International Journal of Power Electronics and Drive System (IJPEDS)
Vol. 8, No. 3, September 2017, pp. 1251~1259
ISSN: 2088-8694, DOI: 10.11591/ijpeds.v8i3.pp1251-1259  1251
Journal homepage: http://iaesjournal.com/online/index.php/IJPEDS
Filter Implementation Using Output Transformer of UPS for
Power Quality Improvement
Anandh N., Pramod Antony D'Sa, M.V. Gautam, V. Sai Sandeep
Department of Electrical and Electronics Engineering, Manipal Institute of Technology, Manipal University, India
Article Info ABSTRACT
Article history:
Received Mar 27, 2017
Revised Jul 26, 2017
Accepted Aug 14, 2017
Power electronics play a significant role in different areas of technology,
more usage of power electronic devices lead to more harmonic content and
various power quality issues in the system. Therefore, power quality gains
more significance in the current era of research. Power electronics
equipment’s with non-linear loads concludes with more harmonic
disturbances and lower power factor. Harmonic impurities are the major
problem ingredient due to the connection of non-linear load. To lessen the
harmonics usually passive filters are used. The major objective of this work
is to monitor and analyse the power quality of uninterrupted power supply by
means of DAQ system that gathers real time data on the system and then the
data is analysed using National Instruments LabVIEW. Once power quality
analysis is done, a new technique of filter implementation using output
transformer of the UPS was explored and passive filter was simulated using
MATLAB/Simulink and then simulated filter was implemented in order to
achieve power quality improvement.
Keyword:
DAQ system
Harmonics
Passive shunt tuned filter
Power quality improvement
Uninterrupted power supply
Copyright ©2017 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Anandh N,
Department of Electrical and Electronics Engineering,
Manipal Institute of Technology, Manipal University,
Manipal – 576104, Karnataka, India.
Email: anandh.n@manipal.edu.
1. INTRODUCTION
Recently power electronics devices are widely used for rectification, inversion and several other
applications. Besides being effective they also introduce harmonics in the power system. Arrangement of
many sine waves with different frequencies than the fundamental frequency is termed as harmonics.
Normally, the voltage and current waveforms are expected to be purely sinusoidal, but when the system is
attached to any non-linear load it gets distorted. Examples of non-linear load include static power converters
(rectifiers, adjustable speed drives, switched mode power supply and rotating electrical machines etc) [1].
Harmonics causes many ill-effects such as overheating, mechanical and electrical oscillations in alternators
and prime movers, faulty operation of protective relays, intervention with communication equipments and
decreasing the power generation, transmission and utilization efficiency. To overcome these harms, harmonic
mitigation is significant for both utility and consumer ends. Using passive filters to filter out harmonics from
the power system is one of the most primitive method used [2].
The power quality issues in power system became very severe because of vast usage of non-linear
loads and power electronic components. Researchers are working upon to resolve the power quality issues,
like current harmonics, reactive power etc. Hybrid active power filter (HAPF) comprises of passive filters
(PF) and a series APF [3]. Thus, HAPF takes the benefits of both PF and APF. PFs can withstand high
voltage and capacity alternatively, APF can filter harmonics efficiently. At all time, PF can only pay
compensation to current harmonics with stable frequencies as like 5th
and 7th
harmonics. For other current
harmonics, impedance is quiet high in PF branches and the load voltage waveforms gets worsen. To
 ISSN: 2088-8694
IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259
1252
overwhelm these drawbacks, a unified power quality conditioner was used linking shunt APF and series
APF, UPQC can increase voltage and also current quality [4]-[6].
The fast growth of power electronics technology lead to the huge usage of non-linear, rectifier and
impulse loads in the power grid [7]. The above mentioned loads creates harmonic contamination in power
system and increases source voltage hindrances. The traditional power quality monitoring devices usually
works in offline mode and it is measured by power quality indicator [8-9]. These equipments does not have
the functions of complete measurement, statistical analysis and conclusion. The power quality monitoring
system network completely observes the power quality. On-line monitoring of electric load by PLC based
system provides access to a web page wherein the current waveforms of electric load can be examined was
discussed in literature [10]. An electrical power quality evaluation scheme is developed by using web-based
distributed measurement system was highlighted in the paper [11] wherein, a network power quality monitor
system was established. Web centered network monitoring system has independent language, cross-platform,
cross-regional and fast transmission characteristics. Monitoring and managing the power quality through a
browser is done very easily by the workers. Meanwhile, the necessities of real-time, accessability and
reliability are confirmed. An idea on shunt hybrid filter design using PQ theory in order to improve the power
quality for 3 phase distribution system feeding various non-linear loads was proposed in literature [12]. An
Artificial Neural Network controller based shunt active power filter produces the controlled pulses needed for
IGBT inverter in order to mitigate the harmonics of distribution system was discussed [13].
The main goal of this work is to monitor and analyse the power quality of uninterrupted power
supply using a DAQ system that collects real time data on the system and then the data is analysed using
National Instruments LabVIEW. Once power quality analysis is done, a new technique of filter
implementation using output transformer of the UPS was explored and passive filter is simulated with
MATLAB/Simulink then the simulated filter was implemented in order to achieve power quality
improvement.
2. CIRCUIT ANALYSIS AND METHODOLOGY
PQ monitoring system comprises of both hardware and software modules. It has current and voltage
sensors. The UPS is connected to load (i.e. 10 computers). Power quality analysis is progressed with the aid
of a DAQ system, which gathers real time data on the system. Later the data is analysed with the assistance
of National Instruments LabVIEW. Once analysis is done appropriate filter is chosen, simulated with
MATLAB/Simulink and then implemented. The Figure 1 below shows the block diagram of power quality
monitoring system.
Figure 1. Power quality monitoring system block diagram
PQ
monitoring
System
Filter
UPS
Load
Battery
Pack
Ac
Supply
IJPEDS ISSN: 2088-8694 
Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N)
1253
A PC centered power quality analyser, comprising a group of tools in one real-time system,
proficient to run all devices in parallel and can be easily accessible in future. Based on recent IEC and EN
standards, measurement and data processing procedures are accounted and have a remote accessible
instruments through ethernet design following SPIPI standard. A software application can be developed by
