23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0029
CIRED 2015 1/4
TAP CHANGER POSITION DETERMINATION USING NEW ALGORITHM AND
POSSIBILITIES OF INTELLIGENT ELECTRONIC DEVICES
Siniša SPREMIĆ Mileta SENTIN Dušan PETROVIĆ
EPS-P.D. Elektrovojvodina - Serbia EPS-P.D. Elektrovojvodina - Serbia EPS-P.D. Elektrovojvodina - Serbia
sinisa.spremic@ev.rs mileta.sentin@ev.rs dusan.petrovic@su.ev.rs
Zoran RISTANOVIĆ
Energotehnika Južna Bačka - Serbia
zoran.ristanovic@entjuba.rs
ABSTRACT
Paper consider possibility for determining On-Load Tap
Changer (in following text: OLTC) position using
primary and secondary (tertiary) currents and voltages of
transformers equipped with OLTC. New algorithm for
OLTC position determination using primary and
secondary (tertiary) currents and voltages is presented.
Different influences on algorithm accuracy like analog
inputs errors of Intelligent Electronic Devices (in
following text: IED), transformer turn ratio errors,
instrument transformers accuracy errors, errors due to
magnetizing (no load) currents and voltage drop were
considered. Results of practical check are given in order
to prove applicability with aim to improve reliability in
particular segments of electricity distribution:
automation, protection and control (supervision).
INTRODUCTION
Modern IEDs for transformers protection incorporate all
necessary protection and automation functions and
signaling. They are programming devices so it is possible
to make additional protection, automation and control
functions and signaling or existent could be expand in
order to improve existent functions and reliability and to
make new functions using communication possibilities.
OLTC position data is necessary for local and remote
supervision purposes, for parallel operation of
transformers using master-follower method and could be
used for more sensitive adjustment of differential
protection. Existent OLTC position data is obtained from
OLTC`s motor drive unit using different types of output.
Possible outputs are resistance, mA (more common) or V
(less common), contact range and codes (BCD, Grey and
Binary). Those devices are reliable but sometimes
different malfunctions occur. Mechanical, electrical,
chemical and electromechanical malfunctions like broken
parts, bad contact, rust, stain, etc. lead to false or no
OLTC position data which will cause blocking of parallel
operation of transformers using master-follower method
and to less sensitive differential protection in IEDs which
have this option. Less important but not negligible is
missing remote supervision data. One of nowadays trends
is reliability improvement in every segment of electricity
distribution. Using advanced possibilities of modern
IEDs and new algorithm for OLTC position
determination using primary and secondary (tertiary)
currents and voltages could improve reliability.
ERRORS OF OLTC POSITION
DETERMINATION USING CURRENTS
Errors of OLTC position determination using currents in
new algorithm are analog inputs errors of IED,
transformer turn ratio errors, current transformers
accuracy errors and errors due to magnetizing (no load)
currents of transformers.
Absolute values of errors for current analog inputs in
IEDs are less than 1 %, mostly lower than 0,5 % up to In.
Turn ratio errors of transformers are limited by standard
[1] and should be in 0,5 %. According to test reports of
transformers, measured values of turn ratios are
significantly lower than 0,5 % and they are similar among
phases.
Current transformers accuracy classes at 110 kV side are
0,2 % or 0,5 %. At low voltage side accuracy class is
mostly 1 %. Phase class is negligible for this
consideration (up to 30 min). Accuracy errors according
to test reports are significantly lower than accuracy class
at nominal current and power factor 0,8. Current
transformer producers during designing and producing
made certain correction in order to shift accuracy curve
with positive error at higher loads and negative at lower
loads.
Most interesting are errors due to magnetizing (no load)
currents. No load currents depend of design and materials
used in transformer production [2]. Older transformers
110/x kV with poorer quality of steel sheets have no load
currents from 1 % to 3 % of nominal current of
transformer and newer from 0,2 % to 0,5 % at Un. No
