Tired of repairing failed bus ducts? Learn about the technical and safety aspects of our no-maintenance cable bus as an alternative to bus ducts, wire in conduit and cable trays. Visit us at http://www.superiortray.com/ for more information.
9. • Cable bracing prevents displacement in short circuit
• Every cable protected by shock absorber
• Prevents insulation damage in short circuit event
• Non magnetic and non metallic support system
11. • Fully insulated power cables (protection to workers)
• No issues with sprinklers, water leaks, or moisture
• No splice joints
• Materials are fire retardant and UV resistant
13. • Ethylene Propylene Rubber (EPR) preferred insulation
• EPR has advantages over Cross Linked Polyethylene (XLPE)
• XLPE is victim to "water-treeing“
• EPR insulation is far more flexible and easier to install
19. • In a balanced system a short circuit is carried evenly by all
conductors.
• In short circuit event, a balanced system has a greatly
reduced maximum magnetic force due to opposing magnetic
forces that cancel out.
21. • Ampacity: Most phasing arrangements provide inter-phase
balance of the currents due to the load impedance, but only
specific arrangements provide an intra-phase current
balance.
• Properly balanced systems ensure that the ampacity balance
is within 3% between all conductors.
22. • Impedance: A balanced impedance ensures a similar load per
each conductor. This allows cables to be run at their full
rated capacity rather than one particular conductor limiting
the capacity of the entire system.
• Magnetic Field: An unbalanced system has higher risk of
cable insulation damage due to higher magnetic forces.
25. • Cable rated to 90°C Low Voltage, and 105°C Medium Voltage
• Switchgear rated to 75°C
• Much myth and confusion surrounds temperature rating of
switchgear and equipment
27. • Ampacity is calculated according to the Ampacity Standards
as dictated by the International Conductor Engineers
Association (ICEA) found in both the NEC and the CEC
• Table 310.17, 310.19, and 310.69 in the NEC.
• Table 1, and 3 in the CEC
29. • All systems designed to achieve the required voltage drop
• Measured in percentage drop (2% to 3% at best)
• Voltage drop is a function of conductor sizing
• Voltage drop is proportional to distance
• More conducting material for a given ampacity, the lower the
voltage drop
31. • Cables available with FT4 or FT1 rating
• Required flame test rating will depend on local and national
building code
• Both tests relate to the smoke development classification
and the flame spread rating of the cable
34. According to NBC Article 3.2.2.30 any cable installed into a
building constructed of non combustible materials (any building
of storey area greater than 4800 square meters) must have at
least the FT4 rating
FT1 cables can be used in combustible buildings. Determination
of non-combustibility as per NBC Article 1.1.1.3.2. Many cables
with XLPE insulation are only available in FT1.
39. • Conduit has no phase balancing or free air rating
• Cables generally need to be de-rated
• One of the most difficult systems to install
• High cost of material