Indonesian Journal of Electrical Engineering and Computer Science
Vol. 6, No. 3, June 2017, pp. 583 ~ 590
DOI: 10.11591/ijeecs.v6.i3.pp583-590  583
Received January 2, 2017; Revised April 25, 2017; Accepted May 11, 2017
Impact of Distributed Generation on Voltage Profile in
Radial Feeder
Charles R. Sarimuthu*, Vigna K. Ramachandaramurthy, H. Mokhlis, K. R. Agileswari
Power Quality Research Group, Department of Electrical Power Engineering, Universiti Tenaga Nasional,
Jalan IKRAM-UNITEN, 43000 Kajang, Selangor, Malaysia.
*Corresponding author, e-mail: charlzray@yahoo.com
Abstract
The use of distributed generation (DG) within distribution systems has increased for the last two
decades due to worldwide increase in demand for electricity and governmental policy change from
“conventional” energy to “green” energy. High levels of penetration of DG have many significant benefits
but also come with many drawbacks such as voltage drop and power losses. This study presents the
impact of DG at different locations in a distribution feeder in terms of the feeder voltage profile. A radial
distribution system is simulated using PSCAD/EMTDC simulation software while changing the size and
location of DG in the system. The obtained results are used for better understanding on the impact of DG
on voltage profile in radial distribution feeder.
Keywords: voltage profile, radial distribution network, distributed generation, distribution systems
Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved.
1. Introduction
Electrical power generation, transmission and distribution sectors are the three different
categories of electrical power systems where each category are owned and operated by a
separate company. For profitable operation, these electrical companies often maximize their
profits and minimize their operating costs. This is done by way of reducing spending on the
maintenance, which leads to a lot of technical problems in the electrical network [1].
The most expensive technical problems usually happen in the distribution system.
Voltage regulation is one of the main problems in radial distribution network [2]. The most
common devices and techniques used for maintaining the voltage levels are transformer
equipped by load tap changer (LTC), supplementary line regulators installed on distributed
feeders, shunt capacitor switched on distribution feeders [3] and shifting transformers towards
the load center [4]. A substation’s LTC transformer equipped with a Line Drop Compensator
(LDC) operation increases its output voltage to readjust the voltage level and to compensate the
expected increase of the feeder’s voltage drop [5]. Feeder’s voltage regulator regulates the
voltage at the utilization point between ± 10% of the base voltage. Shunt capacitor is used to
regulate the voltage and the reactive power flow at the point of connection with the distribution
feeder with the aim of improving the voltage profile at the far-end feeder point. Switch shunt
capacitor are usually placed in distribution feeder together with voltage regulators in the same
distribution network to maintain adequate voltage profile especially for long feeders [6].
Implementing DG as a source of active power in the distribution system is considered a
new effective approach to solve the voltage regulation problem [7]. DG includes conventional
and renewable technologies such as photovoltaic, wind turbines and hydro, storage energy
devices, batteries and flywheel, fuel cells [8, 9], combined heat and power modules (CHP) and
microturbines. In the past, DGs were available in small size and designed to serve a single end-
user’s site but nowadays it is considered as large co-generation providing up to hundreds of
MWatts to customers or back to grid. Characteristics of distributed sources are different. While
synchronous generators can produce real power and produce and consume reactive power,
induction generators used for wind applications can only produce active power and they need
reactive power [10]. Photovoltaics and fuel cells are DC sources and require power electronics
interface to connect to an AC system [10].
Based on IEEE Standard 1547, all types of distributed sources should not actively
regulate distribution system voltages [11]. Therefore, constant power factor control mode of
 ISSN: 2502-4752
IJEECS Vol. 6, No. 3, June 2017 : 583 – 590
584
operation is preferred although synchronous generators are capable of controlling voltage at the
point of connection point of DG. The selection of DG size and location is important since
otherwise, adverse effects, such as voltage rise, mis-operation of protection relays may occur
[12].The purpose of this paper is to examine the change in feeder voltage profile depending on
the size and location of DG in the system.
2. Research Method
Most developing countries have experienced progressing demand on their power
system network [13]. Therefore DGs are employed to cater for these demands. The most
common type of voltage control method is by using on-load tap changer transformer [5]. For
operating the tap changer of a power transformer, the automatic voltage control (AVC) relay
initiates a signal to bring the controlled voltage back within the specified limits. When automatic
load-tap-changing transformers operating in parallel are located remotely from each other,
interconnecting control wires are impractical and a modification of the line-drop compensator
setting is necessary to obtain satisfactory operation. This type of control is sometimes referred
to as the "reduced" or "reversed" reactance method. This method serves to distinguish between
circulating current and load current and does this by virtue of a difference in power factor
between these currents. A compensator which employs normal resistance and reverse
reactance results in a characteristic such that high power-factor currents cause the transformer
to increase the voltage and low power-factor currents cause it to decrease. Thus, it is possible
to set compensators so that load currents will cause a boosting operation and circulating
currents will cause a slight bucking operation of transformers with no intervening impedance.
These are the two methods from which we can control the AVC relay namely the negative
reactance compounding (NRC) and LDC. The negative reactance compounding (NRC) method
helps to maintain similar tap positions for paralleled transformers by changing the polarity of
reactance of LDC setting – XLDC.
In NRC operation, transformer T1 has much higher tap position compared to
transformer T2. Due to the difference in tap position, a circulating current will flow between
transformer T1 and transformer T2. The circulating current causes current IT1 to be shifted in
clockwise direction and current IT2 in anti-clockwise direction. Both current IT1 and IT2 which
passes through the ZNRC setting create a voltage drop IT ∙ZNRC. The AVC relay uses this voltage
drop to determine the proper tap position. Since the voltage at transformer T1 is higher than the
target voltage therefore the AVC relay initiates a tap down operation. Similarly the AVC relay of
transformer T2 initiates a tap up operation. The action stops with a similar tap position of both
the parallel transformers when the circulating current is eliminated and target voltage is
achieved. The advantage of NRC scheme is that it can operate with transformers at different
positions in the networks and it does not need to be identical anymore due to the independent
action of each transformer. However, the NRC fails to operate satisfactorily when the power
factor changes from a set point. Integration of irregular DG into the network effects the NRC
