SlideShare a Scribd company logo
1 of 11
Download to read offline
132 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
Fault Ride-Through Capability Improvement of
DFIG-Based Wind Turbine by Employing a
Voltage-Compensation-Type Active SFCL
Amélioration de la robustesse aux défaillances des
tours éoliennes en utilisant le “DFIG” à
travers une compensation de tension active
Lei Chen, Member, IEEE, Feng Zheng, Changhong Deng, Zhe Li, and Fang Guo
Abstract—Based on the considerations in creating a smart grid roadmap, an integrated application of
renewable energy sources and superconducting power devices may bring more positive effects. This paper
suggests a voltage-compensation-type active superconducting fault current limiter (SFCL) to enhance the fault
ride-through capability of doubly fed induction generator (DFIG) for wind power generation. Since the active
SFCL has higher controllability and flexibility than a common resistive- or inductive-type SFCL, its application
may give better results. Related theory derivation, cost evaluation, and simulation analysis are conducted, and
a comparison between the active SFCL and an inductive SFCL is performed. From the results, the active
SFCL can limit the faulty currents flowing through the DFIG’s stator and rotor windings and compensate the
generator terminal voltage. The inductive SFCL may not evacuate the surplus active power during the grid
fault; however, the active SFCL can smooth the DFIG’s power fluctuation, and the stability of the wind power
system can be well strengthened.
Résumé—Dans l’objectif de mettre en place une feuille de route pour un réseau électrique intelligent, une
application intégrée pour les sources d’énergies renouvelables et appareils électriques supraconducteurs peut
avoir un impact positif. Ces travaux de recherche proposent une compensation de tension active pour limiter les
défauts provenant des limiteurs de courants actifs et super conducteur (SFCL) afin d’améliorer la robustesse
aux défaillances du générateur à induction à double alimentation (DFIG) pour la production d’énergie éolienne.
Puisque le SFCL a une contrôlabilité et une flexibilité supérieures à un SFCL résistif ou inductif, son utilisation
pourrait offrir de meilleurs résultats. D’après la théorie, les évaluations des coûts, et les simulations, des
analysesont été proposées et une comparaison entre le SFCL actif et le SFCL inductif est présentée. D’après les
résultats obtenus, le SFCL actif pourrait limiter les courants défectueux à travers les enroulements du stator
et du rotor du DFIG et compenser la tension aux bornes du générateur. Dans certains cas, le SFCL inductif
ne peut pas évacuer le surplus de puissance active lors d’un défaut du réseau. Toutefois, le SFCL actif peut
lisser la fluctuation de puissance du DFIG pour améliorer la stabilité du réseau d’énergie éolienne.
Index Terms—Doubly fed induction generator (DFIG), fault ride-through (FRT) capability, transient
simulation, voltage-compensation-type active superconducting fault current limiter (SFCL).
NOMENCLATURE
RE Renewable energy.
FRT Fault ride through.
Manuscript received August 29, 2014; revised December 29, 2014;
accepted February 20, 2015. Date of current version June 2, 2015.
This work was supported in part by the Fundamental Research
Funds for the Central Universities under Grant 2042014kf0011, in part
by the Wuhan Planning Projects of Science and Technology under
Grant 2013072304010827 and Grant 2013072304020824, and in part
by the Natural Science Foundation of Hubei Province, China, under
Grant 2014CFB706.
L. Chen, F. Zheng, C. Deng, and Z. Li are with the School of
Electrical Engineering, Wuhan University, Wuhan 430072, China (e-mail:
stclchen1982@163.com; 190991761@qq.com; deng_ch@whu.edu.cn;
1103080319@qq.com).
F. Guo is with the China Energy Engineering Group, Department of
Substation, Guang Dong Electric Power Design Institute, Guangzhou 510635,
China (e-mail: 34268545@qq.com).
Associate Editor managing this paper’s review: Houshang Karimi.
Color versions of one or more of the figures in this paper are available
online at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/CJECE.2015.2406665
RSC Rotor side converter.
DFIG Doubly fed induction generator.
SFCL Superconducting fault current limiter.
SMES Superconducting magnetic energy storage.
SPWM Sinusoidal pulsewidth modulation.
STATCOM Static synchronous compensator.
Symbols
i Current [A].
I Effective phase current [A].
k Coupling factor [-].
L Inductance [H].
M Mutual inductance [H].
R Resistance [ ].
t Time [s].
T Time constant [s].
v Voltage [V].
0840-8688 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 133
V Effective phase voltage [V].
X Reactance [ ].
Z Impedance [ ].
ω Angular velocity [rad/s].
ψ, Flux [T].
Subscripts
A Phase A.
B Phase B.
C Phase C.
s1 Superconducting transformer’s primary coil.
s2 Superconducting transformer’s secondary coil.
st Superconducting transformer.
f Filter.
g Grid.
co Converter’s output.
r Rotor.
s Stator.
σ Leakage.
I. INTRODUCTION
THE smart grid is an electrical system that uses informa-
tion, two-way, cyber-secure communication technologies,
and computational intelligence in an integrated fashion across
the entire spectrum of the energy system from the generation
to the end points of consumption of the electricity [1]–[3].
Although there may be varying definitions to suit different
countries’ specific features, the overall goal of building the
smart grid is to improve the efficiency, reliability, economics,
and sustainability of the production and distribution of
electricity. Concerning the smart grid’s technical framework,
RE sources and superconducting power devices are two types
of crucial components. For the former, RE sources that
have vast potential to reduce dependence on fossil fuels and
their high penetrations into power distribution systems have
attracted increasing attention around the world [4]. As for the
latter, superconducting power devices can help to enhance an
electric system’s operating performance from several aspects,
such as current limitation and improvement of transient stabil-
ity as well as power quality [5]–[7]. In a sense, an integrated
application of RE generation and superconducting power may
bring more promising effects [8]–[11].
Currently, with regard to the rapid expansion of wind
power generation, DFIG attracts a wide public interest and
offers many advantages, such as reduced inverter and output
filter costs, due to low rotor- and grid-side power conversion
ratings (25%–30%) [12], [13]. However, DFIG suffers
from high sensitivity to grid disturbances, especially grid
faults [14]–[16]. To guarantee the FRT capability of DFIG,
different kinds of measures have been suggested [17]–[26].
Among the solutions, not only superconducting power
devices but also conventional apparatuses and advanced
control strategies are considered. A brief comparison of them
is given as follows.
The advanced control strategies can be regarded as the
software solutions, but they will not provide the FRT capability
under severe grid fault conditions, since the RSC cannot
supply the voltage as high as rotor back electromotive force
voltage because of dc-link voltage limitation [17], [18].
Fig. 1. Structure of the voltage-compensation-type active SFCL.
The crowbar circuit is the most popular hardware solution
to improve the FRT capability. This solution can protect the
RSC from overcurrent. However, it does not support the utility
to resume normal operation and is not allowed by the grid
connection requirement [19], [20]. STATCOM can be used
for dynamic power compensation, but it can only control the
reactive power and minimize the voltage fluctuation after fault
occurrence [21], [22]. Applying an SMES can stabilize the
dc-link voltage and provide a voltage protection to the RSC,
but it cannot suppress the overcurrent and electromagnetic
torque oscillations [23], [24]. In contrast, using an SFCL can
restrict the fault current, prevent the disruption of protective
equipment, and improve the dynamic performance of DFIG
more directly [25], [26].
Actually, our research group has proposed a voltage-
compensation-type active SFCL adopting high-temperature
superconductor (HTS) materials and power electronic
elements [27]. After the introduction of modern control theory,
the active SFCL offers a variety of operation modes and has
the abilities of controlling fault current and compensating
voltage sag within the expected ranges [28]–[31]. Since the
active SFCL has higher controllability and flexibility than a
common resistive- or inductive-type SFCL, its application in
enhancing the FRT capability of DFIG may play better results.
This paper is organized as follows. Section II introduces the
active SFCL’s structural principle as well as control strategy,
and discusses the influence mechanism of the active SFCL
to the FRT capacity of DFIG. Section III is devoted to
the modeling and simulation of a DFIG-based wind turbine
integrated with the active SFCL, where a comparison between
the active SFCL and an inductive SFCL is also performed.
Finally, the conclusion is drawn in Section IV.
II. THEORETICAL ANALYSIS
A. Structural Principle of the Active SFCL
Fig. 1 shows the topological structure of the voltage-
compensation-type active SFCL, which is composed of three
134 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
air-core superconducting transformers and a three-phase
four-wire converter. Ls1 and Ls2 are the winding self-
inductances, and Mst is the mutual inductance. Z1 is
the circuit impedance, and Z2 is the load impedance.
Cdc1 and Cdc2 are the split dc-link capacitors. L f and C f are
used to filter the high-order harmonics caused by the converter.
In normal (no fault) state, the injected current in the
secondary winding of each phase superconducting transformer
will be controlled to keep a certain value, where the magnetic
field in the air-core can be compensated to zero, so that the
active SFCL will not affect the main circuit. When a short-
circuit fault is detected, the injected current corresponding
to the faulted phase will be timely adjusted in amplitude or
phase angle, so as to control the series compensation voltage
and suppress the fault current.
It should be noted that the short-circuit fault can be
mainly classified as four types: 1) the single-phase grounded
fault; 2) double-phase ungrounded fault (phase-to-phase);
3) double-phase grounded fault; and 4) three-phase fault.
In accordance with the presented current-limiting principle,
the injected currents (is2A, is2B, and is2C) will be unbalanced
in the case that an unsymmetrical fault occurs. Therefore,
a three-phase four-wire voltage source inverter (VSI)
converter, which has split dc-link capacitors, a few electronic
devices, and great function with unbalanced load, serves as a
critical component included in the active SFCL.
Herein, taking the A-phase circuit for example to expound
the active SFCL’s operation mode, the mathematical relation
between the grid-side source voltage VgA and the main current
Is1A can be expressed as
˙VgA = ˙Is1A(Z1 + Z2) + jωLs1 ˙Is1A − jωMst ˙Is2A. (1)
The current is2A is controlled to make jωLs1 ˙Is1A −
jωMst ˙Is2A = 0, and the A-phase superconducting trans-
former’s primary voltage vs1A is regulated to zero. Thus, the
active SFCL’s equivalent impedance in series with the A-phase
circuit is zero, and is2A can be set as
˙Is2A = ˙Is1A Ls1/Mst =
˙Is1A
√
Ls1/Ls2
k
=
˙VgA
√
Ls1/Ls2
(Z1 + Z2)k
(2)
where k is the coupling coefficient and k = Mst/(Ls1Ls2)1/2.
When the node U is grounded and a single-phase fault
happens, the line current will rise from is1A to is1A−F, and
the primary and secondary voltages of the A-phase super-
conducting transformer will increase to vs1A−F and vs2A−F ,
respectively. Then, the following equations can be obtained:
˙Is1A−F =
˙VgA + jωMst ˙Is2A
Z1 + jωLs1
(3)
˙Vs1A−F = jωLs1 ˙Is1A−F − jωMst ˙Is2A
=
˙VgA( jωLs1) − ˙Is2A Z1( jωMst)
Z1 + jωLs1
(4)
˙Vs2A−F = jωLs2 ˙Is2A − jωMst ˙Is1A−F
= jωLs2 ˙Is2A − jωMst
˙VgA + jωMst ˙Is2A
Z1 + jωLs1
. (5)
From (4), changing is2A can play a role in regulating the
primary voltage, and further the current-limiting impedance
ZSFCL can be controlled in
ZSFCL =
˙Vs1A−F ˙Is1A−F = jωLs1−
jωMst ˙Is2A(Z1+ jωLs1)
˙VgA + jωMst ˙Is2A
.
(6)
According to the difference in the regulating objectives
of is2A, there are three operation modes.
1) Making is2A remain the original state, and
ZSFCL−1 = Z1( jωLs1)/(Z1 + Z2 + jωLs1).
2) Controlling is2A to zero, and ZSFCL−2 = jωLs1.
3) Regulating the phase angle of is2A to make the angle
difference between ˙VgA and jωMst ˙Is2A be 180°. Setting
jωMst ˙Is2A = −c ˙VgA, and ZSFCL−3 = cZ1/(1 − c) +
jωLs1/(1 − c).
As the other crucial component adopted in the active SFCL,
the air-core superconducting transformer has many advantages,
such as the absence of iron losses and magnetic saturation,
and it has more possibility of reduction in size, weight, and
harmonic than the conventional iron-core superconducting
transformer [32], [33]. On the other hand, the air-core-type
coupling coils might serve as a shunt reactor with large
magnetizing current, and it can be applied in an inductive
pulsed-power supply to decrease energy loss and improve
transfer efficiency [34], [35]. One point should be noted
particularly, and it is essential that lack of flux saturation in the
air-core can help to ensure the current-limiting impedance’s
linearity and reduce the possible high-order harmonics.
B. Control Strategy for the Converter Included in the SFCL
To make the active SFCL have higher controllability and
flexibility, this section suggests a suitable control strategy for
the converter. Assuming that the switching devices are ideal
and Cdc1 = Cdc2, the following mathematical equations can
be derived (R denotes the equivalent resistance of L f ):
⎧
⎪⎪⎪⎪⎪⎨
⎪⎪⎪⎪⎪⎩
L f
dicoA
dt
+ RicoA = −vs2A + vcoA
L f
dicoB
dt
+ RicoB = −vs2B + vcoB
L f
dicoC
dt
+ RicoC = −vs2C + vcoC
(7)
⎧
⎪⎪⎪⎪⎨
⎪⎪⎪⎪⎩
C f
dvs2A
dt
= icoA − is2A
C f
dvs2B
dt
= icoB − is2B
C f
dvs2C
dt
= icoC − is2C.
(8)
Furthermore, the mathematical equations in dq0 reference
frame can be obtained
⎧
⎪⎪⎪⎪⎪⎨
⎪⎪⎪⎪⎪⎩
L f
dicod
dt
= −Ricod + ωL f icoq − us2d + ucod
L f
dicoq
dt
= −Ricoq − ωL f icod − us2q + ucoq
L f
dico0
dt
= −Rico0 − us20 + uco0
(9)
⎧
⎪⎪⎪⎪⎨
⎪⎪⎪⎪⎩
C f
dvs2d
dt
= ωC f vs2q + icod − is2d
C f
dvs2q
dt
= −ωC f vs2d + icoq − is2q
C f
dvs20
dt
= ico0 − is20.
(10)
CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 135
Fig. 2. Block diagram of the control strategy designed for the three-phase
four-wire VSI converter included in the active SFCL.
After dq0 transformation, the control objects (vs2d and vs2q)
can be determined, and the control system designed for the
three-phase four-wire converter should be consisting of two
subsystems: 1) coupling dq-axis system that needs to be
decoupled and 2) 0-axis system.
Since the injected currents (is2A, is2B, and is2C) will be
unbalanced under unsymmetrical fault conditions, not only
the sum of Vdc1 and Vdc2 should be essentially controlled
to maintain a constant value, but also the voltage balance
control for the split dc-link capacitors (Cdc1 and Cdc2) should
be considered [36]. The balance equation is arranged in
⎧
⎨
⎩
vdc1 + vdc2 = vdc
Cdc2
dvdc2
dt
− Cdc1
dvdc1
dt
= 3 is20 + C f
dus20
dt
.
(11)
In the light of (9)–(11), Fig. 2 shows the control block
diagram of the converter. From this figure, our research group
presents a double-loop control strategy, including an outer
loop for voltage control and an inner loop for current control.
After a series of computations from the referenced signals, the
calculated voltages (vcod, vcoq, and vco0) will be transferred to
the module of SPWM, and the pulse signals will be produced
to drive the converter.
C. Influence Mechanism of the Suggested SFCL
to the FRT Improvement of DFIG
Fig. 3 shows the schematic of a DFIG-based wind
