SlideShare a Scribd company logo
1 of 4
LOW VOLTAGE MCC – STUDY REPORT ON UNWANTED BREAKER
OFF PROBLEM DURING EXTERNAL FAULTS
LOCATION : RO PLANT KHORFAKKAN
EQUIPMENT DETALIS : RO PLANT MCC & SEA WATER MCC
Report Prepared By:
Mr.Rajendrakumar.A.P
Electrical Supervisor
SEWA RO plant Khorfakkan
THE PROBLEMAND ITS HISTORY
Since the beginning of the plant in 2009, it has been observed that during any external faults
i.e., faults in distribution network in khorfakkan RO plant MCC as well as Sea Water intake MCC
incomer breakers are getting off and the system shows no indication of faults. The faults in the
distribution networks are quite common especially during summer due to cable faults, which results
in unwanted tripping of the RO trains.
PRELIMINARY OBSERVATIONS
When referred to the drawing (figure No.1Breaker open control circuit) I concluded the possibilities
to the following two points.
1. OFF command from DCS
2. Breaker opens through under/over voltage relay contact(12UVR1)
The first point was ruled out when checked the DCS history. In the DCS history there was
no OFF command to the breakers. The second point needed to be confirmed. The settings of the
relay (time delay) found to be disturbed and were in the higher side. On delay found as high as 10
sec and it was reduced to 5 sec. So, with the permission of Plant Manager the breaker opening
contact of the under/over voltage relay kept open in the sea water intake incomer # 2 which is
having relatively un important loads(up-stream system gives back up protection for the same).
During another external fault it was found that sea water incomer breaker #2 remained ON and all
other three breakers got OFF. Further it was decided to keep sea water incomer breaker # 1 OFF
contact from the under/over voltage relay to keep open. During the next external faults sea water
incomer breakers did not get OFF. So it was almost confirmed that the problem is resulted from the
under/over voltage relay.
FIGURE 1: BREAKER OPEN CONTROL CIRUIT FIGURE 2: UNDER/OVER VOLTAGE RELAY
Then a genuine question arised, how four relays can malfunction simultaneously or behave
similar to a fault. The chance of all relays getting faulty at the same time is a remote possibility, so
it was necessary to find out the root cause. Downloaded the relay manual from internet and studied.
The following points about the relay characteristic found worth noting.
1. DRV3 is immune to voltage dips < 40 ms.
2. When the voltage is < 0.7 Ue for a time longer than 60 ms, the output relay de-energizes
instantaneously.
CONCLUSION
A fault can result in the second condition and instantaneously de-energise the output relay of the
under/over voltage relay resulting in opening of the breaker.
SOLUTION
Introducing a timer relay in the control circuit will be a cost effective and permanent solution to the
problem. The modified circuit diagram is shown .Figure.3.
The required timer delay details:
On Delay timer
Input: 110 V DC (if universal 24 to 240 Volt AC/DC)
Time Range: 1 to 10 sec (0.5to 10 sec)
Aux Contacts: 1 NO & 1 NC.
Compact DIN rail mount, SPDT
Submitting for necessary approval for successful implementation.
Below given isa content from given web address which shows study of similar problem but the report is
not accessible to non members or need to be paid.
http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=5638901&filter%3DAND%28p_IS_Number%3A56
38851%29
Currently, under-voltage trip devices are widely installed in circuit breakers of low-voltage distribution networks and
end users' sides. These protection devices can prevent equipments from damage when voltage sag or power
supply interruption occurs. Although relay protection devices can act correctly and clear the fault as soon as
possible when a ground or inter phase fault occurs in the nearby high-voltage transmission network, instantaneous
action of under-voltage trip devices may lead to widespread loss of load, fluctuation of frequency, even worse,
cascading failure and collapse of the power system. The widespread load loss accidents arising from under-
voltage trip devices happened in recent years are summarized in this paper. Two typical load loss accidents
happened in Beijiao substation are introduced. The effects of under-voltage trip devices on power system are
discussed base on EMS accident recall, PMU, fault recorder and other tools. Finally, suggestions on management
of under-voltage trip devices and accident precautions are proposed.
-THANKS –

More Related Content

What's hot

Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protectionChetan Patil
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protectionSy Thinhbk
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2Rahaf Waheep
 
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENTREPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENTHimanshu Paghdal
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)Adarsh Verma
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relaysmichaeljmack
 
Power System Faults and Protection System
Power System Faults and Protection SystemPower System Faults and Protection System
Power System Faults and Protection SystemHarshalJain48
 
DOCUMENT FOR SOTF PROTECTION FINAL
DOCUMENT FOR SOTF PROTECTION FINALDOCUMENT FOR SOTF PROTECTION FINAL
DOCUMENT FOR SOTF PROTECTION FINALEKANANDHAN G
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protectionRahul Ruddra
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devicesPrakash_13209
 
