Proceedings of ICONE15:
15th International Conference on Nuclear Engineering
April 22-26, 2007, Nagoya, Japan
ICONE15-10754
CONDITIONS OF THE FLUID IN THE RHRS PIPE LINE AFTER THE LOSS AND
RESTART OF THE RHRS PUMP
Dr. Ching Guey/FP&L
700 University Blvd
Juno Beach, FL 33408
Phone: 561 694 3137, Pager: 561 722 3860
e-mail: ching_guey@fpl.com
Joseph S. Miller/EDA, Inc.
2015 Woodford Rd
Vienna, VA 22182
Phone: 703 597-2459, Fax: 703 356 4149
e-mail: JoeMiller@edasolutions.com
GPM – Gallons per Minute
MOV – Motor Operated Valve
PWR – Pressurized Water Reactor
RCS – Reactor Coolant System
RHRS – Residual Heat Removal System
SDC – Shutdown Cooling
ABSTRACT
Due to a recent event at pressurized water reactor (PWR), the
impact of a loss of shutdown cooling during reduced RCS
inventory conditions was evaluated. The evaluation for the loss
of RHRS assumed loss of shutdown cooling initially and then
the RHRS pumps were restored. This analysis is based upon a
decay heat rate corresponding to 2.66 days following reactor
shutdown with an initial liquid level at the elevation of the
reactor flange. When the RHRS pump was restored, the
calculation revealed that a void fraction of 10 -50 % could exist
in the hot leg pipe where the RHRS pumps take suction.
The study presented in this paper was conducted to determine
the maximum voids permissible in the hot leg piping and still
ensure that the water entering the RHRS pump did not have
steam voids. RELAP5 was used to perform this evaluation.
RELAP5/M3.3 is a computer code used for the thermal-
hydraulic analysis of transients and small-break accidents and
transients in light-water nuclear power plants. It uses a one-
dimensional, two-fluid model, consisting of steam and water,
with the possibility of the vapor phase containing a non-
condensable component. A model of the piping was developed
and the conditions presented above were analyzed and the fluid
conditions were reviewed.
The results of the RELAP5 analyses indicated that for voids 30
% or less in the hot leg, the RHRS pump would have adequate
suction flow to remain in a stable operational condition.
1. INTRODUCTION
Due to a recent outage event at a PWR, a loss of shutdown
cooling for 8 minutes occurred during reduced RCS inventory
conditions. The head was still on the vessel and water level
was at the flange, or approximately 7 ft from Mid-loop of the
hot leg. A calculation was performed to evaluate the system
response. The calculation showed the possibility of voids in
the hot leg piping where the RHRS pump takes suction for
shutdown cooling. To determine the safety significance of the
event, a concern was raised that the RHRS pumps may not
operate with voids in the hot leg piping. To provide evidence
that the RHRS pumps will operate with some voiding in the hot
leg piping, a RELAP5 model of the RHR piping was
constructed and used to perform simulations of hot leg voiding
scenarios.
2. DISCUSSION
A RELAP5/M3.3 model was constructed to simulate the fluid
in the RHRS line from the Hot Leg to the RHRS pump.
RELAP5/M3.3 (Ref. 1) is a computer code used for the
thermal-hydraulic analysis of transients and small-break
accidents and transients in light-water nuclear power plants.
RELAP5 uses a one-dimensional, two-fluid model, consisting
of steam and water, with the possibility of the vapor phase
containing a non-condensable component. The RELAP5