using the National Instruments LabVIEW graphical development environment that behaves as instrument
firmware. The current sensor is attached serially with input and voltage sensor is connected in parallel with
supply and UPS. This work combines monitoring of power quality of single phase UPS. The data analysis
was done on PC using National Instruments LabVIEW. The input data is 24 bit sampled at 50kS/s.
2.1. Power Quality Monitoring
To process and display the gathered data from the sensors LabVIEW 2015 32-bit version with
electrical power suite add-on is used. Power quality monitoring system has indicators to indicate THDi,
IHD1, IHD3, IHD5, IHD7, IHD9, distorted power factor, active power, FFT spectrum of current waveform. It
also shows RMS values of current and voltage with the aid of gauges and numeric indicators. Data from
DAQ assistant contains data from all the connected sensors. Hence, it is divided and each signal is multiplied
with its matching multiplication factor. Later RMS waveforms of current and voltage to be used in
calculation of active, reactive and apparent power flowing through the system.
Amplitude and measurement blocks determine the RMS values of current and voltage. Spectral
measurements block is utilised for FFT analysis of current waveform. FFT analysis of voltage waveform is
not done because voltage waveform appears perfectly sinusoidal without any abnormalities. Once all the
required variables are calculated the data is to be stored in an excel sheet. IHDn calculation was done in a sub
VI. IHD value upto 9th
harmonic component was calculated. Distortion measurement block is used to
calculate specific harmonic current value for each component. Then the specific harmonic current value is
separated with specific harmonic current of fundamental to get IHD value.
2.2. Power Factor Calculation
Power factor calculation in systems with non-sinusoidal load current is different from that of
sinusoidal load current systems. To calculate power factor in such cases distortion power factor is to be taken
into account. In case of normal loads PF is calculated by
PF = =
( )
Where, Ɵ is phase angle of voltage and ɸ is phase angle of current. But in case of non-linear loads
PF
( )
Distorted Power factor (DPF) ( )
Inductance of transformer is measured by short circuit test. In standard SC test, current and voltage
transducers are used rather than using wattmeter and voltmeter. Values from these sensors is processed using
LabVIEW. Values of power, resistance, impedance, reactance and inductance of the transformer are
calculated pertaining to low voltage side of the transformer. MATLAB/Simulink is used for simulation of
designed filter because it is difficult to simulate with non-linear load. Therefore, supply current is simulated
to match the observed current. This is done by connecting current sources of different amplitudes and
frequency in parallel. Filter is simulated using a RLC series component by giving appropriate R, L, C values.
A current measurement block and scope is used to observe the waveform. A powergui block is added and
FFT analysis for the simulated circuit is carried out.
2.3. Hardware Implementation
2.3.1. NI cDAQ-9184
It is a 4-slot NI CompactDAQ Gigabit ethernet chassis intended for distant or dispersed sensor and
electrical calibrations. Solitary NI CompactDAQ chassis measures till 128 sensor signal channels, analog I/O,
digital I/O and counter/timers with an ethernet interfaced to a PC or laptop.
2.3.2. NI 9227
It is a 4 channel current input C series module. It has a built in anti-aliasing filter. It is compatible
with compactRIO and compactDAQ intended to calculate 5 A nominal and upto 14 A peak on separate
channel with channel-to-channel segregation.
 ISSN: 2088-8694
IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259
1254
2.3.3. LEM LA 25-NP
This is basically a current transducer for measuring the currents, DC, AC, pulsed with galvanic
separation amid of primary and secondary circuits. It has 10 terminals on input side which can be connected
in different configurations for various input current limits. It can measure maximum primary nominal current
of 25 A corresponding to a nominal secondary current of 25 mA. It has to be powered by a +/- 15 V supply.
For the range of connection available and with a maximum current value at 25 A this sensor is selected.
2.3.4. LEM LV 25-400
This is normally a voltage transducer for measuring the voltages, DC, AC, pulsed with galvanic
separation amid of primary and secondary circuits. It has primary nominal voltage of 400 V. Its output is in
current with nominal value of 25 mA. It has to be powered by a +/- 15 V supply. The Figure 2 below shows
the power quality monitoring system implemented in our laboratory.
Figure 2. Power quality monitoring system implemented
The current and voltage transducers are connected to UPS. The output of the sensors is current
which is converted to voltage over a resistor. The analog output is connected to National Instruments analog
input card which is connected to a National Instruments compact data acquisition with an ethernet chassis.
The data acquisition system is connected to PC which is running LabVIEW software.
2.4. Passive Filter Calculation
Initial power quality study was done on a 3 KVA UPS and the filter configuration calculation.
Passive shunt filters fundamentally consist of serial connection of an inductor and a capacitor adjusted to a
certain frequency and behaves as low-impedance path for the harmonics. Initial capacitor size is calculated
from reactive power requirement (Qc) of the load.
Value of Capacitor (Cn) =
Where, Qc - Reactive Power; m - number of branches in passive filter; Vs - fundamental voltage per phase.
To eliminate nth
current harmonics, the nth
-order inductor is calculated as
Ln =
The series resistance for the nth
-order filter inductor is calculated as
Rn =
The values of capacitance obtained for mitigation of 3rd
and 5th
harmonic components are not
manufactured for single phase system because factor of safety goes down. For this reason, power quality
study was done on a modular 1 KVA UPS. In this configuration instead of using external inductance,
inductance of output transformer is used. To limit high di/dt in the circuit, additional inductance is added.
This inductance value was also designed to change effective value of inductance in the circuit and to change
capacitance value to values easily available in the market. The Figure 3 shows the filter implementation using
IJPEDS ISSN: 2088-8694 
Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N)
1255
internal transformer of UPS. Since, inductance value is fixed from the measured inductance of transformer
and additional inductance is to be chosen, the capacitance value easily available in the market for single
phase systems are 2.5 uF, 8 uF and 50 uF. The Figure 4 shows the passive filter implementation in our
laboratory.
Figure 3. Filter implementation using internal transformer of UPS
Figure 4. Passive filter implementation
The above picture displays the passive filter implementation for mitigating 5th
harmonic component
using 50 mfd x 3 and 8 mfd x 3 capacitors. These capacitors are connected in parallel to get 164 mfd
capacitor bank. This capacitor bank and the inductance from the components of the UPS act as a single tuned
passive filter. Thus 5th
harmonic component is mitigated.
3. RESULT ANALYSIS AND DISCUSSIONS
3.1.1. KVA UPS System Results
