Presentation
The RM22 Zelio multifunction control relays monitor the following functions on
3-phase supplies:
Functions RM22TA RM22TU RM22TR RM22TG
Sequence of phases L1, L2 and L3
Phase failure with regeneration
Asymmetry
Undervoltage
Overvoltage and undervoltage
Function performed
Function not performed
Depending on the model these RM22T●●● control relays:
b Accept different nominal 3-phase voltages: up to a 480 V
b Monitor own power supply measured as a true rms value
b Designed for clip-on mounting on DIN rail
b Settings are protected by a sealable cover
b Diagnostic button for load circuit testing
b Relay output status LED
b Fault detection indication LED
b Dial pointer LED indicator for relay power ON status
b Relay output On-delay or Off-delay
Applications
b Control for connection of moving equipments (site equipment, agricultural
equipment, refrigerated trucks)
b Control for protection of persons and equipment against the consequences of
reverse running (lifting, handling, elevators, escalators, etc.)
b Control of sensitive 3-phase supplies
b Protection against the risk of a driving load (phase failure)
b Normal/emergency power supply switching
Description
RM22TA RM22TU 1a Voltage range selector switch
1b Voltage range/On-Off delay selector
2 Time delay adjustment potentiometer Tt
3a Asymmetry threshold setting
potentiometer Asym
3b Undervoltage setting potentiometer <U
3c Overvoltage setting potentiometer >U
4 Diagnostic button
RM22TR RM22TG
Un Green LED: indicates that supply to the relay is on
R Yellow LED: indicates relay output state
DEF Yellow LED: indicates fault detection
Presentation,
description
Zelio Control - Measurement and
control relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG
L1 L2 L3
12 11 14
22 21 24
2
4
6
8 14
16
18
20%
R
>U
RM22TR31
DIAGNOSTIC
-2
-4
-6
-8 -14
-16
-18
-20%
<U
Def
240
220
208
200
240
220
208
200
Tt
ON
DELAY
OFF
DELAY
0,1 30s
5
10 20
25
1b
3c
3b
4
L1 L2 L3
12 11 14
22 21 24
R
RM22TG20
DIAGNOSTIC
Un
4
L1 L2
12 11 14
22 21 24
R
RM22TA31
DIAGNOSTIC
Def
200
208
220
240
8
5
10
12
15%
Asym
L3
Tt
0,1 30s
5
10 20
25
1a
2
3a
4
L1 L2 L3
12 11 14
22 21 24
R
RM22TU23
DIAGNOSTIC
Def
380
400
415
440
480
-2
-4
-6
-8 -14
-16
-18
-20%
<U
1a
3b
4
RM22T●●●
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28614-EN
version: 1.0
3
Operation
Operating principle
Multifunction 3-phase supply control relays monitor:
b Own power supply
b Correct sequencing of phases L1, L2 and L3
b Fault signalling by LED
b Phase failure, including in the case of voltage regeneration
b Undervoltage from - 2…- 20 % of the supply voltage Un
b Overvoltage from 2…20 % of the supply voltage Un
b Asymmetry from 5…15 % of the supply voltage Un
b Voltage selector switch:
v Set the switch to 3-phase supply voltage Un
v Position of this switch is taken into account on energization of the device
v If the switch position is changed while the device is operating, all the LEDs lash
but the product continues to operate normally with the voltage selected at the time of
energization preceding the change of position
v If the switch is returned to the original position selected prior to the last
energization, the LED’s return to their normal state
Phase + asymmetry control relays: RM22TA
b The relay monitors its own supply voltage Un:
v correct sequence of three phases
v failure of at least one of the three phases (U measured < 0.7 x Un)
v asymmetry adjustable from 5…15 % of Un
b In the event of a sequencing or phase failure fault, the relay opens instantly
b In the event of an asymmetry fault, the relay opens at the end of the time delay
set by the user
b On energization of the device with a fault measured, the relay stays open
Function diagram
b Functions:
v Sequence of phases L1, L2, L3
v Phase failure
v Asymmetry Asym
Tt : time delay after crossing of threshold (adjustable on front panel)
Zelio Control - Measurement and
control relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG
L2
L3
0 %
Tt Tt
R/R1/R2
Phase L3
Phase L2
Phase L1
Hysteresis
Asymmetry
Relays
Output
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28614-EN
version: 1.0
4
Operation (continued) Zelio Control - Measurement and
control relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG
Operating principle (continued)
Phase + Undervoltage control relays: RM22TU
b The relay monitors its own supply voltage Un:
v correct sequence of the three phases
v failure of at least one of the three phases (U measured < 0.7 x Un)
v undervoltage adjustable from - 2…- 20 % of Un
b In the event of a sequencing or phase failure fault, the relay opens instantly
b In the event of a voltage fault, the relay opens instantly
b On energization of the device with a fault measured, the relay stays open
Function diagrams
b Function:
v Sequence of phases L1, L2, L3
v Phase failure
30 % Un 30 % Un
30 % Un
L3
L2
R/R1/R2
Phase L3
Phase L2
Phase L1
Relays
Output
v Undervoltage control <U
R/R1/R2
L1/L2/L3
L1
L2
L3
L2
L3
L1
Tt Tt
<U
Threshold
Hysteresis
Relays
Output
Phases
Tt : response time after crossing the threshold
Phase + Undervoltage/overvoltage control relay: RM22TR
b The relay monitors its own supply voltage Un:
v phase failure
v undervoltage and overvoltage
b An adjustable time delay, on crossing the thresholds, provides immunity to transients, and prevents spurious
triggering of the output relay
b In the event of a voltage fault, the relay opens at the end of the time delay set On-delay or Off-delay by the user
b On energization of the device with a fault measured, the relay stays open
b In the event of phase failure, the relay opens instantly
Function diagrams
b Functions:
v Phase failure
30 % Un 30 % Un
30 % Un
R/R1/R2
Phase L3
Phase L2
Phase L1
Relays
Output
v Overvoltage and Undervoltage (Off-delay)
<U
>U
L1
L2
L3
Tt Tt
R/R1/R2
Phases L1/L2/L3
Relays
Output
Hysteresis
Hysteresis
Tt : time delay after crossing of threshold (adjustable on front panel)
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28614-EN
version: 1.0
5
Operation (continued)
references
Operating principle (continued)
Phase control relays: RM22TG
b The RM22TG relay monitors:
v Correct sequencing of the three phases
v Total loss of one or more of the phases
b When phase sequence and voltages are correct (> a 183 V), the output relays are closed
and the yellow LED is on
b When there is a sequencing fault or total loss of one or more phases (detected as soon as
one of the voltages drops below 100 V) the relay opens instantly and the LED goes off
b On energization of the device with a fault measured, the relay stays open
Function diagram
b Function:
v Sequence of phases L1, L2, L3
v Phase failure
100 %
0 %
100 %
0 %
100 %
0 %
Tr Tr Tr Tr
L3
L2
R/R1/R2
Phase L1
Phase L2
Phase L3
Relays
Output
Tr: response time on appearance of a fault
References
Function Rated 3-phase
supply voltage
Measurement
range
Time delay Output Reference Weight
V V kg/lb
b Phase
sequence
b Phase failure
b Asymmetry
a 200…240 a 200…240 Off delay
(0.1...30 s)
2 C/O 8 A RM22TA31 0.090/
0.198
a 380…480 a 380…480 Off delay
(0.1...30 s)
2 C/O 8 A RM22TA33 0.090/
0.198
b Phase
sequence
b Phase failure
b Undervoltage
and
overvoltage
a 200…240 a 200…240 On/Off delay
(0.1...30 s)
2 C/O 8 A RM22TR31 0.090/
0.198
a 380…480 a 380…480 On/Off delay
(0.1...30 s)
2 C/O 8 A RM22TR33 0.090/
0.198
b Phase
sequence
b Phase failure
b Undervoltage
a 200…240 a 200…240 No 2 C/O 8 A RM22TU21 0.090/
0.198
a 380…480 a 380…480 No 2 C/O 8 A RM22TU23 0.090/
0.198
b Phase
sequence
b Phase failure
a 208…480 a 183…528 No 2 C/O 8 A RM22TG20 0.090/
0.198
Zelio Control - Measurement and
control relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG
RM22TG20
RM22TA31 RM22TR31
RM22TU21
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28614-EN
version: 1.0
2
2
Presentation
RM22UA and RM22UB are DC voltage or 1-phase control relays which monitor the
following functions:
Functions RM22 UA2●MR UA3●MR UA33MT UB34
Overvoltage (without memory)
Undervoltage (with/without memory)
Overvoltage (with/without memory)
Overvoltage or undervoltage
(windows mode)
Function performed
Function not performed
The RM22 control relays enable:
b Automatic a.c. or d.c. recognition
b Selection between overvoltage and undervoltage
b Monitor own supply voltage which is measured as true rms value
b Selectable memory function
b Dial pointer LED indicator for relay power ON status
b Relay output status LED
The settings are protected by a sealable cover and the control status is indicated
by a LED. The relays are designed for clip-on mounting on Din rail mounting.
Applications
b Protection of electronic or electromechanical devices against overvoltage and
undervoltage
b Normal/emergency power supply switching
b d.c. motor overspeed control
b Monitoring of a.c. or d.c. supplies
b Battery and Speed monitoring (with tacho-generator)
Description
RM22UA2●MR RM22UA3●MR 1 Coniguration: selection of operating
mode <U (undervoltage), >U
(overvoltage), >U> (overvoltage and
under voltage), MEMORY - NO
MEMORY (with or without memory)
2a Voltage threshold setting potentiometer
U value
2b Undervoltage setting potentiometer <U
2c Overvoltage setting potentiometer >U
3 Time delay adjustment potentiometer Tt
4a Hysteresis adjustment potentiometer
Hys
4b Hysteresis/overvoltage and
undervoltage window mode adjustment
potentiometer Hys/>U>
5 Diagnostic button
6 Coniguration: selection of On-delay or
Off-delay
RM22UA33MT RM22UB34
R Yellow LED: indicates relay output state
Presentation,
description
Zelio Control - Measurement and
control relays
1-phase or DC voltage control relays
RM22UA and RM22UB
RM22UA31MR
A1 A2 M
12 11 14
22 21 24
R
Hys
RM22UA23MR
DIAGNOSTIC
E1 E2 E3
>U
Value
5
10
15
20 35
40
45
50%
10
20
30
40 70
80
90
100%
2c
4a
5
A1 A2 M
12 11 14
E1 E2 E3
22 21 24
U
>
MEMORY
NO
>
MEMORY
R
U
Value
Hys/
>U>
Tt
U>
>
> U
RM22UA31MR
U
<
U
>
< U
DIAGNOSTIC
5
10
15
20 35
40
45
50%
10
20
30
40 70
80
90
100%
0,1
30s
5
10 20
25
1
2a
4b
3
5
A1+ A2-
12 11 14
22 21 24
ON
OFF
DELAY
100
120
140
160 220
240
260
300V
R
>U
<U
Tt
RM22UB34
DIAGNOSTIC
80
280
0,1 30s
5
10 20
25
DELAY
100
120
140
160 220
240
260
300V
80
280
2b
2c
6
3
5
A1 A2 M
12 11 14
E1 E2 E3
22 21 24
R
RM22UA33MT
DIAGNOSTIC
U
>
MEMORY
NO
>
MEMORY
10
20
30
40 70
80
90
100%
5
10
15
20 35
40
45
50%
U
Value
Hys/
>U>
Tt
U>
>
> U
U
<
U
>
U
<
0,1 30s
5
10 20
25
1
2a
4b
3
5
RM22UA21MR
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28615-EN
version: 1.0
3
3
Operation
Operating principle
DC voltage or 1-phase control relays monitor:
b voltages of 1-phase and DC supplies
b its own supply voltage for RM22UB model
An adjustable time delay, on crossing the thresholds, provides immunity to
transients, and prevents spurious triggering of the output relay.
Overvoltage + Undervoltage control relays with/without memory: RM22
UA2●MR/ UA3●MR/UA33MT
The operating mode is ixed by the user:
b Undervoltage with or without memory
b Overvoltage with or without memory
The position of the coniguration switch and the operating mode is read by the
product on energization:
b If the coniguration switch is set to an unacceptable position, the product detects
a fault, the output relay stays open and the LEDs lash to indicate the position error.
b If the coniguration switch position is changed while the device is operating, all