program has been used to solve similar problems to the RHRS
flow problem (Refs. 2 & 3) and has been validated for
calculating fluid flow conditions and resulting forcing
functions (Ref. 4).
1 Copyright © 2007 by JSME
The RELAP5 model was constructed for the RHRS system and
is shown in Figure 1. The model begins from the hot leg
(RELAP5 component 104), which is a 30-inch pipe leaving the
reactor vessel. The 14-inch Residual Heat Removal (RHR)
connects to the hot leg through junction 401 and traverses to
RHRS pump (RELAP5 Component 201) as shown in the
diagram in Figure 1.
The model consists of two pumps, i.e., RHRS pumps A and B.
For these simulations, pump B (RELAP5 Component 202) was
not started. The pumps rated head is 210 feet at a rated flow of
3500 gpm. Two motor operated valves (MOVs), were also
modeled in series. Loss coefficients and sizes were taken from
References 5, 6 & 7. At time equal zero, the RHRS 14” piping
is full of 120° F water. The 14” pipe running from the Hot Leg
to pump A is about 190 feet in length.
3. RESULTS
Four cases were analyzed with RELAP5. The first case
simulated saturated conditions at 55 psia in the hot leg pipe
with the pump A running at a rated flow of 3500 gpm at rated
density. The second case was to simulate slightly less than
10% voids in the Hot Leg piping at 55 psia. The third case was
to simulate 30% voids in the Hot Leg piping at 55 psia and the
fourth case was to simulate greater than 40% in the Hot Leg
piping at 55 psia.
Figure 1 RELAP5 Nodal Diagram of RHRS System
Figure 2 shows the pressure distribution in the RHRS piping
for the saturated liquid at 55-psia case. Figure 2 shows that the
pressure in the piping leading to the pumps is about 64 psia
whereas the pressure at the 14” pipe inlet from the hot leg is
about 54 psia. The elevation head change and pressure drops
from form losses cause the pressure differences from the Hot
Leg to the pump inlet.
Figure 2 Case 1 Pressures for Saturated Liquid in Hot
Leg
Figure 3 shows the densities in the RHRS piping for the
saturated liquid case after the cool water (120° F) has been
flushed through the pump. The density in the hot leg piping
(i.e., RELAP5 Component 104) is approximately 57 lbm/ft3
.
The density in the 14” RHRS inlet piping (RELAP5
Component 301) reduces due to the pressure drop from the hot
leg to the 14” pipe. The density reduces further as the fluid
traverses along the horizontal piping and up the 30° incline at
Elevation 21 feet. Once the fluid flows down into the lower
elevation of the pumps (RELAP5 Components 320 and 322),
the density increases above the saturated density of the hot leg
(RELAP5 Component 104).
2 Copyright © 2007 by JSME
Figure 3 Densities for Saturated Liquid in Hot Leg
Figure 4 Voids in the 14” RHRS Inlet for the 4 Cases
Simulated
Figure 4 shows the voids in the 14” RHRS pipe inlet for the 4
cases. Case 1 assumes saturated liquid in the hot leg, Case 2
assumes slightly less than 10% voids in the hot leg, Case 3
assumes 30 % voids in the hot leg and Case 4 assumes greater
than 40% voids in the hot leg.
Figure 5 shows the density at the RHRS pump inlet for each of
the cases simulated. For Cases 1, 2 and 3 (i.e., saturated liquid
in the hot leg, less than 10% voids in the hot let and 30% voids
in the hot leg, respectively), the density at the RHRS pump
inlet was calculated as 58 lbm/ft3