When filter calculation where done for 3 KVA system the values for a passive filter components for
reducing 3rd
harmonic component was, Capacitance: 7650 Micro farad, Inductance: 147 Micro henry.The
passive filter components value for reducing 5th
harmonic component was, Capacitance: 7650 Micro farad,
Inductance: 52.9 Micro henry.This value of capacitance is not manufactured for low powered single phase
systems because factor of safety becomes low. For this reason, we had to do power quality analysis on a
lower model 1 KVA UPS. Figure 5 and 6 shows the current waveform and FFT analysis of harmonic
spectrum with load as 6 systems of 1 KVA UPS. Figure 7 shows the IHD 5 variation with time. Figure 8
depicts the comparison of THD and current for different loads and Figure 9 shows the distorted power factor
for different systems.
 ISSN: 2088-8694
IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259
1256
Figure 5. Current Waveform with load as 6 systems of 1 KVA UPS
Figure 6. FFT analysis for current waveform of 1 KVA system
Figure 7. IHD 5 variation with time
Figure 8. Comparison of THD and Current for different loads
IJPEDS ISSN: 2088-8694 
Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N)
1257
Figure 9. Distorted power factor for different systems
3.2. Filtered Output Results of I KVA UPS System
Transformer is used as inductor for the passive filter. Inductance value of transformer is measured
using short circuit test. Short circuit on transformer was done with standard method but with aid of current,
voltage sensors and LabVIEW. The transformer is part of the UPS. The transformer is rated at 1 KVA,
45/230 V. The passive filter is shunt connected to the transformer on LV side. Filter uses inductance of
transformer for L of filter. Capacitance used was 164 mfd. This was used to remove 5th
harmonic component.
Capacitance required to remove 3rd
harmonic component is 451 mfd. When 164 mfd capacitor was connected
the power through the transformer exceed the limit. For that reason, 451 mfd was not connected. Therefore, it
difficult to implement harmonic filter for single phase low powered systems. As the power rating increases
availability of required capacitance value also increases. Since the system was single phase low power rated,
passive filter branch to remove 3rd
harmonic component was not implemented. With the connection of a filter
branch the core of the transformer starts vibrating due to resonance between the filter branch and remaining
system. For this reason, filter required to remove 3rd
harmonic component was not connected as the
capacitance required is higher and the vibration caused because of that branch might spoil the transformer.
As it can be observed from above picture 5th
harmonic component value decreased. THDi value improved.
Initial value of THD was at 92 %. Figure 10 and 11 shows the current waveform for 1 KVA system and FFT
analysis for current waveform of 1 KVA system with passive filter implementation. Figure 12 depicts Power
Factor vs Load Current graph.
Figure 10. Current waveform for 1 KVA system with passive filter implemented
Figure 11. FFT analysis for current waveform of 1 KVA system with passive filter implemented
 ISSN: 2088-8694
IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259
1258
Figure 12. Power Factor vs Load Current
Initial analysis on power quality of the system showed high harmonic content with 3rd
and 5th
harmonic components dominating and power factor value was poor. With the implementation of shunt
passive filter branch to reduce 5th
harmonic component THDi value decreased and power factor value
improved.
4. CONCLUSION
A complete power quality analysis on the system was done and various mitigation techniques were
studied. The deep understanding of mitigation schemes made us to select passive filter for simulation and
implementation. While implementing the mitigation technique a new method of implementation of filter
circuit was explored. Implementation of filter by means of output transformer of the UPS was done. The
main constraint of such scheme is the power rating of the filter, because the amount of power flows through
the transformer is fixed during the design of UPS. Adding extra circuits will rises the power flowing through
the transformer and surpasses its limit. While surpassing its limit the transformer core begins to vibrate and
starts making noise. This limits the quantity of harmonic contents and can be detached easily. Alternatively
this work can be implemented by using active filters or unified power quality compensators or shunt active
compensators. Though this work concentrates on low powered system similar principles and techniques can
be stretched to high powered systems and three phase systems.
REFERENCES
[1] D. Gonzalez, J. McCall. Design of Filters to Reduce Harmonic Distortion in Industrial Power Systems. IEEE Trans.
on Industry Applications. 1987; 23(3): 504-511.
[2] M. Tali, A. Obbadi, A. Elfajri, Y. Errami. Passive Filter for Harmonics Mitigation in Standalone PV System for
Non-Linear Load. Renewable and sustainable energy conference, Morocco. 2014; 499-504.
[3] Lee G M, Lee D C, Seok J K. Control of series active power filters compensating for source voltage unbalance and
current harmonics. IEEE Transactions on Industrial Electronics. 2004; 19(1): 132-139.
[4] Fujita H, Akagi H. The unified power quality conditioner: the integration of series-and shunt-active filters. IEEE
Transactions on Power Electronics. 1998; 13(2): 315-322.
[5] Hideaki Fujita, Hiromi Akagi, Yasuhiro Watanabe. Dynamic control and performance of a unified power flow
controller for stabilizing and an AC transmission system. IEEE Transactions on Power Electronics. 2006; 21(4):
1013-1020.
[6] Jong-Kun Lee, Jul-Ki Seok, Dong-Choon Lee. Unified Active Power Filters for Source Voltage Unbalance/Current
Harmonics Compensation and Power Factor Correction. The 30th Annual Conference of the IEEE Industrial
Electronics Society, Busan, Korea. 2004; 540-545.
[7] M. H. J. Bollen. Understanding Power Quality Problems: Voltage Sags and Interruptions. IEEE Press, New York,
2000.
[8] Waclawiak M, Mc Granaghan M, Sabin D. Substation power quality performance monitoring and the internet.
IEEE Power Engineering Society Summer Meeting. 2001; 2: 1110-1111.
[9] Batista J, Monso JL, Martins JS. Low-cost power quality monitor based on a PC. EEE International Symposium on
Industrial Electronics. 2003; 1: 323-328.
[10] Wei-Fu Chang, Yu-Chi Wu, Chui-Wen Chiu. Development of a web-based remote load supervision and control
system. Electrical Power and Energy Systems. 2006; 28: 401–407.
IJPEDS ISSN: 2088-8694 
Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N)
1259
[11] Juan José González de la Rosa, Antonio Moreno Muñoz, Aurora Gil de Castro, Víctor Pallarés López, Jose Antonio
Sánchez Castillejo. A web-based distributed measurement system for electrical power quality assessment.
Measurement. 2010; 43: 771–780.
[12] R. Balasubramanian, S.Palani. Simulation and performance evaluation of shunt hybrid power filter for power
quality improvement using PQ theory. International Journal of Electrical and Computer Engineering. 2016; 6(6):
2603-2609.
[13] Jarupula Somlal, Venu Gopala Rao.Mannam, Narasimha Rao.Vutlapalli. Power quality improvement in distribution
system using ANN based shunt active power filter. International Journal of Power Electronics and Drive Systems.
2015; 5(4): 568-575.