operation. Apart from that, negative value of XLDC setting could cause poor performance of LDC.
An increased value of RLDC is needed in order to maintain the performance of LDC.
The aim of line-drop compensation is to keep the voltage constant, not at the local bus
bar on the transformer secondary, but at some remote load center. Normal practice is to sense
the load current (local to the transformer) and from this to simulate the voltage drop in the line to
the remote load center. Modern voltage-control relays include line-drop compensation as
standard. OLTC consist of two fixed windings and a third tap winding (regulation winding)
connected in series with either winding 1or winding 2. A +30° or - 30° phase shift is introduced
when winding 1 or winding 2 are connected in delta. In automatic mode voltage regulator on
and the signal applied at the Vm inputs is monitored and the voltage regulator asked for tap
change. The three-phase two-winding transformer or autotransformer uses an on-load tap
changer (OLTC) for regulating voltage on a transmission or distribution system. Controlling
voltage on a transmission system will affect primarily flow of reactive power, which, in turn, will
affect the power transfer limits. Although the regulating transformer does not provide as much
flexibility and speed as power-electronics based FACTS, it can be considered as a basic power
flow controller.
To overcome frequent tap operation due to DG interconnection, several artificial
intelligence methods are introduced for AVC relay operation. Fuzzy logic systems are much
IJEECS ISSN: 2502-4752 
Impact of Distributed Generation on Voltage Profile in Radial Feeder (Charles R. Sarimuthu)
585
preferred compared to other artificial intelligent systems because the control rules can be
implemented using simple “IF-THEN” relations [5].
1) Fuzzy Membership Function
a. Secondary voltage of the OLTC transformer: very high (VH), high (H), normal (N), low (L),
very low (LV)
b. Phase angle of current through the OLTC transformer: high (H), normal (N), low (L)
c. Change of current: negative (N), zero (Z), positive (P)
d. Tap position: low (L), normal (N), high (H)
e. AVC relay voltage: high (H), normal (N), low (L)
2) Fuzzy Control Rules
a. If voltage is very low, then AVC relay voltage is low.
b. If voltage is low, tap position is normal and power angle is normal, then AVC relay voltage
is normal.
c. If voltage is low, tap position is low and power angle is normal, then AVC relay voltage is
low.
d. If voltage is normal and power angle is low, then AVC relay voltage is low.
e. If voltage is normal and power angle is normal, then AVC relay voltage is normal.
f. If voltage is normal and power angle is high, then AVC relay voltage is low.
g. If voltage is high, tap position is normal and power angle is normal, then AVC relay voltage
is normal.
h. If voltage is high, tap position is high, then AVC relay voltage is high.
i. If voltage is very high, then AVC relay voltage is high.
j. If voltage is normal and power angle is low, then AVC relay voltage is normal.
k. If voltage is normal and power angle is normal, then AVC relay voltage is normal.
l. If voltage is normal and power angle is high, then AVC relay voltage is high.
The other advantages of these systems are that they are simpler and able to simplify
design complexity and lessen the hardware cost .Fuzzy logic systems are beneficial because
they allow the usage of fuzzy rules which are more expressive than crisp values [14]. The fuzzy
logic systems also requires less computation time.
2.1. Case Study
Small scale DG of less than 10MW is normally connected directly to the utility system at
the sub transmission and distribution level [15]. In this study, a radial distribution test system
operating at nominal voltage level of 11kV is modelled using PSCAD/EMTDC software for
simulation purpose. The radial test system used in the simulation is shown in Figure 1. Different
operating scenarios of DG connections were considered as follows:
a. Case 1, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous
generators each is connected at bus 4.
b. Case 2, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous
generators each is connected at bus 3.
c. Case 3, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous
generators each is connected at bus 2.
d. Case 4, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous
generators each is connected at bus 1.
Figure 1. 11 kV radial type test system
 ISSN: 2502-4752
IJEECS Vol. 6, No. 3, June 2017 : 583 – 590
586
2.2. The Simulation Process
First, the simulation is carried out without inserting the DG into the network. The voltage
at each bus and the active and reactive power feed by the distribution substation are measured.
Second, the simulation is run with implementing the DG into the network (at bus 4). Again, the
voltage at each bus and the active and reactive power feed by the distribution substation and
the installed DG are measured. Third, repeat the second step two times and at each time vary
the location and size of DG at several buses (bus 3, bus 2 and bus 1). The output power of the
DG is kept constant at all cases. The summary of the simulated cases are shown in Table 1. No
tap operation is initiated to study the effect of DG on the feeder voltage profile.
Table 1. The comparison between each case
Test Case Description
No DG connection
1 (a) The distribution system operates with 4.0 MW DG connected at bus 4.
(b) The distribution system operates with 5.5 MW DG connected at bus 4.
(c) The distribution system operates with 6.5 MW DG connected at bus 4.
(d) The distribution system operates with 7.0 MW DG connected at bus 4.
2 (a) The distribution system operates with 4.0 MW DG connected at bus 3.
(b) The distribution system operates with 5.5 MW DG connected at bus 3.
(c) The distribution system operates with 6.5 MW DG connected at bus 3.
(d) The distribution system operates with 7.0 MW DG connected at bus 3.
3 (a) The distribution system operates with 4.0 MW DG connected at bus 2.
(b) The distribution system operates with 5.5 MW DG connected at bus 2.
(c) The distribution system operates with 6.5 MW DG connected at bus 2.
(d) The distribution system operates with 7.0 MW DG connected at bus 2.
4 (a) The distribution system operates with 4.0 MW DG connected at bus 1.
(b) The distribution system operates with 5.5 MW DG connected at bus 1.
(c) The distribution system operates with 6.5 MW DG connected at bus 1.
(d) The distribution system operates with 7.0 MW DG connected at bus 1.
3. Results and Analysis
Figure 2 shows the voltage profile through the whole system’s buses under study
without DG connection. It is observed that the voltage drops linearly starting from the distribution
substation to the far-end load in the distribution network under study.
Figure 2. The distribution’s network voltage profile without DG
From Figure 4 it is obvious that the voltage level at bus 4 increases when DG is
connected (at bus 4). DG’s function of providing part of the required demand in the distribution
network improves the voltage at the point of DG connection.
1.02
1.00
0.98 0.96
0.94
0.96
0.98
1.00
1.02
1.04
1.06
1 2 3 4
Voltageinper
unit
Bus Number
IJEECS ISSN: 2502-4752 
Impact of Distributed Generation on Voltage Profile in Radial Feeder (Charles R. Sarimuthu)
587
Figure 3. 11 kV radial type test system for case 1
Figure 4. The distribution’s network voltage profile for case 1
Figure 4 shows that the DG is able to further improve the voltage profile along the
feeder when its capability is increased. Larger DG size contributes to increased source of active
power which improves the voltage profile throughout the distribution network. It is observed that
