SlideShare a Scribd company logo
1 of 72
Download to read offline
A Guide to IBM System x
                             Uninterruptible Power Supply (UPS)
                                                  Remote emergency
                                                    power-off port                                                    Line-interactive UPS Technology
      Optional                 RS-232                            Optional EBM                   Ground
      NMC Bay                 Connector         USB               Connector                     Screw                                            INPUT                 AVR                                 OUTPUT
                                                                                                                                                 FILTER                                                    FILTER
                                                                                                                            AC SOURCE                                                                               LOAD

                                                                                                                                                                                           INVERTER




                                                                                                                                                     BATTERY
                                                                                                                                                     CHARGER                                     DC LINK


                                                                                                                                                                                                      BATTERY

                                                                                                                              NORMAL POWER FLOW
            Output Circuit       Output Circuit         Output Circuit        Output Circuit        Input Terminal
            Breaker (20A)        Breaker (20A)          Breaker (20A)         Breaker (20A)         Block w/ Cover            STORED ENERGY POWER FLOW
                                                                                                                              RECHARGE ENERGY FLOW
                        4 IEC 320 C19                              4 IEC 320 C19
                      (Load Segment 1)                           (Load Segment 2)




                                                                                                                                    UPS Logical Layout
                   4 IEC 320 C19                                                                   Remote emergency
                 (Load Segment 1)                                                                    power-off port
                                                                                                                                                             Output = 28A Max @ 200-240V
     Output Circuit            Output Circuit                                                   RS-232
     Breaker (20A)             Breaker (20A)
                                                                   Optional                                              Breaker                     10A       C13
                                                                   NMC Bay          USB        Connector
                                                                                                                        Amperage                     10A       C13
                                                                                                                                          15A
                                                                                                                                                     10A       C13
                                                                                                                                                     10A       C13
                                                                                                                                                     10A       C13
                                                                                                                           Outlet
                                                                                                                        Amperage                     10A       C13        Outlet Type
                                                                                                                                          20A
                                                                                                                                                     16A       C19
                                                                                                                                                     16A       C19
                                                                                                                                          20A
                                                                                                                                                     16A       C19
                                                                                                                        AC to DC                     16A       C19
                                                                                                                            then
                                                                                                                        DC to AC

     Optional EBM      Output Circuit       6 IEC 320 C13                                  Input Terminal    Ground                             Input Line
      Connector        Breaker (15A)      (Load Segment 2)                                 Block w/ Cover    Screw                                           Input = 30A Max @ 200-240V




                                                                                                                                                                      Authors:              William S. Champion
                                                                                                                                                                                            wchamp@us.ibm.com

                                                                                                                                                                                            Matthew R. Archibald
                                                                                                                                                                                            archibam@us.ibm.com




                                                                                                                                                                      Version: 1.6.0
                                                                                                                                                                      Date: December 23, 2010




The user of this document is responsible for obtaining the latest copy prior to use. Obsolete copies may be
archived and used for reference purposes only. The latest version of this document is located at:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655
A Guide To IBM System x Uninterruptible Power Supply (UPS)

                                                                                                                  © IBM Corporation 2011
Revision History
1.0.0 – March 25, 2010                 Initial Release
1.1.0 – May 17, 2010                   Updated sections Introduction, How To Use This Guide, Input Connection Block
                                       for IBM UPS7500/10000, IBM System x Server Label Rating, IBM Storage Label
                                       Rating, IEC 309 Pin & Sleeve Plug Decode, and IEC 320 Connectors. Modified
                                       run times to be all in minutes. Added Some Background on Power Factor and
                                       UPS Sizing section.
1.2.0 – July 20, 2010                  Added new rack mounted IBM UPS1500, IBM UPS2200, and IBM UPS3000,
                                       new line cords
1.3.0 – September 28, 2010             Update Helpful Links section. Updated Line Cords and Plugs section. Added
                                       new rack mounted IBM UPS6000.
1.4.0 – October 26, 2010               Add new IBM UPS1000/1500 tower models.
1.5.0 – January 19, 2011               Add new IBM UPS11000. Updated IEC 309 Pin & Sleeve Plug Decode section
                                       and document title to the more common spelling of uninterruptible.
1.5.1 – February 2, 2011               Updated System x server label ratings section.
1.6.0 – December 23, 2011              Remove old UPS1000/1500 Tower models. Updated Label Rating sections and
                                       cover page image.



Contributors
   Marc Hollingsworth MarcHHollingsworth@Eaton.com
   Manager, Global Accounts – Eaton http://www.eaton.com/ibm

     David Walker dgwalker@us.ibm.com
     System x World Wide Options Marketing Manager

     Ben Hilmus bhilmus@us.ibm.com
     Worldwide System x Channel Enablement

     Preston Miller prmiller@apcc.com
     Global Program Manager – American Power Conversion (APC) http://www.apc.com




Notices:

This paper is intended to provide information regarding IBM® System x™ Power Uninterruptible Power Supply (UPS). It discusses findings
based on configurations that were created and tested under laboratory conditions. These findings may not be realized in all customer
environments, and implementation in such environments may require additional steps, configurations and performance analysis. The
information herein is provided “AS IS” with no warranties, express or implied. This information does not constitute a specification or form part
of the warranty for any IBM or non-IBM products.