. For Case 4, the greater than
40% voids in the hot leg case, the density was calculated to be
.25 lbm/ft3
and the pump failed to adequately pump fluid.
Figure 5 Density in the 13” RHRS Pump Inlet for the 4
Cases Simulated
Figure 6 Voids in the 14” RHRS Pump Inlet for the 4 Cases
Simulated
Figure 6 shows the steam void at the RHRS pump inlet for
each of the cases simulated. For Cases 1, 2 and 3 (i.e.,
saturated liquid in the Hot Leg, less than 10% voids in hot
let and 30% voids in hot leg, respectively), the void at the
RHRS pump inlet was calculated as 0.0. For Case 4, the
greater than 40% voids in the hot leg case, the void was
calculated to be 1.0 and the pump failed to pump fluid.
Table 1 presents the results of the 4 cases simulated. Cases
1, 2 and 3 that represented up to 30% voiding in the hot
leg, indicated that no voiding occurred in the pump inlet.
Case 4, which represented the simulated case with greater
than 40% voids in the hot leg, showed that the pump inlet
would be completely voided with no flow through the
pump.
Table 1 Summary of Results for all Cases
RELAP5
Case
Description RELAP5
File
Voids in
Hot Leg
Voids at
Pump 3A
Inlet
1 Saturated
Liquid in Hot
Leg
RHRpg.i None None
2 Less Than
10% Voids in
Hot Leg
RHRpd.i Less
Than
10%
Voids
None
3 30% Voids in
Hot Leg
RHRpe.i 30%
Voids
None
4 Greater Than
40% Voids in
Hot Leg
RHRpf.i Greater
Than
40%
Voids
100%
Voiding
3 Copyright © 2007 by JSME
4. CONCLUSIONS
Four cases were simulated with RELAP5. Case 1 simulated
saturated conditions at 55 psia in the hot leg pipe. Case 2
simulated slightly less than 10 voids in the hot leg piping at 55
psia. Case 3 simulated 30% voids in the hot leg piping at 55
psia and Case 4 simulated greater than 40% in the hot leg
piping at 55 psia. For all cases, the A pump was running at a
rated flow of 3500 gpm at rated density.
The results of the RELAP5 analyses indicated that for voids 30
% or less in the hot leg, the RHRS pump would have adequate
suction density and flow to remain in a stable operational
condition.
REFERENCES
1) NUREG/CR-5535/Rev1, RELAP5/MOD3.3 VOLUMES 1
through 8, Prepared by Information Systems Laboratories,
Inc., Idaho Falls, ID for Division of Systems Research,
NRC, Washington, DC 20555. December 2001.
2) “Solving Reactor Water Clean-up System Anomalies Using
RELAP5MOD3.3”, Joseph S. Miller and Chris Brenan,
11th
International Conference on Nuclear Engineering,
ICONE11, Tokyo, JAPAN, ICONE11-36149, April 20-23,
2003.
3) “Calculation of Forces on Reactor Containment Fan
Cooler Piping”, Joseph S. Miller and Kevin Ramsden, 12th
International Conference on Nuclear Engineering,
ICONE12, Arlington, Virginia, ICONE12-49214, April 25-
29, 2004.
4) “Validation of a Thermal Hydraulic Computer Code to
Perform Two-Phase Multi-Component Force Calculations
for Structural Evaluations”, Joseph S. Miller and Kevin
Ramsden, 13th
International Conference on Nuclear
Engineering, ICONE13, Beijing, China, ICONE13-50297,
May 16-21, 2005.
5) I.E. Idel’ Chik, “Handbook of Hydraulic Resistance,
Coefficients of Local Resistance and of Friction”, AEC-
TR-6630, (1966).
6) “Flow of Fluids Through Valves, Fittings and Pipe”,
Technical Paper No. 410, CRANE, Twenty Fifth Printing
1991.
7) NAVCO PIPING DATALOG, National Valve and
Manufacturing Company, Edition No. 10 (Rev. June 1,
1974) 1966.
4 Copyright © 2007 by JSME