a more uniform voltage profile along the distribution feeder is achievable if the DG is supplying a
large percentage of the required demand. However, generation exceeding the feeder load could
cause DG saturation to occur. DG saturation refers to the point at which large DGs are installed
such that it becomes technically infeasible to operate on a single distribution feeder.
Figure 5. 11 kV radial type test system for case 2
Figure 6. The distribution’s network voltage profile for case 2
0.96
0.98
1
1.02
1.04
1.06
Bus 1 Bus 2 Bus 3 Bus 4
Voltageinperunit
case 1 (a)
case 1 (b)
case 1 (c)
case 1 (d)
0.96
0.98
1
1.02
1.04
1.06
Bus 1 Bus 2 Bus 3 Bus 4
Vltageinperunit
case 2 (a)
case 2 (b)
case 2 (c)
case 2 (d)
 ISSN: 2502-4752
IJEECS Vol. 6, No. 3, June 2017 : 583 – 590
588
Figure 6 shows that the voltage level at bus 3 increases when DG is connected (at
bus 3). Based on simulation results, it is also observed that DG connection at bus 3 reduces the
distribution substation required capabilities all over the distribution network. The results shows
that a more improved voltage profile along the feeder is achievable if the DG is capable of
providing a larger percentage of the required demand in the distribution network.
Figure 7. 11 kV radial type test system for case 3
Figure 8. The distribution’s network voltage profile for case 3
Figure 8 proves that DG output power supplying for a larger part of required demand is
able to improve the overall voltage profile along the distribution feeder. It is observed that higher
voltage level of the far-end load side of the distribution network is achievable when the DG
capability is increased.
Figure 9. 11 kV radial type test system for case 4
0.96
0.98
1
1.02
1.04
1.06
Bus 1 Bus 2 Bus 3 Bus 4
Voltageinperunit
case 3 (a)
case 3 (b)
case 3 (c)
case 3 (d)
IJEECS ISSN: 2502-4752 
Impact of Distributed Generation on Voltage Profile in Radial Feeder (Charles R. Sarimuthu)
589
Figure 10. The distribution’s network voltage profile for case 4
Figure 10 shows that the voltage drops linearly starting from the substation to the far-
end load in the distribution network when DG is connected at bus 1. However, the voltage level
at all the buses is higher compared to without DG connection into the system. Simulation result
proves that the connected DG shares the responsibility of supplying the required demand with
the substation. It is observed that a larger capacity of DG contributes to a larger part of required
demand therefore increasing the voltage level in each bus compared to the scenario without DG
connection.
The summary of the simulation results are shown in Table 2.
Table 2. Simulation result for each case
Test Case Voltage Level (in per unit value)
Bus 1 Bus 2 Bus 3 Bus 4
No DG 1.02 1.00 0.98 0.96
1 (a) 1.03 1.01 0.99 0.97
(b) 1.04 1.02 1.00 0.99
(c) 1.05 1.02 1.01 1.00
(d) 1.05 1.03 1.01 1.00
2 (a) 1.03 1.01 0.99 0.97
(b) 1.04 1.02 1.00 0.99
(c) 1.05 1.02 1.01 0.99
(d) 1.05 1.03 1.01 1.00
3 (a) 1.03 1.01 0.99 0.97
(b) 1.04 1.02 1.00 0.98
(c) 1.05 1.02 1.00 0.99
(d) 1.05 1.03 1.01 0.99
4 (a) 1.03 1.01 0.99 0.98
(b) 1.04 1.02 1.00 0.98
(c) 1.05 1.02 1.00 0.99
(d) 1.05 1.02 1.00 0.99
The siting of DGs at various locations shows positive impact on voltage profile.
However there is a possibility of voltage rise if the DG penetration level is too high [16]. The rise
in voltage could cause misoperation of protective devices and therefore adjustment or changes
of protective devices are required. In order to accommodate more DGs, the voltage profile along
the feeder should be kept within statutory limits (voltage between ± 10% of the base voltage)
and there is a need to employ intelligent devices for this purpose. Development of smart grid
allows for the use of intelligent devices and thus helps to keep the voltage level within statutory
limits.
4. Conclusion
A number of cases are simulated while changing the size and location of DG in the
system. The following conclusions can be drawn from this study.
a. DG mainly provides part of the required demand in the distribution network.
b. DG implementation as a source of active power has a great positive impact on improving
the voltage profile through the entire distribution network.
c. DG reduces the distribution substation required capacities all over the distribution system.
0.96
0.98
1
1.02
1.04
1.06
Bus 1 Bus 2 Bus 3 Bus 4
Voltageinper
unit
case 4 (a)
case 4 (b)
case 4 (c)
case 4 (d)
 ISSN: 2502-4752
IJEECS Vol. 6, No. 3, June 2017 : 583 – 590
590
Acknowledgement
This work is supported by Universiti Tenaga Nasional (UNITEN), Taylor’s University and
University of Malaya, Malaysia.
References
[1] Ding Xu and Girgis A. Optimal load shedding strategy in power systems with distributed generation.
IEEE Power Engineering Society Winter Meeting. 2001; 2: 788-793.
[2] Mahmoud Zadehbaghari, Rahim Ildarabadi, Majid Baghaei Nejad. Review of Dynamic Voltage
Restorer Application for Compensation of Voltage Harmonics in Power Systems. Indonesian Journal
of Electrical Engineering and Computer Science. 2017; 5(1): 58-71.
[3] Barker PP and De Mello RW. Determining the impact of distributed generation on power systems. I.
Radial distribution systems. IEEE Power Engineering Society Meeting. 2000; 3: 1645-1656.
[4] Ijumba NM, Jimoh AA and Nkabinde M. Influence of distribution generation on distribution network
performance. Proc. IEEE AFRICON. 1999; 2: 961-964.
[5] Charles R. Sarimuthu, Vigna K. Ramachandaramurthy, KR Agileswari and HazlieMokhlis. A review
on voltage control methods using on-load tap changer transformers for networks with renewable
energy sources. Renewable and Sustainable Energy Reviews. 2016; 62: 1154-1161.
[6] DIgSILENTPower Factory. Version 13.2. Manual. Germany: DIgSILENT GmbH; 2007.
[7] Joon-Ho Choi and Jae-Chul Kim. Advanced voltage regulation method of power distribution systems
interconnected with dispersed storage and generation systems. IEEE Transactions on Power
Delivery. 2001; 16: 329-334.
[8] Alok Kumar Mohanty, KB Yadav. Performance Characteristics of Six-Phase Induction Generator for
Renewable Power Generation. Indonesian Journal of Electrical Engineering and Computer Science.
2017; 5(2): 299-308.
[9] Lasseter B. Microgrids [distributed power generation]. IEEE Power Engineering Society Winter
Meeting. 2001; 1: 146-149.
[10] T Ackermann, G Anderson and L Soder. Distributed generation. A definition. Electrical Power
Systems Research. 2001; 57: 195-204.
[11] IEEE Standards Association. 1547-2003. IEEE Standard for Interconnecting Distributed Resources
with Electric Power Systems. New York: IEEE Press; 2003.
[12] Fatih M Nuroglu and Aysen Basa Arsoy. Voltage profile and short circuit analysis in distribution
systems with DG. IEEE Electrical Power and Energy Conference. 2008: 1-5.
[13] Mohd Khairuzzaman Mohd Zamani, Ismail Musirin, SaifulIzwan Suliman, Muhammad Murtadha
Othman and Mohd Fadhil Mohd Kamal. Multi-Area Economic Dispatch Performance Using Swarm
Intelligence Technique Considering Voltage Stability. International Journal on Advanced Science,
Engineering and Information Technology. 2017; 1: 1-7.
[14] Mohamed M Ismail, Ahmed F Elbendary, Abdelghany M Abdelghany. A Hybrid Fuzzy Logic FOPID
Position Controller for DC Motor Driving Tracking Systems System. Indonesian Journal of Electrical
Engineering and Computer Science. 2017; 5(2): 327-337.
[15] CJ Mozina. A tutorial on the impact of distributed generation (DG) on distribution systems. 21
st
Annual Conference for Protective Relay Engineers, College Station. 2008: 591-609.
[16] K Balamurugana, Dipti Srinivasana, Thomas Reindal. Impact of distributed generation on power
distribution systems. Energy Procedia. 2012; 25: 93-100.