Information in this document was developed in conjunction with the use of the equipment specified and is limited in application to those
specific hardware and software products and levels.

The information contained in this document has not been submitted to any formal IBM test and is distributed as is. The use of this information
or the implementation of these techniques is a customer responsibility and depends on the customer’s ability to evaluate and integrate them
into the customer’s operational environment. While each item may have been reviewed by IBM for accuracy in a specific situation, there is no
guarantee that the same or similar results will be obtained elsewhere. Customers attempting to adapt these techniques to their own
environments do so at their own risk.

IBM may not officially support techniques mentioned in this document. For questions regarding officially supported techniques, please refer to
the product documentation, announcement letters or contact the IBM Support Line at 1-800-IBM-SERV.

This document makes references to vendor-acquired applications or utilities. It is the customer responsibility to obtain licenses of these utilities
prior to their usage.

© Copyright International Business Machines Corporation 2011. All rights reserved. U.S. Government Users Restricted Rights – Use,
duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.


                                                              Page |2                                             © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Table of Contents
TABLE OF CONTENTS ........................................................................................................................................................... 3
INTRODUCTION ................................................................................................................................................................... 6
   HOW TO USE THIS GUIDE .............................................................................................................................................................. 6
IBM UPS QUICK VIEW .......................................................................................................................................................... 7
IBM UPS1000 TOWER .......................................................................................................................................................... 8
      Optional Accessories ........................................................................................................................................................... 8
   SELECTABLE LINE CORDS – IBM UPS1000 TOWER (230V) ................................................................................................................ 9
   OUTLET DIAGRAM – IBM UPS1000 TOWER (100/120V) ............................................................................................................... 10
      Logical Layout – IBM UPS1000 Tower (100/120V)............................................................................................................ 10
   OUTLET DIAGRAM – IBM UPS1000 TOWER (230V)....................................................................................................................... 11
      Logical Layout – IBM UPS1000 Tower (230V) ................................................................................................................... 11
   RUN TIME – IBM UPS1000 TOWER ............................................................................................................................................. 11
IBM UPS1500 TOWER ........................................................................................................................................................ 12
      Optional Accessories ......................................................................................................................................................... 12
   SELECTABLE LINE CORDS – IBM UPS1500 TOWER .......................................................................................................................... 13
   OUTLET DIAGRAM – IBM UPS1500 TOWER (120V)....................................................................................................................... 14
      Logical Layout – IBM UPS1500 Tower (120V) ................................................................................................................... 14
   OUTLET DIAGRAM – IBM UPS1500 TOWER (100V)....................................................................................................................... 15
      Logical Layout – IBM UPS1500 Tower (100V) ................................................................................................................... 15
   OUTLET DIAGRAM – IBM UPS1500 TOWER (230V)....................................................................................................................... 16
      Logical Layout – IBM UPS1500 Tower (230V) ................................................................................................................... 16
   RUN TIME – IBM UPS1500 TOWER ............................................................................................................................................. 17
IBM UPS1500THV TOWER .................................................................................................................................................. 18
   SELECTABLE LINE CORDS – UPS1500THV ..................................................................................................................................... 18
   OUTLET DIAGRAM – IBM UPS1500THV ...................................................................................................................................... 19
      Logical Layout – IBM UPS1500THV ................................................................................................................................... 19
   RUN TIME – IBM UPS1500THV ................................................................................................................................................. 19
IBM UPS1500 – RACK MOUNTED (RM) .............................................................................................................................. 20
      Optional Accessories ......................................................................................................................................................... 20
   SELECTABLE LINE CORDS – IBM UPS1500 RM .............................................................................................................................. 21
   OUTLET DIAGRAM – IBM UPS1500 RM 100/120V ...................................................................................................................... 21
      Logical Layout – IBM UPS1500 RM 100/120V .................................................................................................................. 21
   OUTLET DIAGRAM – IBM UPS1500 RM 230V.............................................................................................................................. 22
      Logical Layout – IBM UPS1500 RM 230V .......................................................................................................................... 22
   RUN TIME – IBM UPS1500 RM ................................................................................................................................................. 22
IBM UPS2200 – RACK MOUNTED (RM) .............................................................................................................................. 23
      Optional Accessories ......................................................................................................................................................... 23
   SELECTABLE LINE CORDS – IBM UPS2200 RM .............................................................................................................................. 24
   OUTLET DIAGRAM – IBM UPS2200 RM 100/120V ...................................................................................................................... 25
      Logical Layout – IBM UPS2200 RM 100/120V .................................................................................................................. 25
   OUTLET DIAGRAM – IBM UPS2200 RM 230V.............................................................................................................................. 26
      Logical Layout – IBM UPS2200 RM 230V .......................................................................................................................... 26
   RUN TIME – IBM UPS2200 RM – 100/120V .............................................................................................................................. 26
   RUN TIME – IBM UPS2200 RM – 230V ...................................................................................................................................... 27
   EBM CONNECTIONS – IBM UPS2200 RM.................................................................................................................................... 27
IBM UPS3000 – RACK MOUNTED (RM) .............................................................................................................................. 28
       Optional Accessories ......................................................................................................................................................... 28

                                                                             Page |3                                                           © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