load currents have significant increase with voltage
increase. Voltage increase of 10 % lead to increase of no
load currents mostly up to 4 %. No load currents among
phases could be significantly different due to core
construction. This is the reason to use all phase currents
to calculate turn ratio and thus OLTC position. Using
results of no load loss and current measurements for
several transformers, calculation was made in order to
check level of error originated from no load currents.
Secondary voltage values are set to 0,9Un, Un and 1,1Un
for load range from 10 % to 100 % and for values of
power factor (0,8 – 0,85 – 0,9 – 0,95 – 1). Results for one
of considered transformers 110/x kV with low level of no
load currents are given in Figures 1, 2 and 3.
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0029
CIRED 2015 2/4
Fig. 1 Error characteristics at 0,9Un
Fig. 2 Error characteristics at Un
Fig. 3 Error characteristics at 1,1Un
Figures 1, 2 and 3 show that error originated from
magnetizing (no load) currents have tendency of increase
in cases od decreasing load and power factor value and
increasing voltage. Un of considered transformers is 21
kV and normal operating voltages are in range from 20
kV to 21 kV, power factor values are in range from 0,92
to 0,98 and loads which have significant daily or season
changes are mostly greater than 30 %. It can be assumed
that error of magnetizing currents at normal operating
conditions should be less than 0,6 % which is less than
0,4 position for voltage step of 1,6 %.
ERRORS OF OLTC POSITION
DETERMINATION USING VOLTAGES
Errors of OLTC determination using voltages in new
algorithm are analog inputs errors of IED, transformer
turn ratio errors, voltage transformers accuracy errors,
errors due to load currents of transformers and load
asymmetry among phases and error of parallel operation
of transformers.
Absolute values of errors for voltage analog inputs in
IEDs are less than 1 %, mostly lower than 0,5 %.
Turn ratio errors of transformers are limited by standard
[1] and should be in 0,5 %. According to test reports of
transformers, measured values of turn ratios are
significantly lower than 0,5 % and they are similar among
phases.
Voltage transformers accuracy classes at 110 kV side are
0,2 % or 0,5 % [3, 4]. At low voltage side accuracy class
is mostly 1 % [3, 4]. Phase class is negligible for this
consideration (up to 30 min). Accuracy errors according
to test report are significantly lower than accuracy class
at nominal voltage.
Symmetrical or asymmetrical load currents have the
greatest influence in OLTC position determination using
primary and secondary voltages. Voltage drop in
transformer impedance which is mostly reactance have
significant values at normal operating conditions.
Figure 4 shows difference of calculated and set (real)
OLTC position using voltage drop calculation for
considered transformer.
Fig. 4 Difference of calculated and real OLTC position
It is obvious that voltage drop and difference of
calculated and set (real) position have low value at power
factor cos=1 and difference has significant value even
for power factor cos=0,99.
OLTC position determination using voltages of paralleled
transformers is not possible because transformers have
same primary and secondary voltages no matter of actual
positions of paralleled transformers. Because of that it is
not possible to determine accurate OLTC position using
new algorithm from voltages in case of parallel operation
of transformers.
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0029
CIRED 2015 3/4
NEW ALGORITHM FOR OLTC POSITION
DETERMINATION
OLTC position determination using primary and
secondary (tertiary) currents and voltages need certain
prerequisites. In order to simplify consideration only
primary and secondary currents and voltages will be
considered. It is necessary to set some parameters at IED.
Those parameters are nominal turn ratio m12sr, step
voltage Vs (%) and overal number of positions with
different turn ratio nuk (transition positions and positions
without turn ratio change are exluded). IEDs should have
analog inputs for all three primary and secondary currents
and voltages. New algorithm is given in following
equation
100
2
1
100
1
12
12
s
sr
uks
srmeas
ukRS
V
m
nV
mm
nn