More Related Content

What's hot

IRJET- Automatic Load Sharing of Transformer
IRJET- Automatic Load Sharing of TransformerIRJET- Automatic Load Sharing of Transformer
IRJET- Automatic Load Sharing of TransformerIRJET Journal
 
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...idescitation
 
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...ruban8
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET Journal
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSEditor IJMTER
 
Power Flow Control using Quadrature Boosters
Power Flow Control using Quadrature BoostersPower Flow Control using Quadrature Boosters
Power Flow Control using Quadrature Boostersbalasubu2k
 
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Niraj Solanki
 
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using IupqcMitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using IupqcIJMERJOURNAL
 
Enhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEnhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEng Ahmed Salad Osman
 
An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesDr. Sudhir Kumar Srivastava
 
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...IOSR Journals
 
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...IJMER
 
Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerSudeepthg Sudeepth
 
A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...
A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...
A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...paperpublications3
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...IDES Editor
 

What's hot (20)

Microgrid stability and control modes
Microgrid stability and control modes Microgrid stability and control modes
Microgrid stability and control modes
 
IRJET- Automatic Load Sharing of Transformer
IRJET- Automatic Load Sharing of TransformerIRJET- Automatic Load Sharing of Transformer
IRJET- Automatic Load Sharing of Transformer
 
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
Adaptive Modified Minimally Switched Hysteresis Controlled Shunt Active Power...
 
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
 
dstatcom
dstatcomdstatcom
dstatcom
 
Or3425552561
Or3425552561Or3425552561
Or3425552561
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
Power Flow Control using Quadrature Boosters
Power Flow Control using Quadrature BoostersPower Flow Control using Quadrature Boosters
Power Flow Control using Quadrature Boosters
 
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
 
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using IupqcMitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
 
Enhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEnhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOM
 
An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation Techniques
 
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
 
U4501117122
U4501117122U4501117122
U4501117122
 
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
 
Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controller
 
A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...
A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...
A Review On Voltage Regulators Placement In Unbalanced Radial Distribution Sy...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
 

Similar to 12 16134 paper 064 ijeecs(edit)

IRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET Journal
 
High step up boost converter based micro inverter with mppt and current control
High step up boost converter based micro inverter with mppt and current controlHigh step up boost converter based micro inverter with mppt and current control
High step up boost converter based micro inverter with mppt and current controlIAEME Publication
 
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...IAES-IJPEDS
 
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converterFuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converterIJERA Editor
 
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...IJPEDS-IAES
 
Base paper
Base paperBase paper
Base paperRAGHRAGH
 
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...IJMTST Journal
 
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...IJMTST Journal
 
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...IRJET Journal
 
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...IRJET Journal
 
DESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTER
DESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTERDESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTER
DESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTEREditor IJMTER
 
Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...
Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...
Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...IJARIDEA Journal
 

Similar to 12 16134 paper 064 ijeecs(edit) (20)

IRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel Inverter
 
R01043105113
R01043105113R01043105113
R01043105113
 
F42033342
F42033342F42033342
F42033342
 
High step up boost converter based micro inverter with mppt and current control
High step up boost converter based micro inverter with mppt and current controlHigh step up boost converter based micro inverter with mppt and current control
High step up boost converter based micro inverter with mppt and current control
 
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
 
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converterFuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
 
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
 
Base paper
Base paperBase paper
Base paper
 
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
 
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...
Simulation of a 13-Level Inverter with Facts Capability for Distributed Energ...
 
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
 
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
Power Quality Analysis Using Active NPC Multilevel inverter in PV sourced sta...
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
 
Solid-State Transformer (S2T) of Single Phase Matrix Converter
Solid-State Transformer (S2T) of Single Phase Matrix ConverterSolid-State Transformer (S2T) of Single Phase Matrix Converter
Solid-State Transformer (S2T) of Single Phase Matrix Converter
 
DESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTER
DESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTERDESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTER
DESIGNING AND IMPLEMENTATION OF BI - DIRECTIONAL ISOLATED FULL BRIDGE CONVERTER
 
Aq33247251
Aq33247251Aq33247251
Aq33247251
 
Aq33247251
Aq33247251Aq33247251
Aq33247251
 
Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...
Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...
Implementation Of Advanced Control Strategy For High-Frequency Single-Switch ...
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 

More from IAESIJEECS

08 20314 electronic doorbell...
08 20314 electronic doorbell...08 20314 electronic doorbell...
08 20314 electronic doorbell...IAESIJEECS
 