   SELECTABLE LINE CORDS – IBM UPS3000 RM .............................................................................................................................. 29
   OUTLET DIAGRAM – IBM UPS3000 RM 100/120V ...................................................................................................................... 30
      Logical Layout – IBM UPS3000 RM 100/120V .................................................................................................................. 30
   OUTLET DIAGRAM – IBM UPS3000 RM 200/208V ...................................................................................................................... 31
      Logical Layout – IBM UPS3000 RM 200/208V .................................................................................................................. 31
   OUTLET DIAGRAM – IBM UPS3000 RM 230V.............................................................................................................................. 32
      Logical Layout – IBM UPS3000 RM 230V .......................................................................................................................... 32
   RUN TIME – IBM UPS3000 RM 100/120V ................................................................................................................................. 32
   RUN TIME – IBM UPS3000 RM 200/208V ................................................................................................................................. 33
   RUN TIME – IBM UPS3000 RM 230V ........................................................................................................................................ 33
   EBM CONNECTIONS – IBM UPS3000 RM.................................................................................................................................... 34
IBM UPS5000 – RACK MOUNTED ....................................................................................................................................... 35
   SELECTABLE LINE CORDS – IBM UPS5000 ..................................................................................................................................... 35
   OUTLET DIAGRAM – IBM UPS5000 ............................................................................................................................................. 36
      Logical Layout – IBM UPS5000 .......................................................................................................................................... 36
   RUN TIME – IBM UPS5000 ........................................................................................................................................................ 37
   EBM CONNECTIONS – IBM UPS5000 .......................................................................................................................................... 37
IBM UPS6000 – RACK MOUNTED ....................................................................................................................................... 38
      Optional Accessories ......................................................................................................................................................... 38
   OUTLET DIAGRAM – IBM UPS6000 200/208V ............................................................................................................................ 39
      Logical Layout – IBM UPS6000 200/208V ......................................................................................................................... 39
   OUTLET DIAGRAM – IBM UPS6000 230V .................................................................................................................................... 40
      Logical Layout – IBM UPS6000 230V ................................................................................................................................ 40
   RUN TIME – IBM UPS6000 ........................................................................................................................................................ 41
   EBM CONNECTIONS – IBM UPS6000 .......................................................................................................................................... 41
   INPUT CONNECTION BLOCK – IBM UPS6000 ................................................................................................................................. 42
IBM UPS7500/10000 – RACK MOUNTED ............................................................................................................................ 43
   OUTLET DIAGRAM – IBM UPS7500/10000 ................................................................................................................................. 44
      Logical Layout – IBM UPS7500/10000 .............................................................................................................................. 44
   RUN TIME – IBM UPS7500/10000 ............................................................................................................................................ 45
   EBM CONNECTIONS – IBM UPS7500/10000 .............................................................................................................................. 46
   INPUT CONNECTION BLOCK – IBM UPS7500/10000 ..................................................................................................................... 47
      International Connection Only .......................................................................................................................................... 47
      North American Connection Only ...................................................................................................................................... 47
IBM UPS11000 – RACK MOUNTED ..................................................................................................................................... 48
      Optional Accessories ......................................................................................................................................................... 48
   OUTLET DIAGRAM – IBM UPS11000 ........................................................................................................................................... 49
      Logical Layout – IBM UPS11000 ........................................................................................................................................ 49
   RUN TIME – IBM UPS11000 ...................................................................................................................................................... 50
   EBM CONNECTIONS – IBM UPS11000 ........................................................................................................................................ 50
   INPUT CONNECTION BLOCK – IBM UPS11000 ............................................................................................................................... 51
LINE CORDS AND PLUGS .................................................................................................................................................... 52
   100/120V NEMA 5-15P (NORTH AMERICA & JAPAN) UPS1500 RM & TOWER ............................................................................... 52
   100/120V NEMA 5-20P (NORTH AMERICA & JAPAN) UPS2200 RM ............................................................................................. 52
   100/120V NEMA L5-30P (NORTH AMERICA & JAPAN) UPS3000 RM ............................................................................................ 52
   200/208V NEMA L6-20P (NORTH AMERICA & JAPAN) UPS3000 RM ............................................................................................ 53
   CEE7-VII (EUROPE) ................................................................................................................................................................... 53
   DK2-5A (DENMARK) .................................................................................................................................................................. 54
   SEV 1011-S24507 (SWITZERLAND) ............................................................................................................................................. 54
   SI 32 (ISRAEL) ........................................................................................................................................................................... 54
   CEI 23-16 (ITALY) ..................................................................................................................................................................... 55

                                                                                Page |4                                                             © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