 

 (1)
or in simplified form
5,05,0
12
1
100









 ukn
srm
measm
sVRSn (2)
Equation for calculated turn ratio from primary and
secondary currents mmeas is
primLprimLprimL
LLL
III
III
measm
321
sec3sec2sec1


 (3)
or from primary and secondary voltages mmeas is
sec3sec2sec1
321
LLL
primLprimLprimL
UUU
UUU
measm


 (4)
Calculated („measured“) OLTC position nRS using new
algorithm shall be rounded to integer value. Using
averaged value of currents or voltages at certain period
(e.g. several sine periods) is the way to use algortihm.
Because of faults in supplied network or at opposite side
of the transformer there is possibility that high values of
currents or sudden voltage changes occur. This could lead
to higher level of accuracy errors at particular periods of
time. Increased accuracy errors is the reason to ignore
this periods. This will not cause any malfunction because
faults with high currents should be disconnected by
protecting devices very fast and automatic voltage
regulation is slow procedure compared to protection
functions. Whole process of OLTC position change,
depending of type of OLTC, lasts from 2 to 7 seconds so
exluding some periods will not cause reliability decrease.
Higher voltage drop, depending on parameters set at
automatic voltage regulator, will cause that automatic
voltage regulator block OLTC operation so calculated
OLTC position prior to blocking will be in use.
PRACTICAL CHECK OF NEW ALGORTHM
In order to prove applicability of proposed algorithm
practical check was made. Several different transformers
110/21/10,5 kV/kV/kV and 110/36,75/10,5 kV/kV/kV
with nominal power of 31,5 and 20 MVA and step
voltage 1,6 % and 1,5 % were checked. Transformers
have IED units of three different producers.
Power factor values were within range of 0,93 to 0,99.
Primary voltages were within range of 108 kV to 116,9
kV. Secondary voltages were within ranges of 19,9 kV to
21,17 kV and 35,14 kV to 36,09 kV. Whole OLTC
position range is from 1 to 21 and for practical check it
was from 6 to 21.
Figure 5 shows difference of “measured” OLTC position
using currents and real OLTC position. All differences
are less than 0,5 so rounded value of “measured” OLTC
position will be equal to real OLTC position.
Fig. 5 Difference of measured and real OLTC position
Figure 6 shows difference of “measured” OLTC position
using voltages and real OLTC position. One phase to
phase voltage was used in calculation instead all three
phase voltages. Load increasing lead to OLTC position
difference increasing similar to characteristics from
Figure 4. Up to about 30 % of load difference of
“measured” to real OLTC position is less than 0,5 so
rounded OLTC position will be equal to real.
Fig. 6 Difference of measured and real OLTC position
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0029
CIRED 2015 4/4
Addition of all errors for currents could give overall error
of about 5 % which is in case of step voltage of 1,6 %
more than 3 OLTC positions error. Some of errors
compensate each other. For example current transformers
usually have positive error at currents from 0,25In to
1,2In. Current transformer of low voltage side of the
transformer are of lower accuracy class than current
transformers of high voltage side so it is expected that
ratio Isec/Iprim has positive error. Contrary influence of
magnetizing currents have negative influence at whole
range of currents for ratio Isec/Iprim so current transformer
error is compensated with magnetizing current influence.
It is possible that other errors compensate each other at
certain level.
Practical check at load range from about 20 % and 90 %
shows applicability of proposed algorithm for OLTC
position calculation using measured primary and
secondary currents and voltages.
Currents usage shows good results at range from 20 % to
about 90 % of load. It could be expected that current
could be used for loads up to 120 % and possibly more.
Voltage usage shows good results at range from 0 % up
to about 30 % of load.
Hitherto practical checks lead to recommendation to use
voltages up to 20 % of load and currents from 20 %
upward for OLTC position calculation.
It is necessary to make additional numerous practical
checks in order to prove applicability at loads lower than
20 % and greater than 90 % and to check range from 20
% to 30 % of load. Range from 20 % to 30 % of load is
boundary area in which average value of OLTC position
determined from currents and voltages could be the best
option to use.
ALGORITHM APPLICABILITY
OLTC position determination using proposed algorithm
could be applied for:
- Basic OLTC position data in case of old motor drive
units with inoperable device for OLTC position without
possibility to simple repair or change.
- Spare OLTC position data in case of malfunction of
device for basic OLTC position data useful for local and
remote supervision purposes and for parallel operation of
transformers using master-follower method avoiding
parallel operation blocking. Even in case of one or two
real OLTC position difference among paralleled
transformers because of errors in measuring chain there
will be no parallel operation blocking. Parallel operation
blocking is undesirable because it could lead to big
voltage fluctuations.
- Control (supervision) OLTC position data in case of
non reliable data from OLTC position device due to
contact problem (rust, stain).
- Differential protection could be set more sensitive using
OLTC position data. For example if current transformers
on both sides are rated 5P10 (i.e. composite error is max.
5 %) and the OLTC range is 10x1,6 % calculate starting
ratio setting S = 5 % (HV CT) + 5 % (LV CT) + 10x1,6
% (OLTC) + 4 % (relay) + 5 % (margin) = 35 %. If
OLTC influence should be compensated automatically
starting ratio setting S = 5 % (HV CT) + 5 % (LV CT) +
4 % (relay) + 5 % (margin) = 19 % which is significantly
lower than without compensation. If we include margin
of OLTC position error obtained with algorithm of two
positions starting ratio setting will be S = 5 % (HV CT) +
5 % (LV CT) + 2x1,6 % (OLTC) + 4 % (relay) + 5 %
(margin) = 22,2 % which is also significantly lower than
value in first calculation. There is no need for analogue
input for OLTC position in IEDs.
Even if IED has not got analogue inputs for all voltages
and currents it could receive data using IEC 61850 or
other protocol communication. Received data must be
synchronized with data obtained by IED`s analogue
inputs to avoid calculation errors of data from different
time periods.
CONCLUSION
Proposed algorithm for OLTC position determination is
simple and applicable in modern IEDs. It could improve
reliability in small but relevant segment of automation,
e.g. parallel operation of transformers using mater-
follower method avoiding parallel operation blocking in
case malfunction of device for OLTC position data. It is
applicable in protection improving sensitivity of
differential protection without need for analogue input or
inputs for OLTC position data. It is also useful for basic,
spare or supervision OLTC position data in case of
malfunction of device for basic OLTC position data.
Further consideration will comprise numerous practical
checks in order to test whole range of loads with attention
on range from 20 % to 30 % of load as boundary between
good results of OLTC position determined from
measured voltages or currents and to review correction
possibilities.
REFERENCES
[1] IEC 60076-1:1993+A1:1999, "Power transformers –
Part 1: General"
[2] Branko Mitraković, 1979, Transformatori, Naučna
knjiga, Beograd, Serbia, 93-107.
[3] S. Spremić, D. Petrović, Z. Ristanović, M. Sentin,
"Unapređenje funkcija uređaja mikroprocesorske
zaštite transformatora", CIRED Srbija – VIII
savetovanje o elektrodistributivnim mrežama Srbije
sa regionalnim učešćem, 2012, paper R-4.14, p.8,
Vrnjačka Banja.
[4] M. Sentin, Z. Ristanović, S. Spremić, D. Petrović,
"Praktična provera primenjivosti određivanja
položaja regulacione sklopke korišćenjem struja
primara i sekundara transformatora", CIRED Srbija –
VIII savetovanje o elektrodistributivnim mrežama
Srbije sa regionalnim učešćem, 2012, paper R-4.20,
p.5, Vrnjačka Banja.

