo moncada lider
 
Giuliano bozzo moncada h istoria
Giuliano bozzo moncada h istoriaGiuliano bozzo moncada h istoria
Giuliano bozzo moncada h istoria
 
Giuliano bozzo moncada heridas por proyectil de arma de fuego
Giuliano bozzo moncada heridas por proyectil de arma de fuegoGiuliano bozzo moncada heridas por proyectil de arma de fuego
Giuliano bozzo moncada heridas por proyectil de arma de fuego
 
Giuliano bozzo moncada clase practica-dig silent
Giuliano bozzo moncada clase practica-dig silentGiuliano bozzo moncada clase practica-dig silent
Giuliano bozzo moncada clase practica-dig silent
 
Giuliano bozzo moncada cinematica del trauma
Giuliano bozzo moncada cinematica del traumaGiuliano bozzo moncada cinematica del trauma
Giuliano bozzo moncada cinematica del trauma
 
Giuliano bozzo moncada casa mirador san damian fichas tecnicas 28 09-09
Giuliano bozzo moncada casa mirador san damian  fichas tecnicas 28 09-09Giuliano bozzo moncada casa mirador san damian  fichas tecnicas 28 09-09
Giuliano bozzo moncada casa mirador san damian fichas tecnicas 28 09-09
 
Giuliano bozzo moncada ril 11 m
Giuliano bozzo moncada  ril 11 mGiuliano bozzo moncada  ril 11 m
Giuliano bozzo moncada ril 11 m
 
Giuliano bozzo moncada presentacion de tarifas de suministro electrico v2.0 ...
Giuliano bozzo moncada  presentacion de tarifas de suministro electrico v2.0 ...Giuliano bozzo moncada  presentacion de tarifas de suministro electrico v2.0 ...
Giuliano bozzo moncada presentacion de tarifas de suministro electrico v2.0 ...
 
Giuliano bozzo moncada legalidad
Giuliano bozzo moncada  legalidadGiuliano bozzo moncada  legalidad
Giuliano bozzo moncada legalidad
 
Giuliano Bozzo Moncada rrdon
Giuliano Bozzo Moncada rrdonGiuliano Bozzo Moncada rrdon
Giuliano Bozzo Moncada rrdon
 
Giuliano Bozzo Moncada que es gerencia de proyectos
Giuliano Bozzo Moncada que es gerencia de proyectosGiuliano Bozzo Moncada que es gerencia de proyectos
Giuliano Bozzo Moncada que es gerencia de proyectos
 
1089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-1
1089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-11089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-1
1089Giuliano Bozzo Moncada 15 1100 swg001-0324-001-1
 
manual de mantencion Giuliano Bozzo Moncada de equipos
 manual de mantencion Giuliano Bozzo Moncada de equipos manual de mantencion Giuliano Bozzo Moncada de equipos
manual de mantencion Giuliano Bozzo Moncada de equipos
 

Recently uploaded

Call Girls Nagpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Nagpur Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Nagpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Nagpur Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Call Girls Kochi Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Kochi Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Kochi Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Kochi Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...
Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...
Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...astropune
 
♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...
♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...
♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...astropune
 
(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...
(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...
(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...Taniya Sharma
 
Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...
Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...
Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...Dipal Arora
 
(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...
(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...
(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...indiancallgirl4rent
 
Call Girls Dehradun Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Dehradun Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Dehradun Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Dehradun Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Call Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Call Girls Mumbai Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Mumbai Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Mumbai Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Mumbai Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Bangalore Call Girls Nelamangala Number 7001035870 Meetin With Bangalore Esc...
Bangalore Call Girls Nelamangala Number 7001035870  Meetin With Bangalore Esc...Bangalore Call Girls Nelamangala Number 7001035870  Meetin With Bangalore Esc...
Bangalore Call Girls Nelamangala Number 7001035870 Meetin With Bangalore Esc...narwatsonia7
 
Bangalore Call Girl Whatsapp Number 100% Complete Your Sexual Needs
Bangalore Call Girl Whatsapp Number 100% Complete Your Sexual NeedsBangalore Call Girl Whatsapp Number 100% Complete Your Sexual Needs
Bangalore Call Girl Whatsapp Number 100% Complete Your Sexual NeedsGfnyt
 
💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...
💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...
💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...Taniya Sharma
 
Call Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Call Girls Bareilly Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Bareilly Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Bareilly Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Bareilly Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Russian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls Jaipur
Russian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls JaipurRussian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls Jaipur
Russian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls Jaipurparulsinha
 
Call Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore Escorts
Call Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore EscortsCall Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore Escorts
Call Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore Escortsvidya singh
 
Call Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Call Girls Cuttack Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Cuttack Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Cuttack Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Cuttack Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Call Girls Siliguri Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Siliguri Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Siliguri Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Siliguri Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 

Recently uploaded (20)

Call Girls Nagpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Nagpur Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Nagpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Nagpur Just Call 9907093804 Top Class Call Girl Service Available
 
Call Girls Kochi Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Kochi Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Kochi Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Kochi Just Call 9907093804 Top Class Call Girl Service Available
 
Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...
Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...
Best Rate (Hyderabad) Call Girls Jahanuma ⟟ 8250192130 ⟟ High Class Call Girl...
 
♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...
♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...
♛VVIP Hyderabad Call Girls Chintalkunta🖕7001035870🖕Riya Kappor Top Call Girl ...
 
(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...
(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...
(👑VVIP ISHAAN ) Russian Call Girls Service Navi Mumbai🖕9920874524🖕Independent...
 
Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...
Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...
Best Rate (Guwahati ) Call Girls Guwahati ⟟ 8617370543 ⟟ High Class Call Girl...
 
(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...
(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...
(Rocky) Jaipur Call Girl - 09521753030 Escorts Service 50% Off with Cash ON D...
 