More Related Content

Similar to Conditions of Fluid in RHRS Line after Loss and Restart of RHRS Pump.pdf

International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)inventionjournals
 
Experimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer Coefficent
Experimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer CoefficentExperimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer Coefficent
Experimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer CoefficentIRJET Journal
 
2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...
2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...
2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...Komandur Sunder Raj, P.E.
 
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptxNUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptxbatan5455
 
IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...
IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...
IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...IRJET Journal
 
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art  Phased Array Radar CoolingSBIR, Low Cost High Performance State-of-the Art  Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Coolingmartyp01
 
IRJET- Experimental Investigation on the Performance of V.C.R. System using R...
IRJET- Experimental Investigation on the Performance of V.C.R. System using R...IRJET- Experimental Investigation on the Performance of V.C.R. System using R...
IRJET- Experimental Investigation on the Performance of V.C.R. System using R...IRJET Journal
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Using A Hydraulic Ram to Pump Livestock Water
Using A Hydraulic Ram to Pump Livestock WaterUsing A Hydraulic Ram to Pump Livestock Water
Using A Hydraulic Ram to Pump Livestock WaterFifi62z
 
Rayegan thermo i-cengel-chapter 5-2
Rayegan thermo i-cengel-chapter 5-2Rayegan thermo i-cengel-chapter 5-2
Rayegan thermo i-cengel-chapter 5-2Larry Howard
 
Heat recovery steam generator
Heat recovery steam generatorHeat recovery steam generator
Heat recovery steam generatorumar farooq
 
PLC Based Instrumentation of Closed Loop Gas System for RPC Detectors
PLC Based Instrumentation of Closed Loop Gas System for RPC DetectorsPLC Based Instrumentation of Closed Loop Gas System for RPC Detectors
PLC Based Instrumentation of Closed Loop Gas System for RPC DetectorsIOSRJAP
 

Similar to Conditions of Fluid in RHRS Line after Loss and Restart of RHRS Pump.pdf (20)

International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
Experimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer Coefficent
Experimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer CoefficentExperimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer Coefficent
Experimental Analysis on Thermosyphon Heatpipe to Find Heat Transfer Coefficent
 
Vacuum MEtallurgy Pressure and throughput distribution in vacuum systems
Vacuum MEtallurgy Pressure and throughput distribution in vacuum systemsVacuum MEtallurgy Pressure and throughput distribution in vacuum systems
Vacuum MEtallurgy Pressure and throughput distribution in vacuum systems
 
2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...
2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...
2003 ASME Power Conference Performance Evaluation of Feedwater Heaters for Nu...
 
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptxNUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
 
Lecture 6
Lecture 6Lecture 6
Lecture 6
 
IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...
IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...
IRJET- Uncertainty Analysis of Flat Plate Oscillating Heat Pipe with Differen...
 
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art  Phased Array Radar CoolingSBIR, Low Cost High Performance State-of-the Art  Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling
 
ProjectBRevision
ProjectBRevisionProjectBRevision
ProjectBRevision
 
hvac refragration Pipes size and table
hvac refragration Pipes size and tablehvac refragration Pipes size and table
hvac refragration Pipes size and table
 
IRJET- Experimental Investigation on the Performance of V.C.R. System using R...
IRJET- Experimental Investigation on the Performance of V.C.R. System using R...IRJET- Experimental Investigation on the Performance of V.C.R. System using R...
IRJET- Experimental Investigation on the Performance of V.C.R. System using R...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
0exp11 pipe friction_01
0exp11 pipe friction_010exp11 pipe friction_01
0exp11 pipe friction_01
 
D013161520
D013161520D013161520
D013161520
 
Using A Hydraulic Ram to Pump Livestock Water
Using A Hydraulic Ram to Pump Livestock WaterUsing A Hydraulic Ram to Pump Livestock Water
Using A Hydraulic Ram to Pump Livestock Water
 
Using a Hydraulic Ram to Pump Livestock Water - British Columbia
Using a Hydraulic Ram to Pump Livestock Water - British ColumbiaUsing a Hydraulic Ram to Pump Livestock Water - British Columbia
Using a Hydraulic Ram to Pump Livestock Water - British Columbia
 
The Science and Economics of Multiphase Flow
The Science and Economics of Multiphase FlowThe Science and Economics of Multiphase Flow
The Science and Economics of Multiphase Flow
 
Rayegan thermo i-cengel-chapter 5-2
Rayegan thermo i-cengel-chapter 5-2Rayegan thermo i-cengel-chapter 5-2
Rayegan thermo i-cengel-chapter 5-2
 
Heat recovery steam generator
Heat recovery steam generatorHeat recovery steam generator
Heat recovery steam generator
 
PLC Based Instrumentation of Closed Loop Gas System for RPC Detectors
PLC Based Instrumentation of Closed Loop Gas System for RPC DetectorsPLC Based Instrumentation of Closed Loop Gas System for RPC Detectors
PLC Based Instrumentation of Closed Loop Gas System for RPC Detectors
 