turbine integrated with the active SFCL. Herein, the DFIG
is connected to the electric power grid through a step-up
transformer and the active SFCL is introduced before the
transformer. Supposing that a three-phase short-circuit
happens, the SFCL’s influence on the DFIG is conducted.
Based on the equivalent circuit of a DFIG for transient
analysis [37], the following equations can be obtained:
−→
Vs = Rs
−→
is + d
−→
ψs/dt + jωs
−→
ψs (12)
−→
Vr = Rr
−→
ir + d
−→
ψr /dt + j(ωs − ωr )
−→
ψr (13)
−→
ψs = Ls
−→
is + Lm
−→
ir (14)
−→
ψr = Lm
−→
is + Lr
−→
ir (15)
Fig. 3. Schematic of a DFIG-based wind turbine with the active SFCL.
where V, i, ψ, R, and L are, respectively, the voltage, current,
flux, resistance, and inductance of the DFIG, subscripts s and r
represent, respectively, the DFIG’s stator and rotor windings.
Besides, knowing that Ls = Lsσ + Lm and Lr = Lrσ + Lm,
Lsσ /Lrσ is the leakage inductance.
According to (14) and (15), the currents flowing through
the DFIG’s stator and rotor windings can be expressed as
−→
is =
−→
ψs/Ls − kr
−→
ψr /Ls (16)
−→
ir = −ks
−→
ψs/Lr +
−→
ψr /Lr (17)
where Ls = Ls − L2
m/Lr , Lr = Lr − L2
m/Ls, and ks, kr are,
respectively, signified as ks = Lm/Ls, kr = Lm/Lr .
In the fault state, a series of transient electromagnetic
changes will be caused, and the changes of stator and rotor
fluxes are critical. Due to the power transformer, the DFIG’s
terminal voltage will not directly drop to zero, and after a
stage of concussion, the terminal voltage will tend to a steady
value.
Consequently, a voltage-drop coefficient A1 (0 ≤ A1 ≤ 1)
is introduced, and the terminal voltage is described as
−→
Vs = (1 − A1)Vsejωst(t ≥ t0). According to the constant-
linkage theorem [38], [39], the stator flux can be indicated as
−→
ψs =
⎧
⎪⎪⎪⎪⎨
⎪⎪⎪⎪⎩
LsVs
Rs + jωs Ls
ejωst
+
Rs Ls Ir
Rs + j ωs Ls
ejωst
t < t0
Ls(1 − A1)Vs
Rs + jωs Ls
ejωst
+
Rs Ls Ir
Rs + j ωs Ls
ejωst
+
−→
ψs0e−Rs t/Ls t ≥ t0
(18)
where
−→
ψs0 = Ls A1Vsejωst0 /(Rs + jωs Ls). In a similar
way, the rotor flux is
−→
ψr = (ks LsVs)/(Rs + jωs Ls)ejωst +
Ir Lr ejωst0 e−Rr t/Lr t ≥ t0.
By neglecting the stator resistance and substituting the stator
and rotor fluxes in (16) and (17), the fault currents flowing
through the stator and rotor windings can be expressed as
−→
is =
(1 − A1)Vs
jωs
ejωst
+
−→
ψs0e−Rs t/Ls
/Ls
− kr
ksVs
jωs
ejωst
+ Ir Lr ejωst0
e−Rr t/Lr
/Ls (19)
−→
ir = −ks
(1 − A1)Vs
jωs
ejωst
+
−→
ψs0e−Rst/Ls
/Lr
+
ksVs
jωs
ejωst
+ Ir Lr ejωst0 e−Rr t/Lr
/Lr . (20)
136 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
In the case that the active SFCL is applied, the contribution
of introducing the current-limiting impedance ZSFCL is to
improve Ls and meanwhile to reduce ks. Taking mode 2 for
example, the current-limiting inductance Ls1 will be added
into the main circuit, and the expressions of Ls and ks will be
changed into Ls1 + Ls − L2
m/Lr and Lm/(Ls + Ls1), respec-
tively. From (19) and (20), the fault currents flowing through
the DFIG’s stator and rotor sides can be both suppressed.
Regarding the voltage compensation from the active SFCL,
the desired voltage boosting level should be considered.
In terms of the presented three operation modes, the
performance behavior under mode 3 is the best, but the
control philosophy under mode 1 is easy to implement
(without additional controls for the injected current’s initial
amplitude or phase angle). To make the active SFCL carry
out a mode switching smoothly, a specific criterion related
to voltage dip may be used. For instance, mode 1 can play
the role in response to grid faults that produce a voltage
dip of 30% and low, and in case that the dip is relatively
larger, mode 1 will be replaced by mode 2 or mode 3.
It should be noted that if the voltage dip is 100%, the active
SFCL can undertake part compensation, which is determined
by the air-core transformer’s design parameters and the
VSI converter’s rated capacity, and the remaining voltage
compensation can be provided through the DFIG converters as
injected reactive current to fulfill the grid code requirements.
D. Technical Discussions on the Active SFCL’s Cost
In view of that cost is an important factor affecting a
superconducting power device’s practical application, some
technical issues related to the active SFCL’s cost are discussed
in this section.
According to the previous studies of technical and economic
impacts on a power system by introducing a SFCL [40]–[42],
the annual cost of a SFCL is commonly composed of invest-
ment cost, maintenance cost, refrigeration cost, and so on.
Applying a SFCL may also achieve prospective benefits and
operation cost savings, in the case of considering the factors
such as increase of system reliability and reduction of expected
fault current. With regard to a SFCL’s installation site, the
most promising locations are found in distribution network,
low voltage (400 V), and industrial systems [40]. From the
reports in [43], the comparison between a dynamic voltage
restorer and a hybrid-type SFCL for the FRT improvement
is conducted, and it is stated that, when a SFCL is applied
for individual wind generator, the cost is expensive and
unacceptable. But in our opinion, regarding the FRT capacity
enhancement of a wind farm, including multiple generators,
the technoeconomic feasibility of using a SFCL may be
preferably demonstrated.
On the basis of the annual cost method, our research group
roughly evaluates the cost of the active SFCL at a 35-kV
power distribution network [42], where a large wind farm
(50-MW capacity) is accessed. During the calculation, the
second-generation HTS is used, and the calculation data come
from the voltage-compensation-type active SFCL developed
by Huazhong University of Science and Technology, China.
TABLE I
PARAMETERS FOR ECONOMICAL EVALUATION
The active SFCL’s annual cost cSFCL can be computed in [44]
cSFCL = ci + cm + co − ce (21)
where ci, cm, co, and ce are, respectively, the annual invest-
ment cost, maintenance cost, operating cost (including loss
cost as well as refrigeration cost), and economical benefits.
Considering the reduction of expected fault current (lower
network losses), enhancement of power quality, delay of
system improvement, and lower dimensioning of installa-
tions and devices resulted from the active SFCL, ce can be
expressed as [45]
ce =
k2Tn Pn
r2
+
cn
(P/A, b, n)
−
cn
(P/A, b, n + n1)
+ k3Cb
(22)
where (P/A, i, n) is the annual present value factor; Tn and Pn
are, respectively, the annual operating time and the rated
power of the network; r is the factor obtained by the ratio
of maximum power to the rated power; n1 is the delay year
number; and k3 and Cb are, respectively, the ratios of the
reduced dimensioning of installations and devices to the initial
one, and the installation cost as well as engineering cost.
The main parameters for an economical evaluation are listed
in Table I. In combination with the formula calculating and the
conceptual design of the active SFCL in a power distribution
system [46], the total cost of a 35-kV class three-phase active
SFCL is ∼4049 k¥ ($650 k) that includes HTS materials
cost 790 k¥, cryogenic vessel cost 154 k¥, converter cost
3000 k¥, and so on. As a matter of fact, in terms of the
active SFCL’s application in enhancing the wind farm’s FRT
capacity, improving this mean’s economical efficiency will
be considerably beneficial to demonstrating the feasibility.
A practicable method of reducing the total cost is to optimize
the superconducting transformer’s winding structure and
coupling factor, and accordingly the compensation capacity
contributed by the three-phase four-wire converter can
be decreased. The detailed technoeconomic analysis and
optimization calculation will be carried out in the near future,
and the results will be reported in later articles. Section III
is devoted to investigating the active SFCL’s performance
behaviors by electromagnetic transient simulation.
CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 137
Fig. 4. Fault detection method applied to the simulation model for the active
SFCL’s operation mode switching.
TABLE II
MAIN SIMULATION PARAMETERS OF THE SYSTEM MODEL
III. SIMULATION STUDY
For quantitatively evaluating the active SFCL’s effects on the
DFIG’s FRT capability, the simulation model corresponding to
Fig. 3 is created through MATLAB software, where the fault
detection method is shown in Fig. 4. During the simulation,
current-limiting mode 1 and mode 3 are considered (the former
will be triggered automatically, and the latter will depend on
the fault detection). In addition, parts of simulation parameters
are expressed in Table II.
A. Symmetric Fault Simulation
In normal condition, the line current’s peak value
is ∼1.75 kA. Supposing that a three-phase grounded fault
happens at t = 1 s, and the fault duration/resistance is
0.4 s/0.1 , Figs. 5 and 6 show the operational characteristics
of the DFIG-based wind turbine without and with the active
SFCL (only mode 1 plays its role). From the figures, applying
the active SFCL can limit the first peak of the fault currents
(iAf, iBf, and iCf) to 2.62, 3.41, and 3.12 kA, respectively,
in contrast with 6.91, 9.26, and 6.59 kA without SFCL.
Fig. 5. Stator current waveform of the DFIG under the symmetric fault.
(a) Without SFCL. (b) With the active SFCL (mode 1).
Fig. 6. Stator voltage waveform of the DFIG under the symmetric fault.
(a) Without SFCL. (b) With the active SFCL (mode 1).
The reduction rate of the expected fault currents will be about
62.1%, 63.2%, and 52.7%, respectively. It is observed that,
employing the active SFCL can also compensate the DFIG’s
terminal voltage to 60% of normal value. By contrast, the
terminal voltage will decrease to 7% of normal value without
any additional current-limiting or voltage-compensation
devices.
Furthermore, owing to the mode switching driven by the
fault detection, mode 3 will smoothly replace mode 1 to
improve the active SFCL’s performance, and the A-phase
circuit is selected to state the wind power integrated system’s
transient characteristics. Fig. 7(a) reflects the active SFCL’s
effects on the line fault current (the DFIG’s stator current)
under mode 3, and Fig. 7(b) shows the injected current in the
A-phase superconducting transformer’s secondary winding.
It is clear that the mode switching is effectively implemented.
As mode 3 appears and plays its role, the first peak of the
A-phase fault current can be limited to 1.95 kA, and the
reduction rate of the expected fault current is ∼71.8%.
138 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
Fig. 7. Currents flowing through the A-phase superconducting transformer
under the symmetric fault. (a) Primary winding. (b) Secondary winding.
Fig. 8. Effects of the fault resistance on the DFIG’s terminal-voltage under
the symmetric fault. (a) Without SFCL. (b) With the active SFCL (mode 3).
Since the fault resistance may directly affect the DFIG’s
transient behaviors, relevant simulation analysis is performed
and denoted in Fig. 8. When the fault resistance is,
respectively, set as 1, 5, 10, and 15 , the DFIG’s terminal-
voltage without SFCL will be down to 12.5%, 48.3%, 68.8%,
and 79.2% of normal value, respectively. In the case that the
active SFCL operates under its current-limiting mode 3, the
DFIG’s terminal-voltage can be, respectively, compensated to
62.1%, 86.7%, 95.2%, and 97.4% of normal value.
Note that, to show a comparison between the active SFCL
and other methods for improving the DFIG’s FRT capacity,
a flux-coupling-type SFCL (an inductive SFCL) is introduced
and built in MATLAB [47], [48], and its inductance
parameters are similar to the imitated air-core superconducting
transformer. Accordingly, the two different SFCLs’ effects on
the DFIG’s operating characteristics are both assessed and
stated as follows.
The evaluation of rms voltage in pu at the terminals of the
wind turbine generator is shown in Fig. 9, where the fault
Fig. 9. Influence of the two different SFCLs on the DFIG’s terminal-voltage
under the symmetric fault. (a) Active SFCL. (b) Inductive SFCL.
Fig. 10. Influence of the two different SFCLs on the DFIG’s power fluctuation
under the symmetric fault. (a) Active SFCL. (b) Inductive SFCL.
duration/resistance is 0.4 s/0.1 . It is recognized that the
DFIG’s terminal voltage during the fault can be maintained at
78% of normal value. As the highest minimum voltage level
required worldwide is ∼0.25 pu [49], the introduction of the
active SFCL (mode 3) can well meet the demand for ensuring
the DFIG’s low-voltage ride-through capacity. Concerning the
inductive SFCL’s impacts on improving the DFIG’s terminal-
voltage, its contribution is between the active SFCL’s mode 1
and mode 3.
Increased current in the rotor circuit is very harmful to the
RSC, and the DFIG’s power fluctuation is closely related to
the wind power system’s stability. Hence, the DFIG’s power
fluctuation and rotor current are selected as the key indicators
to compare the two SFCLs’ performance behaviors, and the
detailed simulation results are shown in Figs. 10 and 11, where
the change of the rotor current is described. From the given
two figures, employing the active SFCL and the inductive
SFCL can both make the DFIG’s rotor current be limited
within a safety margin, and consequently, the probability of
CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 139
Fig. 11. Effects of the two different SFCLs on the DFIG’s rotor current
under the symmetric fault. (a) Active SFCL. (b) Inductive SFCL.
Fig. 12. Stator current waveform of the DFIG under the unsymmetrical fault.
(a) Without SFCL. (b) With the active SFCL (mode 3).
the DFIG being disconnected from the electric power grid
can be well reduced. It is also observed that, applying the
inductive SFCL can only restrain the DFIG’s power oscillation
amplitude to a certain extent, but it may not provide a more
positive effect on evacuating the surplus active power during a
fault incident. By comparison, the active SFCL’s contributions
include consuming the DFIG’s active power and decreasing the
output power oscillation, and thus the operational stability of
the wind power integrated system can be effectively enhanced.
B. Unsymmetrical Fault Simulation
In this section, the DFIG’s dynamic response characteristics
under an unsymmetrical fault are imitated. Supposing that a
phase-to-phase (B-phase and C-phase) fault happens at t = 1 s,
and the fault duration is 0.4 s, Figs. 12 and 13 show the DFIG’s
stator current and stator voltage behaviors under the fault,
where the active SFCL’s current-limiting mode 3 is applied.
Fig. 13. Stator voltage waveform of the DFIG under the unsymmetrical fault.
(a) Without SFCL. (b) With the active SFCL (mode 3).
Fig. 14. Effects of the active SFCL on the DFIG’s terminal-voltage under
the unsymmetrical fault. (a) B-phase voltage. (b) C-phase voltage.
As the aforementioned comparison between the active SFCL
and the inductive SFCL can describe the essential difference
between the two means, this section does not simulate the
inductive SFCL’s current-limiting characteristics.
In the case of installing the active SFCL, reduction of
the fault-phase currents and improvement of the terminal-
voltage can both be achieved. Aiming at the DFIG’s
B-phase and C-phase voltages, the evaluation of the rms
characteristics in pu is shown in Fig. 14. By observing the
characteristic curves at t = 1.3 s, the two phase voltages
will, respectively, drop to 70% and 24.3% of normal value
without SFCL. When the active SFCL’s mode 3 comes into
play and the transient impedance is added into each of the
fault-phase circuit, the DFIG’s B-phase and C-phase voltages
can be compensated to 94.1% and 87.2% of normal value,
respectively. Herein, it should be pointed out that, for dealing
140 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