   SABS 164 (SOUTH AFRICA) ......................................................................................................................................................... 55
   BS 1363/A (UK) ...................................................................................................................................................................... 56
   AS/NZS 3112 (AUS/NZ) ........................................................................................................................................................... 56
   KSC 8305 (S. KOREA) ................................................................................................................................................................ 57
   IS6538 (INDIA) ......................................................................................................................................................................... 57
   GB 2099.1 (CHINA) .................................................................................................................................................................. 58
   NBR 6147 (BRAZIL) ................................................................................................................................................................... 58
   IRAM 2073 (ARGENTINA) .......................................................................................................................................................... 59
   IEC 309 P+N+G (DENMARK/SWITZERLAND).................................................................................................................................. 59
   NBR 14136 (BRAZIL)................................................................................................................................................................. 59
   SEV 1011 T23 (SWITZERLAND) ................................................................................................................................................... 60
   CNS 10917 – 125V (TAIWAN) ................................................................................................................................................... 60
   CNS 10917 – 250V (TAIWAN) ................................................................................................................................................... 60
   40K9612 - IBM DPI 32A CORD (IEC 309 P+N+G) ....................................................................................................................... 61
   40K9614 - IBM DPI 30A CORD (NEMA L6-30P)......................................................................................................................... 61
   40K9617 – IBM DPI 32A CORD (AUS/NZ 3112 32A) ................................................................................................................. 61
   40K9618 – IBM DPI 30A CORD (KSC 8305 30A) ........................................................................................................................ 62
REFERENCE MATERIAL ....................................................................................................................................................... 63
   IBM BLADECENTER CHASSIS LABEL RATING .................................................................................................................................... 63
   IBM STORAGE LABEL RATING ....................................................................................................................................................... 63
   IBM SYSTEM X SERVER LABEL RATING............................................................................................................................................ 64
   IBM SYSTEM X SERVER LABEL RATING – CONTINUED ........................................................................................................................ 65
   IBM SYSTEM X TOP OF RACK ETHERNET SWITCH LABEL RATING .......................................................................................................... 65
   IBM XSERIES SERVER LABEL RATING .............................................................................................................................................. 65
   IBM IDATAPLEX CHASSIS LABEL RATING......................................................................................................................................... 66
   IBM IDATAPLEX CHASSIS LABEL RATING – CONTINUED ..................................................................................................................... 67
   SOME BACKGROUND ON POWER FACTOR AND UPS SIZING ................................................................................................................ 68
   IEC 309 PIN & SLEEVE PLUG DECODE ........................................................................................................................................... 69
   INGRESS PROTECTION (IP) DECODE ............................................................................................................................................... 70
   IEC 320 CONNECTORS ................................................................................................................................................................ 70
   60A THREE PHASE DELTA POWER CALCULATIONS ............................................................................................................................ 71
   32A THREE PHASE WYE POWER CALCULATIONS .............................................................................................................................. 71
   UPS INSTALLATION MANUAL LINKS ............................................................................................................................................... 72
   HELPFUL LINKS........................................................................................................................................................................... 72




                                                                               Page |5                                                             © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


Introduction
The Uninterruptible Power Supply (UPS) systems covered in this guide are those that are currently marketed
worldwide. The intent of this guide is to provide UPS information when needed when planning power for System
x and BladeCenter solutions.

This guide is best used in softcopy form since it contains hyperlinks for navigation. This document can still be
used in hardcopy as reference only. You can obtain the latest copy of this document by sending an email to
wchamp@us.ibm.com or archibam@us.ibm.com (put “Latest UPS Guide” in the subject line).

For more information about how to size and plan for UPS systems, see the “Background on Power Factor and
UPS Sizing” section on page 68 of this document.


How to Use This Guide
In order to size a UPS properly, you need to know the total power requirements of what will be connected to the
UPS. This information is available from the System x & BladeCenter Power Configurator:

        http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html

When the total supported power is know, and appropriately sized UPS can be selected. Once a UPS is selected
the solution wiring needs to be figured out. UPS systems have outlet and group limits, much like PDUs and the
solution needs to be wired so as to not exceed the outlet and/or group rating of the UPS. The IT appliances and
UPS systems need to be wired according to system nameplate rating for compliance with local electrical codes
and product support documentation.

In cases where a UPS fits the electrical load of a solution, but the UPS does not have sufficient C13 outlets, DPI
Universal Rack PDUs (P/N: 39Y8951 F/C: 5950) may be able to be used to offer additional C13 outlets. When
wiring the solution using PDUs, the same restrictions apply in that the outlet and group limitations of the UPS and
PDUs are not exceeded.