More Related Content

What's hot

Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 
UNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMUNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMerramansaini1947
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculationsmichaeljmack
 
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...vaibyfrndz
 
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay PerformanceImpact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay PerformanceRadita Apriana
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculationsmichaeljmack
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6Nageswar Rao
 
A step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsA step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsH. Kheir
 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixTrupesh Rupareliya
 
Power systems symmetrical components
Power systems symmetrical componentsPower systems symmetrical components
Power systems symmetrical componentsanoopeluvathingal
 
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATIONSOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATIONvaibyfrndz
 
Effect of change in burden and power factor on CTs
Effect of change in burden and power factor on  CTsEffect of change in burden and power factor on  CTs
Effect of change in burden and power factor on CTsManish Sadhu
 
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisUp/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisCSCJournals
 

What's hot (20)

Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
Pullbox sizing
Pullbox sizingPullbox sizing
Pullbox sizing
 
UNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMUNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEM
 
Comparative Study of Diagnostic of Inverter Three and Five Levels Associate...
Comparative Study of   Diagnostic of Inverter Three and Five Levels Associate...Comparative Study of   Diagnostic of Inverter Three and Five Levels Associate...
Comparative Study of Diagnostic of Inverter Three and Five Levels Associate...
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculations
 
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMP...
 
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay PerformanceImpact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
 
E044043336
E044043336E044043336
E044043336
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculations
 
Substation design-guideliness
Substation design-guidelinessSubstation design-guideliness
Substation design-guideliness
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
 
Dead time pwm
Dead time pwmDead time pwm
Dead time pwm
 
A step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsA step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systems
 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrix
 
Ratio, Burden, and Admittance Testing
Ratio, Burden, and Admittance TestingRatio, Burden, and Admittance Testing
Ratio, Burden, and Admittance Testing
 
Power systems symmetrical components
Power systems symmetrical componentsPower systems symmetrical components
Power systems symmetrical components
 
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATIONSOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
 
Effect of change in burden and power factor on CTs
Effect of change in burden and power factor on  CTsEffect of change in burden and power factor on  CTs
Effect of change in burden and power factor on CTs
 
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability AnalysisUp/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
Up/Down Converter Linear Model with Feed Forward and Feedback Stability Analysis
 
DC DC Converter
DC DC ConverterDC DC Converter
DC DC Converter
 

Viewers also liked

ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)AB Amit
 
Ppt db electrical
Ppt db electricalPpt db electrical
Ppt db electricalRechalhyan
 
Oil filled transformer accessories - copy
Oil  filled  transformer   accessories - copyOil  filled  transformer   accessories - copy
Oil filled transformer accessories - copyayyadurai SHANMUGAM
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
 
25 p.10.4 transformation of electrical energy ppt (2) (1)
25  p.10.4 transformation of electrical energy ppt (2) (1)25  p.10.4 transformation of electrical energy ppt (2) (1)
25 p.10.4 transformation of electrical energy ppt (2) (1)Christine Snyder
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersShailendra Shakya
 
earth air tunnel latest ppt
earth air tunnel latest pptearth air tunnel latest ppt
earth air tunnel latest pptvikas mahala
 
(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...
(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...
(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...Md Abu Jauad Khan Aliv
 
Switchgear and protection 5
Switchgear and protection 5Switchgear and protection 5
Switchgear and protection 5Md Irshad Ahmad
 
OLTC Function Selection, Operation
OLTC Function Selection, OperationOLTC Function Selection, Operation
OLTC Function Selection, OperationMax Philipp
 
Differential protection of power transformer
Differential protection of power transformerDifferential protection of power transformer
Differential protection of power transformerSaad Muftah
 
electricity supply ppt
electricity supply pptelectricity supply ppt
electricity supply pptsameerchat
 

Viewers also liked (20)

ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Ppt db electrical
Ppt db electricalPpt db electrical
Ppt db electrical
 
RVR-1(3) automatic step voltage regulator
RVR-1(3) automatic step voltage regulatorRVR-1(3) automatic step voltage regulator
RVR-1(3) automatic step voltage regulator
 
Oil filled transformer accessories - copy
Oil  filled  transformer   accessories - copyOil  filled  transformer   accessories - copy
Oil filled transformer accessories - copy
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
Agc wp-onloadtapchangerfiltsys
Agc wp-onloadtapchangerfiltsysAgc wp-onloadtapchangerfiltsys
Agc wp-onloadtapchangerfiltsys
 
25 p.10.4 transformation of electrical energy ppt (2) (1)
25  p.10.4 transformation of electrical energy ppt (2) (1)25  p.10.4 transformation of electrical energy ppt (2) (1)
25 p.10.4 transformation of electrical energy ppt (2) (1)
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit Breakers
 
earth air tunnel latest ppt
earth air tunnel latest pptearth air tunnel latest ppt
earth air tunnel latest ppt
 
(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...
(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...
(Aliv) Multiple Transformers Oil Temperature Monitoring with Automatic Circui...
 