Fig. 15. Effects of the active SFCL on the DFIG’s operational characteristics
under the unsymmetrical fault. (a) Power fluctuation. (b) Change of rotor
current.
with the unsymmetrical fault more efficiently (since the
unbalance between the two fault-phases is relatively obvious),
not only the angle of the current flowing through the
C-phase superconducting transformer’s secondary winding
will be adjusted, but also the amplitude will be properly
enlarged by the converter. As a result, the active SFCL can
act on the two fault phases more balancedly.
Concerning the DFIG’s power fluctuation and rotor fault
current under the unsymmetrical fault, the active SFCL’s
effects on them are indicated in Fig. 15. From this figure,
applying the active SFCL can availably reduce the DFIG’s
power fluctuation, and the inhibition rate is ∼32.1%.
Meanwhile, the increase of the circuit impedance will slightly
lengthen the duration of the fluctuation process. On the other
hand, the unsymmetrical fault will make some additional
ac and dc components be induced in the DFIG’s rotor
current. Introducing the active SFCL can also suppress
their amplitudes, and the maximum reduction ratio can be
up to 68.9%.
IV. CONCLUSION
In this paper, according to theory derivation, cost
evaluation, and simulation analysis, our research group
studies the application of a voltage-compensation-type active
SFCL for improving the FRT capability of DFIG-based
wind turbine. In addition, a brief comparison between the
active SFCL and a common inductive SFCL is conducted
to estimate the difference. From the results, the following
conclusions can be obtained.
1) Installing the active SFCL can effectively limit the fault
currents flowing through the DFIG’s stator and rotor
windings.
2) Applying the active SFCL can evidently compensate the
DFIG’s terminal-voltage and decrease its output power
fluctuation, which helps to strengthen the operational
stability of the wind power integrated system.
3) Employing the inductive SFCL can only restrain the
DFIG’s power oscillation amplitude, but it may not
provide a more promising effect on evacuating the
surplus active power during the grid fault.
Admittedly, concerning the proposed technical idea that is
used to enhance the DFIG’s transient performance, a number
of aspects should be enriched, such as optimization design and
technoeconomic analysis of the active SFCL, and protection
cooperation considered self-adaptive adjustment. Moreover,
for a wind farm, which may be consisting of hundreds of
wind turbines, the active SFCL should be installed for the
whole wind farm instead of individual wind turbines, so as to
reduce the cost as far as possible These research tasks will be
carried out in the near future.
REFERENCES
[1] V. C. Gungor et al., “Smart grid technologies: Communication tech-
nologies and standards,” IEEE Trans. Ind. Informat., vol. 7, no. 4,
pp. 529–539, Nov. 2011.
[2] G. W. Arnold, “Challenges and opportunities in smart grid: A position
article,” Proc. IEEE, vol. 99, no. 6, pp. 922–927, Jun. 2011.
[3] A. A. Moghaddam and A. R. Seifi, “Study of forecasting renewable
energies in smart grids using linear predictive filters and neural
networks,” IET. Renew. Power Generat., vol. 5, no. 6, pp. 470–480,
Nov. 2011.
[4] M. Hamzeh, H. Mokhtari, and H. Karimi, “A decentralized self-adjusting
control strategy for reactive power management in an islanded multi-bus
MV microgrid,” Can. J. Elect. Comput. Eng., vol. 36, no. 1, pp. 18–25,
Winter 2013.
[5] I. Ngamroo and S. Vachirasricirikul, “Coordinated control of opti-
mized SFCL and SMES for improvement of power system transient
stability,” IEEE Trans. Appl. Supercond., vol. 22, no. 3, Jun. 2012,
Art. ID 5600805.
[6] A. Morandi, “Fault current limiter: An enabler for increasing safety and
power quality of distribution networks,” IEEE Trans. Appl. Supercond.,
vol. 23, no. 6, Dec. 2013, Art. ID 5604608.
[7] Y. Xin et al., “Factory and field tests of a 220 kV/300 MVA statured
iron-core superconducting fault current limiter,” IEEE Trans. Appl.
Supercond., vol. 23, no. 3, Jun. 2013, Art. ID 5602305.
[8] J. W. Shim, Y. Cho, S.-J. Kim, S. W. Min, and K. Hur, “Synergistic
control of SMES and battery energy storage for enabling dispatchability
of renewable energy sources,” IEEE Trans. Appl. Supercond., vol. 23,
no. 3, Jun. 2013, Art. ID 5701205.
[9] R. Qu, Y. Liu, and J. Wang, “Review of superconducting generator
topologies for direct-drive wind turbines,” IEEE Trans. Appl. Supercond.,
vol. 23, no. 3, Jun. 2013, Art. ID 5201108.
[10] N. G. A. Hemdan and M. Kurrat, “Time series analysis of rural distri-
bution grids in the presence of HTS cables and intermittent renewable
resources,” IEEE Trans. Appl. Supercond., vol. 24, no. 5, Oct. 2014,
Art. ID 5400507.
[11] K. Zhang, C. Mao, J. Lu, D. Wang, X. Chen, and J. Zhang, “Optimal
control of state-of-charge of superconducting magnetic energy storage
for wind power system,” IET Renew. Power Generat., vol. 8, no. 1,
pp. 58–66, Jan. 2014.
[12] L. Yang, G. Y. Yang, Z. Xu, Z. Y. Dong, K. P. Wong, and X. Ma,
“Optimal controller design of a doubly-fed induction generator wind
turbine system for small signal stability enhancement,” IET Generat.,
Transmiss. Distrib., vol. 4, no. 5, pp. 579–597, May 2010.
[13] J. P. da Costa, H. Pinheiro, T. Degner, and G. Arnold, “Robust controller
for DFIGs of grid-connected wind turbines,” IEEE Trans. Ind. Electron.,
vol. 58, no. 9, pp. 4023–4038, Sep. 2011.
[14] M. El-Moursi, G. Joos, and C. Abbey, “A secondary voltage control
strategy for transmission level interconnection of wind generation,” IEEE
Trans. Power Electron., vol. 23, no. 3, pp. 1178–1190, May 2008.
[15] J. Lopez, E. Gubia, E. Olea, J. Ruiz, and L. Marroyo, “Ride through
of wind turbines with doubly fed induction generator under sym-
metrical voltage dips,” IEEE Trans. Ind. Electron., vol. 56, no. 10,
pp. 4246–4254, Oct. 2009.
[16] G. Pannell, D. J. Atkinson, and B. Zahawi, “Analytical study of grid-
fault response of wind turbine doubly fed induction generator,” IEEE
Trans. Energy Convers., vol. 25, no. 4, pp. 1081–1091, Dec. 2010.
CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 141
[17] H. Geng, C. Liu, and G. Yang, “LVRT capability of DFIG-based WECS
under asymmetrical grid fault condition,” IEEE Trans. Ind. Electron.,
vol. 60, no. 6, pp. 2495–2509, Jun. 2013.
[18] S. Xiao, G. Yang, H. Zhou, and H. Geng, “Analysis of the control limit
for rotor-side converter of doubly fed induction generator-based wind
energy conversion system under various voltage dips,” IET Renew. Power
Generat., vol. 7, no. 1, pp. 71–81, Feb. 2013.
[19] S. Tohidi, H. Oraee, M. R. Zolghadri, S. Shao, and P. Tavner, “Analysis
and enhancement of low-voltage ride-through capability of brushless
doubly fed induction generator,” IEEE Trans. Ind. Electron., vol. 60,
no. 3, pp. 1146–1155, Mar. 2013.
[20] J. Vidal, G. Abad, J. Arza, and S. Aurtenechea, “Single-phase
DC crowbar topologies for low voltage ride through fulfillment of high-
power doubly fed induction generator-based wind turbines,” IEEE Trans.
Energy Convers., vol. 28, no. 3, pp. 768–781, Sep. 2013.
[21] S. M. Muyeen, M. A. Mannan, M. H. Ali, R. Takahashi, T. Murata,
and J. Tamura, “Stabilization of wind turbine generator system
by STATCOM,” IEEJ Trans. Power Energy, vol. 126, no. 10,
pp. 1073–1082, Oct. 2006.
[22] H. Gaztanaga, I. Etxeberria-Otadui, D. Ocnasu, and S. Bacha, “Real-
time analysis of the transient response improvement of fixed-speed wind
farms by using a reduced-scale STATCOM prototype,” IEEE Trans.
Power Syst., vol. 22, no. 2, pp. 658–666, May 2007.
[23] J. Shi, Y. Tang, Y. Xia, L. Ren, and J. Li, “SMES based excitation
system for doubly-fed induction generator in wind power application,”
IEEE Trans. Appl. Supercond., vol. 21, no. 3, pp. 1105–1108, Jun. 2011.
[24] W. Guo, L. Xiao, and S. Dai, “Enhancing low-voltage ride-through
capability and smoothing output power of DFIG with a superconducting
fault-current limiter–magnetic energy storage system,” IEEE Trans.
Energy Convers., vol. 27, no. 2, pp. 277–295, Jun. 2012.
[25] M. E. Elshiekh, D. A. Mansour, and A. M. Azmy, “Improving fault ride-
through capability of DFIG-based wind turbine using superconducting
fault current limiter,” IEEE Trans. Appl. Supercond., vol. 23, no. 3,
Jun. 2013, Art. ID 5601204.
[26] W. Guo et al., “LVRT capability enhancement of DFIG with switch-
type fault current limiter,” IEEE Trans. Ind. Electron., vol. 62, no. 1,
pp. 332–342, Jan. 2015.
[27] L. Chen, Y. Tang, J. Shi, and Z. Sun, “Simulations and experimental
analyses of the active superconducting fault current limiter,” Phys. C,
Supercond., vol. 459, nos. 1–2, pp. 27–32, Aug. 2007.
[28] L. Chen et al., “Influence of a voltage compensation type active
superconducting fault current limiter on the transient stability of power
system,” Phys. C, Supercond., vol. 469, nos. 15–20, pp. 1760–1764,
Oct. 2009.
[29] L. Chen et al., “Effects of a voltage compensation type active super-
conducting fault current limiter on distance relay protection,” Phys. C,
Supercond., vol. 470, no. 20, pp. 1662–1665, Nov. 2010.
[30] J. Wang, L. Zhou, J. Shi, and Y. Tang, “Experimental investigation
of an active superconducting current controller,” IEEE Trans. Appl.
Supercond., vol. 21, no. 3, pp. 1258–1262, Jun. 2011.
[31] L. Chen, C. Deng, F. Guo, Y. Tang, J. Shi, and L. Ren, “Reducing the
fault current and overvoltage in a distribution system with distributed
generation units through an active type SFCL,” IEEE Trans. Appl.
Supercond., vol. 24, no. 3, Jun. 2014, Art. ID 5600305.
[32] H. Yamaguchi and T. Kataoka, “Stability analysis of air-core supercon-
ducting power transformer,” IEEE Trans. Appl. Supercond., vol. 7, no. 2,
pp. 1013–1016, Jun. 1997.
[33] H. Yamaguchi, T. Kataoka, H. Matsuoka, T. Mouri, S. Nishikata,
and Y. Sato, “Magnetic field and electromagnetic force analysis of
3-phase air-core superconducting power transformer,” IEEE Trans. Appl.
Supercond., vol. 11, no. 1, pp. 1490–1493, Mar. 2001.
[34] R. Wu, Y. Wang, Z. Yan, W. Luo, and Z. Gui, “Design and experimental
realization of a new pulsed power supply based on the energy transfer
between two capacitors and an HTS air-core pulsed transformer,” IEEE
Trans. Plasma Sci., vol. 41, no. 4, pp. 993–998, Apr. 2013.
[35] R. Wu, Y. Wang, Z. Yan, Z. He, and L. Wang, “Simulation and experi-
mental investigation of an inductive pulsed power supply based on the
head-to-tail series model of an HTS air-core pulsed transformer,” IEEE
Trans. Appl. Supercond., vol. 23, no. 4, Aug. 2013, Art. ID 5701305.
[36] X. Li, S. Duan, Y. Kang, and J. Chen, “Control strategies for series
converter of three-phase four-wire UPQC,” Autom. Electr. Power Syst.,
vol. 31, no. 6, pp. 57–60, Mar. 2007.
[37] J. Morren and S. W. H. de Haan, “Short-circuit current of wind turbines
with doubly fed induction generator,” IEEE Trans. Energy Convers.,
vol. 22, no. 1, pp. 174–180, Mar. 2007.
[38] J. Ouyang and X. Xiong, “Characteristics of short-circuit current of wind
turbine driven DFIG and its impacts on the grid-connected distribution
network,” Autom. Electr. Power Syst., vol. 34, no. 23, pp. 106–110 and
123, Dec. 2010.
[39] S. Alaraifi, A. Moawwad, M. S. El Moursi, and V. Khadkikar,
“Voltage booster schemes for fault ride-through enhancement of variable
speed wind turbines,” IEEE Trans. Sustain. Energy, vol. 4, no. 4,
pp. 1071–1081, Oct. 2013.
[40] M. Sjostrom and D. Politano, “Technical and economical impacts on
a power system by introducing an HTS FCL,” IEEE Trans. Appl.
Supercond., vol. 11, no. 1, pp. 2042–2045, Mar. 2001.
[41] J. Lee and S.-K. Joo, “Economic assessment method for superconducting
fault current limiter (SFCL) in fault current-constrained power system
operation,” IEEE Trans. Appl. Supercond., vol. 23, no. 3, Jun. 2013,
Art. ID 5601104.
[42] L. Ren et al., “Evaluation of three designs for a 35-kV class super-
conducting reactor,” IEEE Trans. Appl. Supercond., vol. 24, no. 4,
Aug. 2014, Art. ID 5400205.
[43] A. A. Hussein and M. H. Ali, “Comparison between DVR and
SFCL for fault ride through capability improvement of fixed-speed
wind generator,” in Proc. IEEE PES T&D Conf. Expo., Apr. 2014,
pp. 1–5.
[44] L. Ren et al., “Techno-economic evaluation of a novel flux-coupling type
superconducting fault current limiter,” IEEE Trans. Appl. Supercond.,
vol. 20, no. 3, pp. 1242–1245, Jun. 2010.
[45] W. Zhang, Theory, Method and Application of Techno-Economic Eval-
uation of Electric Power. Beijing, China: China Electric Power Press,
2004, ch. 5.
[46] L. Chen, Y. J. Tang, M. Song, J. Shi, and L. Ren, “Parameter design and
performance simulation of a 10 kV voltage compensation type active
superconducting fault current limiter,” Phys. C, Supercond., vol. 494,
pp. 349–354, Nov. 2013.
[47] L. Chen, Y. Tang, Z. Li, L. Ren, J. Shi, and S. Cheng, “Current
limiting characteristics of a novel flux-coupling type superconducting
fault current limiter,” IEEE Trans. Appl. Supercond., vol. 20, no. 3,
pp. 1143–1146, Jun. 2010.
[48] L. Chen, H. Pan, C. Deng, F. Zheng, Z. Li, and F. Guo, “Study on the
application of a flux-coupling type superconducting fault current limiter
for decreasing HVDC commutation failure,” Can. J. Elect. Comput.
Eng., to be published.
[49] M. Tsili and S. Papathanassiou, “A review of grid code technical
requirements for wind farms,” IET. Renew. Power Generat., vol. 3, no. 3,
pp. 308–332, Sep. 2009.
Lei Chen (M’12) was born in Jingzhou, China,
in 1982. He received the B.S. and Ph.D. degrees in
electrical engineering from the School of Electrical
and Electronic Engineering, Huazhong University
of Science and Technology (HUST), Hubei, China,
in 2004 and 2010, respectively.
He was with the Post-Doctoral Scientific Research
Workstation, Hubei Electric Power Company, Hubei,
from 2011 to 2013. Since 2013, he has been a
Teacher with the School of Electrical Engineering,
Wuhan University, Wuhan, China. He has authored
over 30 articles. His current research interests include power system real-time
simulation, smart grid, and superconducting power application.
Feng Zheng was born in Wenzhou, China, in 1983.
He received the B.S. degree in automation and the
M.S. degree in electric power system and automation
from the School of Electrical and Information, China
Three Gorges University, Yichang, China, in 2006
and 2009, respectively. He is currently pursuing the
Ph.D. degree in electric power system and automa-
tion with Wuhan University, Wuhan, China.
His current research interests include microgrid
and superconducting fault current limiter.
142 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
Changhong Deng was born in Hubei, China,
in 1963. She received the B.S. degree in electrical
engineering from China Three Gorges University,
Yichang, China, in 1982, and the M.S. and
Ph.D. degrees in electrical engineering from Wuhan
University, Wuhan, China, in 1989 and 2005,
respectively.
She has been a Teacher with the School of Elec-
trical Engineering, Wuhan University, since 2002.
She is currently a Professor and Ph.D. Supervisor.
She has authored over 50 articles. Her current
research interests include power system simulation, distributed generation,
and smart grid.
Zhe Li was born in Zhoukou, China, in 1989. He received the
B.S. and M.S. degrees in electrical engineering from the School of Electrical
Engineering, Wuhan University, Wuhan, China, in 2012 and 2014,
respectively.
His current research interests include microgrid and fault reconstruction.
Fang Guo was born in Jingzhou, China, in 1983. She received the
B.S. and Ph.D. degrees in electrical engineering from the School of Electrical
and Electronic Engineering, Huazhong University of Science and Technology,
Hubei, China, in 2004 and 2010, respectively.
She is currently with the Guang Dong Electric Power Design Institute,
Guangzhou, China. Her current research interests include superconducting
power application and energy storage technology.