More from Joe Miller

TraceLargeBreakLossCoolant.pdf
TraceLargeBreakLossCoolant.pdfTraceLargeBreakLossCoolant.pdf
TraceLargeBreakLossCoolant.pdfJoe Miller
 
BWR6 RELAP4 Model0001.pdf
BWR6 RELAP4 Model0001.pdfBWR6 RELAP4 Model0001.pdf
BWR6 RELAP4 Model0001.pdfJoe Miller
 
validation_of_a_thermal_hydraulic0001 (1).pdf
validation_of_a_thermal_hydraulic0001 (1).pdfvalidation_of_a_thermal_hydraulic0001 (1).pdf
validation_of_a_thermal_hydraulic0001 (1).pdfJoe Miller
 
ABoronTransplant.pdf
ABoronTransplant.pdfABoronTransplant.pdf
ABoronTransplant.pdfJoe Miller
 
bwrsc_online_stability_exclusion_region.pdf
bwrsc_online_stability_exclusion_region.pdfbwrsc_online_stability_exclusion_region.pdf
bwrsc_online_stability_exclusion_region.pdfJoe Miller
 
BWR_Water_Level0002.pdf
BWR_Water_Level0002.pdfBWR_Water_Level0002.pdf
BWR_Water_Level0002.pdfJoe Miller
 
validation_of_a_thermal_hydraulic0001.pdf
validation_of_a_thermal_hydraulic0001.pdfvalidation_of_a_thermal_hydraulic0001.pdf
validation_of_a_thermal_hydraulic0001.pdfJoe Miller
 
safety_significance_of_shorts0001.pdf
safety_significance_of_shorts0001.pdfsafety_significance_of_shorts0001.pdf
safety_significance_of_shorts0001.pdfJoe Miller
 
simulation_coupled_primary_system0001.pdf
simulation_coupled_primary_system0001.pdfsimulation_coupled_primary_system0001.pdf
simulation_coupled_primary_system0001.pdfJoe Miller
 
water_back_fill_Paper0001.pdf
water_back_fill_Paper0001.pdfwater_back_fill_Paper0001.pdf
water_back_fill_Paper0001.pdfJoe Miller
 
alternatives_reducing_thermal_loads0001.pdf
alternatives_reducing_thermal_loads0001.pdfalternatives_reducing_thermal_loads0001.pdf
alternatives_reducing_thermal_loads0001.pdfJoe Miller
 

More from Joe Miller (11)

TraceLargeBreakLossCoolant.pdf
TraceLargeBreakLossCoolant.pdfTraceLargeBreakLossCoolant.pdf
TraceLargeBreakLossCoolant.pdf
 
BWR6 RELAP4 Model0001.pdf
BWR6 RELAP4 Model0001.pdfBWR6 RELAP4 Model0001.pdf
BWR6 RELAP4 Model0001.pdf
 
validation_of_a_thermal_hydraulic0001 (1).pdf
validation_of_a_thermal_hydraulic0001 (1).pdfvalidation_of_a_thermal_hydraulic0001 (1).pdf
validation_of_a_thermal_hydraulic0001 (1).pdf
 
ABoronTransplant.pdf
ABoronTransplant.pdfABoronTransplant.pdf
ABoronTransplant.pdf
 
bwrsc_online_stability_exclusion_region.pdf
bwrsc_online_stability_exclusion_region.pdfbwrsc_online_stability_exclusion_region.pdf
bwrsc_online_stability_exclusion_region.pdf
 
