2. 1.Parts of the GBB/GIB Rotary Actuator.
a. Actuator
b. Self-centering shaft adapter
c. Position indicator
d. Shaft adapter locking clip
e. Position indicator adapter
f. Mounting bracket
g. Mounting screws
3. Product Description The steps for direct-coupled mounting of the OpenAir
GBB/GIB series non-spring return (NSR) 3-position or
2-position rotary electronic damper actuator.
Product Number GBB/GIB17โฆ series
Warning Notation Personal injury/loss of life may occur you do not
follow a procedure as specified.
Caution Notation Equipment damage or loss of data may occur if you do
not follow procedure as specified.
Estimated Installation Time 30 minutes
4. Required Tools
๏ผ 10 mm (13/32-in.) open end wrench
๏ผ 4 mm (5/32-in.) drill bit and drill
๏ผ Phillips screwdriver
๏ผ Marker or pencil
๏ผ Adjustable pliers
6. Figure 3. NEMA 3R Rating with the ASK75.1U Weather
Shield in this Mounting Position Only.
7. The GBB/GIB actuator is UL listed to meet NEMA 3R
requirements (a degree of protection against rain, sleet,
and damage from external ice formation) when installed
with the weather shield, product number ASK75.1U and
out door rated conduit fittings.
The GBB/GIB must be in the vertical position.
Prerequisite ๏ง The actuator is shipped from the factory with a 5ยฐ
pre-load to ensure tight close off of the damper.
๏ง If you want to release the pre-load, press the PUSH
button.
8. Instructions
WARNING: Do not open the actuator.
1. Place the actuator on the damper shaft with the front of the actuator
accessible.
The label and the manual override button are on the front side.
2. Determine the damper shaft rotation. See Figure 4 and
Figure 5 for clockwise-to-open (CW) installation.
See Figure 6 and Figure 7 for counterclockwise-to-open
(CCW); then reverse the 6 and 7 wires at the controller. See Wiring.
9. NOTE:
Place the shaft adapter
right next to the alignment
mark keeping the mark
visible.
Figure 4. Shaft Adapter Placement on Long and Short Shafts for
Clockwise-to-open Dampers.
10. Figure 5. Mount the Actuator to the Damper Shaft for
Clockwise-to-open Dampers.
11. Figure 6. Shaft Adapter Placement on Long and Short Shafts for
Counterclockwise-to-open Dampers.
12. Figure 7. Actuator Mounting to the Damper Shaft for
Counterclockwise-to-open Dampers.
15. Manual Override
To move the damper blades and lock the position with no power
present, do the following:
1. Hold down the PUSH button.
2. Make adjustments to the damper position.
3. Release the PUSH button.
Once power is restored, the actuator returns to automated control.
17. Mechanical Range Adjustment
1. Loosen the shaft adapter from the damper shaft
and remove the actuator from the damper
shaft.
2. Remove the clip and shaft adapter from the
actuator. Figure 11
3. Return the actuator gear train to the "0"
position using the steps which follow for the
clockwise or counterclockwise damper shaft
rotation.
The angular rotation is adjustable between 0ยฐ and
90ยฐ at 5 degree intervals.
Figure 11.
18. Clockwise to open:
a. Insert the shaft adapter to the right as close as
possible to the raised stop. Figure 12.
b. Hold down the PUSH button and rotate the shaft
adapter to the left until it stops. Figure 13.
c. Release the PUSH button.
d. If the shaft adapter is not resting against the left
raised stop, remove the adapter and insert it
against the left stop.
e. Place the position indicator to the "0" position on
the outside scale. Figure 14.
19. Counterclockwise to open:
a. Insert the shaft adapter to the left as close as possible to the
raised stop.
b. Hold down the PUSH button and rotate the shaft adapter to the
right until it stops.
c. Release the PUSH button.
d. If the shaft adapter is not resting against the right raised stop,
remove the adapter and insert it against the right stop.
Place the position indicator to "0" on the inside scale.
20. 4. Determine the angle of rotation for the damper
blade
shaft. Subtract that amount from 90ยฐ.
5. Remove the shaft adapter and insert it with the
position indicator pointing to mark on the scale
calculated in the previous step. Figure 15.
6. Attach the clip.
7. Rotate the damper blade shaft to its "0"
position.
8. Return the actuator to the damper shaft and
tighten
the shaft adapter to the damper shaft.
21. Other settings For adjustment of the auxiliary switches,
References EA GBB/GIB-2 OpenAirโข Non-spring Return Rotary Electric Damper
Actuator 24 Vac Three-position and Two-position Control
Wiring ๏ง All wiring must conform to NEC and local codes and regulations.
๏ง Use earth-ground isolating step-down Class 2 transformers.
๏ง Do not use autotransformers.
๏ง The maximum rating for a Class 2 step down transformer is 100 VA
๏ง Determine the supply transformer rating by summing the VA
ratings of all actuators and all other components used.
๏ง It is recommended that one transformer power no more than 10
actuators (or 80% of its VA).
22. WARNING: Mixed switch operation is not permitted to the switching
outputs of both auxiliary switches (A and B).
Either AC line voltage from the same phase must be applied
to all six outputs of the dual auxiliary switches, or UL-Class 2
voltage must be applied to all six outputs.
NOTE: With Plenum cables, only UL-Class 2 voltage is
permitted.
CAUTION: Do not parallel wire GBB17x or GIB17x actuators with other
types of actuators.
Direction of Damper
Rotation
If the damper blades turn counterclockwise (CCW) to open,
reverse the 6 and 7 wires at the controller.
23. Wire Designations
Standard
Symbol
Function Terminal
Designations
Color
Standard Plenum
1 Supply 24 Vac (+) G Red Red
6 Control signal clockwise Y1 Violet Violet
7 Control signal counterclockwise Y2 Orange Orange
*GND Ground Green/
yellow*
S1 Switch A Common Q11 Gray/red Gray/red
S2 Switch A N.C. Q12 Gray/blue Gray/blue
S3 Switch A N.O. Q14 Gray/pink Gray/pink
S4 Switch B Common Q21 Black/red Black/red
S5 Switch B N.C. Q22 Black/blue Black/blue
S6 Switch B N.O. Q24 Black/pink Black/pink
P1 Feedback Potentiometer 0 to 100% P1 - P2 a White/red Black
P2 Feedback Potentiometer Common b White/blue Black
P3 Feedback Potentiometer 100 to 0% P3 - P2 c White/pink Black
24. 3-position or 2-position Control 24 Vac. Each wire has the standard symbol printed on it.
With dual auxiliary switch only and standard cable only.
25. 3-position control 24 Vac
16. Wiring the GBB/GIB 17x Actuator for 3-position Control.
26. 2-position control 24 Vac
17. Wiring the GBB/GIB 17x Actuator for 2-position Control.