the LEDs lash, but the product continues to operate normally with the function
selected at the time of energization before position change.
b If the coniguration switch is returned to the original position selected prior to the
last energization, the LED’s return to their normal state.
The undervoltage or overvoltage threshold value is set by means of a potentiom-
eter graduated as a percentage of the scale value of U to be monitored.
The hysteresis is adjusted by means of a potentiometer graduated from 5…50 %
of the threshold setting. The hysteresis value must not exceed the limit values of
the measuring range.
b Overvoltage without Memory
If the voltage controlled exceeds the threshold setting for a time greater than t
hat set on the front panel (0.1…30 s), the output relay opens and LED R goes off.
During the time delay, this LED lashes.
As soon as the voltage drops below the value of the threshold setting minus the
hysteresis, the relay instantly closes.
b Undervoltage without Memory
If the voltage controlled falls below the threshold setting for a time greater than
that set on the front panel (0.1…30 s), the output relay opens and LED R goes off.
During the time delay, this LED lashes.
As soon as the voltage rises above the value of the threshold setting plus the
hysteresis, the relay instantly closes.
b Overvoltage/Undervoltage with Memory
If “Memory” mode is selected, the relay opens when crossing of the threshold is
detected and then stays in that position. The power must be switched off to reset
the product.
Function diagram
b Function: Overvoltage control > U
v without memory
v with memory
Zelio Control - Measurement and
control relays
1-phase or DC voltage control relays
RM22UA and RM22UB
>U
Tt
U
R/R1/R2
Relays
Output
Hysteresis
Supply Un
Threshold
>U
U
Tt
R/R1/R2
Relays
Output
Hysteresis
Supply Un
Threshold
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28615-EN
version: 1.0
4
Operation (continued) Zelio Control - Measurement and
control relays
1-phase or DC voltage control relays
RM22UA and RM22UB
Operating principle (continued)
Function diagrams (continued)
b Function: Undervoltage control < U
v without memory
v with memory
Overvoltage + Undervoltage control relay in Windows mode: RM22 UA3●MR/
UA33MT/UB34
These relays operate in window mode where they check that the voltage controlled
stays between a minimum and a maximum threshold.
b The undervoltage or overvoltage threshold values are set by means of two
graduated potentiometers clearly indicating the Un to be monitored. The hysteresis
is ixed at 5 % of the threshold setting.
b If the voltage controlled exceeds the high threshold setting or falls below the low
threshold setting for a time greater than that set time on the front panel (0.1…30 s),
the output relay opens and LED R goes off. During the time delay, this LED lashes.
b As soon as the voltage falls below the high threshold setting value minus the
hysteresis, or rises above the low threshold setting value plus the hysteresis, the
relay instantly closes.
b On energization of the device with a fault measured, the relay stays open.
Function diagrams
b Functions: Overvoltage and Undervoltage control in window mode <U<
U
<U
Tt
R/R1/R2
Relays
Output
Hysteresis
Supply Un
Threshold
U
Tt
<U
R/R1/R2
Relays
Output
Hysteresis
Supply Un
Threshold
Tt Tt
U
>U
<U
R/R1/R2
Relays
Ouput
Hysteresis
Supply Un
Threshold
Hysteresis
Threshold
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28615-EN
version: 1.0
5
References
References
Function Rated supply
voltage
Measurement
range
Time delay Output Reference Weight
V V kg/lb
b Overvoltage
without memory
z 24…240 z 0.05…5 No 2 C/O 8 A RM22UA21MR 0.110/
0.242
z 24…240 z 1…100 No 2 C/O 8 A RM22UA22MR 0.110/
0.242
z 24…240 z 15…500 No 2 C/O 8 A RM22UA23MR 0.110/
0.242
b Overvoltage and
Undervoltage with/
without memory
b Overvoltage and
Undervoltage with
memory window
z 24…240 z 0.05…5 Off delay
(0.1...30 s)
2 C/O 8 A RM22UA31MR 0.110/
0.242
z 24…240 z 1…100 Off delay
(0.1...30 s)
2 C/O 8 A RM22UA32MR 0.110/
0.242
z 24…240 z 15…500 Off delay
(0.1...30 s)
2 C/O 8 A RM22UA33MR 0.110/
0.242
a 380…415 a 15…500 Off delay
(0.1...30 s)
2 C/O 8 A RM22UA33MT 0.110/
0.242
b Overvoltage and
Undervoltage
without memory
z 110…240 z 80…300 On/Off
delay
(0.1...30 s)
2 C/O 8 A RM22UB34 0.090/
0.198
Zelio Control - Measurement and
control relays
1-phase or DC voltage control relays
RM22UA and RM22UB
RM22UA33MT
RM22UA23MR RM22UA33MR
RM22UB34
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28615-EN
version: 1.0
2
Presentation
Multifunction current control relays RM22JA and RM35JA
monitor the following functions.
Functions RM22JA21MR RM22JA31MR RM35JA 32MR/32MT
Overcurrent
(without memory)
Overcurrent
(with/without memory)
Undercurrent
(with/without memory)
Overcurrent and
undercurrent
(with/without memory)
(windows mode)
Function performed
Function not performed
These control relays enable:
b Automatic a.c. or d.c. recognition
b Selection between overcurrent and undercurrent
b Measurement as true rms value
b Selectable memory function
b Dial pointer LED indicator for relay power ON status
b Relay output status LED
The settings are protected by a sealable cover and the control status is indicated
by a LED. The relays are designed for clip-on mounting on Din rail mount.
Applications
b Excitation control of d.c. machines
b Load state control of motors and generators
b Control of current drawn by a 3-phase motor
b Monitoring of heating or lighting circuits
b Control of pump draining (undercurrent)
b Control of overtorque (crushers)
b Monitoring of electromagnetic brakes or clutches.
Description
RM22JA21MR RM22JA31MR 1 Coniguration: selection of operating
mode <I (undercurrent), >I
(overcurrent), >I> (overcurrent and
undercurrent), MEMORY - NO
MEMORY (with or without memory)
2 Current threshold setting
potentiometer I %
3a Hysteresis adjustment
potentiometer Hys
3b Hysteresis/overcurrent and
undercurrent window mode
adjustment potentiometer Hys/>I>
4 Time delay adjustment
potentiometer Tt
5 Diagnostic button
6 Overcurrent setting potentiometer >I
RM35JA32MR RM35JA32MT
R Yellow LED: indicates relay output state.
Presentation,
description
Zelio Control - Measurement and
control relays
Current control relays
RM22JA and RM35JA
RM35JA32MT
A1 A2 M
12 11 14
22 21 24
5
10
15
20 35
40
45
50%
R
Hys
RM22JA21MR
DIAGNOSTIC
10
20
30
40 70
80
90
100%
E1 E2 E3
%
I
I
I
>
3a
6
MEMORY
NO
MEMORY
10
20
30
40 70
80
90
100%
5
10
15
20 35
40
45
50%
0,1 30s
5
10 20
25
A1 A2 M
12 11 14
E1 E2 E3
22 21 24
> >
R
Hys/
Tt
>
>
>
RM22JA31MR
<
>
<
DIAGNOSTIC
%
I
I
I
I
I
I
> >
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
3b
2
1
4
5
<
>
> >
MEMORY
> >
>
<
Hys/
Tt
100%
10
20
30
40 70
80
90
50%
5
10
15
20 35
40
45
30s
0,1
5
10 20
25
A1 A2 E3 E2 E1 M
12 11 14 22 21 24
RM35JA32MT
R
DIAGNOSTIC
%
I
I
I
I
I
I
> >
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
YES NO
3b
2
1
4
5
A1 A2 E3 E2 E1 M
12 11 14 22 21 24
RM35JA32MR
R
DIAGNOSTIC
<
>
> >
MEMORY
> >
>
<
Hys/
Tt
100%
10
20
30
40 70
80
90
50%
5
10
15
20 35
40
45
30s
0,1
5
10 20
25
%
I
I
I
I
I
I
> >
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
YES NO
3b
2
1
4
5
RM22JA21MR
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28616-EN
version: 1.0
3
Operation
Operating principle
The current control relays monitor:
b Current of 1-phase and DC supplies
An adjustable time delay, on crossing the thresholds, provides immunity to
transients, so preventing spurious triggering of the output relay.
Overcurrent + Undercurrent control relays with/without memory:
RM22JA●1MR/ RM35JA32M●
The operating mode is ixed by the user:
b Undercurrent with or without memory
b Overcurrent with or without memory
The position of the coniguration switch and the operating mode is read by the
product on energization:
b If the coniguration switch is set to an unacceptable position, the product detects
a fault, the output relay stays open and the LEDs lash to indicate the position error.
b If the coniguration switch position is changed while the device is operating, all
the LEDs lash, but the product continues to operate normally with the function
selected at the time of energization before position change.
b If the coniguration switch is returned to the original position selected prior to the
last energization, the LED’s return to their normal state.
The undercurrent or overcurrent threshold value is set by means of a potentiom-
eter graduated as a percentage of the scale value of I to be monitored.
The hysteresis is adjusted by means of a potentiometer graduated from 5…50 %
of the threshold setting. The hysteresis value must not exceed the limit values of
the measuring range.
b Overcurrent without Memory
If the current controlled exceeds the threshold setting for a time greater than
that set on the front panel (0.1…30 s), the output relay opens and LED R goes off.
During the time delay, this LED lashes.
As soon as the current drops below the value of the threshold setting minus the
hysteresis, the relay instantly closes.
b Overcurrent with Memory
If “Memory” mode is selected, the relay opens when crossing of the threshold is
detected and then stays in that position. The power must be switched off to reset
the product.
Function diagram
b Function: Overcurrent detection > I
v without memory
v with memory
Note: Ti is not used for this model.
Zelio Control - Measurement and
control relays
Current control relays
RM22JA and RM35JA
R/R1/R2
Tt Tt Ti
Ti
I
>I
Relays
Output
Hysteresis
Supply Un
Threshold
R/R1/R2
Ti Tt Ti
I
>I
Tt
Relays
Output
Hysteresis
Supply Un
Threshold
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28616-EN
version: 1.0
4
Operation (continued) Zelio Control - Measurement and
control relays
Current control relays
RM22JA and RM35JA
Operating principle (continued)
Overcurrent + Undercurrent control relays with/without memory:
RM22JA●1MR/ RM35JA32M● (continued)
b Undercurrent without Memory
If the current controlled falls below the threshold setting for a time greater than that
set on the front panel (0.1…30 s), the output relay opens and LED R goes off. Dur-
ing the time delay, this LED lashes.
As soon as the voltage rises above the value of the threshold setting plus the
hysteresis, the relay instantly closes.
b Undercurrent with Memory
If “Memory” mode is selected, the relay opens when crossing of the threshold is
detected and then stays in that position. The power must be switched off to reset
the product.
Function diagrams
b Function: Undercurrent detection <I
v without memory
v with memory
Note: Ti is not used for this model.
Overcurrent + Undercurrent control relay in windows mode:
RM22JA●1MR/ RM35JA32M●
These relays operate in window mode where they check that the current controlled
stays between a minimum and a maximum threshold.
b The undercurrent or overcurrent threshold values are set by means of two
graduated potentiometers clearly indicating the I to be monitored. The hysteresis is
ixed at 5 % of the threshold setting.
b If the current controlled exceeds the high threshold setting or falls below the low
threshold setting for a time greater than that set time on the front panel (0.1…30 s),
the output relay opens and LED R goes out. During the time delay, this LED lashes.
b As soon as the current falls below the high threshold setting value minus the