BWR_Water_Level0002.pdf
BWR_Water_Level0002.pdfBWR_Water_Level0002.pdf
BWR_Water_Level0002.pdf
 
validation_of_a_thermal_hydraulic0001.pdf
validation_of_a_thermal_hydraulic0001.pdfvalidation_of_a_thermal_hydraulic0001.pdf
validation_of_a_thermal_hydraulic0001.pdf
 
safety_significance_of_shorts0001.pdf
safety_significance_of_shorts0001.pdfsafety_significance_of_shorts0001.pdf
safety_significance_of_shorts0001.pdf
 
simulation_coupled_primary_system0001.pdf
simulation_coupled_primary_system0001.pdfsimulation_coupled_primary_system0001.pdf
simulation_coupled_primary_system0001.pdf
 
water_back_fill_Paper0001.pdf
water_back_fill_Paper0001.pdfwater_back_fill_Paper0001.pdf
water_back_fill_Paper0001.pdf
 
alternatives_reducing_thermal_loads0001.pdf
alternatives_reducing_thermal_loads0001.pdfalternatives_reducing_thermal_loads0001.pdf
alternatives_reducing_thermal_loads0001.pdf
 

Recently uploaded

Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfsumitt6_25730773
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...drmkjayanthikannan
 
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...jabtakhaidam7
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"mphochane1998
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdfKamal Acharya
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdfKamal Acharya
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Call Girls Mumbai
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Servicemeghakumariji156
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptxrouholahahmadi9876
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...HenryBriggs2
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxMuhammadAsimMuhammad6
 

Recently uploaded (20)

Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdf
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 