                                                 Page |6                                  © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS Quick View
                     Option          Input     Max Input    Output
UPS                  Number         Voltage    Amperage     Voltage      Output W / Amperage           Outlets       Page
                                                                                                                1
                    53961AX        120V 1ph                120V 1ph                                    8 / 5-15
UPS1000                     7                    12A                           750W / 7.5A                      1
                    53961JX        100V 1ph                100V 1ph                                    8 / 5-15       8
Tower                       8                                                                                  5
                    53961KX        230V 1ph      10A       230V 1ph           750W / 3.75A             8 / C13
                                                                                                                1
                    53962AX        120V 1ph      12A       120V 1ph                                    8 / 5-15
UPS1500                     7                                                  1000W / 10A                      2
                    53962JX        100V 1ph      16A       100V 1ph                                    8 / 5-20       12
Tower                       8                                                                                  5
                    53962KX        230V 1ph      10A       230V 1ph            1000W / 5A              8 / C13
UPS1500THV                         200-240V                200-240V                                              5
                    2130R6X                      7.5A                         1050W / 5.25A            8 / C13        18
Tower                                 1ph                     1ph
                                                                                                                 1
                                   100-127V                120V 1ph                                    4 / 5-15
UPS1500             53951AX                      13A                           1000W / 10A                     5
                                      1ph                  100V 1ph                                    2 / C13        20
Rack                                                                                                           5
                    53951KX        230V 1ph      7.5A      230V 1ph            1000W / 5A              4 / C13
                                                                                                                2
                                                                                                       6 / 5-20
                                   100-127V                 120V 1ph      1920W / 16A @ 120V                   5
                    53952AX                      16A                                                   2 / C13
UPS2200                              1ph                    100V 1ph      1500W / 16A @ 100V                   6
                                                                                                       2 / C19        23
Rack                                                                                                           5
                                                                                                       8 / C13
                    53952KX        230V 1ph      10A        230V 1ph          1920W / 9.6A                     6
                                                                                                       2 / C19
                                                                                                                2
                                                                                                       2 / 5-20
                                                                                                                 3
                                   100-127V                 120V 1ph     2700W / 22.5A @ 120V         1 / L5-20
                    53953AX                      24A                                                           5
                                     1ph                    100V 1ph     2300W / 22.5A @ 100V          2 / C13
                                                                                                               6
                                                                                                       2 / C19
UPS3000                                                                                                          4
                                                                                                      1 / L6-20       28
Rack                               200V 1ph                 200V 1ph                                           5
                    53953JX                      16A                          2700W / 13.5A            2 / C13
                                   208V 1ph                 208V 1ph                                           6
                                                                                                       2 / C19
                                                                                                               5
                                                                                                       8 / C13
                    53953KX        230V 1ph      16A        230V 1ph          2700W / 13.5A                    6
                                                                                                       2 / C19
                                                                                                               5
UPS5000                            200-240V                200-240V                                    8 / C13
                    24195KX                      25A                          4500W / 22.5A                    6      35
Rack                                 1ph                     1ph                                       2 / C19
                                                                                                                 9
                                   200V 1ph                200V 1ph                                   2 / L6-30
                    53956AX                      30A                                                           6
UPS6000                            208V 1ph                208V 1ph                                    4 / C19
                                                                               5600W / 28A                     5      38
Rack                                                                                                   6 / C13
                    53956KX        230V 1ph      30A        230V 1ph                                           6
                                                                                                       4 / C19
                                   200-240V
                                                 38A
UPS7500                              1ph                   200-240V                                              6
                    21303RX                                                    6000W / 30A             4 / C19        43
Rack                               380-415V                  1ph
                                           8     14A
                                   3ph Wye
                                   200-240V
                                                 50A
UPS10000                             1ph                   200-240V                                              6
                    21304RX                                                    8000W / 40A             4 / C19        43
Rack                               380-415V                  1ph
                                           8     18A
                                   3ph Wye
UPS11000                           200-240V     69.96A        200-                                               6
                    53959KX                                                   10000W / 50A             8 / C19        48
Rack                                 1ph                    240V1ph

1 – “5-15” refers to NEMA 5-15 outlet                          6 – “C19” refers to IEC320 C19 outlet
2 – “5-20” refers to NEMA 5-20 outlet                          7 – Supported only in Japan
3 – “L5-20” refers to NEMA L5-20 outlet                        8 – Not supported in North America or Japan
4 – “L6-20” refers to NEMA L6-20 outlet                        9 – “L6-30” refers to NEMA L6-30 outlet
5 – “C13” refers to IEC320 C13 outlet




                                                        Page |7                                    © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS1000 Tower
                              Back
IBM UPS1000                   53961AX (120V)                 Back
Tower Front                   53961JX (100V)                 53961KX (230V)




                                 UPS1000 120V           UPS1000 100V            UPS1000 230V
Part Number                         5396-1AX               5396-1JX                5396-1KX
Feature Code                   5396-TU1 (FC 6663)     5396-TU1 (FC 6664)      5396-TU1 (FC 6665)
EBMs Supported                        None                   None                    None
EPO Connection                         Yes                    Yes                     Yes
Power Factor                           0.75                   0.75                    0.75
UPS Type                         Line Interactive       Line Interactive        Line Interactive
Supported Country or Region       North America              Japan               International
Input                                 120V                   100V                    230V
Line Cord                       detachable 4.3m,       detachable 4.3m,
                                                                                  Selectable
                                  NEMA 5-15P             NEMA 5-15P
Voltage Range                   84-121V for 100V       84-121V for 100V
                                                                              160V-286V for 230V
                                97-145V for 120V       97-145V for 120V
Max Current                            12A                    12A                      10A
Phase / Frequency               1ph / 50 or 60Hz.      1ph / 50 or 60Hz.       1ph / 50 or 60Hz.
Surge Energy Rating                1200 joules            1200 joules              2400 joules
Output                                120V                   100V                     230V
Watts                                 750W                   750W                     750W
Nominal Voltage                                                                220, 230, or 240V
                               120V (Configurable)    100V (Configurable)
                                                                                 (Configurable)
Maximum Amperage                       7.5A                   7.5A                    3.75A
Receptacles                      8 x NEMA 5-15R         8 x NEMA 5-15R          8 x IEC 320 C13

Optional Accessories
Network Management Card (NMC)             Environmental Monitor Probe
P/N: 46M4110 FC: 6145                     P/N: 46M4113 FC: 6146