More Related Content

What's hot

Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...IAEME Publication
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...IAES-IJPEDS
 
A hybrid algorithm for voltage stability enhancement of distribution systems
A hybrid algorithm for voltage stability enhancement of distribution systems A hybrid algorithm for voltage stability enhancement of distribution systems
A hybrid algorithm for voltage stability enhancement of distribution systems IJECEIAES
 
Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...IJECEIAES
 
The gravitational search algorithm for incorporating TCSC devices into the sy...
The gravitational search algorithm for incorporating TCSC devices into the sy...The gravitational search algorithm for incorporating TCSC devices into the sy...
The gravitational search algorithm for incorporating TCSC devices into the sy...IJECEIAES
 
Investigation of overvoltage on square, rectangular and L-shaped ground grid...
Investigation of overvoltage on square, rectangular and  L-shaped ground grid...Investigation of overvoltage on square, rectangular and  L-shaped ground grid...
Investigation of overvoltage on square, rectangular and L-shaped ground grid...IJECEIAES
 
Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...IJECEIAES
 
Improvement the voltage stability margin of Iraqi power system using the opti...
Improvement the voltage stability margin of Iraqi power system using the opti...Improvement the voltage stability margin of Iraqi power system using the opti...
Improvement the voltage stability margin of Iraqi power system using the opti...IJECEIAES
 
Implementation of a grid-tied emergency back-up power supply for medium and l...
Implementation of a grid-tied emergency back-up power supply for medium and l...Implementation of a grid-tied emergency back-up power supply for medium and l...
Implementation of a grid-tied emergency back-up power supply for medium and l...IJECEIAES
 
VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...
VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...
VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...Journal For Research
 
Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...
Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...
Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...IJECEIAES
 
Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...IAEME Publication
 
Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...IJECEIAES
 
Smart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric GridSmart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric GridPower System Operation
 
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...IDES Editor
 
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...IRJET Journal
 
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...IRJET Journal
 
IMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMS
IMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMSIMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMS
IMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMSSuganthi Thangaraj
 

What's hot (20)

Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
 
A hybrid algorithm for voltage stability enhancement of distribution systems
A hybrid algorithm for voltage stability enhancement of distribution systems A hybrid algorithm for voltage stability enhancement of distribution systems
A hybrid algorithm for voltage stability enhancement of distribution systems
 
Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...
 
The gravitational search algorithm for incorporating TCSC devices into the sy...
The gravitational search algorithm for incorporating TCSC devices into the sy...The gravitational search algorithm for incorporating TCSC devices into the sy...
The gravitational search algorithm for incorporating TCSC devices into the sy...
 
Investigation of overvoltage on square, rectangular and L-shaped ground grid...
Investigation of overvoltage on square, rectangular and  L-shaped ground grid...Investigation of overvoltage on square, rectangular and  L-shaped ground grid...
Investigation of overvoltage on square, rectangular and L-shaped ground grid...
 
Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...Coordinated planning in improving power quality considering the use of nonlin...
Coordinated planning in improving power quality considering the use of nonlin...
 
36 p vplant-modeling-gorgan
36 p vplant-modeling-gorgan36 p vplant-modeling-gorgan
36 p vplant-modeling-gorgan
 
Improvement the voltage stability margin of Iraqi power system using the opti...
Improvement the voltage stability margin of Iraqi power system using the opti...Improvement the voltage stability margin of Iraqi power system using the opti...
Improvement the voltage stability margin of Iraqi power system using the opti...
 
Implementation of a grid-tied emergency back-up power supply for medium and l...
Implementation of a grid-tied emergency back-up power supply for medium and l...Implementation of a grid-tied emergency back-up power supply for medium and l...
Implementation of a grid-tied emergency back-up power supply for medium and l...
 
VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...
VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...
VOLTAGE PROFILE IMPROVEMENT AND LINE LOSSES REDUCTION USING DG USING GSA AND ...
 
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
Multi-Objective Evolutionary Programming for Static VAR Compensator (SVC) in ...
 
Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...
Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...
Moth Flame Optimization Method for Unified Power Quality Conditioner Allocati...
 
Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...Ga based optimal facts controller for maximizing loadability with stability c...
Ga based optimal facts controller for maximizing loadability with stability c...
 
Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...Power system operation considering detailed modelling of the natural gas supp...
Power system operation considering detailed modelling of the natural gas supp...
 
Smart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric GridSmart Inverters and Their Role in the Modern Electric Grid
Smart Inverters and Their Role in the Modern Electric Grid
 
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...Artificial Intelligence Technique based Reactive Power Planning Incorporating...
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
 
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
IRJET- Optimal Performance of Mechanical Load Factor for the Solar Photovolta...
 
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
 
IMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMS
IMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMSIMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMS
IMPROVED SWARM INTELLIGENCE APPROACH TO MULTI OBJECTIVE ED PROBLEMS
 

Similar to 07116665

Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridPower Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridIJMTST Journal
 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...IJECEIAES
 
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...IRJET Journal
 
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...IJERD Editor
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3IAEME Publication
 
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET Journal
 
A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...
A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...
A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...IRJET Journal
 
Operation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RES
Operation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RESOperation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RES
Operation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RESIAES-IJPEDS
 
A high efficiency pv module integrated dc dc
A high efficiency pv module integrated dc dcA high efficiency pv module integrated dc dc
A high efficiency pv module integrated dc dcmarutipammar
 
Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...
Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...
Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...IRJET Journal
 
Fuzzy logic control of hybrid systems including renewable energy in microgrids
Fuzzy logic control of hybrid systems including renewable energy in microgrids Fuzzy logic control of hybrid systems including renewable energy in microgrids
Fuzzy logic control of hybrid systems including renewable energy in microgrids IJECEIAES
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadIAEME Publication
 
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET Journal
 
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...Dr. Amarjeet Singh
 
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power QualityA Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power QualityIRJET Journal
 

Similar to 07116665 (20)

Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...
 
IJET-V3I1P8
IJET-V3I1P8IJET-V3I1P8
IJET-V3I1P8
 
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for MicrogridPower Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
Power Quality Improvement with Multilevel Inverter Based IPQC for Microgrid
 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...
 
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
Power-Sharing of Parallel Inverters in Micro-Grids via Droop control and Virt...
 
Stability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faultsStability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faults
 
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3
 
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...IRJET-  	  High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
IRJET- High-Efficiency Three-Level Stacked-Neutral-Point-Clamped Grid-Tie...
 
A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...
A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...
A Review paper on Power Quality Improvement Techniques in a Grid Integrated S...
 
Operation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RES
Operation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RESOperation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RES
Operation and Control of Grid Connected Hybrid AC/DC Microgrid using Various RES
 
Pc3426502658
Pc3426502658Pc3426502658
Pc3426502658
 
A high efficiency pv module integrated dc dc
A high efficiency pv module integrated dc dcA high efficiency pv module integrated dc dc
A high efficiency pv module integrated dc dc
 
Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...
Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...
Simulation studies on developed Solar PV Array based Multipurpose EV Charger ...
 
Fuzzy logic control of hybrid systems including renewable energy in microgrids
Fuzzy logic control of hybrid systems including renewable energy in microgrids Fuzzy logic control of hybrid systems including renewable energy in microgrids
Fuzzy logic control of hybrid systems including renewable energy in microgrids
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable load
 
0178__Waseda__HCMUT
0178__Waseda__HCMUT0178__Waseda__HCMUT
0178__Waseda__HCMUT
 
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
 
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
 
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power QualityA Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
A Grid-Tied Solar Power System with Harmonic Filter to Enhance Power Quality
 

Recently uploaded

Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)dollysharma2066
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIkoyaldeepu123
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 

Recently uploaded (20)

Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AI
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