07 20278 augmented reality...
07 20278 augmented reality...07 20278 augmented reality...
07 20278 augmented reality...IAESIJEECS
 
06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...IAESIJEECS
 
05 20275 computational solution...
05 20275 computational solution...05 20275 computational solution...
05 20275 computational solution...IAESIJEECS
 
04 20268 power loss reduction ...
04 20268 power loss reduction ...04 20268 power loss reduction ...
04 20268 power loss reduction ...IAESIJEECS
 
03 20237 arduino based gas-
03 20237 arduino based gas-03 20237 arduino based gas-
03 20237 arduino based gas-IAESIJEECS
 
02 20274 improved ichi square...
02 20274 improved ichi square...02 20274 improved ichi square...
02 20274 improved ichi square...IAESIJEECS
 
01 20264 diminution of real power...
01 20264 diminution of real power...01 20264 diminution of real power...
01 20264 diminution of real power...IAESIJEECS
 
08 20272 academic insight on application
08 20272 academic insight on application08 20272 academic insight on application
08 20272 academic insight on applicationIAESIJEECS
 
07 20252 cloud computing survey
07 20252 cloud computing survey07 20252 cloud computing survey
07 20252 cloud computing surveyIAESIJEECS
 
06 20273 37746-1-ed
06 20273 37746-1-ed06 20273 37746-1-ed
06 20273 37746-1-edIAESIJEECS
 
05 20261 real power loss reduction
05 20261 real power loss reduction05 20261 real power loss reduction
05 20261 real power loss reductionIAESIJEECS
 
04 20259 real power loss
04 20259 real power loss04 20259 real power loss
04 20259 real power lossIAESIJEECS
 
03 20270 true power loss reduction
03 20270 true power loss reduction03 20270 true power loss reduction
03 20270 true power loss reductionIAESIJEECS
 
02 15034 neural network
02 15034 neural network02 15034 neural network
02 15034 neural networkIAESIJEECS
 
01 8445 speech enhancement
01 8445 speech enhancement01 8445 speech enhancement
01 8445 speech enhancementIAESIJEECS
 
08 17079 ijict
08 17079 ijict08 17079 ijict
08 17079 ijictIAESIJEECS
 
07 20269 ijict
07 20269 ijict07 20269 ijict
07 20269 ijictIAESIJEECS
 
06 10154 ijict
06 10154 ijict06 10154 ijict
06 10154 ijictIAESIJEECS
 
05 20255 ijict
05 20255 ijict05 20255 ijict
05 20255 ijictIAESIJEECS
 

More from IAESIJEECS (20)

08 20314 electronic doorbell...
08 20314 electronic doorbell...08 20314 electronic doorbell...
08 20314 electronic doorbell...
 
07 20278 augmented reality...
07 20278 augmented reality...07 20278 augmented reality...
07 20278 augmented reality...
 
06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...
 
05 20275 computational solution...
05 20275 computational solution...05 20275 computational solution...
05 20275 computational solution...
 
04 20268 power loss reduction ...
04 20268 power loss reduction ...04 20268 power loss reduction ...
04 20268 power loss reduction ...
 
03 20237 arduino based gas-
03 20237 arduino based gas-03 20237 arduino based gas-
03 20237 arduino based gas-
 
02 20274 improved ichi square...
02 20274 improved ichi square...02 20274 improved ichi square...
02 20274 improved ichi square...
 
01 20264 diminution of real power...
01 20264 diminution of real power...01 20264 diminution of real power...
01 20264 diminution of real power...
 
08 20272 academic insight on application
08 20272 academic insight on application08 20272 academic insight on application
08 20272 academic insight on application
 
07 20252 cloud computing survey
07 20252 cloud computing survey07 20252 cloud computing survey
07 20252 cloud computing survey
 
06 20273 37746-1-ed
06 20273 37746-1-ed06 20273 37746-1-ed
06 20273 37746-1-ed
 
05 20261 real power loss reduction
05 20261 real power loss reduction05 20261 real power loss reduction
05 20261 real power loss reduction
 
04 20259 real power loss
04 20259 real power loss04 20259 real power loss
04 20259 real power loss
 
03 20270 true power loss reduction
03 20270 true power loss reduction03 20270 true power loss reduction
03 20270 true power loss reduction
 
02 15034 neural network
02 15034 neural network02 15034 neural network
02 15034 neural network
 
01 8445 speech enhancement
01 8445 speech enhancement01 8445 speech enhancement
01 8445 speech enhancement
 
08 17079 ijict
08 17079 ijict08 17079 ijict
08 17079 ijict
 
07 20269 ijict
07 20269 ijict07 20269 ijict
07 20269 ijict
 
06 10154 ijict
06 10154 ijict06 10154 ijict
06 10154 ijict
 
05 20255 ijict
05 20255 ijict05 20255 ijict
05 20255 ijict
 

Recently uploaded

Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)dollysharma2066
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 

Recently uploaded (20)

🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 

12 16134 paper 064 ijeecs(edit)