Switchgear and protection 5
Switchgear and protection 5Switchgear and protection 5
Switchgear and protection 5
 
OLTC Function Selection, Operation
OLTC Function Selection, OperationOLTC Function Selection, Operation
OLTC Function Selection, Operation
 
Tap Changer
Tap ChangerTap Changer
Tap Changer
 
Air Circuit breaker
Air Circuit breakerAir Circuit breaker
Air Circuit breaker
 
Tap changer
Tap changerTap changer
Tap changer
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Circuit breakers
Circuit breakers Circuit breakers
Circuit breakers
 
Differential protection of power transformer
Differential protection of power transformerDifferential protection of power transformer
Differential protection of power transformer
 
electricity supply ppt
electricity supply pptelectricity supply ppt
electricity supply ppt
 

Similar to CIRED2015_0029_SpremicEtAll

IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET Journal
 
Study and implementation of comparator in cmos 50 nm technology
Study and implementation of comparator in cmos 50 nm technologyStudy and implementation of comparator in cmos 50 nm technology
Study and implementation of comparator in cmos 50 nm technologyeSAT Journals
 
Study and implementation of comparator in cmos 50 nm
Study and implementation of comparator in cmos 50 nmStudy and implementation of comparator in cmos 50 nm
Study and implementation of comparator in cmos 50 nmeSAT Publishing House
 
06 current -__voltage_transformers
06 current -__voltage_transformers06 current -__voltage_transformers
06 current -__voltage_transformersKrishna Das
 
PID Controller Response to Set-Point Change in DC-DC Converter Control
PID Controller Response to Set-Point Change in DC-DC Converter ControlPID Controller Response to Set-Point Change in DC-DC Converter Control
PID Controller Response to Set-Point Change in DC-DC Converter ControlIAES-IJPEDS
 
Soft Switched Resonant Converters with Unsymmetrical Control
Soft Switched Resonant Converters with Unsymmetrical ControlSoft Switched Resonant Converters with Unsymmetrical Control
Soft Switched Resonant Converters with Unsymmetrical ControlIOSR Journals
 
Best-transformer-test-procedures-en
  Best-transformer-test-procedures-en  Best-transformer-test-procedures-en
Best-transformer-test-procedures-enbala12984
 
Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...
Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...
Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...Ghazal Falahi
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-enSuresh Patil
 
Analysis of direct power control AC-DC converter under unbalance voltage supp...
Analysis of direct power control AC-DC converter under unbalance voltage supp...Analysis of direct power control AC-DC converter under unbalance voltage supp...
Analysis of direct power control AC-DC converter under unbalance voltage supp...IJECEIAES
 
automatic power factor correction report
automatic power factor correction reportautomatic power factor correction report
automatic power factor correction reportamaljo joju e
 
Simulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationSimulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationIJECEIAES
 
Design & Implementation of Zero Voltage Switching Buck Converter
Design & Implementation of Zero Voltage Switching Buck ConverterDesign & Implementation of Zero Voltage Switching Buck Converter
Design & Implementation of Zero Voltage Switching Buck ConverterIJERA Editor
 
Power converter lab manual by chaturvedula
Power converter lab manual by chaturvedulaPower converter lab manual by chaturvedula
Power converter lab manual by chaturvedulaKumarChaturvedula
 
Soft-Switching Two-Switch Resonant AC-DC Converter
Soft-Switching Two-Switch Resonant AC-DC ConverterSoft-Switching Two-Switch Resonant AC-DC Converter
Soft-Switching Two-Switch Resonant AC-DC ConverterIRJET Journal
 
THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...
THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...
THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...theijes
 
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...IOSR Journals
 

Similar to CIRED2015_0029_SpremicEtAll (20)

IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply SystemIRJET- Auto Selection of any Available Phase, in Three Phase Supply System
IRJET- Auto Selection of any Available Phase, in Three Phase Supply System
 
Study and implementation of comparator in cmos 50 nm technology
Study and implementation of comparator in cmos 50 nm technologyStudy and implementation of comparator in cmos 50 nm technology
Study and implementation of comparator in cmos 50 nm technology
 
Study and implementation of comparator in cmos 50 nm
Study and implementation of comparator in cmos 50 nmStudy and implementation of comparator in cmos 50 nm
Study and implementation of comparator in cmos 50 nm
 
06 current -__voltage_transformers
06 current -__voltage_transformers06 current -__voltage_transformers
06 current -__voltage_transformers
 
PID Controller Response to Set-Point Change in DC-DC Converter Control
PID Controller Response to Set-Point Change in DC-DC Converter ControlPID Controller Response to Set-Point Change in DC-DC Converter Control
PID Controller Response to Set-Point Change in DC-DC Converter Control
 
Design of Low Voltage and High Speed Double-Tail Dynamic Comparator for Low P...
Design of Low Voltage and High Speed Double-Tail Dynamic Comparator for Low P...Design of Low Voltage and High Speed Double-Tail Dynamic Comparator for Low P...
Design of Low Voltage and High Speed Double-Tail Dynamic Comparator for Low P...
 
K010116671
K010116671K010116671
K010116671
 
Soft Switched Resonant Converters with Unsymmetrical Control
Soft Switched Resonant Converters with Unsymmetrical ControlSoft Switched Resonant Converters with Unsymmetrical Control
Soft Switched Resonant Converters with Unsymmetrical Control
 
Best-transformer-test-procedures-en
  Best-transformer-test-procedures-en  Best-transformer-test-procedures-en
Best-transformer-test-procedures-en
 
Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...
Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...
Design consideration of an mmc hvdc system based on 4500 v:4000a emitter turn...
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-en
 
Analysis of direct power control AC-DC converter under unbalance voltage supp...
Analysis of direct power control AC-DC converter under unbalance voltage supp...Analysis of direct power control AC-DC converter under unbalance voltage supp...
Analysis of direct power control AC-DC converter under unbalance voltage supp...
 
automatic power factor correction report
automatic power factor correction reportautomatic power factor correction report
automatic power factor correction report
 
Level Shifted Discontinuous PWM Algorithms to Minimize Common Mode Voltage fo...
Level Shifted Discontinuous PWM Algorithms to Minimize Common Mode Voltage fo...Level Shifted Discontinuous PWM Algorithms to Minimize Common Mode Voltage fo...
Level Shifted Discontinuous PWM Algorithms to Minimize Common Mode Voltage fo...
 
Simulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationSimulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulation
 
Design & Implementation of Zero Voltage Switching Buck Converter
Design & Implementation of Zero Voltage Switching Buck ConverterDesign & Implementation of Zero Voltage Switching Buck Converter
Design & Implementation of Zero Voltage Switching Buck Converter
 
Power converter lab manual by chaturvedula
Power converter lab manual by chaturvedulaPower converter lab manual by chaturvedula
Power converter lab manual by chaturvedula
 
Soft-Switching Two-Switch Resonant AC-DC Converter
Soft-Switching Two-Switch Resonant AC-DC ConverterSoft-Switching Two-Switch Resonant AC-DC Converter
Soft-Switching Two-Switch Resonant AC-DC Converter
 
THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...
THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...
THD Minimisation for Phase Voltage of Multilevel Inverters Using Genetic Algo...
 
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
 

CIRED2015_0029_SpremicEtAll

  • 1. 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0029 CIRED 2015 1/4 TAP CHANGER POSITION DETERMINATION USING NEW ALGORITHM AND POSSIBILITIES OF INTELLIGENT ELECTRONIC DEVICES Siniša SPREMIĆ Mileta SENTIN Dušan PETROVIĆ EPS-P.D. Elektrovojvodina - Serbia EPS-P.D. Elektrovojvodina - Serbia EPS-P.D. Elektrovojvodina - Serbia sinisa.spremic@ev.rs mileta.sentin@ev.rs dusan.petrovic@su.ev.rs Zoran RISTANOVIĆ Energotehnika Južna Bačka - Serbia zoran.ristanovic@entjuba.rs ABSTRACT Paper consider possibility for determining On-Load Tap Changer (in following text: OLTC) position using primary and secondary (tertiary) currents and voltages of transformers equipped with OLTC. New algorithm for OLTC position determination using primary and secondary (tertiary) currents and voltages is presented. Different influences on algorithm accuracy like analog inputs errors of Intelligent Electronic Devices (in following text: IED), transformer turn ratio errors, instrument transformers accuracy errors, errors due to magnetizing (no load) currents and voltage drop were considered. Results of practical check are given in order to prove applicability with aim to improve reliability in particular segments of electricity distribution: automation, protection and control (supervision). INTRODUCTION Modern IEDs for transformers protection incorporate all necessary protection and automation functions and signaling. They are programming devices so it is possible to make additional protection, automation and control functions and signaling or existent could be expand in order to improve existent functions and reliability and to make new functions using communication possibilities. OLTC position data is necessary for local and remote supervision purposes, for parallel operation of transformers using master-follower method and could be used for more sensitive adjustment of differential protection. Existent OLTC position data is obtained from OLTC`s motor drive unit using different types of output. Possible outputs are resistance, mA (more common) or V (less common), contact range and codes (BCD, Grey and Binary). Those devices are reliable but sometimes different malfunctions occur. Mechanical, electrical, chemical and electromechanical malfunctions like broken parts, bad contact, rust, stain, etc. lead to false or no OLTC position data which will cause blocking of parallel operation of transformers using master-follower method and to less sensitive differential protection in IEDs which have this option. Less important but not negligible is missing remote supervision data. One of nowadays trends is reliability improvement in every segment of electricity distribution. Using advanced possibilities of modern IEDs and new algorithm for OLTC position determination using primary and secondary (tertiary) currents and voltages could improve reliability. ERRORS OF OLTC POSITION DETERMINATION USING CURRENTS Errors of OLTC position determination using currents in new algorithm are analog inputs errors of IED, transformer turn ratio errors, current transformers accuracy errors and errors due to magnetizing (no load) currents of transformers. Absolute values of errors for current analog inputs in IEDs are less than 1 %, mostly lower than 0,5 % up to In. Turn ratio errors of transformers are limited by standard [1] and should be in 0,5 %. According to test reports of transformers, measured values of turn ratios are significantly lower than 0,5 % and they are similar among phases. Current transformers accuracy classes at 110 kV side are 0,2 % or 0,5 %. At low voltage side accuracy class is mostly 1 %. Phase class is negligible for this consideration (up to 30 min). Accuracy errors according to test reports are significantly lower than accuracy class at nominal current and power factor 0,8. Current transformer producers during designing and producing made certain correction in order to shift accuracy curve with positive error at higher loads and negative at lower loads. Most interesting are errors due to magnetizing (no load) currents. No load currents depend of design and materials used in transformer production [2]. Older transformers 110/x kV with poorer quality of steel sheets have no load currents from 1 % to 3 % of nominal current of transformer and newer from 0,2 % to 0,5 % at Un. No load currents have significant increase with voltage increase. Voltage increase of 10 % lead to increase of no load currents mostly up to 4 %. No load currents among phases could be significantly different due to core construction. This is the reason to use all phase currents to calculate turn ratio and thus OLTC position. Using results of no load loss and current measurements for several transformers, calculation was made in order to check level of error originated from no load currents. Secondary voltage values are set to 0,9Un, Un and 1,1Un for load range from 10 % to 100 % and for values of power factor (0,8 – 0,85 – 0,9 – 0,95 – 1). Results for one of considered transformers 110/x kV with low level of no load currents are given in Figures 1, 2 and 3.