Call Girls Dehradun Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Dehradun Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Dehradun Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Dehradun Just Call 9907093804 Top Class Call Girl Service Available
 
Call Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Jabalpur Just Call 9907093804 Top Class Call Girl Service Available
 
Call Girls Mumbai Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Mumbai Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Mumbai Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Mumbai Just Call 9907093804 Top Class Call Girl Service Available
 
Bangalore Call Girls Nelamangala Number 7001035870 Meetin With Bangalore Esc...
Bangalore Call Girls Nelamangala Number 7001035870  Meetin With Bangalore Esc...Bangalore Call Girls Nelamangala Number 7001035870  Meetin With Bangalore Esc...
Bangalore Call Girls Nelamangala Number 7001035870 Meetin With Bangalore Esc...
 
Bangalore Call Girl Whatsapp Number 100% Complete Your Sexual Needs
Bangalore Call Girl Whatsapp Number 100% Complete Your Sexual NeedsBangalore Call Girl Whatsapp Number 100% Complete Your Sexual Needs
Bangalore Call Girl Whatsapp Number 100% Complete Your Sexual Needs
 
💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...
💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...
💎VVIP Kolkata Call Girls Parganas🩱7001035870🩱Independent Girl ( Ac Rooms Avai...
 
Call Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 9907093804 Top Class Call Girl Service Available
 
Call Girls Bareilly Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Bareilly Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Bareilly Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Bareilly Just Call 9907093804 Top Class Call Girl Service Available
 
Russian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls Jaipur
Russian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls JaipurRussian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls Jaipur
Russian Call Girls in Jaipur Riya WhatsApp ❤8445551418 VIP Call Girls Jaipur
 
Call Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore Escorts
Call Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore EscortsCall Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore Escorts
Call Girls Horamavu WhatsApp Number 7001035870 Meeting With Bangalore Escorts
 
Call Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Aurangabad Just Call 9907093804 Top Class Call Girl Service Available
 
Call Girls Cuttack Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Cuttack Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Cuttack Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Cuttack Just Call 9907093804 Top Class Call Girl Service Available
 
Call Girls Siliguri Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Siliguri Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Siliguri Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Siliguri Just Call 9907093804 Top Class Call Girl Service Available
 