Generator Protection
Generator ProtectionGenerator Protection
Generator ProtectionPriten Vasa
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]moiz89
 
Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsArjay Automation
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...
SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...
SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...Jobin Abraham
 
7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relayashwini reliserv
 

What's hot (20)

Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
Switchgear
Switchgear Switchgear
Switchgear
 
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENTREPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relays
 
Power System Faults and Protection System
Power System Faults and Protection SystemPower System Faults and Protection System
Power System Faults and Protection System
 
DOCUMENT FOR SOTF PROTECTION FINAL
DOCUMENT FOR SOTF PROTECTION FINALDOCUMENT FOR SOTF PROTECTION FINAL
DOCUMENT FOR SOTF PROTECTION FINAL
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devices
 
Types of relay
Types of relayTypes of relay
Types of relay
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault Protections
 
7SR11 Overcurrent Relay
7SR11 Overcurrent Relay7SR11 Overcurrent Relay
7SR11 Overcurrent Relay
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...
SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...
SWITCH GEAR AND PROTECTION. distance protection of transmission lines. PREPAR...
 
7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay7SR12 Directional Over Current Relay
7SR12 Directional Over Current Relay
 

Viewers also liked

Viewers also liked (11)

VFD1 MAINTENACE REPOR T RO KHOR
VFD1 MAINTENACE REPOR T RO KHORVFD1 MAINTENACE REPOR T RO KHOR
VFD1 MAINTENACE REPOR T RO KHOR
 
Presen parasito
Presen parasitoPresen parasito
Presen parasito
 
Tatiana leon diapositivas
Tatiana leon   diapositivasTatiana leon   diapositivas
Tatiana leon diapositivas
 
behavioural-economics
behavioural-economicsbehavioural-economics
behavioural-economics
 
Technical magazine analysis
Technical magazine analysisTechnical magazine analysis
Technical magazine analysis
 
Font research
Font researchFont research
Font research
 
Arévalo
ArévaloArévalo
Arévalo
 
Mise en-scene research
Mise en-scene researchMise en-scene research
Mise en-scene research
 
Energía Inalambrica
Energía InalambricaEnergía Inalambrica
Energía Inalambrica
 
Using contract lawyers to scale your law practice
Using contract lawyers to scale your law practiceUsing contract lawyers to scale your law practice
Using contract lawyers to scale your law practice
 
Profile_CV
Profile_CVProfile_CV
Profile_CV
 

Similar to LOW VOLTAGE MCC STUDY REPORT ON UNWANTED BREAKER OFF

Protection system
Protection systemProtection system
Protection systemAIRMANGESH
 
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020nacetwincities
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsJames S Nasby
 
Report on minor project
Report on minor projectReport on minor project
Report on minor projectAnil Maurya
 
POWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docxPOWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docxJeffrey Dorsey
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
Vaccum Circuit Breaker
Vaccum Circuit BreakerVaccum Circuit Breaker
Vaccum Circuit BreakerRAHUL-GOPU
 
Mosfet based ups cum-eps
Mosfet based ups cum-epsMosfet based ups cum-eps
Mosfet based ups cum-epsjayonline_4u
 
final year project report
final year project reportfinal year project report
final year project reportAnuj Kumar
 
three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...Vikram Rawani
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat
 
GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)siddharth sharma
 
powerqualityppt-130820010049-phpapp02.pdf
powerqualityppt-130820010049-phpapp02.pdfpowerqualityppt-130820010049-phpapp02.pdf
powerqualityppt-130820010049-phpapp02.pdfgiahuy646563
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit iivenki249
 

Similar to LOW VOLTAGE MCC STUDY REPORT ON UNWANTED BREAKER OFF (20)

Protection system
Protection systemProtection system
Protection system
 
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC Considerations
 
EE-524 Project report
EE-524 Project reportEE-524 Project report
EE-524 Project report
 
Fy3610821086
Fy3610821086Fy3610821086
Fy3610821086
 
Report on minor project
Report on minor projectReport on minor project
Report on minor project
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
POWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docxPOWER DISTRIBUTION 2.docx
POWER DISTRIBUTION 2.docx
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
 
Vaccum Circuit Breaker
Vaccum Circuit BreakerVaccum Circuit Breaker
Vaccum Circuit Breaker
 
Wapda Engineering Acadmy Report
Wapda Engineering Acadmy ReportWapda Engineering Acadmy Report
Wapda Engineering Acadmy Report
 