Conditions of Fluid in RHRS Line after Loss and Restart of RHRS Pump.pdf

  • 1. Proceedings of ICONE15: 15th International Conference on Nuclear Engineering April 22-26, 2007, Nagoya, Japan ICONE15-10754 CONDITIONS OF THE FLUID IN THE RHRS PIPE LINE AFTER THE LOSS AND RESTART OF THE RHRS PUMP Dr. Ching Guey/FP&L 700 University Blvd Juno Beach, FL 33408 Phone: 561 694 3137, Pager: 561 722 3860 e-mail: ching_guey@fpl.com Joseph S. Miller/EDA, Inc. 2015 Woodford Rd Vienna, VA 22182 Phone: 703 597-2459, Fax: 703 356 4149 e-mail: JoeMiller@edasolutions.com GPM – Gallons per Minute MOV – Motor Operated Valve PWR – Pressurized Water Reactor RCS – Reactor Coolant System RHRS – Residual Heat Removal System SDC – Shutdown Cooling ABSTRACT Due to a recent event at pressurized water reactor (PWR), the impact of a loss of shutdown cooling during reduced RCS inventory conditions was evaluated. The evaluation for the loss of RHRS assumed loss of shutdown cooling initially and then the RHRS pumps were restored. This analysis is based upon a decay heat rate corresponding to 2.66 days following reactor shutdown with an initial liquid level at the elevation of the reactor flange. When the RHRS pump was restored, the calculation revealed that a void fraction of 10 -50 % could exist in the hot leg pipe where the RHRS pumps take suction. The study presented in this paper was conducted to determine the maximum voids permissible in the hot leg piping and still ensure that the water entering the RHRS pump did not have steam voids. RELAP5 was used to perform this evaluation. RELAP5/M3.3 is a computer code used for the thermal- hydraulic analysis of transients and small-break accidents and transients in light-water nuclear power plants. It uses a one- dimensional, two-fluid model, consisting of steam and water, with the possibility of the vapor phase containing a non- condensable component. A model of the piping was developed and the conditions presented above were analyzed and the fluid conditions were reviewed. The results of the RELAP5 analyses indicated that for voids 30 % or less in the hot leg, the RHRS pump would have adequate suction flow to remain in a stable operational condition. 1. INTRODUCTION Due to a recent outage event at a PWR, a loss of shutdown cooling for 8 minutes occurred during reduced RCS inventory conditions. The head was still on the vessel and water level was at the flange, or approximately 7 ft from Mid-loop of the hot leg. A calculation was performed to evaluate the system response. The calculation showed the possibility of voids in the hot leg piping where the RHRS pump takes suction for shutdown cooling. To determine the safety significance of the event, a concern was raised that the RHRS pumps may not operate with voids in the hot leg piping. To provide evidence that the RHRS pumps will operate with some voiding in the hot leg piping, a RELAP5 model of the RHR piping was constructed and used to perform simulations of hot leg voiding scenarios. 2. DISCUSSION A RELAP5/M3.3 model was constructed to simulate the fluid in the RHRS line from the Hot Leg to the RHRS pump. RELAP5/M3.3 (Ref. 1) is a computer code used for the thermal-hydraulic analysis of transients and small-break accidents and transients in light-water nuclear power plants. RELAP5 uses a one-dimensional, two-fluid model, consisting of steam and water, with the possibility of the vapor phase containing a non-condensable component. The RELAP5 program has been used to solve similar problems to the RHRS flow problem (Refs. 2 & 3) and has been validated for calculating fluid flow conditions and resulting forcing functions (Ref. 4). 1 Copyright © 2007 by JSME
  • 2. The RELAP5 model was constructed for the RHRS system and is shown in Figure 1. The model begins from the hot leg (RELAP5 component 104), which is a 30-inch pipe leaving the reactor vessel. The 14-inch Residual Heat Removal (RHR) connects to the hot leg through junction 401 and traverses to RHRS pump (RELAP5 Component 201) as shown in the diagram in Figure 1. The model consists of two pumps, i.e., RHRS pumps A and B. For these simulations, pump B (RELAP5 Component 202) was not started. The pumps rated head is 210 feet at a rated flow of 3500 gpm. Two motor operated valves (MOVs), were also modeled in series. Loss coefficients and sizes were taken from References 5, 6 & 7. At time equal zero, the RHRS 14” piping is full of 120° F water. The 14” pipe running from the Hot Leg to pump A is about 190 feet in length. 