07116665

  • 1. 132 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015 Fault Ride-Through Capability Improvement of DFIG-Based Wind Turbine by Employing a Voltage-Compensation-Type Active SFCL Amélioration de la robustesse aux défaillances des tours éoliennes en utilisant le “DFIG” à travers une compensation de tension active Lei Chen, Member, IEEE, Feng Zheng, Changhong Deng, Zhe Li, and Fang Guo Abstract—Based on the considerations in creating a smart grid roadmap, an integrated application of renewable energy sources and superconducting power devices may bring more positive effects. This paper suggests a voltage-compensation-type active superconducting fault current limiter (SFCL) to enhance the fault ride-through capability of doubly fed induction generator (DFIG) for wind power generation. Since the active SFCL has higher controllability and flexibility than a common resistive- or inductive-type SFCL, its application may give better results. Related theory derivation, cost evaluation, and simulation analysis are conducted, and a comparison between the active SFCL and an inductive SFCL is performed. From the results, the active SFCL can limit the faulty currents flowing through the DFIG’s stator and rotor windings and compensate the generator terminal voltage. The inductive SFCL may not evacuate the surplus active power during the grid fault; however, the active SFCL can smooth the DFIG’s power fluctuation, and the stability of the wind power system can be well strengthened. Résumé—Dans l’objectif de mettre en place une feuille de route pour un réseau électrique intelligent, une application intégrée pour les sources d’énergies renouvelables et appareils électriques supraconducteurs peut avoir un impact positif. Ces travaux de recherche proposent une compensation de tension active pour limiter les défauts provenant des limiteurs de courants actifs et super conducteur (SFCL) afin d’améliorer la robustesse aux défaillances du générateur à induction à double alimentation (DFIG) pour la production d’énergie éolienne. Puisque le SFCL a une contrôlabilité et une flexibilité supérieures à un SFCL résistif ou inductif, son utilisation pourrait offrir de meilleurs résultats. D’après la théorie, les évaluations des coûts, et les simulations, des analysesont été proposées et une comparaison entre le SFCL actif et le SFCL inductif est présentée. D’après les résultats obtenus, le SFCL actif pourrait limiter les courants défectueux à travers les enroulements du stator et du rotor du DFIG et compenser la tension aux bornes du générateur. Dans certains cas, le SFCL inductif ne peut pas évacuer le surplus de puissance active lors d’un défaut du réseau. Toutefois, le SFCL actif peut lisser la fluctuation de puissance du DFIG pour améliorer la stabilité du réseau d’énergie éolienne. Index Terms—Doubly fed induction generator (DFIG), fault ride-through (FRT) capability, transient simulation, voltage-compensation-type active superconducting fault current limiter (SFCL). NOMENCLATURE RE Renewable energy. FRT Fault ride through. Manuscript received August 29, 2014; revised December 29, 2014; accepted February 20, 2015. Date of current version June 2, 2015. This work was supported in part by the Fundamental Research Funds for the Central Universities under Grant 2042014kf0011, in part by the Wuhan Planning Projects of Science and Technology under Grant 2013072304010827 and Grant 2013072304020824, and in part by the Natural Science Foundation of Hubei Province, China, under Grant 2014CFB706. L. Chen, F. Zheng, C. Deng, and Z. Li are with the School of Electrical Engineering, Wuhan University, Wuhan 430072, China (e-mail: stclchen1982@163.com; 190991761@qq.com; deng_ch@whu.edu.cn; 1103080319@qq.com). F. Guo is with the China Energy Engineering Group, Department of Substation, Guang Dong Electric Power Design Institute, Guangzhou 510635, China (e-mail: 34268545@qq.com). Associate Editor managing this paper’s review: Houshang Karimi. Color versions of one or more of the figures in this paper are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/CJECE.2015.2406665 RSC Rotor side converter. DFIG Doubly fed induction generator. SFCL Superconducting fault current limiter. SMES Superconducting magnetic energy storage. SPWM Sinusoidal pulsewidth modulation. STATCOM Static synchronous compensator. Symbols i Current [A]. I Effective phase current [A]. k Coupling factor [-]. L Inductance [H]. M Mutual inductance [H]. R Resistance [ ]. t Time [s]. T Time constant [s]. v Voltage [V]. 0840-8688 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
  • 2. CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 133 V Effective phase voltage [V]. X Reactance [ ]. Z Impedance [ ]. ω Angular velocity [rad/s]. ψ, Flux [T]. Subscripts A Phase A. B Phase B. C Phase C. s1 Superconducting transformer’s primary coil. s2 Superconducting transformer’s secondary coil. st Superconducting transformer. f Filter. g Grid. co Converter’s output. r Rotor. s Stator. σ Leakage. I. INTRODUCTION THE smart grid is an electrical system that uses informa- tion, two-way, cyber-secure communication technologies, and computational intelligence in an integrated fashion across the entire spectrum of the energy system from the generation to the end points of consumption of the electricity [1]–[3]. Although there may be varying definitions to suit different countries’ specific features, the overall goal of building the smart grid is to improve the efficiency, reliability, economics, and sustainability of the production and distribution of electricity. Concerning the smart grid’s technical framework, RE sources and superconducting power devices are two types of crucial components. For the former, RE sources that have vast potential to reduce dependence on fossil fuels and their high penetrations into power distribution systems have attracted increasing attention around the world [4]. As for the latter, superconducting power devices can help to enhance an electric system’s operating performance from several aspects, such as current limitation and improvement of transient stabil- ity as well as power quality [5]–[7]. In a sense, an integrated application of RE generation and superconducting power may bring more promising effects [8]–[11]. Currently, with regard to the rapid expansion of wind power generation, DFIG attracts a wide public interest and offers many advantages, such as reduced inverter and output filter costs, due to low rotor- and grid-side power conversion ratings (25%–30%) [12], [13]. However, DFIG suffers from high sensitivity to grid disturbances, especially grid faults [14]–[16]. To guarantee the FRT capability of DFIG, different kinds of measures have been suggested [17]–[26]. Among the solutions, not only superconducting power devices but also conventional apparatuses and advanced control strategies are considered. A brief comparison of them is given as follows. The advanced control strategies can be regarded as the software solutions, but they will not provide the FRT capability under severe grid fault conditions, since the RSC cannot supply the voltage as high as rotor back electromotive force voltage because of dc-link voltage limitation [17], [18]. Fig. 1. Structure of the voltage-compensation-type active SFCL. The crowbar circuit is the most popular hardware solution to improve the FRT capability. This solution can protect the RSC from overcurrent. However, it does not support the utility to resume normal operation and is not allowed by the grid connection requirement [19], [20]. STATCOM can be used for dynamic power compensation, but it can only control the reactive power and minimize the voltage fluctuation after fault occurrence [21], [22]. Applying an SMES can stabilize the dc-link voltage and provide a voltage protection to the RSC, but it cannot suppress the overcurrent and electromagnetic torque oscillations [23], [24]. In contrast, using an SFCL can restrict the fault current, prevent the disruption of protective equipment, and improve the dynamic performance of DFIG more directly [25], [26]. Actually, our research group has proposed a voltage- compensation-type active SFCL adopting high-temperature superconductor (HTS) materials and power electronic elements [27]. After the introduction of modern control theory, the active SFCL offers a variety of operation modes and has the abilities of controlling fault current and compensating voltage sag within the expected ranges [28]–[31]. Since the active SFCL has higher controllability and flexibility than a common resistive- or inductive-type SFCL, its application in enhancing the FRT capability of DFIG may play better results. This paper is organized as follows. Section II introduces the active SFCL’s structural principle as well as control strategy, and discusses the influence mechanism of the active SFCL to the FRT capacity of DFIG. Section III is devoted to the modeling and simulation of a DFIG-based wind turbine integrated with the active SFCL, where a comparison between the active SFCL and an inductive SFCL is also performed. Finally, the conclusion is drawn in Section IV. II. THEORETICAL ANALYSIS A. Structural Principle of the Active SFCL Fig. 1 shows the topological structure of the voltage- compensation-type active SFCL, which is composed of three
  • 3. 134 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015 air-core superconducting transformers and a three-phase four-wire converter. Ls1 and Ls2 are the winding self- inductances, and Mst is the mutual inductance. Z1 is the circuit impedance, and Z2 is the load impedance. Cdc1 and Cdc2 are the split dc-link capacitors. L f and C f are used to filter the high-order harmonics caused by the converter. In normal (no fault) state, the injected current in the secondary winding of each phase superconducting transformer will be controlled to keep a certain value, where the magnetic field in the air-core can be compensated to zero, so that the active SFCL will not affect the main circuit. When a short- circuit fault is detected, the injected current corresponding to the faulted phase will be timely adjusted in amplitude or phase angle, so as to control the series compensation voltage and suppress the fault current. It should be noted that the short-circuit fault can be mainly classified as four types: 1) the single-phase grounded fault; 2) double-phase ungrounded fault (phase-to-phase); 3) double-phase grounded fault; and 4) three-phase fault. In accordance with the presented current-limiting principle, the injected currents (is2A, is2B, and is2C) will be unbalanced in the case that an unsymmetrical fault occurs. Therefore, a three-phase four-wire voltage source inverter (VSI) converter, which has split dc-link capacitors, a few electronic devices, and great function with unbalanced load, serves as a critical component included in the active SFCL. Herein, taking the A-phase circuit for example to expound the active SFCL’s operation mode, the mathematical relation between the grid-side source voltage VgA and the main current Is1A can be expressed as ˙VgA = ˙Is1A(Z1 + Z2) + jωLs1 ˙Is1A − jωMst ˙Is2A. (1) The current is2A is controlled to make jωLs1 ˙Is1A − jωMst ˙Is2A = 0, and the A-phase superconducting trans- former’s primary voltage vs1A is regulated to zero. Thus, the active SFCL’s equivalent impedance in series with the A-phase circuit is zero, and is2A can be set as ˙Is2A = ˙Is1A Ls1/Mst = ˙Is1A √ Ls1/Ls2 k = ˙VgA √ Ls1/Ls2 (Z1 + Z2)k (2) where k is the coupling coefficient and k = Mst/(Ls1Ls2)1/2. When the node U is grounded and a single-phase fault happens, the line current will rise from is1A to is1A−F, and the primary and secondary voltages of the A-phase super- conducting transformer will increase to vs1A−F and vs2A−F , respectively. Then, the following equations can be obtained: ˙Is1A−F = ˙VgA + jωMst ˙Is2A Z1 + jωLs1 (3) ˙Vs1A−F = jωLs1 ˙Is1A−F − jωMst ˙Is2A = ˙VgA( jωLs1) − ˙Is2A Z1( jωMst) Z1 + jωLs1 (4) ˙Vs2A−F = jωLs2 ˙Is2A − jωMst ˙Is1A−F = jωLs2 ˙Is2A − jωMst ˙VgA + jωMst ˙Is2A Z1 + jωLs1 . (5) From (4), changing is2A can play a role in regulating the primary voltage, and further the current-limiting impedance ZSFCL can be controlled in ZSFCL = ˙Vs1A−F ˙Is1A−F = jωLs1− jωMst ˙Is2A(Z1+ jωLs1) ˙VgA + jωMst ˙Is2A . (6) According to the difference in the regulating objectives of is2A, there are three operation modes. 1) Making is2A remain the original state, and ZSFCL−1 = Z1( jωLs1)/(Z1 + Z2 + jωLs1). 2) Controlling is2A to zero, and ZSFCL−2 = jωLs1. 3) Regulating the phase angle of is2A to make the angle difference between ˙VgA and jωMst ˙Is2A be 180°. Setting jωMst ˙Is2A = −c ˙VgA, and ZSFCL−3 = cZ1/(1 − c) + jωLs1/(1 − c). As the other crucial component adopted in the active SFCL, the air-core superconducting transformer has many advantages, such as the absence of iron losses and magnetic saturation, and it has more possibility of reduction in size, weight, and harmonic than the conventional iron-core superconducting transformer [32], [33]. On the other hand, the air-core-type coupling coils might serve as a shunt reactor with large magnetizing current, and it can be applied in an inductive pulsed-power supply to decrease energy loss and improve transfer efficiency [34], [35]. One point should be noted particularly, and it is essential that lack of flux saturation in the air-core can help to ensure the current-limiting impedance’s linearity and reduce the possible high-order harmonics. B. Control Strategy for the Converter Included in the SFCL To make the active SFCL have higher controllability and flexibility, this section suggests a suitable control strategy for the converter. Assuming that the switching devices are ideal and Cdc1 = Cdc2, the following mathematical equations can be derived (R denotes the equivalent resistance of L f ): ⎧ ⎪⎪⎪⎪⎪⎨ ⎪⎪⎪⎪⎪⎩ L f dicoA dt + RicoA = −vs2A + vcoA L f dicoB dt + RicoB = −vs2B + vcoB L f dicoC dt + RicoC = −vs2C + vcoC (7) ⎧ ⎪⎪⎪⎪⎨ ⎪⎪⎪⎪⎩ C f dvs2A dt = icoA − is2A C f dvs2B dt = icoB − is2B C f dvs2C dt = icoC − is2C. (8) Furthermore, the mathematical equations in dq0 reference frame can be obtained ⎧ ⎪⎪⎪⎪⎪⎨ ⎪⎪⎪⎪⎪⎩ L f dicod dt = −Ricod + ωL f icoq − us2d + ucod L f dicoq dt = −Ricoq − ωL f icod − us2q + ucoq L f dico0 dt = −Rico0 − us20 + uco0 (9) ⎧ ⎪⎪⎪⎪⎨ ⎪⎪⎪⎪⎩ C f dvs2d dt = ωC f vs2q + icod − is2d C f dvs2q dt = −ωC f vs2d + icoq − is2q C f dvs20 dt = ico0 − is20. (10)