Giuliano bozzo moncada hrvs dn s 05-06

  • 1. Medium Voltage Soft Starters SOLCON
  • 2. SOLCON Soft Starting Limiting the Starting Current : Long supply cables Loaded transformers Diesel generator supply Limiting the Starting Torque : Preventing Water Hammer High inertia loads Complicated mechanical systems Reducing maintenance
  • 3. SOLCON D.O.L vs. Soft Start D.O.L Soft-starter Motor Current Motor Torque
  • 4. SOLCON Soft Starter Advantages Electronic soft starters provide: Solid state, no moving parts, reduced maintenance Reduction of starting current Reduction of starting torque & mechanical shock Smooth acceleration & deceleration Closed current loop starting Easy adjustments for all applications Comprehensive motor protection package Special features: “Pump Control”, Soft Stop, Dual Adjustments. Communication for full setting, control and supervision
  • 5. SOLCON HRVS-DN Advantages  Complete line 60-1800A, 1500-15000V  Third generation, Microprocessor design  Superior Starting & Stopping Characteristics: Torque Control, Current Control and Pump Control  Advanced Motor Protection package  Easy commissioning and maintenance - field testing with a L.V. motor  Patent pending - Wireless SCR firing control system  Patent pending – Electronic Voltage measurement system  Fiber optic control (also for mains voltage measurement)  Meets “Partial Discharge Test Requirements”  Friendly operation -Multi Languages LCD, English, German, French & Spanish  Communication: MODBUS, PROFIBUS, TCP/IP, DEVICENET and others  Chassis or cabinet type, various options are available  Solcon is offering the most advanced M.V. soft Starter
  • 6. SOLCON Heavy Duty Design  Starting & Operation conditions  Max. Starting Current 400 % I n  Max. Starting Time 30 sec.  Max. Ambient Temp. 40°C  Max. Number of Starts 4 starts / hour at max. starting conditions  Special cases: One starter for few motors.
  • 7. SOLCON Typical Applications  Typical applications:  Pumps  Chillers  Conveyors  Compressors  Fans and blowers  Complicated mechanical drives and loads  Marine applications  Thrusters  LNG Ships  Pumps-ballast  Hydraulic systems
  • 8. SOLCON Medium Voltage motor starting  Range 50-1000A, 1500-13800V  Standard configuration includes:  - Soft starter  - Line Contactor  - Bypass Contactors  - Cabinet IP30  - L.V. Controls  Options are available L.V. Compartmen t M.V. Compartme nt upper door M.V. Compartment lower door Operating Buttons M.V. Compartment Main (central) door Status indications Operating Panel (behind glass) Emergency stop Motor Protection Relay (Optional) Name plate with soft starter data
  • 9. SOLCON Options In H.V compartment - Line Switch (On / Off load) - Main Fuses (opt. Striker pin) - Incoming Section - Space Heater, Thermostat, C/B - Fan at top, air inlet at bottom, C/B - Special Painting In L.V compartment - Motor Protection Relay (MPR 2000) - Digital Panel Meter (DPM-10) - Other control components Line Connection (in the back) Ground Bus Line Contactor Soft Starter Power Section Cabinet Light Bypass Contactor Electronic Transformer (Transmitter) Motor Connection Door Switch Space Heater Customer Control Terminals
  • 10. SOLCON PERDIDAS ELECTRICAS P = 3 x Vscrs x I EXAMPLE 4.16KV, 200 A, 1200 KW, 1600 HP P = 3 x (2x3) x 4IFLA P = 14.4 KW 2starts x 20 seconds in one hour Pav = 14400 x 40 /3600 = 160 W
  • 11. 11 11 By-pass Contactor Fault x2 x1 Line Contactor LightN ~ 230VAC Off On Contactor Line On By-pass Contactor x2 x1 x2x2 x1 2 Red x2 x1 x2 x1 GreenGreen Red Line contactor RC1 92 A2 10 A1 A2 2 A1 C1 9 21 7 7 4 3 C2 FT 22 6 RC1 22 3 6 24 21 21 24 24 21 8 21 18 24 21 22 24 11 MPR Trip 14 11 14 17 18 17 24 10 10 12 21 C1 11 6 5 6 5 16A 10A ES2 (Customer) 1 ~230VAC 2 1 Control e2 2 3P Acceleration Immediate End0f Fault 2 2 A2 C2 A1 A2 10 A1 Remote 20 21 186 SoftStarter 321 4 5 12987 1011 151413 1617 19 TR1* 11 14 212019 RC1 Aux TB2 TB1 Immediate By-pass DoorTrip K1 C2 LS1FT/1 31 34 14 L 13 0 16 1NO -Start 31 34 16 1NC -Stop 15 15 Contactor Switch Start D.O.L. 3 1 B.P. 1 2 12 2 54 53 RS K3RS e1 e2 ES1 LS1 4 4 3 LR1 L1 L2 L3 L4 6 RC1 K1 FT 9 3P 22 10 A2 A1 10 A2 A1 FT/1FT FR 3P 3P 6 K2 -TB4-Internal Terminals-TB1, -Customer Terminals-TB2,TB3 Remarks: 20 21 FR RS R FT 3P 10 A2 A1 10 A2 10 A2 A1 A1 2 2 2 K2 x2 x1 White 2 A2 10 A1 RSL5K3K1 Space Heater 2 N~230V ~230VAC 60W H 3 ~230V 1 1 HS HS 2x120 Pri. 24Vac Sec. Module Power 19/1 60W H
  • 12. SOLCON Patent Pending SCR Firing  Fully isolated HV from LV, “wireless” system (patent pending)  Diagnostics with firing and fault indication LED’s
  • 13. SOLCON EPT (Electronic Potential Transformer) EPT Transmitter & Receiver The EPT (Patent Pending) * Measures 3 phase current and turns it to a PWM sign. Transmits it to the receiver which turns the PWM sign to a sine wave. * The connection between the transmitter and the receiver is by fiber optic wires for maximum safety and reliability.
  • 14. SOLCON Power Section Power section with 12-18 thyristors 2300-6900V ∼3 L 1 L 2 L 3
  • 15. SOLCON SCR’s Firing System The left SCR conducts during the positive period of the sine wave, when Vc is On and can be turned Off when the current is at zero crossing. Vc
  • 16. SOLCON SCR’s Firing System The other SCR is coupled in an anti-parallel method and conducts in the negative half cycle. Vc
  • 17. SOLCON SCR’s Firing System SCR firing controls the soft starter output voltage U start Zero Crossing t soft start Phase Control
