More Related Content Similar to Mag 8000 gsm ast 2015 w35 Similar to Mag 8000 gsm ast 2015 w35 (20) Mag 8000 gsm ast 2015 w351. page 1 I IA SC PS3
s
SITRANS F M MAG 8000 GSM / GPRS
Automated Meter Reading system
Welcome to
Advance Service Training
2. page 2 I IA SC PS3
s
What are your;
• Expectations to the training
• Knowledge with MAG 8000 GSM/ GPRS
(good and bad)
• Questions you want an answer on
SITRANS F M MAG 8000 GSM / GPRS
3. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
3
MAG 8000 Water Meter Applications
Billing meters
DMA / Leakage Monitoring meters
4. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
4
Automated Meter Reading (AMR) – via GSM / GPRS
Network Management
Leakage Monitoring Services
Billing Services
Asset Management
5. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
5
MAG 8000 GSM / GPRS Solution
Monitoring / Leakage
Volume, Flow, Direction
Consumption Profile
Leakage alert
Statistic
Datalogger
Alarms
Pressure & 1 more
Billing
Volume (direction)
Tariffs
Settling date
Datalogger
Alarms
Pressure
(Delivery/Quality)
6. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
6
MAG 8000 GSM / GPRS Solution
Mag 8000 GSM / GPRS
Based on the GSM / GPRS technology
Built-in system not compromising the
IP68 protection of the MAG 8000 meter
Remote antenna 5 m cable length
Easy plug & play for retrofit
Optional two analogue inputs
One input 5 V DC powered by MAG
8000 (Pressure)
One standard 4–20 mA
(externally supplied)
7. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
7
Battery operation time
(Total battery calculation MAG 8000 + GSM/GPRS)
Typical lifetime transmitting once a day
(Good signal connections / 25 degree Celsius)
- Internal battery 3 years (4,5)
- External battery 7 years (9)
MAG 8000 battery power, charge the GSM re-chargeable battery (min 8
hours charging time the first time, to reach 3,8 volt on the GSM battery.
MAG 8000 GSM / GPRS Solution
8. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
8
Internal data logger, with defined logging values for up to 1440 records
(send as a CSV file in a Email / SMS text)
Different sample rates and transmission time to offer open logs for various
applications (from 1 min logging to 255h / 1 min-1Month)
MAG 8000 GSM / GPRS Solution
9. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
9
System and data is protected because;
GSM module is one-way communication system, i.e. GSM module will
only send measurement data in SMS or email, and can't receive data from
internet, i.e. no IP address visible on internet, therefore no way to hack the
module from internet.
GSM module can only be configured via SMS command, were a whitelist
protec and define which mobile numbers can configure the GSM module
GSM module only read data from MAG8000, and will therefore not
change data to MAG8000.
MAG 8000 GSM / GPRS Solution
10. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
10
Simple configuration via SMS
commands
Basic SMS reporting and alarms for
simple interfaces / billing information
MAG 8000 GSM / GPRS Solution
11. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
11
MAG 8000 GSM / GPRS – MAG 8000 Apps (Android)
Configuration
Commands
Log
12. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
12
AMR – Via MAG 8000 GSM / GPRS
POP 3
Pressure Input
2G
GPRS
SMS
Email
CSV data file
OPC HDA Server
OPC Client
Data
Data
Settings
125005H021 2011-05-10 17:08
FL 6.635 m3/h
T1 26.242
T2 0.151
T3 26.242
VU m3
A1 0.0 mA
A2 0.0 V
BT 99%
AL 02 06 07 11 13
124905H021 2011-05-10 17:05
BT 99%
Market experience ??
13. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
13
GSM / GPRS
access
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
Module configuration - Steps to make:
1. Installation & Voice Call test
2. Basic setting: SMS Configuration
1. Provider /SMS Server/ Internet
2. Commands test
3. User / Operation
3. Email Information: Check Web Mail & OPC Server
14. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
14
GSM / GPRS
access
Module configuration - Step 1:
1. Installation & Voice Call test
Always reset GSM module after installation
& Power up - 25 sec activation of GSM
module push button (stop after 4 LED flash
– correct reset by 4 fast LED flash).
SMS
EMAIL
MAG 8000 GSM / GPRS – Installation
Push button
ON/Factory Reset
Indication LED
ON/Factory Reset
15. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
15
Terminal connection
for analog inputs
Rechargeable
battery inlet
SIM Card / SD card
Combo Slot
Antenna connector
MAG 8000 GSM / GPRS module
Push button
ON/Factory Reset
Indication LED
ON/OFF/Factory Reset
16. For internal use only / © Siemens AG 2013. All Rights Reserved.
Step 1:
Open de enclosure, remove
battery and holder
Step 2:
Remove right gland lock from
MAG 8000 enclosure
Step 3:
Assemble antenna cable and
cable adapter and place gland
MAG 8000 GSM / GPRS – Installation
17. For internal use only / © Siemens AG 2013. All Rights Reserved.
Step 4:
Secure cable antenna and connect
it into GSM/GPRS module (click)
Step 5:
Place SIM card into module before
plugging module into MAG 8000.