hysteresis, or rises above the low threshold setting value plus the hysteresis, the
relay instantly closes.
b On energization of the device with a fault measured, the relay stays open.
Function diagrams
b Functions: Overcurrent and Undercurrent control in window mode <I<
R/R1/R2
Ti
Tt Tt
Ti
I
<I
Relays
Output
Hysteresis
Supply Un
Threshold
R/R1/R2
Ti Ti
I
<I
Tt Tt
Relays
Output
Hysteresis
Supply Un
Threshold
Without memory
Power Supply
Threshold
Hysteresis
Hysteresis
Threshold
>I
<I
Relays
Output Tt
<Tt
U
<Tt
Tt
R/R1/R2
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28616-EN
version: 1.0
5
References
References
Function Rated supply
voltage
Measurement
range
Time
delay
Output Reference Weight
V mA kg/lb
b Overcurrent
without memory
z 24…240 z 4…1000 No 2 C/O 8 A RM22JA21MR 0.110/
0.242
b Overcurrent with/
without memory
b Undercurrent with/
without memory
b Overcurrent and
undercurrent
(windows mode)
with/without
memory
z 24…240 z 4…1000 Off delay
(0.1...30 s)
2 C/O 8 A RM22JA31MR 0.110/
0.242
z 24…240 z 1500…15000 Off delay
(0.1...30 s)
2 C/O 8 A RM35JA32MR 0.120/
0.264
a 380…415 a1500…15000 Off delay
(0.1...30 s)
2 C/O 8 A RM35JA32MT 0.120/
0.264
Zelio Control - Measurement and
control relays
Current control relays
RM22JA and RM35JA
RM35JA32MR
RM22JA21MR RM22JA31MR
RM35JA32MT
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28616-EN
version: 1.0
2
Presentation
Level control relays RM22LA and RM22LG control one or two levels, with ill or
empty function:
Functions RM22LA 32MR/32MT RM22LG 11MR/11MT
Level 1/Level 2
Fill operation
Empty operation
Low sensitivity
Standard sensitivity
High sensitivity
Function performed
Function not performed
The RM22 liquid level control relays enable:
b Dial pointer LED indicator for relay power ON status
b Relay output status LED
The settings are protected by a sealable cover and the control status is indicated
by a LED. The relays are designed for clip-on mounting on Din rail.
Applications
These devices monitor the levels of conductive liquid.
They control the actuation of pumps or valves to regulate levels. They are also
suitable for protecting submersible pumps against dry running, or protecting tanks
from “overlow”. They can also be used to control dosing of liquids in mixing
processes and to protect heating elements in the event of non immersion.
They have a transparent, hinged cover on their front panel to avoid any accidental
alteration of the settings. This cover can be directly sealed.
b Application examples for compatible liquids
v spring, town, industrial and sea water
v metallic salt, acid or base solutions
v liquid fertilizers
v non concentrated alcohol (< 40 %)
v liquids in the food-processing industry: milk, beer, coffee, etc.
Description
RM22LG11MR RM22LG11MT 1 Coniguration: selection of the
operating mode: Fill or Empty, and the
sensitivity range. LS/St/HS
2 Sensitivity control potentiometer (kΩ or %)
3 Coniguration: selection of Number of
levels; and On/Off time Delay
4 Time delay control potentiometer Tt
5 Diagnostic button
RM22LA32MR RM22LA32MT
R Yellow LED: indicates relay output state.
Presentation,
description
Zelio Control - Measurement and
control relays
Liquid level control relays
RM22LA and RM22LG
A1 A2 NC
12 11 14
10
20
30 70
80
100
R
Sens
Level
RM22LG11MR
DIAGNOSTIC
5
90
Min Max C
40 60
1
2
KΩ
A1 A2 NC
12 11 14
R
Sens
Level
RM22LG11MT
DIAGNOSTIC
Min Max C
10
20
30 70
80
100
5
90
40 60
1
2
KΩ
RM22LA32MT
3 3
2 2
1 1
A1 A2 NC
12 11 14
22 21 24
RM22LA32MT
DIAGNOSTIC
Min Max C
Sens
Level
Tt
St. St.
HS
LS
LS
HS
1
2
1
2
10
20
30 70
80
100%
5
90
40 60
ON
DELAY
OFF
DELAY
0,1 30s
5
10 20
25
R
A1 A2 NC
12 11 14
22 21 24
R
Sens
Level
Tt
RM22LA32MR
DIAGNOSTIC
Min Max C
St. St.
HS
LS
LS
HS
1
2
1
2
10
20
30 70
80
100%
5
90
40 60
ON
DELAY
OFF
DELAY
0,1 30s
5
10 20
25
3 3
2 2
1 1
4 4
5 5
5 5
RM22LG11MR
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28617-EN
version: 1.0
3
Operation
Operating principle
The liquid level control relays are designed to control levels of:
b Conductive liquid
Relay controls the levels of conductive liquids and measures the levels by means
of resistive probes.
The operating principle is based on measurement of the apparent resistance of the
liquid between two submerged probes. When this value is less than the threshold
setting on the front panel of the device, the relay changes state. To avoid electro-
lytic phenomena, an a.c. current runs across the probes.
The control of one single level can be achieved by using the 2nd selector switch.
In this case, the Max. level probe stays up in the air and an adjustable time delay
avoids any wave effect. These two products activate their output relay when a tank is
either emptying or illing.
Level control relay with adjustable sensitivity range
In these relays, a selector coniguration switch on the front panel allows selection
of the required sensitivity range and the empty or ill function. A second switch
allows selection of the number of levels (1 or 2) and the type of time delay in the
case of level 1 mode.
The coniguration of these switches is taken into account on energization.
b If the coniguration switch is set to an unacceptable position, the product detects a
fault, the output relay stays open and the LEDs lash to signal the position error.
b If the coniguration switch position is changed while the device is operating, all the
LEDs lash, but the product continues to operate normally with the function selected
at the time of energization preceding the change of position.
b If the coniguration switch is returned to the original position selected prior to the
last energization, the LED’s return to their normal state.
b Control of two levels, empty and ill function
v empty function
level: 2, function:
- LS (Low Sensitivity: 250 W…5 kW),
- St (Standard Sensitivity: 5 kW…100 kW),
- HS (High Sensitivity: 50 kW…1 MW).
The output relay stays open until the liquid reaches the Max. level probe. As
soon as the Max. level is reached, the contact closes and then allows emptying of
the tank (valve opens, pump starts, ...). When the level drops below the Min. level,
the contact opens to stop the emptying process.
v ill function
level: 2, function:
- LS (Low Sensitivity: 250 W…5 kW),
- St (Standard Sensitivity: 5 kW…100 kW),
- HS (High Sensitivity: 50 kW…1 MW).
The output relay stays energized until the liquid reaches the Max. level probe.
As soon as the Max. level is reached, the contact opens and the pump stops.
When the level drops below the Min. level, the contact closes again and
pumping re-starts to raise the level.
Function diagram
b Fill/Empty function (Two levels)
Zelio Control - Measurement and
control relays
Liquid level control relays
RM22LA and RM22LG
R/R1/R2
R/R1/R2
Supply Un
Relays
Output
Relays
Output
Max. level
Min. level
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28617-EN
version: 1.0
4
Operation (continued) Zelio Control - Measurement and
control relays
Liquid level control relays
RM22LA and RM22LG
Operating principle (continued)
Level control relay with adjustable sensitivity range (continued)
b Control of one level, empty function
v level: 1 - on delay functions:
- LS (Low Sensitivity: 250 W…5 kW),
- St (Standard Sensitivity: 5 kW…100 kW),
- HS (High Sensitivity: 50 kW…1 MW).
When the liquid level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energized and stays energized until the
liquid level drops back to the probe.
If the liquid drops back below the set level before the end of the time delay, the relay
does not energize.
Function diagram
b Empty function T on
b Control of one level, empty function
v level: 1 - off delay functions:
- LS (Low Sensitivity: 250 W…5 kW),
- St (Standard Sensitivity: 5 kW…100 kW),
- HS (High Sensitivity: 50 kW…1 MW).
When the liquid level rises above the probe, the relay instantly energizes and stays
energized until the liquid again reaches the probe level for a time Tt set on the front
panel.
If the liquid drops back below the set level before the end of the time delay period,
the relay stays energized.
Function diagram
b Empty function T off
b Control of one level, ill function
v level: 1 - on delay functions:
- LS (Low Sensitivity: 250 W…5 kW),
- St (Standard Sensitivity: 5 kW…100 kW),
- HS (High Sensitivity: 50 kW…1 MW).
When the liquid level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energized and stays energized until the
liquid level rises back up to the probe.
If the liquid rises back above the set level before the end of the time delay period, the
relay does not energize.
Function diagram
b Fill function T on
Tt Tt Tt
R/R1/R2
Supply Un
Relays
Output
Level
Tt Tt Tt
R/R1/R2
Supply Un
Relays
Output
Level
Tt Tt Tt
R/R1/R2
Supply Un
Relays
Output
Level
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28617-EN
version: 1.0
5
Operation (continued),
references
Zelio Control - Measurement and
control relays
Liquid level control relays
RM22LA and RM22LG
Operating principle (continued)
Level control relay with adjustable sensitivity range (continued)
v level: 1 - off delay functions:
- LS (Low Sensitivity: 250 W…5 kW),
- St (Standard Sensitivity: 5 kW…100 kW),
- HS (High Sensitivity: 50 kW…1 MW).
When the liquid level drops below the probe, the relay instantly energizes and stays
energized until the liquid level again reaches the probe level and stays above it for
a time greater than the time delay period Tt set on the front panel.
If the liquid drops back below the set level before the end of the time delay period,
the relay stays energized.
Function diagram
b Fill function T off
References
Function Rated supply
voltage
Measurement
range
Time
delay
Output Reference Weight
V Ω kg/lb
b Level 1/
Level 2
b Fill
operation
b Empty
operation
z 24…240 5 K…100 K No 1 C/O 8 A RM22LG11MR 0.100/
0.220
a 380…415 5 K…100 K No 1 C/O 8 A RM22LG11MT 0.100/
0.220
z 24…240 250...1 M On/Off
delay
(0.1...30 s)
2 C/O 8 A RM22LA32MR 0.110/
0.242
a 380…415 250...1 M On/Off
delay
(0.1...30 s)
2 C/O 8 A RM22LA32MT 0.110/
0.242
Tt Tt Tt
R/R1/R2
Supply Un
Relays
Output
Level
RM22LA32MR
RM22LG11MR RM22LG11MT
RM22LA32MT
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
28617-EN
version: 1.0
Vecchia gamma NUOVA GAMMA
RM4JA01B RM22JA21MR
RM4JA01F RM22JA21MR
RM4JA01M RM22JA21MR
RM4JA31F RM22JA31MR
RM4JA31M RM22JA31MR
RM4JA31MW RM22JA31MR
RM4JA31Q obsoleto,nessuna sostituzione
RM4JA32F RM35JA32MR
RM4JA32M RM35JA32MR
RM4JA32MW RM35JA32MR
RM4JA32Q RM35JA32MT
RM4UA01B RM22UA21MR
RM4UA01F RM22UA21MR
RM4UA01M RM22UA21MR
RM4UA02B RM22UA22MR
RM4UA02F RM22UA22MR
RM4UA02M RM22UA22MR
RM4UA03B RM22UA23MR
RM4UA03F RM22UA23MR
RM4UA03M RM22UA23MR
RM4UA31F RM22UA31MR
RM4UA31M RM22UA31MR
RM4UA31MW RM22UA31MR
RM4UA31Q obsoleto,nessuna sostituzione
RM4UA32F RM22UA32MR
RM4UA32M RM22UA32MR
RM4UA32MW RM22UA32MR
RM4UA32Q obsoleto,nessuna sostituzione
RM4UA33F RM22UA33MR
RM4UA33M RM22UA33MR
RM4UA33MW RM22UA33MR
RM4UA33Q RM22UA33MT
RM4UB34 RM22UB34
RM4UB35 RM22UB34
RM4TA01 RM22TA31
RM4TA02 RM22TA33
RM4TA31 RM22TA31
RM4TA32 RM22TA33
RM4TG20 RM22TG20
RM4TR31 RM22TR31
RM4TR32 RM22TR33
RM4TR33 RM22TR31
RM4TR34 RM22TR33
RM4TR35 obsoleto,nessuna sostituzione
RM4TU01 RM22TU21
RM4TU02 RM22TU23
RM4LA32B RM22LA32MR
RM4LA32F RM22LA32MR
RM4LA32M RM22LA32MR
RM4LA32MW RM22LA32MR
RM4LA32Q RM22LA32MT
RM4LG01B RM22LG11MR
RM4LG01F RM22LG11MR
RM4LG01M RM22LG11MR
RM4LG01Q RM22LG11MT