More Related Content

What's hot

IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...IRJET Journal
 
Improvement of the electric power quality using
Improvement of the electric power quality usingImprovement of the electric power quality using
Improvement of the electric power quality usingVikram Rawani
 
Optimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerOptimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerIRJET Journal
 
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...IJMER
 
Design of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonicDesign of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonicsager alswed
 
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...IRJET Journal
 
IRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy Meter
IRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy MeterIRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy Meter
IRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy MeterIRJET Journal
 
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...IJERA Editor
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD Editor
 
A Novel Approach for Power Quality Improvement in Distributed Generation
A Novel Approach for Power Quality Improvement in Distributed GenerationA Novel Approach for Power Quality Improvement in Distributed Generation
A Novel Approach for Power Quality Improvement in Distributed Generationseema appa
 
presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015sager alswed
 
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...IRJET Journal
 
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemPower Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemIRJET Journal
 
Dhiraj power system automation
Dhiraj power system automationDhiraj power system automation
Dhiraj power system automationvision2d16
 
A new fuzzy based control strategy for three phase shunt active power filters
A new fuzzy based control strategy for three phase shunt active power filtersA new fuzzy based control strategy for three phase shunt active power filters
A new fuzzy based control strategy for three phase shunt active power filtersIAEME Publication
 
Power System Contingency Ranking Using Fast Decoupled Load Flow Method
Power System Contingency Ranking Using Fast Decoupled Load Flow MethodPower System Contingency Ranking Using Fast Decoupled Load Flow Method
Power System Contingency Ranking Using Fast Decoupled Load Flow Methodpaperpublications3
 

What's hot (20)

IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
IRJET- A Review on Power Quality Improvement using Shunt Active Filter with M...
 
Improvement of the electric power quality using
Improvement of the electric power quality usingImprovement of the electric power quality using
Improvement of the electric power quality using
 
Optimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi ControllerOptimize Controlling of Active Filters Controlled by Pi Controller
Optimize Controlling of Active Filters Controlled by Pi Controller
 
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
 
Design of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonicDesign of shunt active power filter to mitigate harmonic
Design of shunt active power filter to mitigate harmonic
 
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
IRJET- Reduction of So Urce Current Harmonics in an Inverter Fed Induction Mo...
 
Predictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power ControlPredictive Approach for Power Quality Improvement Based Direct Power Control
Predictive Approach for Power Quality Improvement Based Direct Power Control
 
IRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy Meter
IRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy MeterIRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy Meter
IRJET- Hall Effect Sensor Based Digital Smart Three Phase Energy Meter
 
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
Adaptive Fuzzy PID Based Control Strategy For 3Phase 4Wire Shunt Active Filte...
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
A Novel Approach for Power Quality Improvement in Distributed Generation
A Novel Approach for Power Quality Improvement in Distributed GenerationA Novel Approach for Power Quality Improvement in Distributed Generation
A Novel Approach for Power Quality Improvement in Distributed Generation
 
presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015presentation of Conference On Electrical And Electronic Engineering 2015
presentation of Conference On Electrical And Electronic Engineering 2015
 
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
Improving Efficiency of Active Power Filter for Renewable Power Generation Sy...
 