  • 18. SOLCON Calculating Motor’s Torque Motor torque with soft starter M soft = ( U soft / U n) 2 * M start Assuming M start = 1.8 * M n Assuming U start =0.5 Un M=(0.50)2 M soft = (0.25) * 1.8 = 0.45 M start Torque is reduced by the square of the voltage reduction
  • 19. SOLCON Block Diagram EPT Transmiter (Tx) Fiber optic Line Contactor ML2 L1 Feedback Sensor Firing Trafo .. / 24V Fiber optic Molex Plug C/T Control Module X 6 Power Supply Firing Control EPT Receiver (Rx) L3 By-pass Contactor
  • 21. SOLCON Control Module MMI, local or door mounted (IP30) Control Terminals Fiber optic connections
  • 22. SOLCON The Control Module * Analogue board Analogue output related to motor’s current Insulation board Communication Board, RS 485 Power Supply Board EEPROM Dip Switch µP Fiber optic board Optional cards: 3 Auxiliary Relays
  • 23. SOLCON Dip Switch 1 Display Minimum Maximum 2 Tacho feedback Disabled Enabled 3 Mains / Generator Mains Generator 4 Always Off 5+6 Language selector English, French, German, Spanish 7 Extended range settings Disabled Enabled 8 Software lock Unlocked Locked No. Function Off On 1 2 3 4 5 6 7 8 Off (factory default)
  • 24. SOLCON Line, Bypass & Capacitor Contactors Power factor correction Capacitors - when used, must be at Line side, on top of starter. L1 L2 L3 ∼3 Bypass Contactor (must be used) Line Contactor (must be used)
  • 25. SOLCON Control Wiring 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Stop SoftStop Start Input#3(Ext.Fault-1) Input#4(Ext.Fault-2) Common-B Aux.Contact “Immediate” L1 N FaultContact (Fault/FailSafe) Aux.Contact EndOfAccel.” Input#1-Test/Reset Common-A Control CommandsControl Supply Input#2-D.Adjust/Reset Ext. Faults Note: Terminals 2, 19-20-21 differ from same in low voltage starter RVSDN FiringTransformerControl
  • 26. SOLCON Control wiring - optional cards 25 26 27 Motor Insulation Alarm 23 24 22 Communication Board (+) RS485 (-) RS485 N.C. 25 26 27 Digital Tacho Board Encoder (-) (+) Ground (+) Analogue (-) Analogue Thermistor Thermistor 28 29 30 31 32 Analogue I/O Board Ground
  • 27. SOLCON Control Supply Voltage L N Same voltage for Control Supply (1-3) and Control Commands (4-9) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Common SoftStop Test/Reset D.Adjust/Reset Start Stop Electronics
  • 28. SOLCON Control Supply Voltage Different voltages for Control Commands (4-9) can be AC or DC (must be specified) NL Control Commands 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Common SoftStop Test/Reset D.Adjust/Reset Start Stop Electronics
  • 29. SOLCON Soft Start & Immediate Stop Motor will soft start when C closes and stop immediately when C opensL N 1 2 3 4 5 6 7 8 9 Common SoftStop Stop Reset D.Adjust/Reset Start C
  • 30. SOLCON Soft Start & Soft Stop Motor will soft start when C closes and soft stop when C opensL N 1 2 3 4 5 6 7 8 9 Common SoftStop Stop Reset D.Adjust/Reset Start C
  • 31. SOLCON Soft Start, Immediate & Soft Stop L N 1 2 3 4 5 6 7 8 9 Common SoftStop Stop Reset D.Adjust/Reset Start C2 With Start, Stop push buttons C1 - Start and Soft Stop C 2 - Emergency Stop C1
  • 32. SOLCON Start - Stop With Push Buttons L N 1 2 3 4 5 6 7 8 9 Common SoftStop Stop Reset D.Adjust/Reset Start C1 C – Start button C2 – Soft Stop button C1 – Emergency Stop Button CC2
  • 33. SOLCON Remote Resetting Remote (hardwire) Resetting via terminal 7 or 8 when designated as Reset. L 1 2 3 4 5 6 7 8 9 Common SoftStop Stop Reset Start N C2C1 Reset
  • 34. SOLCON Auxiliary Relays FaultImmediate End of Acceleration Relay ratings : 8A, 250V, 2000VA 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
  • 35. SOLCON “Immediate Relay” L 1 2 3 4 5 6 7 8 9 10 11 12 Immediate / Shear pin Relay Programmable (I/O Parameters) as: * Immediate - with On and Off delays * Shear pin - Functions only upon Jam, with On delay
  • 36. SOLCON On / Off Time Delays Off Delay after soft stop On delay after start When start / soft Stop are used Off delay after stop When start / stop are used On delay after start (Returns upon Stop, Trip, voltage outage)
  • 37. SOLCON Example for “Immediate” Operation Creating special Starting Curves: 1. Designate “Imm. Relay” as Immediate, set On Delay time 2. Designate Terminal 8 as “Dual Adjust”, setting parameter. 3. Connect the N.O contact to the Dual Adj. Terminal 4. New Current & Torque - are being developed now 1 2 3 4 5 6 7 8 9 10 11 12 D.Adjust Immediate Relay On delay Voltage Ramp-up
  • 38. SOLCON Fault Relay Programmable (I/O Parameters) as: * Fault - changes position upon fault, returns upon fault reset * Fault Fail Safe - changes position upon Control Supply (1-3) connection, returns upon fault. 1 2 3 4…12 13 14 15 16 17 18 19 20 21 Fault Relay
  • 39. SOLCON End of Acceleration Relay L 4…... End of Acceleration Applications * Operating a valve * Operating By-Pass contactor On delay after End of Acceleration 13 14 15 16 17 18 (Returns upon Stop, Soft stop, Trip, voltage outage)
  • 40. SOLCON External Faults External Fault inputs - connected between terminals 19 or 20 and 21, (no need to use short wires as in low voltage starter) 1 2 3 4...9 13 14 15 16 17 18 19 20 21 Input#4 Input#3 Common N
  • 41. SOLCON Parameter Setting 6 keys, Menu driven software, Default parameters Medium Voltage Digital Reduced Voltage Starter HRVS-DN Mode StoreReset Select On Start Run S.Stop Stop Test D.Adjust Fault CURRENT LIMIT 400% 8 LEDs for quick status display  Two lines - 16 characters each, Back light  Selectable languages - English, German, French and Spanish  Communication Setting (software program)