3. RESULTS Four cases were analyzed with RELAP5. The first case simulated saturated conditions at 55 psia in the hot leg pipe with the pump A running at a rated flow of 3500 gpm at rated density. The second case was to simulate slightly less than 10% voids in the Hot Leg piping at 55 psia. The third case was to simulate 30% voids in the Hot Leg piping at 55 psia and the fourth case was to simulate greater than 40% in the Hot Leg piping at 55 psia. Figure 1 RELAP5 Nodal Diagram of RHRS System Figure 2 shows the pressure distribution in the RHRS piping for the saturated liquid at 55-psia case. Figure 2 shows that the pressure in the piping leading to the pumps is about 64 psia whereas the pressure at the 14” pipe inlet from the hot leg is about 54 psia. The elevation head change and pressure drops from form losses cause the pressure differences from the Hot Leg to the pump inlet. Figure 2 Case 1 Pressures for Saturated Liquid in Hot Leg Figure 3 shows the densities in the RHRS piping for the saturated liquid case after the cool water (120° F) has been flushed through the pump. The density in the hot leg piping (i.e., RELAP5 Component 104) is approximately 57 lbm/ft3 . The density in the 14” RHRS inlet piping (RELAP5 Component 301) reduces due to the pressure drop from the hot leg to the 14” pipe. The density reduces further as the fluid traverses along the horizontal piping and up the 30° incline at Elevation 21 feet. Once the fluid flows down into the lower elevation of the pumps (RELAP5 Components 320 and 322), the density increases above the saturated density of the hot leg (RELAP5 Component 104). 2 Copyright © 2007 by JSME
  • 3. Figure 3 Densities for Saturated Liquid in Hot Leg Figure 4 Voids in the 14” RHRS Inlet for the 4 Cases Simulated Figure 4 shows the voids in the 14” RHRS pipe inlet for the 4 cases. Case 1 assumes saturated liquid in the hot leg, Case 2 assumes slightly less than 10% voids in the hot leg, Case 3 assumes 30 % voids in the hot leg and Case 4 assumes greater than 40% voids in the hot leg. Figure 5 shows the density at the RHRS pump inlet for each of the cases simulated. For Cases 1, 2 and 3 (i.e., saturated liquid in the hot leg, less than 10% voids in the hot let and 30% voids in the hot leg, respectively), the density at the RHRS pump inlet was calculated as 58 lbm/ft3 . For Case 4, the greater than 40% voids in the hot leg case, the density was calculated to be .25 lbm/ft3 and the pump failed to adequately pump fluid. Figure 5 Density in the 13” RHRS Pump Inlet for the 4 Cases Simulated Figure 6 Voids in the 14” RHRS Pump Inlet for the 4 Cases Simulated Figure 6 shows the steam void at the RHRS pump inlet for each of the cases simulated. For Cases 1, 2 and 3 (i.e., saturated liquid in the Hot Leg, less than 10% voids in hot let and 30% voids in hot leg, respectively), the void at the RHRS pump inlet was calculated as 0.0. For Case 4, the greater than 40% voids in the hot leg case, the void was calculated to be 1.0 and the pump failed to pump fluid. Table 1 presents the results of the 4 cases simulated. Cases 1, 2 and 3 that represented up to 30% voiding in the hot leg, indicated that no voiding occurred in the pump inlet. Case 4, which represented the simulated case with greater than 40% voids in the hot leg, showed that the pump inlet would be completely voided with no flow through the pump. Table 1 Summary of Results for all Cases RELAP5 Case Description RELAP5 File Voids in Hot Leg Voids at Pump 3A Inlet 1 Saturated Liquid in Hot Leg RHRpg.i None None 2 Less Than 10% Voids in Hot Leg RHRpd.i Less Than 10% Voids None 3 30% Voids in Hot Leg RHRpe.i 30% Voids None 4 Greater Than 40% Voids in Hot Leg RHRpf.i Greater Than 40% Voids 100% Voiding 3 Copyright © 2007 by JSME
  • 4. 4. CONCLUSIONS Four cases were simulated with RELAP5. Case 1 simulated saturated conditions at 55 psia in the hot leg pipe. Case 2 simulated slightly less than 10 voids in the hot leg piping at 55 psia. Case 3 simulated 30% voids in the hot leg piping at 55 psia and Case 4 simulated greater than 40% in the hot leg piping at 55 psia. For all cases, the A pump was running at a rated flow of 3500 gpm at rated density. The results of the RELAP5 analyses indicated that for voids 30 % or less in the hot leg, the RHRS pump would have adequate suction density and flow to remain in a stable operational condition. REFERENCES 1) NUREG/CR-5535/Rev1, RELAP5/MOD3.3 VOLUMES 1 through 8, Prepared by Information Systems Laboratories, Inc., Idaho Falls, ID for Division of Systems Research, NRC, Washington, DC 20555. December 2001. 2) “Solving Reactor Water Clean-up System Anomalies Using RELAP5MOD3.3”, Joseph S. Miller and Chris Brenan, 11th International Conference on Nuclear Engineering, ICONE11, Tokyo, JAPAN, ICONE11-36149, April 20-23, 2003. 3) “Calculation of Forces on Reactor Containment Fan Cooler Piping”, Joseph S. Miller and Kevin Ramsden, 12th International Conference on Nuclear Engineering, ICONE12, Arlington, Virginia, ICONE12-49214, April 25- 29, 2004. 4) “Validation of a Thermal Hydraulic Computer Code to Perform Two-Phase Multi-Component Force Calculations for Structural Evaluations”, Joseph S. Miller and Kevin Ramsden, 13th International Conference on Nuclear Engineering, ICONE13, Beijing, China, ICONE13-50297, May 16-21, 2005. 5) I.E. Idel’ Chik, “Handbook of Hydraulic Resistance, Coefficients of Local Resistance and of Friction”, AEC- TR-6630, (1966). 6) “Flow of Fluids Through Valves, Fittings and Pipe”, Technical Paper No. 410, CRANE, Twenty Fifth Printing 1991. 7) NAVCO PIPING DATALOG, National Valve and Manufacturing Company, Edition No. 10 (Rev. June 1, 1974) 1966. 4 Copyright © 2007 by JSME