  • 4. CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 135 Fig. 2. Block diagram of the control strategy designed for the three-phase four-wire VSI converter included in the active SFCL. After dq0 transformation, the control objects (vs2d and vs2q) can be determined, and the control system designed for the three-phase four-wire converter should be consisting of two subsystems: 1) coupling dq-axis system that needs to be decoupled and 2) 0-axis system. Since the injected currents (is2A, is2B, and is2C) will be unbalanced under unsymmetrical fault conditions, not only the sum of Vdc1 and Vdc2 should be essentially controlled to maintain a constant value, but also the voltage balance control for the split dc-link capacitors (Cdc1 and Cdc2) should be considered [36]. The balance equation is arranged in ⎧ ⎨ ⎩ vdc1 + vdc2 = vdc Cdc2 dvdc2 dt − Cdc1 dvdc1 dt = 3 is20 + C f dus20 dt . (11) In the light of (9)–(11), Fig. 2 shows the control block diagram of the converter. From this figure, our research group presents a double-loop control strategy, including an outer loop for voltage control and an inner loop for current control. After a series of computations from the referenced signals, the calculated voltages (vcod, vcoq, and vco0) will be transferred to the module of SPWM, and the pulse signals will be produced to drive the converter. C. Influence Mechanism of the Suggested SFCL to the FRT Improvement of DFIG Fig. 3 shows the schematic of a DFIG-based wind turbine integrated with the active SFCL. Herein, the DFIG is connected to the electric power grid through a step-up transformer and the active SFCL is introduced before the transformer. Supposing that a three-phase short-circuit happens, the SFCL’s influence on the DFIG is conducted. Based on the equivalent circuit of a DFIG for transient analysis [37], the following equations can be obtained: −→ Vs = Rs −→ is + d −→ ψs/dt + jωs −→ ψs (12) −→ Vr = Rr −→ ir + d −→ ψr /dt + j(ωs − ωr ) −→ ψr (13) −→ ψs = Ls −→ is + Lm −→ ir (14) −→ ψr = Lm −→ is + Lr −→ ir (15) Fig. 3. Schematic of a DFIG-based wind turbine with the active SFCL. where V, i, ψ, R, and L are, respectively, the voltage, current, flux, resistance, and inductance of the DFIG, subscripts s and r represent, respectively, the DFIG’s stator and rotor windings. Besides, knowing that Ls = Lsσ + Lm and Lr = Lrσ + Lm, Lsσ /Lrσ is the leakage inductance. According to (14) and (15), the currents flowing through the DFIG’s stator and rotor windings can be expressed as −→ is = −→ ψs/Ls − kr −→ ψr /Ls (16) −→ ir = −ks −→ ψs/Lr + −→ ψr /Lr (17) where Ls = Ls − L2 m/Lr , Lr = Lr − L2 m/Ls, and ks, kr are, respectively, signified as ks = Lm/Ls, kr = Lm/Lr . In the fault state, a series of transient electromagnetic changes will be caused, and the changes of stator and rotor fluxes are critical. Due to the power transformer, the DFIG’s terminal voltage will not directly drop to zero, and after a stage of concussion, the terminal voltage will tend to a steady value. Consequently, a voltage-drop coefficient A1 (0 ≤ A1 ≤ 1) is introduced, and the terminal voltage is described as −→ Vs = (1 − A1)Vsejωst(t ≥ t0). According to the constant- linkage theorem [38], [39], the stator flux can be indicated as −→ ψs = ⎧ ⎪⎪⎪⎪⎨ ⎪⎪⎪⎪⎩ LsVs Rs + jωs Ls ejωst + Rs Ls Ir Rs + j ωs Ls ejωst t < t0 Ls(1 − A1)Vs Rs + jωs Ls ejωst + Rs Ls Ir Rs + j ωs Ls ejωst + −→ ψs0e−Rs t/Ls t ≥ t0 (18) where −→ ψs0 = Ls A1Vsejωst0 /(Rs + jωs Ls). In a similar way, the rotor flux is −→ ψr = (ks LsVs)/(Rs + jωs Ls)ejωst + Ir Lr ejωst0 e−Rr t/Lr t ≥ t0. By neglecting the stator resistance and substituting the stator and rotor fluxes in (16) and (17), the fault currents flowing through the stator and rotor windings can be expressed as −→ is = (1 − A1)Vs jωs ejωst + −→ ψs0e−Rs t/Ls /Ls − kr ksVs jωs ejωst + Ir Lr ejωst0 e−Rr t/Lr /Ls (19) −→ ir = −ks (1 − A1)Vs jωs ejωst + −→ ψs0e−Rst/Ls /Lr + ksVs jωs ejωst + Ir Lr ejωst0 e−Rr t/Lr /Lr . (20)
  • 5. 136 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015 In the case that the active SFCL is applied, the contribution of introducing the current-limiting impedance ZSFCL is to improve Ls and meanwhile to reduce ks. Taking mode 2 for example, the current-limiting inductance Ls1 will be added into the main circuit, and the expressions of Ls and ks will be changed into Ls1 + Ls − L2 m/Lr and Lm/(Ls + Ls1), respec- tively. From (19) and (20), the fault currents flowing through the DFIG’s stator and rotor sides can be both suppressed. Regarding the voltage compensation from the active SFCL, the desired voltage boosting level should be considered. In terms of the presented three operation modes, the performance behavior under mode 3 is the best, but the control philosophy under mode 1 is easy to implement (without additional controls for the injected current’s initial amplitude or phase angle). To make the active SFCL carry out a mode switching smoothly, a specific criterion related to voltage dip may be used. For instance, mode 1 can play the role in response to grid faults that produce a voltage dip of 30% and low, and in case that the dip is relatively larger, mode 1 will be replaced by mode 2 or mode 3. It should be noted that if the voltage dip is 100%, the active SFCL can undertake part compensation, which is determined by the air-core transformer’s design parameters and the VSI converter’s rated capacity, and the remaining voltage compensation can be provided through the DFIG converters as injected reactive current to fulfill the grid code requirements. D. Technical Discussions on the Active SFCL’s Cost In view of that cost is an important factor affecting a superconducting power device’s practical application, some technical issues related to the active SFCL’s cost are discussed in this section. According to the previous studies of technical and economic impacts on a power system by introducing a SFCL [40]–[42], the annual cost of a SFCL is commonly composed of invest- ment cost, maintenance cost, refrigeration cost, and so on. Applying a SFCL may also achieve prospective benefits and operation cost savings, in the case of considering the factors such as increase of system reliability and reduction of expected fault current. With regard to a SFCL’s installation site, the most promising locations are found in distribution network, low voltage (400 V), and industrial systems [40]. From the reports in [43], the comparison between a dynamic voltage restorer and a hybrid-type SFCL for the FRT improvement is conducted, and it is stated that, when a SFCL is applied for individual wind generator, the cost is expensive and unacceptable. But in our opinion, regarding the FRT capacity enhancement of a wind farm, including multiple generators, the technoeconomic feasibility of using a SFCL may be preferably demonstrated. On the basis of the annual cost method, our research group roughly evaluates the cost of the active SFCL at a 35-kV power distribution network [42], where a large wind farm (50-MW capacity) is accessed. During the calculation, the second-generation HTS is used, and the calculation data come from the voltage-compensation-type active SFCL developed by Huazhong University of Science and Technology, China. TABLE I PARAMETERS FOR ECONOMICAL EVALUATION The active SFCL’s annual cost cSFCL can be computed in [44] cSFCL = ci + cm + co − ce (21) where ci, cm, co, and ce are, respectively, the annual invest- ment cost, maintenance cost, operating cost (including loss cost as well as refrigeration cost), and economical benefits. Considering the reduction of expected fault current (lower network losses), enhancement of power quality, delay of system improvement, and lower dimensioning of installa- tions and devices resulted from the active SFCL, ce can be expressed as [45] ce = k2Tn Pn r2 + cn (P/A, b, n) − cn (P/A, b, n + n1) + k3Cb (22) where (P/A, i, n) is the annual present value factor; Tn and Pn are, respectively, the annual operating time and the rated power of the network; r is the factor obtained by the ratio of maximum power to the rated power; n1 is the delay year number; and k3 and Cb are, respectively, the ratios of the reduced dimensioning of installations and devices to the initial one, and the installation cost as well as engineering cost. The main parameters for an economical evaluation are listed in Table I. In combination with the formula calculating and the conceptual design of the active SFCL in a power distribution system [46], the total cost of a 35-kV class three-phase active SFCL is ∼4049 k¥ ($650 k) that includes HTS materials cost 790 k¥, cryogenic vessel cost 154 k¥, converter cost 3000 k¥, and so on. As a matter of fact, in terms of the active SFCL’s application in enhancing the wind farm’s FRT capacity, improving this mean’s economical efficiency will be considerably beneficial to demonstrating the feasibility. A practicable method of reducing the total cost is to optimize the superconducting transformer’s winding structure and coupling factor, and accordingly the compensation capacity contributed by the three-phase four-wire converter can be decreased. The detailed technoeconomic analysis and optimization calculation will be carried out in the near future, and the results will be reported in later articles. Section III is devoted to investigating the active SFCL’s performance behaviors by electromagnetic transient simulation.
  • 6. CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 137 Fig. 4. Fault detection method applied to the simulation model for the active SFCL’s operation mode switching. TABLE II MAIN SIMULATION PARAMETERS OF THE SYSTEM MODEL III. SIMULATION STUDY For quantitatively evaluating the active SFCL’s effects on the DFIG’s FRT capability, the simulation model corresponding to Fig. 3 is created through MATLAB software, where the fault detection method is shown in Fig. 4. During the simulation, current-limiting mode 1 and mode 3 are considered (the former will be triggered automatically, and the latter will depend on the fault detection). In addition, parts of simulation parameters are expressed in Table II. A. Symmetric Fault Simulation In normal condition, the line current’s peak value is ∼1.75 kA. Supposing that a three-phase grounded fault happens at t = 1 s, and the fault duration/resistance is 0.4 s/0.1 , Figs. 5 and 6 show the operational characteristics of the DFIG-based wind turbine without and with the active SFCL (only mode 1 plays its role). From the figures, applying the active SFCL can limit the first peak of the fault currents (iAf, iBf, and iCf) to 2.62, 3.41, and 3.12 kA, respectively, in contrast with 6.91, 9.26, and 6.59 kA without SFCL. Fig. 5. Stator current waveform of the DFIG under the symmetric fault. (a) Without SFCL. (b) With the active SFCL (mode 1). Fig. 6. Stator voltage waveform of the DFIG under the symmetric fault. (a) Without SFCL. (b) With the active SFCL (mode 1). The reduction rate of the expected fault currents will be about 62.1%, 63.2%, and 52.7%, respectively. It is observed that, employing the active SFCL can also compensate the DFIG’s terminal voltage to 60% of normal value. By contrast, the terminal voltage will decrease to 7% of normal value without any additional current-limiting or voltage-compensation devices. Furthermore, owing to the mode switching driven by the fault detection, mode 3 will smoothly replace mode 1 to improve the active SFCL’s performance, and the A-phase circuit is selected to state the wind power integrated system’s transient characteristics. Fig. 7(a) reflects the active SFCL’s effects on the line fault current (the DFIG’s stator current) under mode 3, and Fig. 7(b) shows the injected current in the A-phase superconducting transformer’s secondary winding. It is clear that the mode switching is effectively implemented. As mode 3 appears and plays its role, the first peak of the A-phase fault current can be limited to 1.95 kA, and the reduction rate of the expected fault current is ∼71.8%.
  • 7. 138 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015 Fig. 7. Currents flowing through the A-phase superconducting transformer under the symmetric fault. (a) Primary winding. (b) Secondary winding. Fig. 8. Effects of the fault resistance on the DFIG’s terminal-voltage under the symmetric fault. (a) Without SFCL. (b) With the active SFCL (mode 3). Since the fault resistance may directly affect the DFIG’s transient behaviors, relevant simulation analysis is performed and denoted in Fig. 8. When the fault resistance is, respectively, set as 1, 5, 10, and 15 , the DFIG’s terminal- voltage without SFCL will be down to 12.5%, 48.3%, 68.8%, and 79.2% of normal value, respectively. In the case that the active SFCL operates under its current-limiting mode 3, the DFIG’s terminal-voltage can be, respectively, compensated to 62.1%, 86.7%, 95.2%, and 97.4% of normal value. Note that, to show a comparison between the active SFCL and other methods for improving the DFIG’s FRT capacity, a flux-coupling-type SFCL (an inductive SFCL) is introduced and built in MATLAB [47], [48], and its inductance parameters are similar to the imitated air-core superconducting transformer. Accordingly, the two different SFCLs’ effects on the DFIG’s operating characteristics are both assessed and stated as follows. The evaluation of rms voltage in pu at the terminals of the wind turbine generator is shown in Fig. 9, where the fault Fig. 9. Influence of the two different SFCLs on the DFIG’s terminal-voltage under the symmetric fault. (a) Active SFCL. (b) Inductive SFCL. Fig. 10. Influence of the two different SFCLs on the DFIG’s power fluctuation under the symmetric fault. (a) Active SFCL. (b) Inductive SFCL. duration/resistance is 0.4 s/0.1 . It is recognized that the DFIG’s terminal voltage during the fault can be maintained at 78% of normal value. As the highest minimum voltage level required worldwide is ∼0.25 pu [49], the introduction of the active SFCL (mode 3) can well meet the demand for ensuring the DFIG’s low-voltage ride-through capacity. Concerning the inductive SFCL’s impacts on improving the DFIG’s terminal- voltage, its contribution is between the active SFCL’s mode 1 and mode 3. Increased current in the rotor circuit is very harmful to the RSC, and the DFIG’s power fluctuation is closely related to the wind power system’s stability. Hence, the DFIG’s power fluctuation and rotor current are selected as the key indicators to compare the two SFCLs’ performance behaviors, and the detailed simulation results are shown in Figs. 10 and 11, where the change of the rotor current is described. From the given two figures, employing the active SFCL and the inductive SFCL can both make the DFIG’s rotor current be limited within a safety margin, and consequently, the probability of
  • 8. CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 139 Fig. 11. Effects of the two different SFCLs on the DFIG’s rotor current under the symmetric fault. (a) Active SFCL. (b) Inductive SFCL. Fig. 12. Stator current waveform of the DFIG under the unsymmetrical fault. (a) Without SFCL. (b) With the active SFCL (mode 3). the DFIG being disconnected from the electric power grid can be well reduced. It is also observed that, applying the inductive SFCL can only restrain the DFIG’s power oscillation amplitude to a certain extent, but it may not provide a more positive effect on evacuating the surplus active power during a fault incident. By comparison, the active SFCL’s contributions include consuming the DFIG’s active power and decreasing the output power oscillation, and thus the operational stability of the wind power integrated system can be effectively enhanced. B. Unsymmetrical Fault Simulation In this section, the DFIG’s dynamic response characteristics under an unsymmetrical fault are imitated. Supposing that a phase-to-phase (B-phase and C-phase) fault happens at t = 1 s, and the fault duration is 0.4 s, Figs. 12 and 13 show the DFIG’s stator current and stator voltage behaviors under the fault, where the active SFCL’s current-limiting mode 3 is applied. Fig. 13. Stator voltage waveform of the DFIG under the unsymmetrical fault. (a) Without SFCL. (b) With the active SFCL (mode 3). Fig. 14. Effects of the active SFCL on the DFIG’s terminal-voltage under the unsymmetrical fault. (a) B-phase voltage. (b) C-phase voltage. As the aforementioned comparison between the active SFCL and the inductive SFCL can describe the essential difference between the two means, this section does not simulate the inductive SFCL’s current-limiting characteristics. In the case of installing the active SFCL, reduction of the fault-phase currents and improvement of the terminal- voltage can both be achieved. Aiming at the DFIG’s B-phase and C-phase voltages, the evaluation of the rms characteristics in pu is shown in Fig. 14. By observing the characteristic curves at t = 1.3 s, the two phase voltages will, respectively, drop to 70% and 24.3% of normal value without SFCL. When the active SFCL’s mode 3 comes into play and the transient impedance is added into each of the fault-phase circuit, the DFIG’s B-phase and C-phase voltages can be compensated to 94.1% and 87.2% of normal value, respectively. Herein, it should be pointed out that, for dealing