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV SystemPower Angle Control Scheme for Integration of UPQC In Grid Connected PV System
Power Angle Control Scheme for Integration of UPQC In Grid Connected PV System
 
Dhiraj power system automation
Dhiraj power system automationDhiraj power system automation
Dhiraj power system automation
 
C04111114
C04111114C04111114
C04111114
 
A new fuzzy based control strategy for three phase shunt active power filters
A new fuzzy based control strategy for three phase shunt active power filtersA new fuzzy based control strategy for three phase shunt active power filters
A new fuzzy based control strategy for three phase shunt active power filters
 
Ir3314761483
Ir3314761483Ir3314761483
Ir3314761483
 
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
 
Power System Contingency Ranking Using Fast Decoupled Load Flow Method
Power System Contingency Ranking Using Fast Decoupled Load Flow MethodPower System Contingency Ranking Using Fast Decoupled Load Flow Method
Power System Contingency Ranking Using Fast Decoupled Load Flow Method
 

Similar to Filter Implementation Using Output Transformer of UPS for Power Quality Improvement

Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...IAES-IJPEDS
 
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...IJERA Editor
 
Advance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCAdvance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCIJPEDS-IAES
 
IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...
IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...
IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...IRJET Journal
 
Unified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt FiltersUnified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt FiltersIAES-IJPEDS
 
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...ijtsrd
 
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...AI Publications
 
A Review on Unified Power Quality Conditioner for 3P4W System
A Review on Unified Power Quality Conditioner for 3P4W SystemA Review on Unified Power Quality Conditioner for 3P4W System
A Review on Unified Power Quality Conditioner for 3P4W SystemIRJET Journal
 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNOIRJET Journal
 
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET Journal
 
Power quality improvement by series active power filter- a review
Power quality improvement by series active power filter- a reviewPower quality improvement by series active power filter- a review
Power quality improvement by series active power filter- a reviewIRJET Journal
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD Editor
 
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET Journal
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...IJERA Editor
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET Journal
 

Similar to Filter Implementation Using Output Transformer of UPS for Power Quality Improvement (20)

Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...Power Quality Improvement in Distribution System using ANN Based Shunt Active...
Power Quality Improvement in Distribution System using ANN Based Shunt Active...
 
A0710113
A0710113A0710113
A0710113
 
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
Performance Analysis Of PV Interfaced Neural Network Based Hybrid Active Powe...
 
Advance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCAdvance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQC
 
A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...
 
IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...
IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...
IRJET- Simulation and Experimental Verification of Single Phase Unity Power F...
 
Unified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt FiltersUnified Power Quality Conditioner Model Based with Series and Shunt Filters
Unified Power Quality Conditioner Model Based with Series and Shunt Filters
 
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
 
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...
 
A Review on Unified Power Quality Conditioner for 3P4W System
A Review on Unified Power Quality Conditioner for 3P4W SystemA Review on Unified Power Quality Conditioner for 3P4W System
A Review on Unified Power Quality Conditioner for 3P4W System
 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNO
 
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Power quality improvement by series active power filter- a review
Power quality improvement by series active power filter- a reviewPower quality improvement by series active power filter- a review
Power quality improvement by series active power filter- a review
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
u.pdf
u.pdfu.pdf
u.pdf
 
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQCIRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
IRJET- Mitigation of Current and Voltage Harmonics using MAF based UPQC
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 

More from International Journal of Power Electronics and Drive Systems

More from International Journal of Power Electronics and Drive Systems (20)

Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...
 
Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...
 
Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...
 
Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...
 
Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...
 
Soft computing and IoT based solar tracker
Soft computing and IoT based solar trackerSoft computing and IoT based solar tracker
Soft computing and IoT based solar tracker
 
Comparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farmsComparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farms
 
Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...
 
Performance of solar modules integrated with reflector
Performance of solar modules integrated with reflectorPerformance of solar modules integrated with reflector
Performance of solar modules integrated with reflector
 
Generator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion systemGenerator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion system
 
Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...
 
Comparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping systemComparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping system
 
Prospect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in BangladeshProspect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in Bangladesh
 
A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...
 
Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...
 
Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...
 
Short and open circuit faults study in the PV system inverter
Short and open circuit faults study in the PV system inverterShort and open circuit faults study in the PV system inverter
Short and open circuit faults study in the PV system inverter
 
A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...
 
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
 
Comparison of electronic load using linear regulator and boost converter
Comparison of electronic load using linear regulator and boost converterComparison of electronic load using linear regulator and boost converter
Comparison of electronic load using linear regulator and boost converter
 

Recently uploaded

ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 

Recently uploaded (20)

ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 

Filter Implementation Using Output Transformer of UPS for Power Quality Improvement