More Related Content

What's hot

Circuitos elétricos industriais_2014
Circuitos elétricos industriais_2014Circuitos elétricos industriais_2014
Circuitos elétricos industriais_2014
Marcio Oliani
 
xxxQxxx Quotation Estimate for Electrical Work of Poultry Processing Plant
xxxQxxx Quotation Estimate for Electrical Work of Poultry Processing PlantxxxQxxx Quotation Estimate for Electrical Work of Poultry Processing Plant
xxxQxxx Quotation Estimate for Electrical Work of Poultry Processing Plant
Muhammad Sarfraz
 
UPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection SolutionUPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection Solution
iTQAN Maju Resources
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings
Vijay Kumar
 
Como especificar um disjuntor
Como especificar um disjuntorComo especificar um disjuntor
Como especificar um disjuntor
Cássio Rezende
 
Memorial de calculo de carga instalada e demanda
Memorial de calculo de carga instalada e demandaMemorial de calculo de carga instalada e demanda
Memorial de calculo de carga instalada e demanda
Paulo H Bueno
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Partha Parida
 

What's hot (20)

Guia eletricista-residencial completo
Guia eletricista-residencial completoGuia eletricista-residencial completo
Guia eletricista-residencial completo
 
Transmission Loss Calculation on 33 / 66 / 132 KV Lines for Solar Power Plant
Transmission Loss Calculation on 33 / 66 / 132 KV  Lines for Solar Power PlantTransmission Loss Calculation on 33 / 66 / 132 KV  Lines for Solar Power Plant
Transmission Loss Calculation on 33 / 66 / 132 KV Lines for Solar Power Plant
 
Circuitos elétricos industriais_2014
Circuitos elétricos industriais_2014Circuitos elétricos industriais_2014
Circuitos elétricos industriais_2014
 
MAJOR PROJECT REPORT ON "RENEWABLE ENERGY (SOLAR) BASED HOME -AUTOMATION
MAJOR PROJECT REPORT ON "RENEWABLE ENERGY (SOLAR) BASED HOME -AUTOMATION MAJOR PROJECT REPORT ON "RENEWABLE ENERGY (SOLAR) BASED HOME -AUTOMATION
MAJOR PROJECT REPORT ON "RENEWABLE ENERGY (SOLAR) BASED HOME -AUTOMATION
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
Dimensionamento cabos baixa tensão
Dimensionamento cabos baixa tensãoDimensionamento cabos baixa tensão
Dimensionamento cabos baixa tensão
 
PPT ON 33/11KV SUBSTATION
PPT ON 33/11KV SUBSTATIONPPT ON 33/11KV SUBSTATION
PPT ON 33/11KV SUBSTATION
 
Neutral sizing - Power cable
Neutral sizing - Power cableNeutral sizing - Power cable
Neutral sizing - Power cable
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector group
 
MCC PANEL WIRING, GA and BOM Sample
MCC PANEL WIRING, GA and BOM SampleMCC PANEL WIRING, GA and BOM Sample
MCC PANEL WIRING, GA and BOM Sample
 
xxxQxxx Quotation Estimate for Electrical Work of Poultry Processing Plant
xxxQxxx Quotation Estimate for Electrical Work of Poultry Processing PlantxxxQxxx Quotation Estimate for Electrical Work of Poultry Processing Plant
xxxQxxx Quotation Estimate for Electrical Work of Poultry Processing Plant
 
Switchyard
SwitchyardSwitchyard
Switchyard
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
UPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection SolutionUPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection Solution
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings
 
Como especificar um disjuntor
Como especificar um disjuntorComo especificar um disjuntor
Como especificar um disjuntor
 
Manual do-eletricista-residencial
Manual do-eletricista-residencialManual do-eletricista-residencial
Manual do-eletricista-residencial
 
Memorial de calculo de carga instalada e demanda
Memorial de calculo de carga instalada e demandaMemorial de calculo de carga instalada e demanda
Memorial de calculo de carga instalada e demanda
 