                                            Page |8                               © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Selectable Line Cords – IBM UPS1000 Tower (230V)
2.8m        4.3m
Line Cord   Line Cord   Plug Type            Country or Region
39Y7917     81Y2376     CEE7-VII             Europe
39Y7918     81Y2382     DK2-5a               Denmark
39Y7919     81Y2390     SEV 1011-S24507      Switzerland
39Y7920     81Y2381     SI 32                Israel
39Y7921     81Y2380     CEI 23-16            Italy
39Y7922     81Y2379     SABS 164             South Africa
39Y7923     81Y2377     BS 1363/A            United Kingdom
39Y7924     81Y2383     AS/NZS 3112          Australia / New Zealand
39Y7925     81Y2385     KSC 8305             South Korea
39Y7927     81Y2386     IS6538               India
39Y7928     81Y2378     GB 2099.1            China
81Y2374     81Y2388     CNS 10917 (125V)     Taiwan
81Y2375     81Y2389     CNS 10917 (250V)     Taiwan
39Y7929     81Y2387     NBR 6147             Brazil
39Y7930     81Y2384     IRAM 2073            Argentina




                                            Page |9                    © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS1000 Tower (100/120V)

                                                            Optional
 Remote emergency
                                                            NMC Bay
   power-off port

                                                              RS-232
             USB                                             Connector

                                                               2 NEMA 5-15P
                                                             (Load Segment 1)




                                                              6 NEMA 5-15P
                                                            (Load Segment 2)

      Detachable
      Line Cord




Logical Layout – IBM UPS1000 Tower (100/120V)

   Outlet                           Output = 7.5A Max 100-120V
Amperage
                            15A      5-15
                            15A      5-15

                            15A      5-15       Outlet Type
                            15A      5-15
                            15A      5-15
                            15A      5-15
AC to DC                    15A      5-15
    then                    15A      5-15
DC to AC

                       Input Line
                                    Input = 12A 100-120V




                                             P a g e | 10                       © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS1000 Tower (230V)


                                                                              Optional
  Remote emergency
                                                                              NMC Bay
    power-off port

                                                                                RS-232
                 USB                                                           Connector


                                                                                 2 IEC 320 C13
                                                                               (Load Segment 1)




                                                                                6 IEC 320 C13
                                                                              (Load Segment 2)


        Detachable
        Line Cord




Logical Layout – IBM UPS1000 Tower (230V)

   Outlet                                      Output = 3.75A Max 200-240V
Amperage
                                     10A         C13
                                     10A         C13

                                     10A         C13           Outlet Type
                                     10A         C13
                                     10A         C13
                                     10A         C13
 AC to DC                            10A         C13
     then                            10A         C13
 DC to AC

                               Input Line
                                               Input = 10A 200-240V



Run Time – IBM UPS1000 Tower

                                 Internal
  %          Load (W)           Batteries *
 25%           188                  25
 50%           375                  15
 75%           573                   7
100%           750                   6

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes

                                                           P a g e | 11                                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS1500 Tower
IBM UPS1500                   Back                          Back                     Back
Tower Front                   53962AX (120V)                53962JX (100V)           53962KX (230V)




                                 UPS1500 120V           UPS1500 100V           UPS1500 230V
Part Number                         5396-2AX               5396-2JX               5396-2KX
Feature Code                   5396-TU2 (FC 6666)     5396-TU2 (FC 6667)     5396-TU2 (FC 6668)
EBMs Supported                         None                  None                   None
EPO Connection                          Yes                   Yes                    Yes
Power Factor                            0.7                   0.7                    0.7
UPS Type                         Line Interactive       Line Interactive       Line Interactive
Supported Country or Region       North America              Japan              International
Input                                  120V                  100V                   230V
Line Cord                       detachable 2.8m,       detachable 2.5m,
                                                                                 Selectable
                                  NEMA 5-15P             NEMA 5-20P
Voltage Range                        97-145V               84-121V                160V-286V
Max Current                            12A                    16A                     10A
Phase / Frequency               1ph / 50 or 60Hz.      1ph / 50 or 60Hz.      1ph / 50 or 60Hz.
Surge Energy Rating                1200 joules            1200 joules             2400 joules
Output                                 120V                  100V                    230V
Watts                                 1000W                 1000W                   1000W
Nominal Voltage                                                               220, 230, or 240V
                               120V (Configurable)    100V (Configurable)
                                                                                (Configurable)
Maximum Amperage                       10A                       10A                   5A
Receptacles                      8 x NEMA 5-15R            8 x NEMA 5-15R      8 x IEC 320 C13

Optional Accessories
Network Management Card (NMC)             Environmental Monitor Probe
P/N: 46M4110 FC: 6145                     P/N: 46M4113 FC: 6146