  • 42. SOLCON PAGE 0 PAGE 1 PAGE 2 PAGE 3 PAGE 9 ? Mode Store Select I1 I2 I3 A MAIN & PROTECT. PARAMETERS STARTER FLC 150 AMP. MOTOR FLA 150 AMP. START PARAMETERS SOFT START CURVE 0 (STANDARD) START TACHO GAIN 0 (MIN. GAIN) PULSE TIME 0 SEC. INITIAL VOLTAGE 30 % CURRENT LIMIT 400 % OF FLA ACC. TIME 10 SEC. MAX. START TIME 30 SEC. NUMBER OF STARTS 1 STARTS PERIOD 20 MIN. START INHIBIT 15 MIN. RUN CONTACT DEL. 5 SEC. STORE ENABLE START PARAMETERS STOP PARAMETERS SOFT STOP CURVE 0 (STANDARD) STOP TACHO GAIN 0 (MIN. GAIN) DEC. TIME 10 SEC. FINAL TORQUE 0 (MIN.) STORE ENABLE STOP PARAMETERS UNDERCURR.DELAY 10 SEC. O/C - SHEAR PIN 850 % OF FLA UNDERCURR. TRIP 0 % OF FLA STATISTICAL DATA LAST STRT PERIOD NO DATA LAST START MAX. I NO DATA TOTAL RUN TIME 0 HOURS TOTAL # OF START 0 LAST TRIP NO DATA TRIP CURRENT 0 % OF FLA TOTAL # OF TRIPS 0 Minimized Mode O/C - DELAY 0.5 SEC OVERLOAD DELAY 4 SEC - AT 5 FLA 1 2 3 4 5 6 7 8 SOFT START CURVE * 4 (TORQUE) SOFT STOP CURVE * 4 (TORQUE) * Window appears* Window appears when previous windowwhen previous window exceeded its maximumexceeded its maximum range.range. INITIAL CURRENT * 100-400 % OPTION CARD NOT INSTALLED STORE ENABLE MAIN PARAMETERS UNBALANCE TRIP 20 % OF FLA GND FAULT TRIP 20% OF FLA UNDERVOLT. TRIP 75% Un UNDERVOLT. DELAY 5 SEC. OVERVOLT. TRIP 120% Un OVERVOLT. DELAY 2 SEC. OVERLOAD TRIP 115 % OF FLA OVERLOAD DELAY 4 SEC - AT 5 FLA UNBALANCE DELAY 5 SEC. GND FAULT DELAY 5 SEC.
  • 43. SOLCON COMM. PARAMETERS STORE ENABLE COMM. PARAMETERS Maximized Mode PAGE 4 PAGE 5 PAGE 6 PAGE 7 PAGE 9 FUTURE FUTURE FUTURE STORE ENABLE DRIVE NUMBER 0 BAUD RATE 9600 PARITY CHECK EVEN SERIAL LINK NO 248 (OFF) ? Mode Store Select DUAL ADJUSTMENT PARAMETERS DA: INIT. VOLT. 30% DA: CUR. LIMIT 400 % OF FLA DA: ACC. TIME 10 SEC. DA: DEC. TIME 10 SEC. DA: MOTOR FLA 105 AMP. D. ADJ: GENERATOR PARAMETERS FAULT PARAMETERS TRIP AFTER BYPAS ENABLE UNDER CUR. RESET OFF I/O PROGRAMMING PARAMETERS PROG. INPUT #1 TEST PROG. INPUT #2 DUAL ADJUSTMENT FAULT RELAY TYPE FAULT ANALOG OUTPUT NORMAL STORE ENABLE I/O PROG.PARAM. IMM / S.PIN RELAY IMMEDIATE RELAY ON DELAY 0 SEC. RELAY OFF DEL. 0 SEC. STORE ENABLE D.ADJ. PARAMETERS UV & PL AUTO RST NO 1 2 3 4 5 6 7 8 BY-PASS AUTO RST NO STORE ENABLE FAULT PARAMETERS BYPASS OPEN TRIP ENABLE
  • 44. SOLCON Start & Stop Parameters Fully Voltage Ramp, Current Ramp , Torque Ramp Initial Voltage OR Initial Current Acceleration Time (Ramp-up Time) Current Limit Deceleration Time (Ramp-down Time) - Soft Stop Pump Control Dual Adjustments Diesel Generator Starting Tacho. feedback
  • 45. SOLCON Initial Voltage Initial Voltage - determines the Initial Voltage and Torque (the Torque is reduced in the square proportion of the voltage reduction). Adjustable : 10-50% (5% - 80%) Un, should be set for the motor to start turning immediately after Start signal is initiated. Initial Current : above maximum value of initial voltage, setting change to Initial Current of 100%, for Current Ramp. 10% Initial Voltage 50% Un
  • 46. SOLCON Acceleration Time Acceleration Time - Determines the Voltage Ramp-up Time, from Initial to Full Voltage. Adjustable :1-30 (90) sec. Set to the shortest acceptable time. Time Voltage Ramp-up Time Un U start 30 sec2
  • 47. SOLCON Current Limit Current Limit - Determines the maximum current during acceleration process and the acceleration time to full speed. Adjustable :100-400% (500%) I FLA, Set to the highest acceptable current. Current Limit U start t soft start U C. L U1 Un I start RPM 400% 100%
  • 48. SOLCON Current Limit / Start Time Ratio Lower Current Limit => longer Start Time Time 4 x In 5 10 15 20 25 30 In 3 x In
  • 49. SOLCON Deceleration Time “Soft Stop” Deceleration Time - Determines the Voltage Ramp-down Time, from Un to zero. Adjustable: 1-30 (90) sec. Set to the shortest acceptable time. Un Speed Deceleration Time 2 30 / 90 sec
  • 50. SOLCON High Acceleration Torque causes rapid increase in pump speed, fast change in flow & consequently high Pressure in the pipe sys This high pressure may result in damage to pipes, fittings, joints, etc. Pump Starting - D.O.L TimeTime Torque M start Accel. Torque Motor DOL Voltage Speed Load Speed
  • 51. SOLCON Pump Starting - Soft Starter (standard) Standard soft starters drastically reduce the Starting Torque, however Peak Torque still remains high, causing high Acceleration Torque and rapid acceleration towards end of starting process. Peak Torque & Acceleration Torque must be reduced to extend Acceleration time Time Torque M start Accel. Torque Motor DOL With soft starter Voltage Slow Accel. Speed Load Speed Motor soft starter Time
  • 52. SOLCON Pump Control – Start Curves Pump Control “Start Curves” - Three special voltage ramp-up curves to reduce peak torque & extend Acceleration time. Adjustable: 0-4 Curves, set as required, 5=Torque Curve (6 = Virtual Current Curve is achieved when increasing Initial Voltage above full range and adjusting Initial current to the required setting) Time Voltage Area of Pump Control Start Curves With soft starter Speed Time 2 3 4 DOL 0 5,6 Torque 3 Speed D.O.L 2 1 0 4 5 1
  • 53. SOLCON Pump Stopping – D.O.L  When motor starter (DOL) is opened, abruptly stopping the pump, speed and flow are quickly reduced. This may cause a Water Hammer (mechanical shock and audible noise with severe damage to pipes, joints, fittings, valves, etc. )DOL opens Un Speed