  • 1. Indonesian Journal of Electrical Engineering and Computer Science Vol. 6, No. 3, June 2017, pp. 583 ~ 590 DOI: 10.11591/ijeecs.v6.i3.pp583-590  583 Received January 2, 2017; Revised April 25, 2017; Accepted May 11, 2017 Impact of Distributed Generation on Voltage Profile in Radial Feeder Charles R. Sarimuthu*, Vigna K. Ramachandaramurthy, H. Mokhlis, K. R. Agileswari Power Quality Research Group, Department of Electrical Power Engineering, Universiti Tenaga Nasional, Jalan IKRAM-UNITEN, 43000 Kajang, Selangor, Malaysia. *Corresponding author, e-mail: charlzray@yahoo.com Abstract The use of distributed generation (DG) within distribution systems has increased for the last two decades due to worldwide increase in demand for electricity and governmental policy change from “conventional” energy to “green” energy. High levels of penetration of DG have many significant benefits but also come with many drawbacks such as voltage drop and power losses. This study presents the impact of DG at different locations in a distribution feeder in terms of the feeder voltage profile. A radial distribution system is simulated using PSCAD/EMTDC simulation software while changing the size and location of DG in the system. The obtained results are used for better understanding on the impact of DG on voltage profile in radial distribution feeder. Keywords: voltage profile, radial distribution network, distributed generation, distribution systems Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved. 1. Introduction Electrical power generation, transmission and distribution sectors are the three different categories of electrical power systems where each category are owned and operated by a separate company. For profitable operation, these electrical companies often maximize their profits and minimize their operating costs. This is done by way of reducing spending on the maintenance, which leads to a lot of technical problems in the electrical network [1]. The most expensive technical problems usually happen in the distribution system. Voltage regulation is one of the main problems in radial distribution network [2]. The most common devices and techniques used for maintaining the voltage levels are transformer equipped by load tap changer (LTC), supplementary line regulators installed on distributed feeders, shunt capacitor switched on distribution feeders [3] and shifting transformers towards the load center [4]. A substation’s LTC transformer equipped with a Line Drop Compensator (LDC) operation increases its output voltage to readjust the voltage level and to compensate the expected increase of the feeder’s voltage drop [5]. Feeder’s voltage regulator regulates the voltage at the utilization point between ± 10% of the base voltage. Shunt capacitor is used to regulate the voltage and the reactive power flow at the point of connection with the distribution feeder with the aim of improving the voltage profile at the far-end feeder point. Switch shunt capacitor are usually placed in distribution feeder together with voltage regulators in the same distribution network to maintain adequate voltage profile especially for long feeders [6]. Implementing DG as a source of active power in the distribution system is considered a new effective approach to solve the voltage regulation problem [7]. DG includes conventional and renewable technologies such as photovoltaic, wind turbines and hydro, storage energy devices, batteries and flywheel, fuel cells [8, 9], combined heat and power modules (CHP) and microturbines. In the past, DGs were available in small size and designed to serve a single end- user’s site but nowadays it is considered as large co-generation providing up to hundreds of MWatts to customers or back to grid. Characteristics of distributed sources are different. While synchronous generators can produce real power and produce and consume reactive power, induction generators used for wind applications can only produce active power and they need reactive power [10]. Photovoltaics and fuel cells are DC sources and require power electronics interface to connect to an AC system [10]. Based on IEEE Standard 1547, all types of distributed sources should not actively regulate distribution system voltages [11]. Therefore, constant power factor control mode of
  • 2.  ISSN: 2502-4752 IJEECS Vol. 6, No. 3, June 2017 : 583 – 590 584 operation is preferred although synchronous generators are capable of controlling voltage at the point of connection point of DG. The selection of DG size and location is important since otherwise, adverse effects, such as voltage rise, mis-operation of protection relays may occur [12].The purpose of this paper is to examine the change in feeder voltage profile depending on the size and location of DG in the system. 2. Research Method Most developing countries have experienced progressing demand on their power system network [13]. Therefore DGs are employed to cater for these demands. The most common type of voltage control method is by using on-load tap changer transformer [5]. For operating the tap changer of a power transformer, the automatic voltage control (AVC) relay initiates a signal to bring the controlled voltage back within the specified limits. When automatic load-tap-changing transformers operating in parallel are located remotely from each other, interconnecting control wires are impractical and a modification of the line-drop compensator setting is necessary to obtain satisfactory operation. This type of control is sometimes referred to as the "reduced" or "reversed" reactance method. This method serves to distinguish between circulating current and load current and does this by virtue of a difference in power factor between these currents. A compensator which employs normal resistance and reverse reactance results in a characteristic such that high power-factor currents cause the transformer to increase the voltage and low power-factor currents cause it to decrease. Thus, it is possible to set compensators so that load currents will cause a boosting operation and circulating currents will cause a slight bucking operation of transformers with no intervening impedance. These are the two methods from which we can control the AVC relay namely the negative reactance compounding (NRC) and LDC. The negative reactance compounding (NRC) method helps to maintain similar tap positions for paralleled transformers by changing the polarity of reactance of LDC setting – XLDC. In NRC operation, transformer T1 has much higher tap position compared to transformer T2. Due to the difference in tap position, a circulating current will flow between transformer T1 and transformer T2. The circulating current causes current IT1 to be shifted in clockwise direction and current IT2 in anti-clockwise direction. Both current IT1 and IT2 which passes through the ZNRC setting create a voltage drop IT ∙ZNRC. The AVC relay uses this voltage drop to determine the proper tap position. Since the voltage at transformer T1 is higher than the target voltage therefore the AVC relay initiates a tap down operation. Similarly the AVC relay of transformer T2 initiates a tap up operation. The action stops with a similar tap position of both the parallel transformers when the circulating current is eliminated and target voltage is achieved. The advantage of NRC scheme is that it can operate with transformers at different positions in the networks and it does not need to be identical anymore due to the independent action of each transformer. However, the NRC fails to operate satisfactorily when the power factor changes from a set point. Integration of irregular DG into the network effects the NRC operation. Apart