                                            P a g e | 12                         © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Selectable Line Cords – IBM UPS1500 Tower
2.8m        4.3m
Line Cord   Line Cord   Plug Type            Country or Region
39Y7917     81Y2376     CEE7-VII             Europe
39Y7918     81Y2382     DK2-5a               Denmark
39Y7919     81Y2390     SEV 1011-S24507      Switzerland
39Y7920     81Y2381     SI 32                Israel
39Y7921     81Y2380     CEI 23-16            Italy
39Y7922     81Y2379     SABS 164             South Africa
39Y7923     81Y2377     BS 1363/A            United Kingdom
39Y7924     81Y2383     AS/NZS 3112          Australia / New Zealand
39Y7925     81Y2385     KSC 8305             South Korea
39Y7927     81Y2386     IS6538               India
39Y7928     81Y2378     GB 2099.1            China
81Y2374     81Y2388     CNS 10917 (125V)     Taiwan
81Y2375     81Y2389     CNS 10917 (250V)     Taiwan
39Y7929     81Y2387     NBR 6147             Brazil
39Y7930     81Y2384     IRAM 2073            Argentina




                                            P a g e | 13               © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS1500 Tower (120V)

                                                           Optional
 Remote emergency
                                                           NMC Bay
   power-off port

                                                              RS-232
             USB                                             Connector

                                                               2 NEMA 5-15P
                                                             (Load Segment 1)




                                                             6 NEMA 5-15P
                                                           (Load Segment 2)

      Detachable
      Line Cord




Logical Layout – IBM UPS1500 Tower (120V)

   Outlet                           Output = 10A Max 100-120V
Amperage
                            15A      5-15
                            15A      5-15

                            15A      5-15       Outlet Type
                            15A      5-15
                            15A      5-15
                            15A      5-15
AC to DC                    15A      5-15
    then                    15A      5-15
DC to AC

                       Input Line
                                    Input = 12A 100-120V




                                            P a g e | 14                        © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS1500 Tower (100V)

                                                            Optional
 Remote emergency
                                                            NMC Bay
   power-off port

                                                              RS-232
             USB                                             Connector

                                                               2 NEMA 5-20P
                                                             (Load Segment 1)




                                                              6 NEMA 5-20P
                                                            (Load Segment 2)

      Detachable
      Line Cord




Logical Layout – IBM UPS1500 Tower (100V)

            IBM UPS1500LV 100V
   Outlet                           Output = 10A Max 100V
Amperage
                            20A      5-20
                            20A      5-20

                            20A      5-20       Outlet Type
                            20A      5-20
                            20A      5-20
                            20A      5-20
AC to DC                    20A      5-20
    then                    20A      5-20
DC to AC

                       Input Line
                                    Input = 16A 100V




                                             P a g e | 15                       © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS1500 Tower (230V)


                                                             Optional
 Remote emergency
                                                             NMC Bay
   power-off port

                                                              RS-232
             USB                                             Connector


                                                                2 IEC 320 C13
                                                              (Load Segment 1)




                                                               6 IEC 320 C13
                                                             (Load Segment 2)


      Detachable
      Line Cord




Logical Layout – IBM UPS1500 Tower (230V)

            IBM UPS1500LV 230V
   Outlet                           Output = 5A Max 200-240V
Amperage
                            10A      C13
                            10A      C13

                            10A      C13        Outlet Type
                            10A      C13
                            10A      C13
                            10A      C13
AC to DC                    10A      C13
    then                    10A      C13
DC to AC

                       Input Line
                                    Input = 10A 200-240V




                                            P a g e | 16                         © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Run Time – IBM UPS1500 Tower

                                 Internal
  %          Load (W)           Batteries *
 25%           255                  36
 50%           510                  15
 75%           750                   9
100%           970                   6

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes




                                                           P a g e | 17                                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS1500THV Tower
UPS1500THV
   Back




                      UPS1500THV
Part Number              2130R6X
EBMs Supported              None
EPO Connection              None
Power Factor                 0.7
UPS Type            Double Conversion
Input                 High Voltage
                                     1
Supported Region       International
Line Cord                Selectable
Voltage                  200-240V
VA                        1500 VA
Max Current                 7.5A
Phase / Frequency    1ph / 50 or 60Hz.
Output                High Voltage
Watts                     1050 W
Nominal voltage          200-240V
Max Current                 5.25A
Receptacles                8 / C13

1 – Does not include support for North America or Japan


Selectable Line Cords – UPS1500THV
Line Cord     Plug Type             Country or Region
39Y7917       CEE7-VII              Europe
39Y7918       DK2-5a                Denmark
39Y7919       SEV 1011-S24507       Switzerland
39Y7920       SI 32                 Israel
39Y7921       CEI 23-16             Italy
39Y7922       SABS 164              South Africa
39Y7923       BS 1363/A             United Kingdom
39Y7924       AS/NZS 3112           Australia / New Zealand
39Y7925       KSC 8305              South Korea
39Y7927       IS6538                India
39Y7928       GB 2099.1             China
39Y7929       NBR 6147              Brazil
39Y7930       IRAM 2073             Argentina




                                              P a g e | 18    © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS1500THV

                                                    Battery Connector *



                                                    15A Circuit Breaker




Outlets
                                                    Input Line Cord Connector

Logical Layout – IBM UPS1500THV
   Outlet                                      Output = 5.25A Max 200-240V
Amperage
                                     10A         C13
                                     10A         C13
 Breaker
                                     10A         C13           Outlet Type
Amperage                   15A
                                     10A         C13
                                     10A         C13
                                     10A         C13
 AC to DC                            10A         C13
     then                            10A         C13
 DC to AC