  • 54. SOLCON Pump Stopping - Soft Starter (standard)  When using a standard soft starter, while pumping to a higher elevation, motor torque may quickly fall below load torque (as torque decreases at the square route of voltage reduction). This may cause abrupt stalling instead of smoothly decreasing speed to zero, creating the Water Hammer phenomenon. Stalling point Un Speed“Soft stop”
  • 55. SOLCON Pump Control – Stop Curves  Pump Control “Stop Curves” - enables selection between 3 special voltage ramp-down curves preventing stall condition and eliminating Water Hammer.  Adjustable:0-4 Curve, Set as required (4 = Torque controlled curve) Time Voltage Area of Pump Control Stop Curves Time With soft starter Speed 2 3 4 DOL 0 51 Torque 3 Speed D.O.L 2 1 0 4 5
  • 56. SOLCON Pump Control - Final Torque  Before reaching end of deceleration, motor torque reaches a level where the load torque is higher than motor's torque and motor stalls while current continues flowing through the motor heating the windings.  Final Torque feature enables setting a point where current stops when the motor stops rotating. Time Check Valve closes and motor stops Voltage Speed Area of Pump Control Final Torque Time DOL
  • 57. SOLCON Starting from a Diesel-Generator When starting from older D.G. sets (especially those equipped with low cost Voltage Regulators) both voltage and frequency are unstable, causing irregular thyristor firing. The HRVS-DN is equipped with a special program overcoming the voltage and frequency instability. Two options to operate Generator Mode:  Use Basic Curve.  set Dip Switch 3 to On and energize the Dual Adjustment Terminal. When testing in Generator mode at low voltage, motor must be loaded. When motor can operate from Mains and D.G (stand-by D.G) set Dip Switch # 3 to On. However, Dual Adjustment Terminal should be energized only when D.G. is running. 1 2 3 4 5 6 7 8
  • 58. SOLCON Dual Adjustment Parameters  Generator Mode: Special starting mode (D.G. supply)  Initial Voltage: 10 - 50% Un  Current Limit: 100 - 400% Motor FLA setting  Acceleration Time: 1 - 30 sec.  Deceleration Time: 1 - 30 sec.  Motor FLA: 50 - 100% Starter FLC setting Note - Set Dip Switch # 3 to On for Generator Mode and connect control voltage to terminal 8. Dual Adjust Characteristic Voltage Time Standard Characteristic
  • 59. SOLCON Motor & Starter Protection - 1  Too Many Start (No. of starts, Start period & Start Inhibit Time)  Long Start Time (Stall)  Over Current Shear pin (Jam)  Electronic Overload with selectable curves  Under Current  Under / No voltage  Over Voltage  Phase Loss  Phase Sequence  Wrong Connections / Shorted SCR  Continues on next page
  • 60. SOLCON Motor & Starter Protection - 2  Heatsink Over-temp.  External Fault 1 & 2  Unbalance Current  Ground Fault Current  Power On & no Start  Bypass Open - It is possible to disable.  It is possible to disable most of the protections after by-pass is closed.
  • 61. SOLCON Upon Fault  The starter locks in a Fault Mode  The starter records the Fault Data and updated Faults record.  Fault LED lights  LCD describes fault cause  Fault Relay changes position  Data is transferred through the communication
  • 62. SOLCON Resetting After Fault Resetting after fault has been removed, provided Start signal does not exist.  Local resetting – front panel key  Remote resetting – hard wire (terminals 7 & 8)  Remote resetting – through communication  Auto resetting – for Under Voltage & Phase Loss  Auto resetting – for Under Current  Auto resetting – for Faults occur after by-pass is closed
  • 63. SOLCON Motor & Starter Protection Start Run Soft Stop Stop  Too Many Starts + - - -  Long Start Time (Stall) + - - -  O/C Shear pin + + + +  Overload - + - -  Under Current - + - -  Under / No Voltage + + + -  Over Voltage + + + -  Phase Loss + + + -  Phase Sequence + + + -  Wrong Con/ Shorted SCR + - + -  Continues on next page
  • 64. SOLCON Motor & Starter Protection Start Run Soft Stop Stop  Heatsink Over temp. + - + -  External Fault 1 & 2 + + + +  Unbalance Current + + + -  Ground Fault Current. + + + -  Power On & no Start - - - +  By-pass Open - + - -
  • 65. SOLCON Max. C/L Adjustment, diff. Between LV & MV  In low voltage Max Current Limit is 500% (Extended Setting)  In Medium Voltage Max Current Limit setting is 400 * FLC / FLA 400* (FLC) FLA
  • 66. SOLCON Too Many Starts Note: 3 sec. Time delay after stop, before restarting Max. Number of Starts - preventing excessive starts during a short period of time. Adjustments:  Permitted Number of Starts: Off, 1- 10  Start period: 1- 60 min.  Start Inhibit Time (after Too Many Starts): 1- 60 min.
  • 67. SOLCON Stalled Motor Max. start time - Preventing Stall condition, trips the starter if current is not reduced below Motor FLA within the adjusted time. Adjustments: 1-30 (240) sec. Max. Starting Time Starting current 2010 30
  • 68. SOLCON Jam Protection Jam Protection - Trips the starter in less than 1 cycle when current exceeds 850% IFLA. Trip 850% IFLA Applications * Conveyors * Agitators * Complex Machinery
  • 69. SOLCON Shear-pin (“Immediate Relay” set to “Shear-pin”) - Stops (no trip) the motor when current exceeds the set level, with an adjustable time delay. Adjustments:  Trip Current 200 - 850% Motor FLA (during starting 850%)  Shear-pin Delay 0.5 - 5 sec (no delay at 850%) Trip 850% IFLA Electronic Shear-pin Applications * Shredders * Complicated drive systems