  • 1. International Journal of Power Electronics and Drive System (IJPEDS) Vol. 8, No. 3, September 2017, pp. 1251~1259 ISSN: 2088-8694, DOI: 10.11591/ijpeds.v8i3.pp1251-1259  1251 Journal homepage: http://iaesjournal.com/online/index.php/IJPEDS Filter Implementation Using Output Transformer of UPS for Power Quality Improvement Anandh N., Pramod Antony D'Sa, M.V. Gautam, V. Sai Sandeep Department of Electrical and Electronics Engineering, Manipal Institute of Technology, Manipal University, India Article Info ABSTRACT Article history: Received Mar 27, 2017 Revised Jul 26, 2017 Accepted Aug 14, 2017 Power electronics play a significant role in different areas of technology, more usage of power electronic devices lead to more harmonic content and various power quality issues in the system. Therefore, power quality gains more significance in the current era of research. Power electronics equipment’s with non-linear loads concludes with more harmonic disturbances and lower power factor. Harmonic impurities are the major problem ingredient due to the connection of non-linear load. To lessen the harmonics usually passive filters are used. The major objective of this work is to monitor and analyse the power quality of uninterrupted power supply by means of DAQ system that gathers real time data on the system and then the data is analysed using National Instruments LabVIEW. Once power quality analysis is done, a new technique of filter implementation using output transformer of the UPS was explored and passive filter was simulated using MATLAB/Simulink and then simulated filter was implemented in order to achieve power quality improvement. Keyword: DAQ system Harmonics Passive shunt tuned filter Power quality improvement Uninterrupted power supply Copyright ©2017 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Anandh N, Department of Electrical and Electronics Engineering, Manipal Institute of Technology, Manipal University, Manipal – 576104, Karnataka, India. Email: anandh.n@manipal.edu. 1. INTRODUCTION Recently power electronics devices are widely used for rectification, inversion and several other applications. Besides being effective they also introduce harmonics in the power system. Arrangement of many sine waves with different frequencies than the fundamental frequency is termed as harmonics. Normally, the voltage and current waveforms are expected to be purely sinusoidal, but when the system is attached to any non-linear load it gets distorted. Examples of non-linear load include static power converters (rectifiers, adjustable speed drives, switched mode power supply and rotating electrical machines etc) [1]. Harmonics causes many ill-effects such as overheating, mechanical and electrical oscillations in alternators and prime movers, faulty operation of protective relays, intervention with communication equipments and decreasing the power generation, transmission and utilization efficiency. To overcome these harms, harmonic mitigation is significant for both utility and consumer ends. Using passive filters to filter out harmonics from the power system is one of the most primitive method used [2]. The power quality issues in power system became very severe because of vast usage of non-linear loads and power electronic components. Researchers are working upon to resolve the power quality issues, like current harmonics, reactive power etc. Hybrid active power filter (HAPF) comprises of passive filters (PF) and a series APF [3]. Thus, HAPF takes the benefits of both PF and APF. PFs can withstand high voltage and capacity alternatively, APF can filter harmonics efficiently. At all time, PF can only pay compensation to current harmonics with stable frequencies as like 5th and 7th harmonics. For other current harmonics, impedance is quiet high in PF branches and the load voltage waveforms gets worsen. To
  • 2.  ISSN: 2088-8694 IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259 1252 overwhelm these drawbacks, a unified power quality conditioner was used linking shunt APF and series APF, UPQC can increase voltage and also current quality [4]-[6]. The fast growth of power electronics technology lead to the huge usage of non-linear, rectifier and impulse loads in the power grid [7]. The above mentioned loads creates harmonic contamination in power system and increases source voltage hindrances. The traditional power quality monitoring devices usually works in offline mode and it is measured by power quality indicator [8-9]. These equipments does not have the functions of complete measurement, statistical analysis and conclusion. The power quality monitoring system network completely observes the power quality. On-line monitoring of electric load by PLC based system provides access to a web page wherein the current waveforms of electric load can be examined was discussed in literature [10]. An electrical power quality evaluation scheme is developed by using web-based distributed measurement system was highlighted in the paper [11] wherein, a network power quality monitor system was established. Web centered network monitoring system has independent language, cross-platform, cross-regional and fast transmission characteristics. Monitoring and managing the power quality through a browser is done very easily by the workers. Meanwhile, the necessities of real-time, accessability and reliability are confirmed. An idea on shunt hybrid filter design using PQ theory in order to improve the power quality for 3 phase distribution system feeding various non-linear loads was proposed in literature [12]. An Artificial Neural Network controller based shunt active power filter produces the controlled pulses needed for IGBT inverter in order to mitigate the harmonics of distribution system was discussed [13]. The main goal of this work is to monitor and analyse the power quality of uninterrupted power supply using a DAQ system that collects real time data on the system and then the data is analysed using National Instruments LabVIEW. Once power quality analysis is done, a new technique of filter implementation using output transformer of the UPS was explored and passive filter is simulated with MATLAB/Simulink then the simulated filter was implemented in order to achieve power quality improvement. 2. CIRCUIT ANALYSIS AND METHODOLOGY PQ monitoring system comprises of both hardware and software modules. It has current and voltage sensors. The UPS is connected to load (i.e. 10 computers). Power quality analysis is progressed with the aid of a DAQ system, which gathers real time data on the system. Later the data is analysed with the assistance of National Instruments LabVIEW. Once analysis is done appropriate filter is chosen, simulated with MATLAB/Simulink and then implemented. The Figure 1 below shows the block diagram of power quality monitoring system. Figure 1. Power quality monitoring system block diagram PQ monitoring System Filter UPS Load Battery Pack Ac Supply