Corrente nominal de motores trifásicos 220v
Corrente nominal de motores trifásicos 220vCorrente nominal de motores trifásicos 220v
Corrente nominal de motores trifásicos 220v
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 

Similar to Rm22

Report on minor project
Report on minor projectReport on minor project
Report on minor project
Anil Maurya
 
Advanced motion controls sr60a40
Advanced motion controls sr60a40Advanced motion controls sr60a40
Advanced motion controls sr60a40
Electromate
 
Advanced motion controls sr60a40
Advanced motion controls sr60a40Advanced motion controls sr60a40
Advanced motion controls sr60a40
Electromate
 
Advanced motion controls sr60a40ac
Advanced motion controls sr60a40acAdvanced motion controls sr60a40ac
Advanced motion controls sr60a40ac
Electromate
 
Advanced motion controls sr10a40
Advanced motion controls sr10a40Advanced motion controls sr10a40
Advanced motion controls sr10a40
Electromate
 
Advanced motion controls sr30a40
Advanced motion controls sr30a40Advanced motion controls sr30a40
Advanced motion controls sr30a40
Electromate
 
Advanced motion controls be25a20i
Advanced motion controls be25a20iAdvanced motion controls be25a20i
Advanced motion controls be25a20i
Electromate
 

Similar to Rm22 (20)

F5 m instruction manual
F5 m instruction manualF5 m instruction manual
F5 m instruction manual
 
Report on minor project
Report on minor projectReport on minor project
Report on minor project
 
Lm 3915
Lm 3915Lm 3915
Lm 3915
 
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
Instructions To Use Electronic Controller Logik 25-S in Screw Compressor
 
Ds012846
Ds012846Ds012846
Ds012846
 
Advanced motion controls be30a8
Advanced motion controls be30a8Advanced motion controls be30a8
Advanced motion controls be30a8
 
Advanced motion controls sr60a40
Advanced motion controls sr60a40Advanced motion controls sr60a40
Advanced motion controls sr60a40
 
Advanced motion controls sr60a40
Advanced motion controls sr60a40Advanced motion controls sr60a40
Advanced motion controls sr60a40
 
Advanced motion controls sr60a40ac
Advanced motion controls sr60a40acAdvanced motion controls sr60a40ac
Advanced motion controls sr60a40ac
 
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15 Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisation
 
Advanced motion controls sr10a40
Advanced motion controls sr10a40Advanced motion controls sr10a40
Advanced motion controls sr10a40
 
Advanced motion controls sr30a40
Advanced motion controls sr30a40Advanced motion controls sr30a40
Advanced motion controls sr30a40
 
Fermator door operator_vvvf3
Fermator door operator_vvvf3Fermator door operator_vvvf3
Fermator door operator_vvvf3
 
SIEMENS RWD CONTROLLER SERIES
SIEMENS RWD  CONTROLLER SERIES SIEMENS RWD  CONTROLLER SERIES
SIEMENS RWD CONTROLLER SERIES
 
Advanced motion controls be25a20i
Advanced motion controls be25a20iAdvanced motion controls be25a20i
Advanced motion controls be25a20i
 
Advanced motion controls 25a20
Advanced motion controls 25a20Advanced motion controls 25a20
Advanced motion controls 25a20
 
Exp2 voltage regulator
Exp2 voltage regulatorExp2 voltage regulator
Exp2 voltage regulator
 
R38 Controller
R38 ControllerR38 Controller
R38 Controller
 
2 Sed2 Drive Applications
2 Sed2 Drive Applications2 Sed2 Drive Applications
2 Sed2 Drive Applications
 

More from Hoàng Phương JSC

More from Hoàng Phương JSC (20)

Cong tac o cam schneider t12 2018 - premium
Cong tac o cam schneider t12 2018 - premiumCong tac o cam schneider t12 2018 - premium
Cong tac o cam schneider t12 2018 - premium
 
Avatar on schneider electric
Avatar on schneider electricAvatar on schneider electric
Avatar on schneider electric
 
Contactor lc1 d schneider
Contactor lc1 d schneiderContactor lc1 d schneider
Contactor lc1 d schneider
 
Overload relays
Overload relaysOverload relays
Overload relays
 
Easy pacttvs catalogues lc1e
Easy pacttvs catalogues lc1eEasy pacttvs catalogues lc1e
Easy pacttvs catalogues lc1e
 
Contactor lc1 f schneider
Contactor lc1 f schneiderContactor lc1 f schneider
Contactor lc1 f schneider
 
Lc1 d
Lc1 dLc1 d
Lc1 d
 
Cptg011 en (web)
Cptg011 en (web)Cptg011 en (web)
Cptg011 en (web)
 
Contactor hoangphuongjsc.com
Contactor   hoangphuongjsc.comContactor   hoangphuongjsc.com
Contactor hoangphuongjsc.com
 
Evolis circuit breakers_17_5kv
Evolis circuit breakers_17_5kvEvolis circuit breakers_17_5kv
Evolis circuit breakers_17_5kv
 
Fuses mv
Fuses mvFuses mv
Fuses mv
 
Compact ins catalogue 2013
Compact ins catalogue 2013Compact ins catalogue 2013
Compact ins catalogue 2013
 
Socket 2012
Socket 2012Socket 2012
Socket 2012
 
Series 56 industrial switches ip66 schneider clipsal
Series 56 industrial switches ip66 schneider   clipsalSeries 56 industrial switches ip66 schneider   clipsal
Series 56 industrial switches ip66 schneider clipsal
 
56 series ip66 schneider clipsal
56 series ip66 schneider   clipsal56 series ip66 schneider   clipsal
56 series ip66 schneider clipsal
 
Magelis xbt gt, xbt gk 2016
Magelis xbt gt, xbt gk 2016Magelis xbt gt, xbt gk 2016
Magelis xbt gt, xbt gk 2016
 
Modicon
ModiconModicon
Modicon
 
Modicon m241 logic
Modicon m241 logicModicon m241 logic
Modicon m241 logic
 
Power and meter
Power and meterPower and meter
Power and meter
 
Easy logic power meter
Easy logic power meterEasy logic power meter
Easy logic power meter
 

Recently uploaded

result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
Tonystark477637
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 

Recently uploaded (20)