  • 70. SOLCON Overload Overload - Trips the starter when current increases above the O/L Trip level after the inverse time curve delay. Remember - Overload protection is functional only during RUN condition, after Max Start Time. During Start time motor is protected by Max Start Time. Adjustments:  Trip Current: 75-150% I FLA  Trip Delay at 500% I FLA : 1-10 sec. 150% 10 sec t 75% 500% 1 sec I 115% trip time at 500% FLA O/L setting
  • 71. SOLCON Under Current Under current - Trips the starter when current decreases below the U/C Trip level after the selectable time delay. Under current auto reset allows for restarting after a predefined period of time, to re-check the under current status. Adjustments:  Trip Current: Off, 20-90% I FLA  Trip Delay 1-40 sec. Start I FLA 20% 40 sec. 80% 20 90% 2 Applications * Dry running pumps * Broken belt / gear * Closed air inlet (fan)
  • 72. SOLCON Under / No Voltage Under Voltage - Trips the starter when voltage drops below the U/V Trip level after the selectable time delay. With programmable auto-reset. Adjustments:  Trip level 50-90% of Un (Line - Line)  Trip Delay 1-10 sec.  The starter will trip immediately, overriding the the time delay, in case voltage drops to zero
  • 73. SOLCON Over Voltage Over Voltage - Trips the starter when voltage increases above the O/V Trip level after the selectable time delay. Adjustments:  Trip level 110-125% of Un (Line - Line)  Trip Delay 1-10 sec.
  • 74. SOLCON Phase Loss & Phase Sequence Phase Loss - Trips the starter when one or two phases are missing for over 1 sec. With programmable auto-reset. Phase Sequence - Trips the starter immediately when phase sequence is wrong Note - There is no setting to allow working with wrong phase sequence
  • 75. SOLCON S.SCR / Wrong Motor Connection  Trips the starter if motor is not properly connected to starters’ Load terminals, 1,2 or 3 wires.  Trips if current waveforms are wrong  Disabled when in curve 0.  Disabled for Generator starting. C R 4160V
  • 76. SOLCON Heatsink Over-temp. Heatsink Over Temperature - Trips the starter if thermal sensors mounted on starter’s heatsink sense temperatures above 85 Deg. C. - Sensors are of the N/O type - Sensors are located on the top Heatsinks. - Sensors are not isolated from Medium Voltage Heatsinks. - “Sensor hot “ information is transferred to control module via fiber optic
  • 77. SOLCON External Fault External Fault – Inputs from two N.O. contacts. The starter trips 2 sec. after the any of the contact closes. RVS-DN Applications * Water level for pumps * Oil level for compressors
  • 78. SOLCON Current Imbalance Current Imbalance - Trips the motor when the unbalanced current increases above the preset current, and for time period above the preset delay. Adjustments:  Trip level 10-100% of I FLA  Trip Delay 1-60 sec.
  • 79. SOLCON Ground Fault Current Ground Fault - Trips the motor when Ground Current increases above the preset current, and for more then time period delay. Adjustments:  Trip level 10-100% of I FLA  Trip Delay 1-60 sec.  Protection can be disabled with dip switch
  • 80. SOLCON Power on & No start Power On and No Start - This protection becomes operational upon mains voltage connection. It trips the motor when mains is connected to the HRVS-DN for more then 30 seconds without a Start signal. Designed to prevent overheating of the voltage dividing resistors in the power section.
  • 81. SOLCON By - Pass Open By - Pass Open - Becomes operational when the by-pass contactor did not close after EOA contact command the pilot ( interposing) relay to close.
  • 82. SOLCON Main Parameters & Protection  Starter FLC 20 - 800A  Motor FLA 50 - 100% of starter FLC setting  Under Current Trip Off, 20 - 90% of motor FLA setting  Under Current Delay 1 - 40 sec.  O/C Shear pin 200 - 850% of motor FLA setting  O/C Shear pin Delay 0.5 - 5 sec.  Overload Trip 75 - 150% of motor FLA setting  Overload Delay 1 - 10 sec. (at 500% motor FLA)  Unbalance Trip 10-100% of motor FLA  Unbalance Delay 1-60sec.  Ground Fault Trip 10-100% of motor FLA  Ground Fault Delay 1-60sec. Continues on next slide
  • 83. SOLCON Main Parameters - cont.  Under-voltage Trip 50 - 90% of Un  Under-voltage Delay 1 - 10 sec.  Over-voltage Trip 110 - 125%of Un  Over-voltage Delay 1 - 10 sec.
  • 84. SOLCON Start Parameters  Soft start curve 11 selectable curves, including:  Start Tacho Gain 5 levels of Tacho Gain  Torque Control  Pulse Time 0 - 2 sec.  Initial Voltage/Current 10 - 50% (5-80%) Un, 100-400% In  Current Limit 100 - 400% (600) Motor FLA setting  Acceleration Time 1 - 30 (90) sec.  Max Start Time 1 - 30 (250)sec.  Number of Starts 1 - 10, Off  Starts Period 1 - 60 min.  Start Inhibit Period 1 - 60 min.  Run Contact Delay 0 - 120 sec.  3 sec. time delay before immediate restart  Current limit 410..600%, only for RVS_FLC > Motor_FLA
  • 85. SOLCON Stop Parameters  Soft stop curve 11 selectable curves, including:  Stop Tacho Gain 5 levels of Tacho Gain  Torque Control  Deceleration Time 1 - 30 (90) sec.  Final Torque 0 - 10
  • 86. SOLCON Dual Adjustment Parameters  Generator Mode Special starting mode (D.G. supply)  Initial Voltage 10 - 50% Un  Current Limit 100 - 400% (600) Motor FLA setting  Acceleration Time 1 - 30 sec.  Deceleration Time 1 - 30 sec.  Motor FLA 50 - 100% Starter FLC setting Note - Set Dip Switch # 3 to On for Generator Mode and connect control voltage to terminal 8. Dual Adjust Characteristic Voltage Time Standard Characteristic