  • 2. 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0029 CIRED 2015 2/4 Fig. 1 Error characteristics at 0,9Un Fig. 2 Error characteristics at Un Fig. 3 Error characteristics at 1,1Un Figures 1, 2 and 3 show that error originated from magnetizing (no load) currents have tendency of increase in cases od decreasing load and power factor value and increasing voltage. Un of considered transformers is 21 kV and normal operating voltages are in range from 20 kV to 21 kV, power factor values are in range from 0,92 to 0,98 and loads which have significant daily or season changes are mostly greater than 30 %. It can be assumed that error of magnetizing currents at normal operating conditions should be less than 0,6 % which is less than 0,4 position for voltage step of 1,6 %. ERRORS OF OLTC POSITION DETERMINATION USING VOLTAGES Errors of OLTC determination using voltages in new algorithm are analog inputs errors of IED, transformer turn ratio errors, voltage transformers accuracy errors, errors due to load currents of transformers and load asymmetry among phases and error of parallel operation of transformers. Absolute values of errors for voltage analog inputs in IEDs are less than 1 %, mostly lower than 0,5 %. Turn ratio errors of transformers are limited by standard [1] and should be in 0,5 %. According to test reports of transformers, measured values of turn ratios are significantly lower than 0,5 % and they are similar among phases. Voltage transformers accuracy classes at 110 kV side are 0,2 % or 0,5 % [3, 4]. At low voltage side accuracy class is mostly 1 % [3, 4]. Phase class is negligible for this consideration (up to 30 min). Accuracy errors according to test report are significantly lower than accuracy class at nominal voltage. Symmetrical or asymmetrical load currents have the greatest influence in OLTC position determination using primary and secondary voltages. Voltage drop in transformer impedance which is mostly reactance have significant values at normal operating conditions. Figure 4 shows difference of calculated and set (real) OLTC position using voltage drop calculation for considered transformer. Fig. 4 Difference of calculated and real OLTC position It is obvious that voltage drop and difference of calculated and set (real) position have low value at power factor cos=1 and difference has significant value even for power factor cos=0,99. OLTC position determination using voltages of paralleled transformers is not possible because transformers have same primary and secondary voltages no matter of actual positions of paralleled transformers. Because of that it is not possible to determine accurate OLTC position using new algorithm from voltages in case of parallel operation of transformers.
  • 3. 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0029 CIRED 2015 3/4 NEW ALGORITHM FOR OLTC POSITION DETERMINATION OLTC position determination using primary and secondary (tertiary) currents and voltages need certain prerequisites. In order to simplify consideration only primary and secondary currents and voltages will be considered. It is necessary to set some parameters at IED. Those parameters are nominal turn ratio m12sr, step voltage Vs (%) and overal number of positions with different turn ratio nuk (transition positions and positions without turn ratio change are exluded). IEDs should have analog inputs for all three primary and secondary currents and voltages. New algorithm is given in following equation 100 2 1 100 1 12 12 s sr uks srmeas ukRS V m nV mm nn                 (1) or in simplified form 5,05,0 12 1 100           ukn srm measm sVRSn (2) Equation for calculated turn ratio from primary and secondary currents mmeas is primLprimLprimL LLL III III measm 321 sec3sec2sec1    (3) or from primary and secondary voltages mmeas is sec3sec2sec1 321 LLL primLprimLprimL UUU UUU measm    (4) Calculated („measured“) OLTC position nRS using new algorithm shall be rounded to integer value. Using averaged value of currents or voltages at certain period (e.g. several sine periods) is the way to use algortihm. Because of faults in supplied network or at opposite side of the transformer there is possibility that high values of currents or sudden voltage changes occur. This could lead to higher level of accuracy errors at particular periods of time. Increased accuracy errors is the reason to ignore this periods. This will not cause any malfunction because faults with high currents should be disconnected by protecting devices very fast and automatic voltage regulation is slow procedure compared to protection functions. Whole process of OLTC position change, depending of type of OLTC, lasts from 2 to 7 seconds so exluding some periods will not cause reliability decrease. Higher voltage drop, depending on parameters set at automatic voltage regulator, will cause that automatic voltage regulator block OLTC operation so calculated OLTC position prior to blocking will be in use. PRACTICAL CHECK OF NEW ALGORTHM In order to prove applicability of proposed algorithm practical check was made. Several different transformers 110/21/10,5 kV/kV/kV and 110/36,75/10,5 kV/kV/kV with nominal power of 31,5 and 20 MVA and step voltage 1,6 % and 1,5 % were checked. Transformers have IED units of three different producers. Power factor values were within range of 0,93 to 0,99. Primary voltages were within range of 108 kV to 116,9 kV. Secondary voltages were within ranges of 19,9 kV to 21,17 kV and 35,14 kV to 36,09 kV. Whole OLTC position range is from 1 to 21 and for practical check it was from 6 to 21. Figure 5 shows difference of “measured” OLTC position using currents and real OLTC position. All differences are less than 0,5 so rounded value of “measured” OLTC position will be equal to real OLTC position. Fig. 5 Difference of measured and real OLTC position Figure 6 shows difference of “measured” OLTC position using voltages and real OLTC position. One phase to phase voltage was used in calculation instead all three phase voltages. Load increasing lead to OLTC position difference increasing similar to characteristics from Figure 4. Up to about 30 % of load difference of “measured” to real OLTC position is less than 0,5 so rounded OLTC position will be equal to real. Fig. 6 Difference of measured and real OLTC position