(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 

Rm22

  • 1. 2 Presentation The RM22 Zelio multifunction control relays monitor the following functions on 3-phase supplies: Functions RM22TA RM22TU RM22TR RM22TG Sequence of phases L1, L2 and L3 Phase failure with regeneration Asymmetry Undervoltage Overvoltage and undervoltage Function performed Function not performed Depending on the model these RM22T●●● control relays: b Accept different nominal 3-phase voltages: up to a 480 V b Monitor own power supply measured as a true rms value b Designed for clip-on mounting on DIN rail b Settings are protected by a sealable cover b Diagnostic button for load circuit testing b Relay output status LED b Fault detection indication LED b Dial pointer LED indicator for relay power ON status b Relay output On-delay or Off-delay Applications b Control for connection of moving equipments (site equipment, agricultural equipment, refrigerated trucks) b Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.) b Control of sensitive 3-phase supplies b Protection against the risk of a driving load (phase failure) b Normal/emergency power supply switching Description RM22TA RM22TU 1a Voltage range selector switch 1b Voltage range/On-Off delay selector 2 Time delay adjustment potentiometer Tt 3a Asymmetry threshold setting potentiometer Asym 3b Undervoltage setting potentiometer <U 3c Overvoltage setting potentiometer >U 4 Diagnostic button RM22TR RM22TG Un Green LED: indicates that supply to the relay is on R Yellow LED: indicates relay output state DEF Yellow LED: indicates fault detection Presentation, description Zelio Control - Measurement and control relays Multifunction 3-phase control relays RM22TA, RM22TU, RM22TR, and RM22TG L1 L2 L3 12 11 14 22 21 24 2 4 6 8 14 16 18 20% R >U RM22TR31 DIAGNOSTIC -2 -4 -6 -8 -14 -16 -18 -20% <U Def 240 220 208 200 240 220 208 200 Tt ON DELAY OFF DELAY 0,1 30s 5 10 20 25 1b 3c 3b 4 L1 L2 L3 12 11 14 22 21 24 R RM22TG20 DIAGNOSTIC Un 4 L1 L2 12 11 14 22 21 24 R RM22TA31 DIAGNOSTIC Def 200 208 220 240 8 5 10 12 15% Asym L3 Tt 0,1 30s 5 10 20 25 1a 2 3a 4 L1 L2 L3 12 11 14 22 21 24 R RM22TU23 DIAGNOSTIC Def 380 400 415 440 480 -2 -4 -6 -8 -14 -16 -18 -20% <U 1a 3b 4 RM22T●●● 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28614-EN version: 1.0
  • 2. 3 Operation Operating principle Multifunction 3-phase supply control relays monitor: b Own power supply b Correct sequencing of phases L1, L2 and L3 b Fault signalling by LED b Phase failure, including in the case of voltage regeneration b Undervoltage from - 2…- 20 % of the supply voltage Un b Overvoltage from 2…20 % of the supply voltage Un b Asymmetry from 5…15 % of the supply voltage Un b Voltage selector switch: v Set the switch to 3-phase supply voltage Un v Position of this switch is taken into account on energization of the device v If the switch position is changed while the device is operating, all the LEDs lash but the product continues to operate normally with the voltage selected at the time of energization preceding the change of position v If the switch is returned to the original position selected prior to the last energization, the LED’s return to their normal state Phase + asymmetry control relays: RM22TA b The relay monitors its own supply voltage Un: v correct sequence of three phases v failure of at least one of the three phases (U measured < 0.7 x Un) v asymmetry adjustable from 5…15 % of Un b In the event of a sequencing or phase failure fault, the relay opens instantly b In the event of an asymmetry fault, the relay opens at the end of the time delay set by the user b On energization of the device with a fault measured, the relay stays open Function diagram b Functions: v Sequence of phases L1, L2, L3 v Phase failure v Asymmetry Asym Tt : time delay after crossing of threshold (adjustable on front panel) Zelio Control - Measurement and control relays Multifunction 3-phase control relays RM22TA, RM22TU, RM22TR, and RM22TG L2 L3 0 % Tt Tt R/R1/R2 Phase L3 Phase L2 Phase L1 Hysteresis Asymmetry Relays Output 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28614-EN version: 1.0
  • 3. 4 Operation (continued) Zelio Control - Measurement and control relays Multifunction 3-phase control relays RM22TA, RM22TU, RM22TR, and RM22TG Operating principle (continued) Phase + Undervoltage control relays: RM22TU b The relay monitors its own supply voltage Un: v correct sequence of the three phases v failure of at least one of the three phases (U measured < 0.7 x Un) v undervoltage adjustable from - 2…- 20 % of Un b In the event of a sequencing or phase failure fault, the relay opens instantly b In the event of a voltage fault, the relay opens instantly b On energization of the device with a fault measured, the relay stays open Function diagrams b Function: v Sequence of phases L1, L2, L3 v Phase failure 30 % Un 30 % Un 30 % Un L3 L2 R/R1/R2 Phase L3 Phase L2 Phase L1 Relays Output v Undervoltage control <U R/R1/R2 L1/L2/L3 L1 L2 L3 L2 L3 L1 Tt Tt <U Threshold Hysteresis Relays Output Phases Tt : response time after crossing the threshold Phase + Undervoltage/overvoltage control relay: RM22TR b The relay monitors its own supply voltage Un: v phase failure v undervoltage and overvoltage b An adjustable time delay, on crossing the thresholds, provides immunity to transients, and prevents spurious triggering of the output relay b In the event of a voltage fault, the relay opens at the end of the time delay set On-delay or Off-delay by the user b On energization of the device with a fault measured, the relay stays open b In the event of phase failure, the relay opens instantly Function diagrams b Functions: v Phase failure 30 % Un 30 % Un 30 % Un R/R1/R2 Phase L3 Phase L2 Phase L1 Relays Output v Overvoltage and Undervoltage (Off-delay) <U >U L1 L2 L3 Tt Tt R/R1/R2 Phases L1/L2/L3 Relays Output Hysteresis Hysteresis Tt : time delay after crossing of threshold (adjustable on front panel) 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28614-EN version: 1.0
  • 4. 5 Operation (continued) references Operating principle (continued) Phase control relays: RM22TG b The RM22TG relay monitors: v Correct sequencing of the three phases v Total loss of one or more of the phases b When phase sequence and voltages are correct (> a 183 V), the output relays are closed and the yellow LED is on b When there is a sequencing fault or total loss of one or more phases (detected as soon as one of the voltages drops below 100 V) the relay opens instantly and the LED goes off b On energization of the device with a fault measured, the relay stays open Function diagram b Function: v Sequence of phases L1, L2, L3 v Phase failure 100 % 0 % 100 % 0 % 100 % 0 % Tr Tr Tr Tr L3 L2 R/R1/R2 Phase L1 Phase L2 Phase L3 Relays Output Tr: response time on appearance of a fault References Function Rated 3-phase supply voltage Measurement range Time delay Output Reference Weight V V kg/lb b Phase sequence b Phase failure b Asymmetry a 200…240 a 200…240 Off delay (0.1...30 s) 2 C/O 8 A RM22TA31 0.090/ 0.198 a 380…480 a 380…480 Off delay (0.1...30 s) 2 C/O 8 A RM22TA33 0.090/ 0.198 b Phase sequence b Phase failure b Undervoltage and overvoltage a 200…240 a 200…240 On/Off delay (0.1...30 s) 2 C/O 8 A RM22TR31 0.090/ 0.198 a 380…480 a 380…480 On/Off delay (0.1...30 s) 2 C/O 8 A RM22TR33 0.090/ 0.198 b Phase sequence b Phase failure b Undervoltage a 200…240 a 200…240 No 2 C/O 8 A RM22TU21 0.090/ 0.198 a 380…480 a 380…480 No 2 C/O 8 A RM22TU23 0.090/ 0.198 b Phase sequence b Phase failure a 208…480 a 183…528 No 2 C/O 8 A RM22TG20 0.090/ 0.198 Zelio Control - Measurement and control relays Multifunction 3-phase control relays RM22TA, RM22TU, RM22TR, and RM22TG RM22TG20 RM22TA31 RM22TR31 RM22TU21 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28614-EN version: 1.0
  • 5. 2 2 Presentation RM22UA and RM22UB are DC voltage or 1-phase control relays which monitor the following functions: Functions RM22 UA2●MR UA3●MR UA33MT UB34 Overvoltage (without memory) Undervoltage (with/without memory) Overvoltage (with/without memory) Overvoltage or undervoltage (windows mode) Function performed Function not performed The RM22 control relays enable: b Automatic a.c. or d.c. recognition b Selection between overvoltage and undervoltage b Monitor own supply voltage which is measured as true rms value b Selectable memory function b Dial pointer LED indicator for relay power ON status b Relay output status LED The settings are protected by a sealable cover and the control status is indicated by a LED. The relays are designed for clip-on mounting on Din rail mounting. Applications b Protection of electronic or electromechanical devices against overvoltage and undervoltage b Normal/emergency power supply switching b d.c. motor overspeed control b Monitoring of a.c. or d.c. supplies b Battery and Speed monitoring (with tacho-generator) Description RM22UA2●MR RM22UA3●MR 1 Coniguration: selection of operating mode <U (undervoltage), >U (overvoltage), >U> (overvoltage and under voltage), MEMORY - NO MEMORY (with or without memory) 2a Voltage threshold setting potentiometer U value 2b Undervoltage setting potentiometer <U 2c Overvoltage setting potentiometer >U 3 Time delay adjustment potentiometer Tt 4a Hysteresis adjustment potentiometer Hys 4b Hysteresis/overvoltage and undervoltage window mode adjustment potentiometer Hys/>U> 5 Diagnostic button 6 Coniguration: selection of On-delay or Off-delay RM22UA33MT RM22UB34 R Yellow LED: indicates relay output state Presentation, description Zelio Control - Measurement and control relays 1-phase or DC voltage control relays RM22UA and RM22UB RM22UA31MR A1 A2 M 12 11 14 22 21 24 R Hys RM22UA23MR DIAGNOSTIC E1 E2 E3 >U Value 5 10 15 20 35 40 45 50% 10 20 30 40 70 80 90 100% 2c 4a 5 A1 A2 M 12 11 14 E1 E2 E3 22 21 24 U > MEMORY NO > MEMORY R U Value Hys/ >U> Tt U> > > U RM22UA31MR U < U > < U DIAGNOSTIC 5 10 15 20 35 40 45 50% 10 20 30 40 70 80 90 100% 0,1 30s 5 10 20 25 1 2a 4b 3 5 A1+ A2- 12 11 14 22 21 24 ON OFF DELAY 100 120 140 160 220 240 260 300V R >U <U Tt RM22UB34 DIAGNOSTIC 80 280 0,1 30s 5 10 20 25 DELAY 100 120 140 160 220 240 260 300V 80 280 2b 2c 6 3 5 A1 A2 M 12 11 14 E1 E2 E3 22 21 24 R RM22UA33MT DIAGNOSTIC U > MEMORY NO > MEMORY 10 20 30 40 70 80 90 100% 5 10 15 20 35 40 45 50% U Value Hys/ >U> Tt U> > > U U < U > U < 0,1 30s 5 10 20 25 1 2a 4b 3 5 RM22UA21MR 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28615-EN version: 1.0