from that, negative value of XLDC setting could cause poor performance of LDC. An increased value of RLDC is needed in order to maintain the performance of LDC. The aim of line-drop compensation is to keep the voltage constant, not at the local bus bar on the transformer secondary, but at some remote load center. Normal practice is to sense the load current (local to the transformer) and from this to simulate the voltage drop in the line to the remote load center. Modern voltage-control relays include line-drop compensation as standard. OLTC consist of two fixed windings and a third tap winding (regulation winding) connected in series with either winding 1or winding 2. A +30° or - 30° phase shift is introduced when winding 1 or winding 2 are connected in delta. In automatic mode voltage regulator on and the signal applied at the Vm inputs is monitored and the voltage regulator asked for tap change. The three-phase two-winding transformer or autotransformer uses an on-load tap changer (OLTC) for regulating voltage on a transmission or distribution system. Controlling voltage on a transmission system will affect primarily flow of reactive power, which, in turn, will affect the power transfer limits. Although the regulating transformer does not provide as much flexibility and speed as power-electronics based FACTS, it can be considered as a basic power flow controller. To overcome frequent tap operation due to DG interconnection, several artificial intelligence methods are introduced for AVC relay operation. Fuzzy logic systems are much
  • 3. IJEECS ISSN: 2502-4752  Impact of Distributed Generation on Voltage Profile in Radial Feeder (Charles R. Sarimuthu) 585 preferred compared to other artificial intelligent systems because the control rules can be implemented using simple “IF-THEN” relations [5]. 1) Fuzzy Membership Function a. Secondary voltage of the OLTC transformer: very high (VH), high (H), normal (N), low (L), very low (LV) b. Phase angle of current through the OLTC transformer: high (H), normal (N), low (L) c. Change of current: negative (N), zero (Z), positive (P) d. Tap position: low (L), normal (N), high (H) e. AVC relay voltage: high (H), normal (N), low (L) 2) Fuzzy Control Rules a. If voltage is very low, then AVC relay voltage is low. b. If voltage is low, tap position is normal and power angle is normal, then AVC relay voltage is normal. c. If voltage is low, tap position is low and power angle is normal, then AVC relay voltage is low. d. If voltage is normal and power angle is low, then AVC relay voltage is low. e. If voltage is normal and power angle is normal, then AVC relay voltage is normal. f. If voltage is normal and power angle is high, then AVC relay voltage is low. g. If voltage is high, tap position is normal and power angle is normal, then AVC relay voltage is normal. h. If voltage is high, tap position is high, then AVC relay voltage is high. i. If voltage is very high, then AVC relay voltage is high. j. If voltage is normal and power angle is low, then AVC relay voltage is normal. k. If voltage is normal and power angle is normal, then AVC relay voltage is normal. l. If voltage is normal and power angle is high, then AVC relay voltage is high. The other advantages of these systems are that they are simpler and able to simplify design complexity and lessen the hardware cost .Fuzzy logic systems are beneficial because they allow the usage of fuzzy rules which are more expressive than crisp values [14]. The fuzzy logic systems also requires less computation time. 2.1. Case Study Small scale DG of less than 10MW is normally connected directly to the utility system at the sub transmission and distribution level [15]. In this study, a radial distribution test system operating at nominal voltage level of 11kV is modelled using PSCAD/EMTDC software for simulation purpose. The radial test system used in the simulation is shown in Figure 1. Different operating scenarios of DG connections were considered as follows: a. Case 1, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous generators each is connected at bus 4. b. Case 2, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous generators each is connected at bus 3. c. Case 3, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous generators each is connected at bus 2. d. Case 4, a DG unit consisting of a 4.0 MW, 5.5 MW, 6.5 MW and 7.0 MW synchronous generators each is connected at bus 1. Figure 1. 11 kV radial type test system
  • 4.  ISSN: 2502-4752 IJEECS Vol. 6, No. 3, June 2017 : 583 – 590 586 2.2. The Simulation Process First, the simulation is carried out without inserting the DG into the network. The voltage at each bus and the active and reactive power feed by the distribution substation are measured. Second, the simulation is run with implementing the DG into the network (at bus 4). Again, the voltage at each bus and the active and reactive power feed by the distribution substation and the installed DG are measured. Third, repeat the second step two times and at each time vary the location and size of DG at several buses (bus 3, bus 2 and bus 1). The output power of the DG is kept constant at all cases. The summary of the simulated cases are shown in Table 1. No tap operation is initiated to study the effect of DG on the feeder voltage profile. Table 1. The comparison between each case Test Case Description No DG connection 1 (a) The distribution system operates with 4.0 MW DG connected at bus 4. (b) The distribution system operates with 5.5 MW DG connected at bus 4. (c) The distribution system operates with 6.5 MW DG connected at bus 4. (d) The distribution system operates with 7.0 MW DG connected at bus 4. 2 (a) The distribution system operates with 4.0 MW DG connected at bus 3. (b) The distribution system operates with 5.5 MW DG connected at bus 3. (c) The distribution system operates with 6.5 MW DG connected at bus 3. (d) The distribution system operates with 7.0 MW DG connected at bus 3. 3 (a) The distribution system operates with 4.0 MW DG connected at bus 2. (b) The distribution system operates with 5.5 MW DG connected at bus 2. (c) The distribution system operates with 6.5 MW DG connected at bus 2. (d) The distribution system operates with 7.0 MW DG connected at bus 2. 4 (a) The distribution system operates with 4.0 MW DG connected at bus 1. (b) The distribution system operates with 5.5 MW DG connected at bus 1. (c) The distribution system operates with 6.5 MW DG connected at bus 1. (d) The distribution system operates with 7.0 MW DG connected at bus 1. 3. Results and Analysis Figure 2 shows the voltage profile through the whole system’s buses under study without DG connection. It is observed that the voltage drops linearly starting from the distribution substation to the far-end load in the distribution network under study. Figure 2. The distribution’s network voltage profile without DG From Figure 4 it is obvious that the voltage level at bus 4 increases when DG is connected (at bus 4). DG’s function of providing part of the required demand in the distribution network improves the voltage at the point of DG connection. 1.02 1.00 0.98 0.96 0.94 0.96 0.98 1.00 1.02 1.04 1.06 1 2 3 4 Voltageinper unit Bus Number