Mosfet based ups cum-eps
Mosfet based ups cum-epsMosfet based ups cum-eps
Mosfet based ups cum-eps
 
final year project report
final year project reportfinal year project report
final year project report
 
three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 Webinar
 
GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)
 
powerqualityppt-130820010049-phpapp02.pdf
powerqualityppt-130820010049-phpapp02.pdfpowerqualityppt-130820010049-phpapp02.pdf
powerqualityppt-130820010049-phpapp02.pdf
 
Et601 chapter1 ayu
Et601  chapter1 ayuEt601  chapter1 ayu
Et601 chapter1 ayu
 
Power quality ppt
Power quality pptPower quality ppt
Power quality ppt
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit ii
 

LOW VOLTAGE MCC STUDY REPORT ON UNWANTED BREAKER OFF

  • 1. LOW VOLTAGE MCC – STUDY REPORT ON UNWANTED BREAKER OFF PROBLEM DURING EXTERNAL FAULTS LOCATION : RO PLANT KHORFAKKAN EQUIPMENT DETALIS : RO PLANT MCC & SEA WATER MCC Report Prepared By: Mr.Rajendrakumar.A.P Electrical Supervisor SEWA RO plant Khorfakkan
  • 2. THE PROBLEMAND ITS HISTORY Since the beginning of the plant in 2009, it has been observed that during any external faults i.e., faults in distribution network in khorfakkan RO plant MCC as well as Sea Water intake MCC incomer breakers are getting off and the system shows no indication of faults. The faults in the distribution networks are quite common especially during summer due to cable faults, which results in unwanted tripping of the RO trains. PRELIMINARY OBSERVATIONS When referred to the drawing (figure No.1Breaker open control circuit) I concluded the possibilities to the following two points. 1. OFF command from DCS 2. Breaker opens through under/over voltage relay contact(12UVR1) The first point was ruled out when checked the DCS history. In the DCS history there was no OFF command to the breakers. The second point needed to be confirmed. The settings of the relay (time delay) found to be disturbed and were in the higher side. On delay found as high as 10 sec and it was reduced to 5 sec. So, with the permission of Plant Manager the breaker opening contact of the under/over voltage relay kept open in the sea water intake incomer # 2 which is having relatively un important loads(up-stream system gives back up protection for the same). During another external fault it was found that sea water incomer breaker #2 remained ON and all other three breakers got OFF. Further it was decided to keep sea water incomer breaker # 1 OFF contact from the under/over voltage relay to keep open. During the next external faults sea water incomer breakers did not get OFF. So it was almost confirmed that the problem is resulted from the under/over voltage relay. FIGURE 1: BREAKER OPEN CONTROL CIRUIT FIGURE 2: UNDER/OVER VOLTAGE RELAY Then a genuine question arised, how four relays can malfunction simultaneously or behave similar to a fault. The chance of all relays getting faulty at the same time is a remote possibility, so it was necessary to find out the root cause. Downloaded the relay manual from internet and studied. The following points about the relay characteristic found worth noting. 1. DRV3 is immune to voltage dips < 40 ms.
  • 3. 2. When the voltage is < 0.7 Ue for a time longer than 60 ms, the output relay de-energizes instantaneously. CONCLUSION A fault can result in the second condition and instantaneously de-energise the output relay of the under/over voltage relay resulting in opening of the breaker. SOLUTION Introducing a timer relay in the control circuit will be a cost effective and permanent solution to the problem. The modified circuit diagram is shown .Figure.3. The required timer delay details: On Delay timer Input: 110 V DC (if universal 24 to 240 Volt AC/DC) Time Range: 1 to 10 sec (0.5to 10 sec) Aux Contacts: 1 NO & 1 NC. Compact DIN rail mount, SPDT Submitting for necessary approval for successful implementation.
  • 4. Below given isa content from given web address which shows study of similar problem but the report is not accessible to non members or need to be paid. http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=5638901&filter%3DAND%28p_IS_Number%3A56 38851%29 Currently, under-voltage trip devices are widely installed in circuit breakers of low-voltage distribution networks and end users' sides. These protection devices can prevent equipments from damage when voltage sag or power supply interruption occurs. Although relay protection devices can act correctly and clear the fault as soon as possible when a ground or inter phase fault occurs in the nearby high-voltage transmission network, instantaneous action of under-voltage trip devices may lead to widespread loss of load, fluctuation of frequency, even worse, cascading failure and collapse of the power system. The widespread load loss accidents arising from under- voltage trip devices happened in recent years are summarized in this paper. Two typical load loss accidents happened in Beijiao substation are introduced. The effects of under-voltage trip devices on power system are discussed base on EMS accident recall, PMU, fault recorder and other tools. Finally, suggestions on management of under-voltage trip devices and accident precautions are proposed. -THANKS –