  • 3. IJPEDS ISSN: 2088-8694  Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N) 1253 A PC centered power quality analyser, comprising a group of tools in one real-time system, proficient to run all devices in parallel and can be easily accessible in future. Based on recent IEC and EN standards, measurement and data processing procedures are accounted and have a remote accessible instruments through ethernet design following SPIPI standard. A software application can be developed by using the National Instruments LabVIEW graphical development environment that behaves as instrument firmware. The current sensor is attached serially with input and voltage sensor is connected in parallel with supply and UPS. This work combines monitoring of power quality of single phase UPS. The data analysis was done on PC using National Instruments LabVIEW. The input data is 24 bit sampled at 50kS/s. 2.1. Power Quality Monitoring To process and display the gathered data from the sensors LabVIEW 2015 32-bit version with electrical power suite add-on is used. Power quality monitoring system has indicators to indicate THDi, IHD1, IHD3, IHD5, IHD7, IHD9, distorted power factor, active power, FFT spectrum of current waveform. It also shows RMS values of current and voltage with the aid of gauges and numeric indicators. Data from DAQ assistant contains data from all the connected sensors. Hence, it is divided and each signal is multiplied with its matching multiplication factor. Later RMS waveforms of current and voltage to be used in calculation of active, reactive and apparent power flowing through the system. Amplitude and measurement blocks determine the RMS values of current and voltage. Spectral measurements block is utilised for FFT analysis of current waveform. FFT analysis of voltage waveform is not done because voltage waveform appears perfectly sinusoidal without any abnormalities. Once all the required variables are calculated the data is to be stored in an excel sheet. IHDn calculation was done in a sub VI. IHD value upto 9th harmonic component was calculated. Distortion measurement block is used to calculate specific harmonic current value for each component. Then the specific harmonic current value is separated with specific harmonic current of fundamental to get IHD value. 2.2. Power Factor Calculation Power factor calculation in systems with non-sinusoidal load current is different from that of sinusoidal load current systems. To calculate power factor in such cases distortion power factor is to be taken into account. In case of normal loads PF is calculated by PF = = ( ) Where, Ɵ is phase angle of voltage and ɸ is phase angle of current. But in case of non-linear loads PF ( ) Distorted Power factor (DPF) ( ) Inductance of transformer is measured by short circuit test. In standard SC test, current and voltage transducers are used rather than using wattmeter and voltmeter. Values from these sensors is processed using LabVIEW. Values of power, resistance, impedance, reactance and inductance of the transformer are calculated pertaining to low voltage side of the transformer. MATLAB/Simulink is used for simulation of designed filter because it is difficult to simulate with non-linear load. Therefore, supply current is simulated to match the observed current. This is done by connecting current sources of different amplitudes and frequency in parallel. Filter is simulated using a RLC series component by giving appropriate R, L, C values. A current measurement block and scope is used to observe the waveform. A powergui block is added and FFT analysis for the simulated circuit is carried out. 2.3. Hardware Implementation 2.3.1. NI cDAQ-9184 It is a 4-slot NI CompactDAQ Gigabit ethernet chassis intended for distant or dispersed sensor and electrical calibrations. Solitary NI CompactDAQ chassis measures till 128 sensor signal channels, analog I/O, digital I/O and counter/timers with an ethernet interfaced to a PC or laptop. 2.3.2. NI 9227 It is a 4 channel current input C series module. It has a built in anti-aliasing filter. It is compatible with compactRIO and compactDAQ intended to calculate 5 A nominal and upto 14 A peak on separate channel with channel-to-channel segregation.
  • 4.  ISSN: 2088-8694 IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259 1254 2.3.3. LEM LA 25-NP This is basically a current transducer for measuring the currents, DC, AC, pulsed with galvanic separation amid of primary and secondary circuits. It has 10 terminals on input side which can be connected in different configurations for various input current limits. It can measure maximum primary nominal current of 25 A corresponding to a nominal secondary current of 25 mA. It has to be powered by a +/- 15 V supply. For the range of connection available and with a maximum current value at 25 A this sensor is selected. 2.3.4. LEM LV 25-400 This is normally a voltage transducer for measuring the voltages, DC, AC, pulsed with galvanic separation amid of primary and secondary circuits. It has primary nominal voltage of 400 V. Its output is in current with nominal value of 25 mA. It has to be powered by a +/- 15 V supply. The Figure 2 below shows the power quality monitoring system implemented in our laboratory. Figure 2. Power quality monitoring system implemented The current and voltage transducers are connected to UPS. The output of the sensors is current which is converted to voltage over a resistor. The analog output is connected to National Instruments analog input card which is connected to a National Instruments compact data acquisition with an ethernet chassis. The data acquisition system is connected to PC which is running LabVIEW software. 2.4. Passive Filter Calculation Initial power quality study was done on a 3 KVA UPS and the filter configuration calculation. Passive shunt filters fundamentally consist of serial connection of an inductor and a capacitor adjusted to a certain frequency and behaves as low-impedance path for the harmonics. Initial capacitor size is calculated from reactive power requirement (Qc) of the load. Value of Capacitor (Cn) = Where, Qc - Reactive Power; m - number of branches in passive filter; Vs - fundamental voltage per phase. To eliminate nth current harmonics, the nth -order inductor is calculated as Ln = The series resistance for the nth -order filter inductor is calculated as Rn = The values of capacitance obtained for mitigation of 3rd and 5th harmonic components are not manufactured for single phase system because factor of safety goes down. For this reason, power quality study was done on a modular 1 KVA UPS. In this configuration instead of using external inductance, inductance of output transformer is used. To limit high di/dt in the circuit, additional inductance is added. This inductance value was also designed to change effective value of inductance in the circuit and to change capacitance value to values easily available in the market. The Figure 3 shows the filter implementation using
  • 5. IJPEDS ISSN: 2088-8694  Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N) 1255 internal transformer of UPS. Since, inductance value is fixed from the measured inductance of transformer and additional inductance is to be chosen, the capacitance value easily available in the market for single phase systems are 2.5 uF, 8 uF and 50 uF. The Figure 4 shows the passive filter implementation in our laboratory. Figure 3. Filter implementation using internal transformer of UPS Figure 4. Passive filter implementation The above picture displays the passive filter implementation for mitigating 5th harmonic component using 50 mfd x 3 and 8 mfd x 3 capacitors. These capacitors are connected in parallel to get 164 mfd capacitor bank. This capacitor bank and the inductance from the components of the UPS act as a single tuned passive filter. Thus 5th harmonic component is mitigated. 3. RESULT ANALYSIS AND DISCUSSIONS 3.1.1. KVA UPS System Results When filter calculation where done for 3 KVA system the values for a passive filter components for reducing 3rd harmonic component was, Capacitance: 7650 Micro farad, Inductance: 147 Micro henry.The passive filter components value for reducing 5th harmonic component was, Capacitance: 7650 Micro farad, Inductance: 52.9 Micro henry.This value of capacitance is not manufactured for low powered single phase systems because factor of safety becomes low. For this reason, we had to do power quality analysis on a lower model 1 KVA UPS. Figure 5 and 6 shows the current waveform and FFT analysis of harmonic spectrum with load as 6 systems of 1 KVA UPS. Figure 7 shows the IHD 5 variation with time. Figure 8 depicts the comparison of THD and current for different loads and Figure 9 shows the distorted power factor for different systems.