  • 9. 140 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015 Fig. 15. Effects of the active SFCL on the DFIG’s operational characteristics under the unsymmetrical fault. (a) Power fluctuation. (b) Change of rotor current. with the unsymmetrical fault more efficiently (since the unbalance between the two fault-phases is relatively obvious), not only the angle of the current flowing through the C-phase superconducting transformer’s secondary winding will be adjusted, but also the amplitude will be properly enlarged by the converter. As a result, the active SFCL can act on the two fault phases more balancedly. Concerning the DFIG’s power fluctuation and rotor fault current under the unsymmetrical fault, the active SFCL’s effects on them are indicated in Fig. 15. From this figure, applying the active SFCL can availably reduce the DFIG’s power fluctuation, and the inhibition rate is ∼32.1%. Meanwhile, the increase of the circuit impedance will slightly lengthen the duration of the fluctuation process. On the other hand, the unsymmetrical fault will make some additional ac and dc components be induced in the DFIG’s rotor current. Introducing the active SFCL can also suppress their amplitudes, and the maximum reduction ratio can be up to 68.9%. IV. CONCLUSION In this paper, according to theory derivation, cost evaluation, and simulation analysis, our research group studies the application of a voltage-compensation-type active SFCL for improving the FRT capability of DFIG-based wind turbine. In addition, a brief comparison between the active SFCL and a common inductive SFCL is conducted to estimate the difference. From the results, the following conclusions can be obtained. 1) Installing the active SFCL can effectively limit the fault currents flowing through the DFIG’s stator and rotor windings. 2) Applying the active SFCL can evidently compensate the DFIG’s terminal-voltage and decrease its output power fluctuation, which helps to strengthen the operational stability of the wind power integrated system. 3) Employing the inductive SFCL can only restrain the DFIG’s power oscillation amplitude, but it may not provide a more promising effect on evacuating the surplus active power during the grid fault. Admittedly, concerning the proposed technical idea that is used to enhance the DFIG’s transient performance, a number of aspects should be enriched, such as optimization design and technoeconomic analysis of the active SFCL, and protection cooperation considered self-adaptive adjustment. Moreover, for a wind farm, which may be consisting of hundreds of wind turbines, the active SFCL should be installed for the whole wind farm instead of individual wind turbines, so as to reduce the cost as far as possible These research tasks will be carried out in the near future. REFERENCES [1] V. C. Gungor et al., “Smart grid technologies: Communication tech- nologies and standards,” IEEE Trans. Ind. Informat., vol. 7, no. 4, pp. 529–539, Nov. 2011. [2] G. W. Arnold, “Challenges and opportunities in smart grid: A position article,” Proc. IEEE, vol. 99, no. 6, pp. 922–927, Jun. 2011. [3] A. A. Moghaddam and A. R. Seifi, “Study of forecasting renewable energies in smart grids using linear predictive filters and neural networks,” IET. Renew. Power Generat., vol. 5, no. 6, pp. 470–480, Nov. 2011. [4] M. Hamzeh, H. Mokhtari, and H. Karimi, “A decentralized self-adjusting control strategy for reactive power management in an islanded multi-bus MV microgrid,” Can. J. Elect. Comput. Eng., vol. 36, no. 1, pp. 18–25, Winter 2013. [5] I. Ngamroo and S. Vachirasricirikul, “Coordinated control of opti- mized SFCL and SMES for improvement of power system transient stability,” IEEE Trans. Appl. Supercond., vol. 22, no. 3, Jun. 2012, Art. ID 5600805. [6] A. Morandi, “Fault current limiter: An enabler for increasing safety and power quality of distribution networks,” IEEE Trans. Appl. Supercond., vol. 23, no. 6, Dec. 2013, Art. ID 5604608. [7] Y. Xin et al., “Factory and field tests of a 220 kV/300 MVA statured iron-core superconducting fault current limiter,” IEEE Trans. Appl. Supercond., vol. 23, no. 3, Jun. 2013, Art. ID 5602305. [8] J. W. Shim, Y. Cho, S.-J. Kim, S. W. Min, and K. Hur, “Synergistic control of SMES and battery energy storage for enabling dispatchability of renewable energy sources,” IEEE Trans. Appl. Supercond., vol. 23, no. 3, Jun. 2013, Art. ID 5701205. [9] R. Qu, Y. Liu, and J. Wang, “Review of superconducting generator topologies for direct-drive wind turbines,” IEEE Trans. Appl. Supercond., vol. 23, no. 3, Jun. 2013, Art. ID 5201108. [10] N. G. A. Hemdan and M. Kurrat, “Time series analysis of rural distri- bution grids in the presence of HTS cables and intermittent renewable resources,” IEEE Trans. Appl. Supercond., vol. 24, no. 5, Oct. 2014, Art. ID 5400507. [11] K. Zhang, C. Mao, J. Lu, D. Wang, X. Chen, and J. Zhang, “Optimal control of state-of-charge of superconducting magnetic energy storage for wind power system,” IET Renew. Power Generat., vol. 8, no. 1, pp. 58–66, Jan. 2014. [12] L. Yang, G. Y. Yang, Z. Xu, Z. Y. Dong, K. P. Wong, and X. Ma, “Optimal controller design of a doubly-fed induction generator wind turbine system for small signal stability enhancement,” IET Generat., Transmiss. Distrib., vol. 4, no. 5, pp. 579–597, May 2010. [13] J. P. da Costa, H. Pinheiro, T. Degner, and G. Arnold, “Robust controller for DFIGs of grid-connected wind turbines,” IEEE Trans. Ind. Electron., vol. 58, no. 9, pp. 4023–4038, Sep. 2011. [14] M. El-Moursi, G. Joos, and C. Abbey, “A secondary voltage control strategy for transmission level interconnection of wind generation,” IEEE Trans. Power Electron., vol. 23, no. 3, pp. 1178–1190, May 2008. [15] J. Lopez, E. Gubia, E. Olea, J. Ruiz, and L. Marroyo, “Ride through of wind turbines with doubly fed induction generator under sym- metrical voltage dips,” IEEE Trans. Ind. Electron., vol. 56, no. 10, pp. 4246–4254, Oct. 2009. [16] G. Pannell, D. J. Atkinson, and B. Zahawi, “Analytical study of grid- fault response of wind turbine doubly fed induction generator,” IEEE Trans. Energy Convers., vol. 25, no. 4, pp. 1081–1091, Dec. 2010.
  • 10. CHEN et al.: FRT CAPABILITY IMPROVEMENT OF DFIG-BASED WIND TURBINE 141 [17] H. Geng, C. Liu, and G. Yang, “LVRT capability of DFIG-based WECS under asymmetrical grid fault condition,” IEEE Trans. Ind. Electron., vol. 60, no. 6, pp. 2495–2509, Jun. 2013. [18] S. Xiao, G. Yang, H. Zhou, and H. Geng, “Analysis of the control limit for rotor-side converter of doubly fed induction generator-based wind energy conversion system under various voltage dips,” IET Renew. Power Generat., vol. 7, no. 1, pp. 71–81, Feb. 2013. [19] S. Tohidi, H. Oraee, M. R. Zolghadri, S. Shao, and P. Tavner, “Analysis and enhancement of low-voltage ride-through capability of brushless doubly fed induction generator,” IEEE Trans. Ind. Electron., vol. 60, no. 3, pp. 1146–1155, Mar. 2013. [20] J. Vidal, G. Abad, J. Arza, and S. Aurtenechea, “Single-phase DC crowbar topologies for low voltage ride through fulfillment of high- power doubly fed induction generator-based wind turbines,” IEEE Trans. Energy Convers., vol. 28, no. 3, pp. 768–781, Sep. 2013. [21] S. M. Muyeen, M. A. Mannan, M. H. Ali, R. Takahashi, T. Murata, and J. Tamura, “Stabilization of wind turbine generator system by STATCOM,” IEEJ Trans. Power Energy, vol. 126, no. 10, pp. 1073–1082, Oct. 2006. [22] H. Gaztanaga, I. Etxeberria-Otadui, D. Ocnasu, and S. Bacha, “Real- time analysis of the transient response improvement of fixed-speed wind farms by using a reduced-scale STATCOM prototype,” IEEE Trans. Power Syst., vol. 22, no. 2, pp. 658–666, May 2007. [23] J. Shi, Y. Tang, Y. Xia, L. Ren, and J. Li, “SMES based excitation system for doubly-fed induction generator in wind power application,” IEEE Trans. Appl. Supercond., vol. 21, no. 3, pp. 1105–1108, Jun. 2011. [24] W. Guo, L. Xiao, and S. Dai, “Enhancing low-voltage ride-through capability and smoothing output power of DFIG with a superconducting fault-current limiter–magnetic energy storage system,” IEEE Trans. Energy Convers., vol. 27, no. 2, pp. 277–295, Jun. 2012. [25] M. E. Elshiekh, D. A. Mansour, and A. M. Azmy, “Improving fault ride- through capability of DFIG-based wind turbine using superconducting fault current limiter,” IEEE Trans. Appl. Supercond., vol. 23, no. 3, Jun. 2013, Art. ID 5601204. [26] W. Guo et al., “LVRT capability enhancement of DFIG with switch- type fault current limiter,” IEEE Trans. Ind. Electron., vol. 62, no. 1, pp. 332–342, Jan. 2015. [27] L. Chen, Y. Tang, J. Shi, and Z. Sun, “Simulations and experimental analyses of the active superconducting fault current limiter,” Phys. C, Supercond., vol. 459, nos. 1–2, pp. 27–32, Aug. 2007. [28] L. Chen et al., “Influence of a voltage compensation type active superconducting fault current limiter on the transient stability of power system,” Phys. C, Supercond., vol. 469, nos. 15–20, pp. 1760–1764, Oct. 2009. [29] L. Chen et al., “Effects of a voltage compensation type active super- conducting fault current limiter on distance relay protection,” Phys. C, Supercond., vol. 470, no. 20, pp. 1662–1665, Nov. 2010. [30] J. Wang, L. Zhou, J. Shi, and Y. Tang, “Experimental investigation of an active superconducting current controller,” IEEE Trans. Appl. Supercond., vol. 21, no. 3, pp. 1258–1262, Jun. 2011. [31] L. Chen, C. Deng, F. Guo, Y. Tang, J. Shi, and L. Ren, “Reducing the fault current and overvoltage in a distribution system with distributed generation units through an active type SFCL,” IEEE Trans. Appl. Supercond., vol. 24, no. 3, Jun. 2014, Art. ID 5600305. [32] H. Yamaguchi and T. Kataoka, “Stability analysis of air-core supercon- ducting power transformer,” IEEE Trans. Appl. Supercond., vol. 7, no. 2, pp. 1013–1016, Jun. 1997. [33] H. Yamaguchi, T. Kataoka, H. Matsuoka, T. Mouri, S. Nishikata, and Y. Sato, “Magnetic field and electromagnetic force analysis of 3-phase air-core superconducting power transformer,” IEEE Trans. Appl. Supercond., vol. 11, no. 1, pp. 1490–1493, Mar. 2001. [34] R. Wu, Y. Wang, Z. Yan, W. Luo, and Z. Gui, “Design and experimental realization of a new pulsed power supply based on the energy transfer between two capacitors and an HTS air-core pulsed transformer,” IEEE Trans. Plasma Sci., vol. 41, no. 4, pp. 993–998, Apr. 2013. [35] R. Wu, Y. Wang, Z. Yan, Z. He, and L. Wang, “Simulation and experi- mental investigation of an inductive pulsed power supply based on the head-to-tail series model of an HTS air-core pulsed transformer,” IEEE Trans. Appl. Supercond., vol. 23, no. 4, Aug. 2013, Art. ID 5701305. [36] X. Li, S. Duan, Y. Kang, and J. Chen, “Control strategies for series converter of three-phase four-wire UPQC,” Autom. Electr. Power Syst., vol. 31, no. 6, pp. 57–60, Mar. 2007. [37] J. Morren and S. W. H. de Haan, “Short-circuit current of wind turbines with doubly fed induction generator,” IEEE Trans. Energy Convers., vol. 22, no. 1, pp. 174–180, Mar. 2007. [38] J. Ouyang and X. Xiong, “Characteristics of short-circuit current of wind turbine driven DFIG and its impacts on the grid-connected distribution network,” Autom. Electr. Power Syst., vol. 34, no. 23, pp. 106–110 and 123, Dec. 2010. [39] S. Alaraifi, A. Moawwad, M. S. El Moursi, and V. Khadkikar, “Voltage booster schemes for fault ride-through enhancement of variable speed wind turbines,” IEEE Trans. Sustain. Energy, vol. 4, no. 4, pp. 1071–1081, Oct. 2013. [40] M. Sjostrom and D. Politano, “Technical and economical impacts on a power system by introducing an HTS FCL,” IEEE Trans. Appl. Supercond., vol. 11, no. 1, pp. 2042–2045, Mar. 2001. [41] J. Lee and S.-K. Joo, “Economic assessment method for superconducting fault current limiter (SFCL) in fault current-constrained power system operation,” IEEE Trans. Appl. Supercond., vol. 23, no. 3, Jun. 2013, Art. ID 5601104. [42] L. Ren et al., “Evaluation of three designs for a 35-kV class super- conducting reactor,” IEEE Trans. Appl. Supercond., vol. 24, no. 4, Aug. 2014, Art. ID 5400205. [43] A. A. Hussein and M. H. Ali, “Comparison between DVR and SFCL for fault ride through capability improvement of fixed-speed wind generator,” in Proc. IEEE PES T&D Conf. Expo., Apr. 2014, pp. 1–5. [44] L. Ren et al., “Techno-economic evaluation of a novel flux-coupling type superconducting fault current limiter,” IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1242–1245, Jun. 2010. [45] W. Zhang, Theory, Method and Application of Techno-Economic Eval- uation of Electric Power. Beijing, China: China Electric Power Press, 2004, ch. 5. [46] L. Chen, Y. J. Tang, M. Song, J. Shi, and L. Ren, “Parameter design and performance simulation of a 10 kV voltage compensation type active superconducting fault current limiter,” Phys. C, Supercond., vol. 494, pp. 349–354, Nov. 2013. [47] L. Chen, Y. Tang, Z. Li, L. Ren, J. Shi, and S. Cheng, “Current limiting characteristics of a novel flux-coupling type superconducting fault current limiter,” IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1143–1146, Jun. 2010. [48] L. Chen, H. Pan, C. Deng, F. Zheng, Z. Li, and F. Guo, “Study on the application of a flux-coupling type superconducting fault current limiter for decreasing HVDC commutation failure,” Can. J. Elect. Comput. Eng., to be published. [49] M. Tsili and S. Papathanassiou, “A review of grid code technical requirements for wind farms,” IET. Renew. Power Generat., vol. 3, no. 3, pp. 308–332, Sep. 2009. Lei Chen (M’12) was born in Jingzhou, China, in 1982. He received the B.S. and Ph.D. degrees in electrical engineering from the School of Electrical and Electronic Engineering, Huazhong University of Science and Technology (HUST), Hubei, China, in 2004 and 2010, respectively. He was with the Post-Doctoral Scientific Research Workstation, Hubei Electric Power Company, Hubei, from 2011 to 2013. Since 2013, he has been a Teacher with the School of Electrical Engineering, Wuhan University, Wuhan, China. He has authored over 30 articles. His current research interests include power system real-time simulation, smart grid, and superconducting power application. Feng Zheng was born in Wenzhou, China, in 1983. He received the B.S. degree in automation and the M.S. degree in electric power system and automation from the School of Electrical and Information, China Three Gorges University, Yichang, China, in 2006 and 2009, respectively. He is currently pursuing the Ph.D. degree in electric power system and automa- tion with Wuhan University, Wuhan, China. His current research interests include microgrid and superconducting fault current limiter.
  • 11. 142 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015 Changhong Deng was born in Hubei, China, in 1963. She received the B.S. degree in electrical engineering from China Three Gorges University, Yichang, China, in 1982, and the M.S. and Ph.D. degrees in electrical engineering from Wuhan University, Wuhan, China, in 1989 and 2005, respectively. She has been a Teacher with the School of Elec- trical Engineering, Wuhan University, since 2002. She is currently a Professor and Ph.D. Supervisor. She has authored over 50 articles. Her current research interests include power system simulation, distributed generation, and smart grid. Zhe Li was born in Zhoukou, China, in 1989. He received the B.S. and M.S. degrees in electrical engineering from the School of Electrical Engineering, Wuhan University, Wuhan, China, in 2012 and 2014, respectively. His current research interests include microgrid and fault reconstruction. Fang Guo was born in Jingzhou, China, in 1983. She received the B.S. and Ph.D. degrees in electrical engineering from the School of Electrical and Electronic Engineering, Huazhong University of Science and Technology, Hubei, China, in 2004 and 2010, respectively. She is currently with the Guang Dong Electric Power Design Institute, Guangzhou, China. Her current research interests include superconducting power application and energy storage technology.