  • 5. IJEECS ISSN: 2502-4752  Impact of Distributed Generation on Voltage Profile in Radial Feeder (Charles R. Sarimuthu) 587 Figure 3. 11 kV radial type test system for case 1 Figure 4. The distribution’s network voltage profile for case 1 Figure 4 shows that the DG is able to further improve the voltage profile along the feeder when its capability is increased. Larger DG size contributes to increased source of active power which improves the voltage profile throughout the distribution network. It is observed that a more uniform voltage profile along the distribution feeder is achievable if the DG is supplying a large percentage of the required demand. However, generation exceeding the feeder load could cause DG saturation to occur. DG saturation refers to the point at which large DGs are installed such that it becomes technically infeasible to operate on a single distribution feeder. Figure 5. 11 kV radial type test system for case 2 Figure 6. The distribution’s network voltage profile for case 2 0.96 0.98 1 1.02 1.04 1.06 Bus 1 Bus 2 Bus 3 Bus 4 Voltageinperunit case 1 (a) case 1 (b) case 1 (c) case 1 (d) 0.96 0.98 1 1.02 1.04 1.06 Bus 1 Bus 2 Bus 3 Bus 4 Vltageinperunit case 2 (a) case 2 (b) case 2 (c) case 2 (d)
  • 6.  ISSN: 2502-4752 IJEECS Vol. 6, No. 3, June 2017 : 583 – 590 588 Figure 6 shows that the voltage level at bus 3 increases when DG is connected (at bus 3). Based on simulation results, it is also observed that DG connection at bus 3 reduces the distribution substation required capabilities all over the distribution network. The results shows that a more improved voltage profile along the feeder is achievable if the DG is capable of providing a larger percentage of the required demand in the distribution network. Figure 7. 11 kV radial type test system for case 3 Figure 8. The distribution’s network voltage profile for case 3 Figure 8 proves that DG output power supplying for a larger part of required demand is able to improve the overall voltage profile along the distribution feeder. It is observed that higher voltage level of the far-end load side of the distribution network is achievable when the DG capability is increased. Figure 9. 11 kV radial type test system for case 4 0.96 0.98 1 1.02 1.04 1.06 Bus 1 Bus 2 Bus 3 Bus 4 Voltageinperunit case 3 (a) case 3 (b) case 3 (c) case 3 (d)
  • 7. IJEECS ISSN: 2502-4752  Impact of Distributed Generation on Voltage Profile in Radial Feeder (Charles R. Sarimuthu) 589 Figure 10. The distribution’s network voltage profile for case 4 Figure 10 shows that the voltage drops linearly starting from the substation to the far- end load in the distribution network when DG is connected at bus 1. However, the voltage level at all the buses is higher compared to without DG connection into the system. Simulation result proves that the connected DG shares the responsibility of supplying the required demand with the substation. It is observed that a larger capacity of DG contributes to a larger part of required demand therefore increasing the voltage level in each bus compared to the scenario without DG connection. The summary of the simulation results are shown in Table 2. Table 2. Simulation result for each case Test Case Voltage Level (in per unit value) Bus 1 Bus 2 Bus 3 Bus 4 No DG 1.02 1.00 0.98 0.96 1 (a) 1.03 1.01 0.99 0.97 (b) 1.04 1.02 1.00 0.99 (c) 1.05 1.02 1.01 1.00 (d) 1.05 1.03 1.01 1.00 2 (a) 1.03 1.01 0.99 0.97 (b) 1.04 1.02 1.00 0.99 (c) 1.05 1.02 1.01 0.99 (d) 1.05 1.03 1.01 1.00 3 (a) 1.03 1.01 0.99 0.97 (b) 1.04 1.02 1.00 0.98 (c) 1.05 1.02 1.00 0.99 (d) 1.05 1.03 1.01 0.99 4 (a) 1.03 1.01 0.99 0.98 (b) 1.04 1.02 1.00 0.98 (c) 1.05 1.02 1.00 0.99 (d) 1.05 1.02 1.00 0.99 The siting of DGs at various locations shows positive impact on voltage profile. However there is a possibility of voltage rise if the DG penetration level is too high [16]. The rise in voltage could cause misoperation of protective devices and therefore adjustment or changes of protective devices are required. In order to accommodate more DGs, the voltage profile along the feeder should be kept within statutory limits (voltage between ± 10% of the base voltage) and there is a need to employ intelligent devices for this purpose. Development of smart grid allows for the use of intelligent devices and thus helps to keep the voltage level within statutory limits. 4. Conclusion A number of cases are simulated while changing the size and location of DG in the system. The following conclusions can be drawn from this study. a. DG mainly provides part of the required demand in the distribution network. b. DG implementation as a source of active power has a great positive impact on improving the voltage profile through the entire distribution network. c. DG reduces the distribution substation required capacities all over the distribution system. 0.96 0.98 1 1.02 1.04 1.06 Bus 1 Bus 2 Bus 3 Bus 4 Voltageinper unit case 4 (a) case 4 (b) case 4 (c) case 4 (d)
  • 8.  ISSN: 2502-4752 IJEECS Vol. 6, No. 3, June 2017 : 583 – 590 590 Acknowledgement This work is supported by Universiti Tenaga Nasional (UNITEN), Taylor’s University and University of Malaya, Malaysia. References [1] Ding Xu and Girgis A. Optimal load shedding strategy in power systems with distributed generation. IEEE Power Engineering Society Winter Meeting. 2001; 2: 788-793. [2] Mahmoud Zadehbaghari, Rahim Ildarabadi, Majid Baghaei Nejad. Review of Dynamic Voltage Restorer Application for Compensation of Voltage Harmonics in Power Systems. Indonesian Journal of Electrical Engineering and Computer Science. 2017; 5(1): 58-71. [3] Barker PP and De Mello RW. Determining the impact of distributed generation on power systems. I. Radial distribution systems. IEEE Power Engineering Society Meeting. 2000; 3: 1645-1656. [4] Ijumba NM, Jimoh AA and Nkabinde M. Influence of distribution generation on distribution network performance. Proc. IEEE AFRICON. 1999; 2: 961-964. [5] Charles R. Sarimuthu, Vigna K. Ramachandaramurthy, KR Agileswari and HazlieMokhlis. A review on voltage control methods using on-load tap changer transformers for networks with renewable energy sources. Renewable and Sustainable Energy Reviews. 2016; 62: 1154-1161. [6] DIgSILENTPower Factory. Version 13.2. Manual. Germany: DIgSILENT GmbH; 2007. [7] Joon-Ho Choi and Jae-Chul Kim. Advanced voltage regulation method of power distribution systems interconnected with dispersed storage and generation systems. IEEE Transactions on Power Delivery. 2001; 16: 329-334. [8] Alok Kumar Mohanty, KB Yadav. Performance Characteristics of Six-Phase Induction Generator for Renewable Power Generation. Indonesian Journal of Electrical Engineering and Computer Science. 2017; 5(2): 299-308. [9] Lasseter B. Microgrids [distributed power generation]. IEEE Power Engineering Society Winter Meeting. 2001; 1: 146-149. [10] T Ackermann, G Anderson and L Soder. Distributed generation. A definition. Electrical Power Systems Research. 2001; 57: 195-204. [11] IEEE Standards Association. 1547-2003. IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems. New York: IEEE Press; 2003. [12] Fatih M Nuroglu and Aysen Basa Arsoy. Voltage profile and short circuit analysis in distribution systems with DG. IEEE Electrical Power and Energy Conference. 2008: 1-5. [13] Mohd Khairuzzaman Mohd Zamani, Ismail Musirin, SaifulIzwan Suliman, Muhammad Murtadha Othman and Mohd Fadhil Mohd Kamal. Multi-Area Economic Dispatch Performance Using Swarm Intelligence Technique Considering Voltage Stability. International Journal on Advanced Science, Engineering and Information Technology. 2017; 1: 1-7. [14] Mohamed M Ismail, Ahmed F Elbendary, Abdelghany M Abdelghany. A Hybrid Fuzzy Logic FOPID Position Controller for DC Motor Driving Tracking Systems System. Indonesian Journal of Electrical Engineering and Computer Science. 2017; 5(2): 327-337. [15] CJ Mozina. A tutorial on the impact of distributed generation (DG) on distribution systems. 21 st Annual Conference for Protective Relay Engineers, College Station. 2008: 591-609. [16] K Balamurugana, Dipti Srinivasana, Thomas Reindal. Impact of distributed generation on power distribution systems. Energy Procedia. 2012; 25: 93-100.