Cut Simcard coner outside
Step 6:
Remove the two screws; carefully
mount GSM/GPRS module and
fasten it with screws / plug the
plastic holder.
MAG 8000 GSM / GPRS – Installation
18. For internal use only / © Siemens AG 2013. All Rights Reserved.
Step 7:
Connect boost battery and place it
into MAG 8000
Step 8:
Place battery holder and battery,
connect the power, close the
enclosure (wider part under the
SIM card side).
Note:
For first configuration wait for 8 hours to ensure full charge on
the battery (small GSM battery voltage > 3,8).
MAG 8000 GSM / GPRS – Installation
19. For internal use only / © Siemens AG 2013. All Rights Reserved.
Step 9:
Push the activation button for 5
sec. to connect to the network (1
Led light flash) and module is
connected for 3 min.
Step 10:
Wait ½ min. and make a Voice
Call – OK if normal sound call is
present, and no GSM connection if
voice answering machine start.
Note:
If GSM module has been installed before – Reset the module
by pushing the activation button for 25 sec. (4 LED light & 4
fast LED flashing feedback for rest OK).
MAG 8000 GSM / GPRS – Installation & Test
20. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
20
MAG 8000 GSM / GPRS module – Network Connection
Push button
ON/Factory Reset
Indication LED
ON/Factory Reset
To reduce power consumption is the GSM module default in sleep mode, but
the following function will activate its network connections.
Activation of PUSH button for 5 Sec. (LED Flash 1. time)
Active network connection for min. 3 min. (after last interaction)
Module program to send Email / SMS – defined by last connection time
where transmission interval is configured (P56)
Module sends SMS alarms
Note: Each time it connect will it download SMS (Commands / Configurations)
21. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
21
GSM / GPRS
access
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
Module configuration – Step 2:
1. Installation & Voice Call test
2. Basic setting: SMS Configuration
1. Provider /SMS Server/ Internet
2. Commands test
3. User / Operation
3. Email Information: Check Web Mail & OPC Server
22. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
22
GSM / GPRS
access
Step 2.1: Simcard provider configuration
1. Select Simcard provider ID – MCC / MNC (P2)
2. Select SMS Service Center Number (P3)
3. Select GPRS Email access (P10)
Note: Some provider has more solutions – tried these out
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
23. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
23
MAG 8000 GSM / GPRS provider configuration
Use Google or Wikipedia …..
SIM Card Requirements
Selected Simcard Provider – find configuration information on the Internet
Provider network ID / Mobile Country Code + Mobile Network Code
(MCC+MNC) (P2), a 5 or 6 digit number - e.g. TDC Denmark = 23801
SMS communication / Service Center phone number (P3) –
e.g. TDC Denmark +45 40390999.
Email communication / Access Point Name APN (P10) –
e.g. TDC Denmark = Internet
2G GSM / GPRS network
Security PIN code = MAG8000
(Default 1000) Use phone to change it.
24. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
24
MAG 8000 GSM / GPRS – SMS Communication
SMS configuration
Syntax:
Configuration;<Parameter 1>=<value>;
Note: Every command ends with “;”
Important !!!
SMS Commands always
as CAPITAL LETTERS
Only feedback if message
is correct
25. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
25
MobileCountryCode / MobileNetworkCode selection -
http://en.wikipedia.org/wiki/Mobile_country_code
26. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
26
Provider Settings – TDC Denmark (23801)
Use Google or Wikipedia …..
Email Access Point Name APN
http://wiki.apnchanger.org/Denmark
SMS Service Center Phone Number
http://www.gsmsite.de/smsc.htm
27. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
27
MAG 8000 GSM / GPRS provider configuration
Vodafone Simcard Blue.de (eplus) Simcard
28. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
28
GSM / GPRS
access
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
Module configuration – Step 2:
1. Installation & Voice Call test
2. Basic setting: SMS Configuration
1. Provider /SMS Server/ Internet
2. Commands test
3. User / Operation
3. Email Information: Check Web Mail & OPC Server
29. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
29
MAG 8000 GSM / GPRS – SMS Commands
Always send as CAPITAL LETTERS,
only feedback if message is correct.
30. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
30
GSM / GPRS
access
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
Module configuration – Step 2:
1. Installation & Voice Call test
2. Basic setting: SMS Configuration
1. Provider /SMS Server/ Internet
2. Commands test
3. User / Operation
3. Email Information: Check Web Mail & OPC Server
31. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
31
GSM / GPRS
access
Step 2.3: User & data receiver configuration
1. User security on configuration & commands (P4 to P6)
(White list – special reset function)
1. SMS data receiver (P7 to P9)
2. Email Account (P14 to P20)
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
32. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
32
MAG 8000 GSM / GPRS User configuration
Own Mobile number
for SMS information
P7- P8 Only Alarms
P9 Only Flow Data
33. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
33
AMR – MAG 8000 GPRS System Solution
GPRS
Email CSV data file
Gr.b
Gr.a
Gr.c
mag8000_ast@mag8000.com as main receiver
mag8000_ast?@mag8000.com as meter sender (?=01,02,03…,10)
Note !! Only small letters
One.com
MAG8000.com
Own Email adress
OPC HDA Server OPC Client
34. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
34
MAG 8000 GSM / GPRS Hosting – Domain Server
Email Hosting / Domain server system requirements
POP3 Server
Open port 25
No Secure Socket Layer protocol (SSL Certificated)
No limitation in email traffic (accounts / email per time)
No change of data contence (CSV - CR)
For test purpose use xx@MAG8000.com hosted by
One.com – Web account / email own by Siemens FL
Contact Peder.Spek@Siemens.com for email accounts.
35. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
35
MAG 8000 GSM / GPRS Hosting – One.com
mag8000_ast@mag8000.com as receiving email
Password: 12345678
36. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
36
MAG 8000 GSM / GPRS Hosting – One.com
mag8000_ast@mag8000.com as main receiver
mag8000_ast01@mag8000.com as device email in the groups (02,03, 04..10)
Password: 12345678
Note !! Only small letters
37. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
37
MAG 8000 GSM / GPRS User configuration
Own Email and test Email
for central information
38. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
38
GSM / GPRS
access
Step 2.3: Operation configuration
1. Data collecting / logging interval (P55)
2. Data transmission interval (P56)
3. Data logging start / synchronise (P61)
4. Data transmission form – SMS/Email (P52)
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
39. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
39
Data collection / logging interval (P55)
1. 1 to 255min or 1 to 255h (min - hours)
Data transmission interval (P56)
1. 1 to 744h, 1 to 31d, 1M (hours-days-Month)
Data synchronise time (P61)
1. 00:00 to 23:59
MAG 8000 GSM / GPRS – Hands-On Training
40. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
40
Push button function (LED flash indication)
1 LED - 5 sec. activation enable the network connection for receiving SMS
information
3 LED – Reset communication network
4 LED – 20-25 sec. activation of factory reset – clear the memory (reset
power consumption …), but all setting still remained
MAG 8000 GSM / GPRS – Hands-On Training
41. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
41
GSM / GPRS
access
SMS
EMAIL
MAG 8000 GSM / GPRS – Hands-On Training
Module configuration – Step 2:
1. Installation & Voice Call test
2. Basic setting: SMS Configuration
1. Provider /SMS Server/ Internet
2. Commands test
3. User / Operation
3. Email Information: Check Web Mail & OPC Server
42. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
42
MAG 8000 GSM / GPRS – Email Data
Data receiver of Email information
The GSM module has a list of 3 email adress,
that will receive email information from the meter.
P18 - P20 will receive Email data.
43. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
43
MAG 8000 GSM / GPRS – Email Data
Data receiver of Email information
Analog 1 (4-20mA) - Values presented as 4,0-20,0mA
Analog 2 (0-5V) – Value presented as 0,0-5,0V
Email Alarm value in decimal,
with a bit order were ”1” mean
Active alarm
Example = 96(dec) = 60(Hex)
= 1100000(Bin) / bit alarm
44. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
44
MAG 8000 GSM / GPRS – Configuration Information
Module configuration
Only as Email
45. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
45
Application running on the back
MAG 8000 GSM / GPRS – OPC Server
Mag8000_pm2014@mag8000.com
Mag8000_pm2014@mag8000.com
12345678
pop.one.com
46. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
46
MAG 8000 GSM / GPRS – Analogue Input
Analogue Input
A2 = Current Input from Radiometric Pressure Transducer
Analogue configuration
SMS enabling: Configuration;53=1;
MAG 8000 deliver 5V to the transducer,
signal back from 0,5 to 4,5V equal
transducer pressure rating.
Response time and current consumption
is important, as GSM is specify to 5mA
and measuring window of x mS
47. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
47
MAG8000 GSM – Analog input
Radiometric pressure transmitter
Default von factory
Standard M12 Connection on pressure transmitter – Our connection must be changed
Open our connector and change;
- Move Green (5) to pin 3
- Move Brown (3) to pin 1
- Move White (1) to pin 5
- Kepp Gray wire on pin 2
- Kepp Yellow wire on pin 4
Huba 528 ()
WIKA A-10
48. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
48
MAG 8000 analoge cable with M12 Connector.
Connector in GSM module
MAG8000 GSM – Analog input
Radiometric pressure transmitter
49. For internal use only / © Siemens AG 2009. All Rights Reserved.
Industry Sector
49
MAG 8000 GSM / GPRS – Analogue Input
M12 Wire connection
SIEMENS M12 connector cable do not
fit with transducer pin connections –
It can damage the transducer!!
Two analogue inputs in one cable
MAG 8000 - M12 Wire connection
M12 Wire connections tested with WIKA A-10 & Huba 528
Remember selection of pin connections
HUBA 582 has same connection as
WIKA A10, if ”7” for radiometric
output 10-90% / 5V is selected, and
the ”3” in eletrical connection for
M12 .
50. For internal use only / © Siemens AG 2009. All Rights Reserved.
MAG 8000 /
GSM / GPRS Module
Questions?