  • 6. 3 3 Operation Operating principle DC voltage or 1-phase control relays monitor: b voltages of 1-phase and DC supplies b its own supply voltage for RM22UB model An adjustable time delay, on crossing the thresholds, provides immunity to transients, and prevents spurious triggering of the output relay. Overvoltage + Undervoltage control relays with/without memory: RM22 UA2●MR/ UA3●MR/UA33MT The operating mode is ixed by the user: b Undervoltage with or without memory b Overvoltage with or without memory The position of the coniguration switch and the operating mode is read by the product on energization: b If the coniguration switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs lash to indicate the position error. b If the coniguration switch position is changed while the device is operating, all the LEDs lash, but the product continues to operate normally with the function selected at the time of energization before position change. b If the coniguration switch is returned to the original position selected prior to the last energization, the LED’s return to their normal state. The undervoltage or overvoltage threshold value is set by means of a potentiom- eter graduated as a percentage of the scale value of U to be monitored. The hysteresis is adjusted by means of a potentiometer graduated from 5…50 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range. b Overvoltage without Memory If the voltage controlled exceeds the threshold setting for a time greater than t hat set on the front panel (0.1…30 s), the output relay opens and LED R goes off. During the time delay, this LED lashes. As soon as the voltage drops below the value of the threshold setting minus the hysteresis, the relay instantly closes. b Undervoltage without Memory If the voltage controlled falls below the threshold setting for a time greater than that set on the front panel (0.1…30 s), the output relay opens and LED R goes off. During the time delay, this LED lashes. As soon as the voltage rises above the value of the threshold setting plus the hysteresis, the relay instantly closes. b Overvoltage/Undervoltage with Memory If “Memory” mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position. The power must be switched off to reset the product. Function diagram b Function: Overvoltage control > U v without memory v with memory Zelio Control - Measurement and control relays 1-phase or DC voltage control relays RM22UA and RM22UB >U Tt U R/R1/R2 Relays Output Hysteresis Supply Un Threshold >U U Tt R/R1/R2 Relays Output Hysteresis Supply Un Threshold 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28615-EN version: 1.0
  • 7. 4 Operation (continued) Zelio Control - Measurement and control relays 1-phase or DC voltage control relays RM22UA and RM22UB Operating principle (continued) Function diagrams (continued) b Function: Undervoltage control < U v without memory v with memory Overvoltage + Undervoltage control relay in Windows mode: RM22 UA3●MR/ UA33MT/UB34 These relays operate in window mode where they check that the voltage controlled stays between a minimum and a maximum threshold. b The undervoltage or overvoltage threshold values are set by means of two graduated potentiometers clearly indicating the Un to be monitored. The hysteresis is ixed at 5 % of the threshold setting. b If the voltage controlled exceeds the high threshold setting or falls below the low threshold setting for a time greater than that set time on the front panel (0.1…30 s), the output relay opens and LED R goes off. During the time delay, this LED lashes. b As soon as the voltage falls below the high threshold setting value minus the hysteresis, or rises above the low threshold setting value plus the hysteresis, the relay instantly closes. b On energization of the device with a fault measured, the relay stays open. Function diagrams b Functions: Overvoltage and Undervoltage control in window mode <U< U <U Tt R/R1/R2 Relays Output Hysteresis Supply Un Threshold U Tt <U R/R1/R2 Relays Output Hysteresis Supply Un Threshold Tt Tt U >U <U R/R1/R2 Relays Ouput Hysteresis Supply Un Threshold Hysteresis Threshold 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28615-EN version: 1.0
  • 8. 5 References References Function Rated supply voltage Measurement range Time delay Output Reference Weight V V kg/lb b Overvoltage without memory z 24…240 z 0.05…5 No 2 C/O 8 A RM22UA21MR 0.110/ 0.242 z 24…240 z 1…100 No 2 C/O 8 A RM22UA22MR 0.110/ 0.242 z 24…240 z 15…500 No 2 C/O 8 A RM22UA23MR 0.110/ 0.242 b Overvoltage and Undervoltage with/ without memory b Overvoltage and Undervoltage with memory window z 24…240 z 0.05…5 Off delay (0.1...30 s) 2 C/O 8 A RM22UA31MR 0.110/ 0.242 z 24…240 z 1…100 Off delay (0.1...30 s) 2 C/O 8 A RM22UA32MR 0.110/ 0.242 z 24…240 z 15…500 Off delay (0.1...30 s) 2 C/O 8 A RM22UA33MR 0.110/ 0.242 a 380…415 a 15…500 Off delay (0.1...30 s) 2 C/O 8 A RM22UA33MT 0.110/ 0.242 b Overvoltage and Undervoltage without memory z 110…240 z 80…300 On/Off delay (0.1...30 s) 2 C/O 8 A RM22UB34 0.090/ 0.198 Zelio Control - Measurement and control relays 1-phase or DC voltage control relays RM22UA and RM22UB RM22UA33MT RM22UA23MR RM22UA33MR RM22UB34 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28615-EN version: 1.0
  • 9. 2 Presentation Multifunction current control relays RM22JA and RM35JA monitor the following functions. Functions RM22JA21MR RM22JA31MR RM35JA 32MR/32MT Overcurrent (without memory) Overcurrent (with/without memory) Undercurrent (with/without memory) Overcurrent and undercurrent (with/without memory) (windows mode) Function performed Function not performed These control relays enable: b Automatic a.c. or d.c. recognition b Selection between overcurrent and undercurrent b Measurement as true rms value b Selectable memory function b Dial pointer LED indicator for relay power ON status b Relay output status LED The settings are protected by a sealable cover and the control status is indicated by a LED. The relays are designed for clip-on mounting on Din rail mount. Applications b Excitation control of d.c. machines b Load state control of motors and generators b Control of current drawn by a 3-phase motor b Monitoring of heating or lighting circuits b Control of pump draining (undercurrent) b Control of overtorque (crushers) b Monitoring of electromagnetic brakes or clutches. Description RM22JA21MR RM22JA31MR 1 Coniguration: selection of operating mode <I (undercurrent), >I (overcurrent), >I> (overcurrent and undercurrent), MEMORY - NO MEMORY (with or without memory) 2 Current threshold setting potentiometer I % 3a Hysteresis adjustment potentiometer Hys 3b Hysteresis/overcurrent and undercurrent window mode adjustment potentiometer Hys/>I> 4 Time delay adjustment potentiometer Tt 5 Diagnostic button 6 Overcurrent setting potentiometer >I RM35JA32MR RM35JA32MT R Yellow LED: indicates relay output state. Presentation, description Zelio Control - Measurement and control relays Current control relays RM22JA and RM35JA RM35JA32MT A1 A2 M 12 11 14 22 21 24 5 10 15 20 35 40 45 50% R Hys RM22JA21MR DIAGNOSTIC 10 20 30 40 70 80 90 100% E1 E2 E3 % I I I > 3a 6 MEMORY NO MEMORY 10 20 30 40 70 80 90 100% 5 10 15 20 35 40 45 50% 0,1 30s 5 10 20 25 A1 A2 M 12 11 14 E1 E2 E3 22 21 24 > > R Hys/ Tt > > > RM22JA31MR < > < DIAGNOSTIC % I I I I I I > > I I I I I I I I I I I I I I I I I I 3b 2 1 4 5 < > > > MEMORY > > > < Hys/ Tt 100% 10 20 30 40 70 80 90 50% 5 10 15 20 35 40 45 30s 0,1 5 10 20 25 A1 A2 E3 E2 E1 M 12 11 14 22 21 24 RM35JA32MT R DIAGNOSTIC % I I I I I I > > I I I I I I I I I I I I I I I I I I YES NO 3b 2 1 4 5 A1 A2 E3 E2 E1 M 12 11 14 22 21 24 RM35JA32MR R DIAGNOSTIC < > > > MEMORY > > > < Hys/ Tt 100% 10 20 30 40 70 80 90 50% 5 10 15 20 35 40 45 30s 0,1 5 10 20 25 % I I I I I I > > I I I I I I I I I I I I I I I I I I YES NO 3b 2 1 4 5 RM22JA21MR 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28616-EN version: 1.0
  • 10. 3 Operation Operating principle The current control relays monitor: b Current of 1-phase and DC supplies An adjustable time delay, on crossing the thresholds, provides immunity to transients, so preventing spurious triggering of the output relay. Overcurrent + Undercurrent control relays with/without memory: RM22JA●1MR/ RM35JA32M● The operating mode is ixed by the user: b Undercurrent with or without memory b Overcurrent with or without memory The position of the coniguration switch and the operating mode is read by the product on energization: b If the coniguration switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs lash to indicate the position error. b If the coniguration switch position is changed while the device is operating, all the LEDs lash, but the product continues to operate normally with the function selected at the time of energization before position change. b If the coniguration switch is returned to the original position selected prior to the last energization, the LED’s return to their normal state. The undercurrent or overcurrent threshold value is set by means of a potentiom- eter graduated as a percentage of the scale value of I to be monitored. The hysteresis is adjusted by means of a potentiometer graduated from 5…50 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range. b Overcurrent without Memory If the current controlled exceeds the threshold setting for a time greater than that set on the front panel (0.1…30 s), the output relay opens and LED R goes off. During the time delay, this LED lashes. As soon as the current drops below the value of the threshold setting minus the hysteresis, the relay instantly closes. b Overcurrent with Memory If “Memory” mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position. The power must be switched off to reset the product. Function diagram b Function: Overcurrent detection > I v without memory v with memory Note: Ti is not used for this model. Zelio Control - Measurement and control relays Current control relays RM22JA and RM35JA R/R1/R2 Tt Tt Ti Ti I >I Relays Output Hysteresis Supply Un Threshold R/R1/R2 Ti Tt Ti I >I Tt Relays Output Hysteresis Supply Un Threshold 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28616-EN version: 1.0
  • 11. 4 Operation (continued) Zelio Control - Measurement and control relays Current control relays RM22JA and RM35JA Operating principle (continued) Overcurrent + Undercurrent control relays with/without memory: RM22JA●1MR/ RM35JA32M● (continued) b Undercurrent without Memory If the current controlled falls below the threshold setting for a time greater than that set on the front panel (0.1…30 s), the output relay opens and LED R goes off. Dur- ing the time delay, this LED lashes. As soon as the voltage rises above the value of the threshold setting plus the hysteresis, the relay instantly closes. b Undercurrent with Memory If “Memory” mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position. The power must be switched off to reset the product. Function diagrams b Function: Undercurrent detection <I v without memory v with memory Note: Ti is not used for this model. Overcurrent + Undercurrent control relay in windows mode: RM22JA●1MR/ RM35JA32M● These relays operate in window mode where they check that the current controlled stays between a minimum and a maximum threshold. b The undercurrent or overcurrent threshold values are set by means of two graduated potentiometers clearly indicating the I to be monitored. The hysteresis is ixed at 5 % of the threshold setting. b If the current controlled exceeds the high threshold setting or falls below the low threshold setting for a time greater than that set time on the front panel (0.1…30 s), the output relay opens and LED R goes out. During the time delay, this LED lashes. b As soon as the current falls below the high threshold setting value minus the hysteresis, or rises above the low threshold setting value plus the hysteresis, the relay instantly closes. b On energization of the device with a fault measured, the relay stays open. Function diagrams b Functions: Overcurrent and Undercurrent control in window mode <I< R/R1/R2 Ti Tt Tt Ti I <I Relays Output Hysteresis Supply Un Threshold R/R1/R2 Ti Ti I <I Tt Tt Relays Output Hysteresis Supply Un Threshold Without memory Power Supply Threshold Hysteresis Hysteresis Threshold >I <I Relays Output Tt <Tt U <Tt Tt R/R1/R2 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28616-EN version: 1.0