  • 87. SOLCON Fault Parameters  U/V & Phase Loss Auto Reset Yes / No  Under Current Auto Reset Yes / No  By-Pass Open Trip Enable/Disable  Trip After By-Pass Enable/Disable  By-Pass Auto Reset Yes/No  Disable By-Pass Open Trip - When by-pass is external to Starter’s cabinet and CTs do not “see” current when by-pass is closed.
  • 88. SOLCON I / O Programming  Terminal 7 (Input # 1) Test (future), Reset  Terminal 8 (Input # 2) Dual Adjustment, Reset  Fault Relay Fault, Fault - fail safe  Immediate Relay function Immediate / Shear pin  Immediate Relay On-delay Imm. 0 - 60 sec. / Shear pin 0 - 5 sec.  Immediate Relay Off-delay Imm. 0 - 5 sec. / Shear pin 0 - 5 sec.  Analogue Output Normal, Inverted
  • 89. SOLCON Communication Parameters MODBUS RTU (Optional)  Drive number 0 - 999  Baud rate 1200 - 9600  Parity check Even / Odd  Serial link No. 1 - 247 & 248 =Off RS 485 with MODBUS RTU protocol can control and supervise up to 32 starters through a twisted pair. Other Optional protocols available (Profibus, Modbus TCP/IP...)
  • 90. SOLCON Statistical Data  Last start Period  Last start max. current  Total run time  Total number of starts  last trip  Trip current  Total number of trips  Previous Trips (1-9)
  • 91. SOLCON Multi-Start Application 1100 mm 1100 mm 2500 mm LC0 LC1 MOTOR 1 MOTOR 2 LC2 MOTOR 3 LC3 BP2 BP3BP1 Prot Prot Prot MPS 3000 MPS 3000 MPS 3000 Prot 1100 mm 1100 mm 1100 mm MOTOR 4 Prot MPs 3000 1100 mm BP4 LC4 INCOMING MPS 3000
  • 92. SOLCON About Solcon  Established in 1977  Privately owned (approved investor)  60 employees  Export oriented (approx. 80% export)  ISO 9002  Other approvals CE, UL, cUL, Lloyd’s  Main office - in Herzlia (near Tel-Aviv)  Manufacturing - 3000 sq.m plant in Yokneam (near Haifa)
  • 93. SOLCON Soft Starter History  1978 – Start manufacturing of L.V. soft starters, type RVS  1981 – Introduction of digital soft starters, type RVS-D  1985 – Developed the HRVS-D with digital control for PCC Patriot (a Magnetek company).  1999 – PCC / Motortronics Agreement  2000 – Introduction of the “Third Generation” soft starter, with two patents (pending) for: Wireless SCR Control Electronic Potential Transformer  Offering today the most comprehensive line of soft starter
  • 94. SOLCON Contact Persons  Ami Shahaf – Managing Director  Dr. Yoram Waltuch – Engineering Director  Jacob Gabai – Production Director  Hanan Schwartz – Controller  Eli Wildawski – Marketing Manager  Ofir Goren – Sales Manager  Izzi Eicher – Area Manager
  • 95. SOLCON Other Subjects 11 & 13.8 KV soft starters DNV, ABS (Marine) UL / CSA requirements
  • 96. SOLCON Product Lines  Electronic Soft Starters  Protection Relays  Digital Control Systems
  • 97. SOLCON Marketing M.V. Soft Starters  Agreements with major international companies  Sales through Solcon Distributors  Unique activities in Mexico  Special activities in the marine market in Korea
  • 98. SOLCON Notes  When Ordering:  Specify low voltage level for testing.  Specify Motor FLA  Consult factory for multi - motor starting.  Consult factory for long starts.  Consult factory for long conveyer starting.
  • 99. SOLCON Testing with L.V. Motor Low Voltage Test Harness Firing Test without Mains
  • 100. SOLCON Ratings & Dimensions (mm) Volts FLC KW Chassis (mm) Enclosed (mm) 60 190 110 350 2300 200 650 660 x 1000 x 460 320 1000 400 1300 600 1960 800 x 1200 x 570 800 2620 60 275 900 x 2300 x 1000 110 510 3300 200 940 660 x 1000 x 460 320 1500 400 1880 600 2820 800 x 1200 x 570 800 3760
  • 101. SOLCON Ratings & Dimensions (mm) Volts FLC KW Chassis (mm) Enclosed (mm) 60 350 110 650 4160 200 1180 660 x 1000 x 460 320 1900 900 x 2300 x 1000 400 2370 600 3560 800 x 1200 x 570 800 4750 70 650 140 1310 660 x 1000 x 460 6600 250 2350 1100 x 2300 x 1100 300 2820 400 3770 800 x 1200 x 570 600 4720 Select starter according to motors nominal current and starting conditions.
  • 102. SOLCON Ratings & Dimensions (mm) Volts FLC KW Chassis (mm) Enclosed (mm) 140 2200 11000 250 4000 400 6400 1500 x 2300 x 1500 500 8000 600 10000 800 13000 100 2000 200 4000 13800 300 6000 1500 x 2300 x 1500 400 8000 500 10000 600 12000 800 16000 1000 20000 Select starter according to motors nominal current and starting conditions.
  • 103. SOLCON IP00 Assembly HRVS-DN Soft-Starter Control Panel HRVS-DN Soft-Starter Power Module I 1 I 2 I 3 EPT-Rx Receiver EPT - Tx Transmitter 13 11 { { { CT 3 4 8 9 13 14 13 11 Electric Wire Harness (6 wires) HRVS-DN IP00 Wiring and connections between: Power Module, EPT Receiver , Control module and Transformer 1 3 5 7 8 9 Fiber Optic Harness (6 fibers) Fiber-Optic Inputs 24VAC 115/230VAC 24V Gnd 1 2 3 Auxiliary Relay (Not Supplied) 1 2 3 1 6 11 (R) (S) (T) 115V / 230V Cooper Wire Area - At least 4 mm2 1 1 1 Fiber-Optic links (2 fibers) 15 10 5 11 6 1 White Male Connector White Female Connector Fuse inside Receptacle Segregated Low Voltage Compartment Segregated High Voltage Compartment CT CT
  • 104. SOLCON Firing Boards Assembly Six Red LED’s Six Green LED’s
  • 105. SOLCON Soft Starters components Control Module Power Section Transformer to 24VAC Electronic P/T - Receiver
  • 106. SOLCON Power Section Connections Power Section Harness EPT Rx Two F/O and Three wires Plug at the back of Control Module F/O Plugs at the Top of Control Module
  • 107. SOLCON Electronic P/T Two fiber optic Transmitter Receiver
  • 109. SOLCON Firing Power supply VAC Supply from Trans. L.V. Fuse
  • 111. SOLCON Fiber Optic Board L3 Ground Fault 1&2 0 - Normal 1 - Cancel G/F Protection Current Gain L1 1- off – x 5 Gain On - Normal 2- off - x 13.4 Gain On - Normal L2