The current limiting reactor is an inductive coil having a
large inductive reactances in comparison to their
resistance and is used for limiting short circuit currents
during fault conditions.
Current-voltage reactors also reduced the voltage
disturbances on the rest of the system.
It is installed in feeders and ties, in generators leads,
and between bus sections, for reducing the magnitude
of short circuit currents and the effect of the respective
voltage disturbance.
Current limiting reactor reduces the flow of short circuit
current so as to protect the appliances from mechanical
stress and overheating.
Current reactor reduced the magnitude of voltage
disturbances which is caused by short circuits.
It limits the fault current to flow into the healthy feeders
or parts of the system, thereby avoiding the fault from
spreading. This increase the chances of continuity of
supply.
The main drawbacks of the current limiting
reactors are as follows:-
When the reactor is installed on the network,
the total percentage reactance of the circuit
increases.
It decreases the power factor and thus the
regulation becomes poorer.
Reactors are located at different location in a
power system for reducing the short circuit
current.
The reactors are connected in series with:
Generator Reactors
Feeder Reactors
Busbar Reactors
Generator reactors are inserted between the generator
and the generator bus. Such reactors protect the
machines individually.
In power station generator, reactors are installed along
with the generators. The magnitude of reactors is
approximately about 0.05 per unit.
The main disadvantages of such type of reactors are
that if the fault occurs on one feeder, then the whole of
the system will be adversely affected by it.
Reactors, which is connected in series with the
feeder is called feeders reactor.
When the fault occurs on any one feeder, then the
voltage drops occur only in its reactors and the bus
bar is not affected much. Hence the machines
continue to supply the load.
The other advantage is that the fault occurs on a
feeder will not affect the others feeders, and thus
the effects of fault are localized.
When the reactors are inserted in the bus bar, then it is
called bus-bar reactors.
The constant loss in reactor is avoided by inserting the
reactors in busbars. In this system only a small power
flows through the reactors during normal condition.
During short circuit on the feeder only one generator
feeds the fault directly by passing the reactors.
sometimes the busbars are sectionalized and the
reactors are included only between the sections of the
bus.
powersystemppt-180618041509 (1).pptx
powersystemppt-180618041509 (1).pptx

More Related Content

Similar to powersystemppt-180618041509 (1).pptx

Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...
Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...
Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...
Ekram Bin Mamun
 
Report On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationReport On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-Station
Ekram Bin Mamun
 

Similar to powersystemppt-180618041509 (1).pptx (20)

Generation protection - complete
Generation protection - completeGeneration protection - complete
Generation protection - complete
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
 
El34831851
El34831851El34831851
El34831851
 
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...
Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...
Report on Industrial Visit at Pahartali Textile and Hosiery Mills of M.M. Isp...
 
J0361059064
J0361059064J0361059064
J0361059064
 
Substation equipments & its functions
Substation equipments & its functionsSubstation equipments & its functions
Substation equipments & its functions
 
Synchronous condensers
Synchronous condensersSynchronous condensers
Synchronous condensers
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement technique
 
Report On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationReport On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-Station
 
Chic export company_catalogue
Chic export company_catalogueChic export company_catalogue
Chic export company_catalogue
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
Presentation 2014
Presentation 2014Presentation 2014
Presentation 2014
 
Power System Frequency
Power System Frequency Power System Frequency
Power System Frequency
 
Current Transformer.pptx
Current Transformer.pptxCurrent Transformer.pptx
Current Transformer.pptx
 
Electrical bus bar and its types
Electrical bus bar and its typesElectrical bus bar and its types
Electrical bus bar and its types
 

Recently uploaded

Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 

powersystemppt-180618041509 (1).pptx

  • 2. The current limiting reactor is an inductive coil having a large inductive reactances in comparison to their resistance and is used for limiting short circuit currents during fault conditions. Current-voltage reactors also reduced the voltage disturbances on the rest of the system. It is installed in feeders and ties, in generators leads, and between bus sections, for reducing the magnitude of short circuit currents and the effect of the respective voltage disturbance.
  • 3. Current limiting reactor reduces the flow of short circuit current so as to protect the appliances from mechanical stress and overheating. Current reactor reduced the magnitude of voltage disturbances which is caused by short circuits. It limits the fault current to flow into the healthy feeders or parts of the system, thereby avoiding the fault from spreading. This increase the chances of continuity of supply.
  • 4. The main drawbacks of the current limiting reactors are as follows:- When the reactor is installed on the network, the total percentage reactance of the circuit increases. It decreases the power factor and thus the regulation becomes poorer.
  • 5. Reactors are located at different location in a power system for reducing the short circuit current. The reactors are connected in series with: Generator Reactors Feeder Reactors Busbar Reactors
  • 6. Generator reactors are inserted between the generator and the generator bus. Such reactors protect the machines individually. In power station generator, reactors are installed along with the generators. The magnitude of reactors is approximately about 0.05 per unit. The main disadvantages of such type of reactors are that if the fault occurs on one feeder, then the whole of the system will be adversely affected by it.
  • 7.
  • 8. Reactors, which is connected in series with the feeder is called feeders reactor. When the fault occurs on any one feeder, then the voltage drops occur only in its reactors and the bus bar is not affected much. Hence the machines continue to supply the load. The other advantage is that the fault occurs on a feeder will not affect the others feeders, and thus the effects of fault are localized.
  • 9.
  • 10. When the reactors are inserted in the bus bar, then it is called bus-bar reactors. The constant loss in reactor is avoided by inserting the reactors in busbars. In this system only a small power flows through the reactors during normal condition. During short circuit on the feeder only one generator feeds the fault directly by passing the reactors. sometimes the busbars are sectionalized and the reactors are included only between the sections of the bus.