  • 6.  ISSN: 2088-8694 IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259 1256 Figure 5. Current Waveform with load as 6 systems of 1 KVA UPS Figure 6. FFT analysis for current waveform of 1 KVA system Figure 7. IHD 5 variation with time Figure 8. Comparison of THD and Current for different loads
  • 7. IJPEDS ISSN: 2088-8694  Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N) 1257 Figure 9. Distorted power factor for different systems 3.2. Filtered Output Results of I KVA UPS System Transformer is used as inductor for the passive filter. Inductance value of transformer is measured using short circuit test. Short circuit on transformer was done with standard method but with aid of current, voltage sensors and LabVIEW. The transformer is part of the UPS. The transformer is rated at 1 KVA, 45/230 V. The passive filter is shunt connected to the transformer on LV side. Filter uses inductance of transformer for L of filter. Capacitance used was 164 mfd. This was used to remove 5th harmonic component. Capacitance required to remove 3rd harmonic component is 451 mfd. When 164 mfd capacitor was connected the power through the transformer exceed the limit. For that reason, 451 mfd was not connected. Therefore, it difficult to implement harmonic filter for single phase low powered systems. As the power rating increases availability of required capacitance value also increases. Since the system was single phase low power rated, passive filter branch to remove 3rd harmonic component was not implemented. With the connection of a filter branch the core of the transformer starts vibrating due to resonance between the filter branch and remaining system. For this reason, filter required to remove 3rd harmonic component was not connected as the capacitance required is higher and the vibration caused because of that branch might spoil the transformer. As it can be observed from above picture 5th harmonic component value decreased. THDi value improved. Initial value of THD was at 92 %. Figure 10 and 11 shows the current waveform for 1 KVA system and FFT analysis for current waveform of 1 KVA system with passive filter implementation. Figure 12 depicts Power Factor vs Load Current graph. Figure 10. Current waveform for 1 KVA system with passive filter implemented Figure 11. FFT analysis for current waveform of 1 KVA system with passive filter implemented
  • 8.  ISSN: 2088-8694 IJPEDS Vol. 8, No. 3, September 2017 : 1251–1259 1258 Figure 12. Power Factor vs Load Current Initial analysis on power quality of the system showed high harmonic content with 3rd and 5th harmonic components dominating and power factor value was poor. With the implementation of shunt passive filter branch to reduce 5th harmonic component THDi value decreased and power factor value improved. 4. CONCLUSION A complete power quality analysis on the system was done and various mitigation techniques were studied. The deep understanding of mitigation schemes made us to select passive filter for simulation and implementation. While implementing the mitigation technique a new method of implementation of filter circuit was explored. Implementation of filter by means of output transformer of the UPS was done. The main constraint of such scheme is the power rating of the filter, because the amount of power flows through the transformer is fixed during the design of UPS. Adding extra circuits will rises the power flowing through the transformer and surpasses its limit. While surpassing its limit the transformer core begins to vibrate and starts making noise. This limits the quantity of harmonic contents and can be detached easily. Alternatively this work can be implemented by using active filters or unified power quality compensators or shunt active compensators. Though this work concentrates on low powered system similar principles and techniques can be stretched to high powered systems and three phase systems. REFERENCES [1] D. Gonzalez, J. McCall. Design of Filters to Reduce Harmonic Distortion in Industrial Power Systems. IEEE Trans. on Industry Applications. 1987; 23(3): 504-511. [2] M. Tali, A. Obbadi, A. Elfajri, Y. Errami. Passive Filter for Harmonics Mitigation in Standalone PV System for Non-Linear Load. Renewable and sustainable energy conference, Morocco. 2014; 499-504. [3] Lee G M, Lee D C, Seok J K. Control of series active power filters compensating for source voltage unbalance and current harmonics. IEEE Transactions on Industrial Electronics. 2004; 19(1): 132-139. [4] Fujita H, Akagi H. The unified power quality conditioner: the integration of series-and shunt-active filters. IEEE Transactions on Power Electronics. 1998; 13(2): 315-322. [5] Hideaki Fujita, Hiromi Akagi, Yasuhiro Watanabe. Dynamic control and performance of a unified power flow controller for stabilizing and an AC transmission system. IEEE Transactions on Power Electronics. 2006; 21(4): 1013-1020. [6] Jong-Kun Lee, Jul-Ki Seok, Dong-Choon Lee. Unified Active Power Filters for Source Voltage Unbalance/Current Harmonics Compensation and Power Factor Correction. The 30th Annual Conference of the IEEE Industrial Electronics Society, Busan, Korea. 2004; 540-545. [7] M. H. J. Bollen. Understanding Power Quality Problems: Voltage Sags and Interruptions. IEEE Press, New York, 2000. [8] Waclawiak M, Mc Granaghan M, Sabin D. Substation power quality performance monitoring and the internet. IEEE Power Engineering Society Summer Meeting. 2001; 2: 1110-1111. [9] Batista J, Monso JL, Martins JS. Low-cost power quality monitor based on a PC. EEE International Symposium on Industrial Electronics. 2003; 1: 323-328. [10] Wei-Fu Chang, Yu-Chi Wu, Chui-Wen Chiu. Development of a web-based remote load supervision and control system. Electrical Power and Energy Systems. 2006; 28: 401–407.
  • 9. IJPEDS ISSN: 2088-8694  Filter Implementation using Output Transformer of UPS for Power Quality Improvement (Anandh N) 1259 [11] Juan José González de la Rosa, Antonio Moreno Muñoz, Aurora Gil de Castro, Víctor Pallarés López, Jose Antonio Sánchez Castillejo. A web-based distributed measurement system for electrical power quality assessment. Measurement. 2010; 43: 771–780. [12] R. Balasubramanian, S.Palani. Simulation and performance evaluation of shunt hybrid power filter for power quality improvement using PQ theory. International Journal of Electrical and Computer Engineering. 2016; 6(6): 2603-2609. [13] Jarupula Somlal, Venu Gopala Rao.Mannam, Narasimha Rao.Vutlapalli. Power quality improvement in distribution system using ANN based shunt active power filter. International Journal of Power Electronics and Drive Systems. 2015; 5(4): 568-575.