  • 4. 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0029 CIRED 2015 4/4 Addition of all errors for currents could give overall error of about 5 % which is in case of step voltage of 1,6 % more than 3 OLTC positions error. Some of errors compensate each other. For example current transformers usually have positive error at currents from 0,25In to 1,2In. Current transformer of low voltage side of the transformer are of lower accuracy class than current transformers of high voltage side so it is expected that ratio Isec/Iprim has positive error. Contrary influence of magnetizing currents have negative influence at whole range of currents for ratio Isec/Iprim so current transformer error is compensated with magnetizing current influence. It is possible that other errors compensate each other at certain level. Practical check at load range from about 20 % and 90 % shows applicability of proposed algorithm for OLTC position calculation using measured primary and secondary currents and voltages. Currents usage shows good results at range from 20 % to about 90 % of load. It could be expected that current could be used for loads up to 120 % and possibly more. Voltage usage shows good results at range from 0 % up to about 30 % of load. Hitherto practical checks lead to recommendation to use voltages up to 20 % of load and currents from 20 % upward for OLTC position calculation. It is necessary to make additional numerous practical checks in order to prove applicability at loads lower than 20 % and greater than 90 % and to check range from 20 % to 30 % of load. Range from 20 % to 30 % of load is boundary area in which average value of OLTC position determined from currents and voltages could be the best option to use. ALGORITHM APPLICABILITY OLTC position determination using proposed algorithm could be applied for: - Basic OLTC position data in case of old motor drive units with inoperable device for OLTC position without possibility to simple repair or change. - Spare OLTC position data in case of malfunction of device for basic OLTC position data useful for local and remote supervision purposes and for parallel operation of transformers using master-follower method avoiding parallel operation blocking. Even in case of one or two real OLTC position difference among paralleled transformers because of errors in measuring chain there will be no parallel operation blocking. Parallel operation blocking is undesirable because it could lead to big voltage fluctuations. - Control (supervision) OLTC position data in case of non reliable data from OLTC position device due to contact problem (rust, stain). - Differential protection could be set more sensitive using OLTC position data. For example if current transformers on both sides are rated 5P10 (i.e. composite error is max. 5 %) and the OLTC range is 10x1,6 % calculate starting ratio setting S = 5 % (HV CT) + 5 % (LV CT) + 10x1,6 % (OLTC) + 4 % (relay) + 5 % (margin) = 35 %. If OLTC influence should be compensated automatically starting ratio setting S = 5 % (HV CT) + 5 % (LV CT) + 4 % (relay) + 5 % (margin) = 19 % which is significantly lower than without compensation. If we include margin of OLTC position error obtained with algorithm of two positions starting ratio setting will be S = 5 % (HV CT) + 5 % (LV CT) + 2x1,6 % (OLTC) + 4 % (relay) + 5 % (margin) = 22,2 % which is also significantly lower than value in first calculation. There is no need for analogue input for OLTC position in IEDs. Even if IED has not got analogue inputs for all voltages and currents it could receive data using IEC 61850 or other protocol communication. Received data must be synchronized with data obtained by IED`s analogue inputs to avoid calculation errors of data from different time periods. CONCLUSION Proposed algorithm for OLTC position determination is simple and applicable in modern IEDs. It could improve reliability in small but relevant segment of automation, e.g. parallel operation of transformers using mater- follower method avoiding parallel operation blocking in case malfunction of device for OLTC position data. It is applicable in protection improving sensitivity of differential protection without need for analogue input or inputs for OLTC position data. It is also useful for basic, spare or supervision OLTC position data in case of malfunction of device for basic OLTC position data. Further consideration will comprise numerous practical checks in order to test whole range of loads with attention on range from 20 % to 30 % of load as boundary between good results of OLTC position determined from measured voltages or currents and to review correction possibilities. REFERENCES [1] IEC 60076-1:1993+A1:1999, "Power transformers – Part 1: General" [2] Branko Mitraković, 1979, Transformatori, Naučna knjiga, Beograd, Serbia, 93-107. [3] S. Spremić, D. Petrović, Z. Ristanović, M. Sentin, "Unapređenje funkcija uređaja mikroprocesorske zaštite transformatora", CIRED Srbija – VIII savetovanje o elektrodistributivnim mrežama Srbije sa regionalnim učešćem, 2012, paper R-4.14, p.8, Vrnjačka Banja. [4] M. Sentin, Z. Ristanović, S. Spremić, D. Petrović, "Praktična provera primenjivosti određivanja položaja regulacione sklopke korišćenjem struja primara i sekundara transformatora", CIRED Srbija – VIII savetovanje o elektrodistributivnim mrežama Srbije sa regionalnim učešćem, 2012, paper R-4.20, p.5, Vrnjačka Banja.