  • 12. 5 References References Function Rated supply voltage Measurement range Time delay Output Reference Weight V mA kg/lb b Overcurrent without memory z 24…240 z 4…1000 No 2 C/O 8 A RM22JA21MR 0.110/ 0.242 b Overcurrent with/ without memory b Undercurrent with/ without memory b Overcurrent and undercurrent (windows mode) with/without memory z 24…240 z 4…1000 Off delay (0.1...30 s) 2 C/O 8 A RM22JA31MR 0.110/ 0.242 z 24…240 z 1500…15000 Off delay (0.1...30 s) 2 C/O 8 A RM35JA32MR 0.120/ 0.264 a 380…415 a1500…15000 Off delay (0.1...30 s) 2 C/O 8 A RM35JA32MT 0.120/ 0.264 Zelio Control - Measurement and control relays Current control relays RM22JA and RM35JA RM35JA32MR RM22JA21MR RM22JA31MR RM35JA32MT 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28616-EN version: 1.0
  • 13. 2 Presentation Level control relays RM22LA and RM22LG control one or two levels, with ill or empty function: Functions RM22LA 32MR/32MT RM22LG 11MR/11MT Level 1/Level 2 Fill operation Empty operation Low sensitivity Standard sensitivity High sensitivity Function performed Function not performed The RM22 liquid level control relays enable: b Dial pointer LED indicator for relay power ON status b Relay output status LED The settings are protected by a sealable cover and the control status is indicated by a LED. The relays are designed for clip-on mounting on Din rail. Applications These devices monitor the levels of conductive liquid. They control the actuation of pumps or valves to regulate levels. They are also suitable for protecting submersible pumps against dry running, or protecting tanks from “overlow”. They can also be used to control dosing of liquids in mixing processes and to protect heating elements in the event of non immersion. They have a transparent, hinged cover on their front panel to avoid any accidental alteration of the settings. This cover can be directly sealed. b Application examples for compatible liquids v spring, town, industrial and sea water v metallic salt, acid or base solutions v liquid fertilizers v non concentrated alcohol (< 40 %) v liquids in the food-processing industry: milk, beer, coffee, etc. Description RM22LG11MR RM22LG11MT 1 Coniguration: selection of the operating mode: Fill or Empty, and the sensitivity range. LS/St/HS 2 Sensitivity control potentiometer (kΩ or %) 3 Coniguration: selection of Number of levels; and On/Off time Delay 4 Time delay control potentiometer Tt 5 Diagnostic button RM22LA32MR RM22LA32MT R Yellow LED: indicates relay output state. Presentation, description Zelio Control - Measurement and control relays Liquid level control relays RM22LA and RM22LG A1 A2 NC 12 11 14 10 20 30 70 80 100 R Sens Level RM22LG11MR DIAGNOSTIC 5 90 Min Max C 40 60 1 2 KΩ A1 A2 NC 12 11 14 R Sens Level RM22LG11MT DIAGNOSTIC Min Max C 10 20 30 70 80 100 5 90 40 60 1 2 KΩ RM22LA32MT 3 3 2 2 1 1 A1 A2 NC 12 11 14 22 21 24 RM22LA32MT DIAGNOSTIC Min Max C Sens Level Tt St. St. HS LS LS HS 1 2 1 2 10 20 30 70 80 100% 5 90 40 60 ON DELAY OFF DELAY 0,1 30s 5 10 20 25 R A1 A2 NC 12 11 14 22 21 24 R Sens Level Tt RM22LA32MR DIAGNOSTIC Min Max C St. St. HS LS LS HS 1 2 1 2 10 20 30 70 80 100% 5 90 40 60 ON DELAY OFF DELAY 0,1 30s 5 10 20 25 3 3 2 2 1 1 4 4 5 5 5 5 RM22LG11MR 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28617-EN version: 1.0
  • 14. 3 Operation Operating principle The liquid level control relays are designed to control levels of: b Conductive liquid Relay controls the levels of conductive liquids and measures the levels by means of resistive probes. The operating principle is based on measurement of the apparent resistance of the liquid between two submerged probes. When this value is less than the threshold setting on the front panel of the device, the relay changes state. To avoid electro- lytic phenomena, an a.c. current runs across the probes. The control of one single level can be achieved by using the 2nd selector switch. In this case, the Max. level probe stays up in the air and an adjustable time delay avoids any wave effect. These two products activate their output relay when a tank is either emptying or illing. Level control relay with adjustable sensitivity range In these relays, a selector coniguration switch on the front panel allows selection of the required sensitivity range and the empty or ill function. A second switch allows selection of the number of levels (1 or 2) and the type of time delay in the case of level 1 mode. The coniguration of these switches is taken into account on energization. b If the coniguration switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs lash to signal the position error. b If the coniguration switch position is changed while the device is operating, all the LEDs lash, but the product continues to operate normally with the function selected at the time of energization preceding the change of position. b If the coniguration switch is returned to the original position selected prior to the last energization, the LED’s return to their normal state. b Control of two levels, empty and ill function v empty function level: 2, function: - LS (Low Sensitivity: 250 W…5 kW), - St (Standard Sensitivity: 5 kW…100 kW), - HS (High Sensitivity: 50 kW…1 MW). The output relay stays open until the liquid reaches the Max. level probe. As soon as the Max. level is reached, the contact closes and then allows emptying of the tank (valve opens, pump starts, ...). When the level drops below the Min. level, the contact opens to stop the emptying process. v ill function level: 2, function: - LS (Low Sensitivity: 250 W…5 kW), - St (Standard Sensitivity: 5 kW…100 kW), - HS (High Sensitivity: 50 kW…1 MW). The output relay stays energized until the liquid reaches the Max. level probe. As soon as the Max. level is reached, the contact opens and the pump stops. When the level drops below the Min. level, the contact closes again and pumping re-starts to raise the level. Function diagram b Fill/Empty function (Two levels) Zelio Control - Measurement and control relays Liquid level control relays RM22LA and RM22LG R/R1/R2 R/R1/R2 Supply Un Relays Output Relays Output Max. level Min. level 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28617-EN version: 1.0
  • 15. 4 Operation (continued) Zelio Control - Measurement and control relays Liquid level control relays RM22LA and RM22LG Operating principle (continued) Level control relay with adjustable sensitivity range (continued) b Control of one level, empty function v level: 1 - on delay functions: - LS (Low Sensitivity: 250 W…5 kW), - St (Standard Sensitivity: 5 kW…100 kW), - HS (High Sensitivity: 50 kW…1 MW). When the liquid level rises above the probe for a time greater than the time delay value Tt set on the front panel, the relay is energized and stays energized until the liquid level drops back to the probe. If the liquid drops back below the set level before the end of the time delay, the relay does not energize. Function diagram b Empty function T on b Control of one level, empty function v level: 1 - off delay functions: - LS (Low Sensitivity: 250 W…5 kW), - St (Standard Sensitivity: 5 kW…100 kW), - HS (High Sensitivity: 50 kW…1 MW). When the liquid level rises above the probe, the relay instantly energizes and stays energized until the liquid again reaches the probe level for a time Tt set on the front panel. If the liquid drops back below the set level before the end of the time delay period, the relay stays energized. Function diagram b Empty function T off b Control of one level, ill function v level: 1 - on delay functions: - LS (Low Sensitivity: 250 W…5 kW), - St (Standard Sensitivity: 5 kW…100 kW), - HS (High Sensitivity: 50 kW…1 MW). When the liquid level drops below the probe for a time greater than the time delay value Tt set on the front panel, the relay is energized and stays energized until the liquid level rises back up to the probe. If the liquid rises back above the set level before the end of the time delay period, the relay does not energize. Function diagram b Fill function T on Tt Tt Tt R/R1/R2 Supply Un Relays Output Level Tt Tt Tt R/R1/R2 Supply Un Relays Output Level Tt Tt Tt R/R1/R2 Supply Un Relays Output Level 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28617-EN version: 1.0
  • 16. 5 Operation (continued), references Zelio Control - Measurement and control relays Liquid level control relays RM22LA and RM22LG Operating principle (continued) Level control relay with adjustable sensitivity range (continued) v level: 1 - off delay functions: - LS (Low Sensitivity: 250 W…5 kW), - St (Standard Sensitivity: 5 kW…100 kW), - HS (High Sensitivity: 50 kW…1 MW). When the liquid level drops below the probe, the relay instantly energizes and stays energized until the liquid level again reaches the probe level and stays above it for a time greater than the time delay period Tt set on the front panel. If the liquid drops back below the set level before the end of the time delay period, the relay stays energized. Function diagram b Fill function T off References Function Rated supply voltage Measurement range Time delay Output Reference Weight V Ω kg/lb b Level 1/ Level 2 b Fill operation b Empty operation z 24…240 5 K…100 K No 1 C/O 8 A RM22LG11MR 0.100/ 0.220 a 380…415 5 K…100 K No 1 C/O 8 A RM22LG11MT 0.100/ 0.220 z 24…240 250...1 M On/Off delay (0.1...30 s) 2 C/O 8 A RM22LA32MR 0.110/ 0.242 a 380…415 250...1 M On/Off delay (0.1...30 s) 2 C/O 8 A RM22LA32MT 0.110/ 0.242 Tt Tt Tt R/R1/R2 Supply Un Relays Output Level RM22LA32MR RM22LG11MR RM22LG11MT RM22LA32MT 2 1 3 4 5 6 7 8 9 10 2 1 3 4 5 6 7 8 9 10 28617-EN version: 1.0
  • 17. Vecchia gamma NUOVA GAMMA RM4JA01B RM22JA21MR RM4JA01F RM22JA21MR RM4JA01M RM22JA21MR RM4JA31F RM22JA31MR RM4JA31M RM22JA31MR RM4JA31MW RM22JA31MR RM4JA31Q obsoleto,nessuna sostituzione RM4JA32F RM35JA32MR RM4JA32M RM35JA32MR RM4JA32MW RM35JA32MR RM4JA32Q RM35JA32MT RM4UA01B RM22UA21MR RM4UA01F RM22UA21MR RM4UA01M RM22UA21MR RM4UA02B RM22UA22MR RM4UA02F RM22UA22MR RM4UA02M RM22UA22MR RM4UA03B RM22UA23MR RM4UA03F RM22UA23MR RM4UA03M RM22UA23MR RM4UA31F RM22UA31MR RM4UA31M RM22UA31MR RM4UA31MW RM22UA31MR RM4UA31Q obsoleto,nessuna sostituzione RM4UA32F RM22UA32MR RM4UA32M RM22UA32MR RM4UA32MW RM22UA32MR RM4UA32Q obsoleto,nessuna sostituzione RM4UA33F RM22UA33MR RM4UA33M RM22UA33MR RM4UA33MW RM22UA33MR RM4UA33Q RM22UA33MT RM4UB34 RM22UB34 RM4UB35 RM22UB34 RM4TA01 RM22TA31 RM4TA02 RM22TA33 RM4TA31 RM22TA31 RM4TA32 RM22TA33 RM4TG20 RM22TG20 RM4TR31 RM22TR31 RM4TR32 RM22TR33 RM4TR33 RM22TR31 RM4TR34 RM22TR33 RM4TR35 obsoleto,nessuna sostituzione RM4TU01 RM22TU21
  • 18. RM4TU02 RM22TU23 RM4LA32B RM22LA32MR RM4LA32F RM22LA32MR RM4LA32M RM22LA32MR RM4LA32MW RM22LA32MR RM4LA32Q RM22LA32MT RM4LG01B RM22LG11MR RM4LG01F RM22LG11MR RM4LG01M RM22LG11MR RM4LG01Q RM22LG11MT