Latest technology trends
Pega Hrnjak
pega@illinois.edu
Director ACRC,
Will Stoecker Res. Professor,
University of Illinois, Urbana-Champaign, USA
President, CTS, Creative Thermal Solutions
3. A
P. Hrnjak 3/29
Light commercial refrigeration
• Development was historically pushed by TCCC (The
Coca Cola Company)
• In competition between CO2, R290, and He
(Stirling machine), R744 was a winner
• We have shown that R744 and R134a can have the
same performance and the same cost! Thanks to
that hundreds of thousands units were installed.
• Currently R290 is taking over almost exclusively.
The entire industry is moving to R290
• Strong push to increase the charge limit from 150
g to 300 g or 500 g appears to be successful.
4. A
P. Hrnjak 4/29
Commercial refrigeration with CO2, HC and NH3
• CO2
• Self contained display cases: not as well spread as
centralized
• Centralized (racks) systems extremely successful in Europe
and Japan, USA and Canada behind, China just started
• HC (R290)
• Self contained, low charged only. Very successful
• Water loops are increasingly attractive
• NH3 only as a chiller or high stage in cascades with R744. At
this point just trials.
5. A
P. Hrnjak 5/29
Water looped systems with R290
Each R290
unit to max
charge
As many display
cases per unit as
capacity of R290
unit allows
As many display cases as
needed in supermarket
The way to maximize
capacity for a max allowed
charge
6. A
P. Hrnjak 6/29
Industrial refrigeration
90-95% of industrial refrigeration in USA is with NH3!
Major trends:
• Low charge NH3 systems vs. NH3 and NH3/CO2 systems
• Numerous starts with CO2 transcritical in large projects.
7. A
P. Hrnjak 7/29
Conventional
• Typically applied in:
• Cold stores
• Process industry, …
• Custom designed and built (onsite)
• Steel is major material High capacities, large components, huge
refrigerant charges
• Mostly uses ammonia (NH3)
• Requires professional personnel
• Let me illustrate:
8. A
P. Hrnjak 8/29
Large sizes
• Compressors
• Accompanying vessels
• Charges are very high
11. A
P. Hrnjak 11/29
Ammonia in China
• After several lethal incidents in NH3 plants this excellent
refrigerant, used in 90-95% or cold stores in USA is
questioned
• These incidents were the cases of serious negligence, not of
ammonia
• New approach with low, and ultra low charges is perfect way
to mitigate even that problem:
• Much lower charge
• Factory made systems have much higher quality and
better safety
12. A
P. Hrnjak 12/29
Condenser in wind tunnel
Compressor
Accumulator
Plate
evaporator
Receiver
Flow meter
We have demonstrated: Efficient air cooled NH3 chillers 18 g/kW
1997 2012
13. A
P. Hrnjak 13/29
Three most typical options
water cooled unit
air cooled (dry) unit
air cooled
(adiabatic) unit
It took some time but it is becoming reality
17. A
P. Hrnjak 17/29
Hermetic NH3 compressors
help competiveness of
solutions for smaller systems
700 mm
270 mm
700 mm
270 mm
700 mm
270 mm
Courtesy Mycom, Inc.
18. A
P. Hrnjak 18/29
Why these trends in NH3
• SAFETY!!!
• Fluid like NH3 is the best for charge reduction: thermophysical
properties are good but more importantly mildly toxic and
mildly flammable is the best to be handled by low charge
• It is not a question if there will be disasters like in Fukushima
– that is just a matter of time
• Users want to be proactive
• “Mass” production = lower costs
• Empty market for grab: no OEMs
• Active companies see the opportunity
19. A
P. Hrnjak 19/29
Transport and mobile application
• 20 years ago we developed excellent R744 systems that were
equally efficient as R134a but R1234yf was selected
• Today, heat pumps for electric cars are pushing
• I will leave this topics to prof. Chen
• We have developed the first R744 system for the fastest
Chinese train that is 5% more efficient and 10% smaller than
the baseline HFC
• I will leave that topic to Mr. Bai from CRRC
20. A
P. Hrnjak 20/29
AC & HPs - what is the future?
• The most uncertain predictions
• USA OEMs bets on blends (mixtures): R452, R454,…
• Japanese lean towards R32 or R1224yd/1123 in some mixture
• China seem to be influenced by all above, but strongest push
comes from Europeans towards R290
• I believe eventually R744 will win but after going through one
or two interim solutions.
• Why I think so?
21. A
P. Hrnjak 21/29
Why I think so? Interim solutions
• L2Ls or A3s are very attractive as easier solutions for
businesses
• Flammability will most likely cause some problems
• Experts in industry are aware of that, but are not ready to talk
• Some like R1123 for being A1
22. A
P. Hrnjak 22/29
Why I think so? CO2
A reasonably efficient R410A
system (Q=3.5kW, COP=3.5)
used as a baseline:
- Round tube HXs
- Rotary compressor
CO2 system assembled:
- Microchannel HXs
- Same R410A evaporator
- IHX and intercooler added
- Rotary compressor with permanent
magnets
• We have demonstrated that CO2 can be equal to R410A
23. A
P. Hrnjak 23/29
Components
Gas cooler – microchannel cross-counter flow
face area 2900cm2
Evaporator was the same: R410A and CO2
Condenser – round tube-in-fin
face area 3260cm2
Additional info:
CO2 system had internal HX and intercooler
25. A
P. Hrnjak 25/29
HXs in wind tunnels and they in environmental chambers
Condenser chamber Evaporator chamber
Expansion valve/AccumulatorControls and DAQ
26. A
P. Hrnjak 26/29
0.00
1.00
2.00
3.00
4.00
ARI A ARI B ARI C
Coolingcapacity[kW]
0.00
1.00
2.00
3.00
4.00
ARI A ARI B ARI C
COP[-]
R744 serpentine microchannel
R410A round tube-in-fin
Extremely close performance
27. A
P. Hrnjak 27/29
Efficiency will be less important than today
• Once all or most of electricity will be produced w/o CO2
emission, efficiency is a matter of cost only
• At this point NONFLAMMABLE and NONTOXIC, low GWP is
the most logical choice. There is only one fluid like that
• The knowledge gap will be closed.
• Mechanical engineers will be better educated and have
stronger support.
• Public support will be even stronger
28. A
P. Hrnjak 28/29
Conclusions
• R290 in light commercial
• CO2 in commercial refrigeration, R290 in secondary looped
systems
• Industrial: LOW CHARGE, PREFABRICATED systems (some are
looking in transcitical CO2)
• Transport AC and refrigeration: great steps forward for CO2
• Mobile AC: rejuvenated heat pumps with CO2
• Reversible AC/HP eventually CO2 after interim solutions with
blends