                               Input Line
                                               Input = 7.5A 200-240V

Run Time – IBM UPS1500THV
                   Runtime (minutes)
Load (W)        UPS1000T * UPS1500T *
30                 224          269
60                 127          157
122                 64           80
184                 41           51
247                 29           37
311                 23           28
377                 18           22
447                 15           18
500                13.5         16.5
511                 12           15
579                 11           13
700                  8           11
790                  -            9
936                  -           7.4
1050                 -           6.7

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes


                                                           P a g e | 19                                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS1500 – Rack Mounted (RM)
IBM UPS1500 RM Front                  53951AX (100V, 120V) Back              53951KX (230V) Back




                               UPS1500 100/120V         UPS1500 230V
Part Number                         5395-1AX               5395-1KX
Feature Code                  5395-RU1 (FC 6653)      5395-RU1 (FC 6654)
EBMs Supported                        None                   None
U Space                                 2                      2
EPO Connection                         Yes                    Yes
Power Factor                           0.7                    0.7
UPS Type                         Line Interactive       Line Interactive
Supported Country or Region   North America, Japan       International
Input                               100/120V                 230V
Line Cord                       detachable 4.3m,
                                                             Selectable
                                  NEMA 5-15P
Voltage Range                   84-121V for 100V
                                                      160V-286V for 230V
                                97-145V for 120V
Max Current                            13A                    7.5A
Phase / Frequency               1ph / 50 or 60Hz.      1ph / 50 or 60Hz.
Surge Energy Rating                1200 joules            2400 joules
Output                              100/120V                 230V
Watts                                1000W                  1000W
Nominal Voltage                    100V, 120V          220, 230, or 240V
                                 (Configurable)         (Configurable)
Maximum Amperage                       10A                     5A
Receptacles                     4 x NEMA 5-15R
                                                           4 x IEC 320 C13
                                2 x IEC 320 C13

Optional Accessories
Network Management Card (NMC)             Environmental Monitor Probe
P/N: 46M4110 FC: 6145                     P/N: 46M4113 FC: 6146




                                            P a g e | 20                             © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Selectable Line Cords – IBM UPS1500 RM
2.8m            4.3m
Line Cord       Line Cord   Plug Type                  Country or Region
39Y7917         81Y2376     CEE7-VII                   Europe
39Y7918         81Y2382     DK2-5a                     Denmark
39Y7919         81Y2390     SEV 1011-S24507            Switzerland
39Y7920         81Y2381     SI 32                      Israel
39Y7921         81Y2380     CEI 23-16                  Italy
39Y7922         81Y2379     SABS 164                   South Africa
39Y7923         81Y2377     BS 1363/A                  United Kingdom
39Y7924         81Y2383     AS/NZS 3112                Australia / New Zealand
39Y7925         81Y2385     KSC 8305                   South Korea
39Y7927         81Y2386     IS6538                     India
39Y7928         81Y2378     GB 2099.1                  China
81Y2374         81Y2388     CNS 10917 (125V)           Taiwan
81Y2375         81Y2389     CNS 10917 (250V)           Taiwan
39Y7929         81Y2387     NBR 6147                   Brazil
39Y7930         81Y2384     IRAM 2073                  Argentina


Outlet Diagram – IBM UPS1500 RM 100/120V
      Detachable                                  Optional                    4 NEMA 5-15R
      Line Cord                                   NMC Bay       USB         (Load Segment 1)




 Ground Screw                       Remote emergency          RS-232         2 IEC 320 C13
                                      power-off port         Connector     (Load Segment 2)


Logical Layout – IBM UPS1500 RM 100/120V
   Outlet
Amperage                                 Output = 10A Max @ 100-120V

                                 10A       C13
                                 10A       C13               Outlet Type

                                 15A       5-15
                                 15A       5-15
AC to DC                         15A       5-15
    then                         15A       5-15
DC to AC

                            Input Line
                                         Input = 13A Max @ 100-120V

       Note: Color Indicates Load Grouping




                                                    P a g e | 21                               © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS1500 RM 230V
       Detachable                                        Optional                         2 IEC320 C13
       Line Cord                                         NMC Bay       USB              (Load Segment 1)




   Ground                                Remote emergency           RS-232           2 IEC320 C13
   Screw                                   power-off port                          (Load Segment 2)



Logical Layout – IBM UPS1500 RM 230V
   Outlet
Amperage                                      Output = 5A Max @ 220-240V

                                      10A         C13
                                      10A         C13             Outlet Type

                                      15A         C13
                                      15A         C13
 AC to DC
     then
 DC to AC

                               Input Line
                                              Input = 7.5A Max @ 220-240V

          Note: Color Indicates Load Grouping


Run Time – IBM UPS1500 RM

                                     Internal
     %              Load (W)        Batteries *
    25%                250              14
    50%                500              11
    75%                750               7
   100%               1000               5

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes




                                                           P a g e | 22                                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS2200 – Rack Mounted (RM)
IBM UPS2200 RM Front                   53952AX (100V, 120V) Back          53952KX (230V) Back




IBM UPS2200 EBM Front




                       UPS2200 100/120V          UPS2200 230V               EBM
Part Number                 5395-2AX                5395-2KX              46M4108
Feature Code           5395-RU2 (FC 6655)      5395-RU2 (FC 6656)    5395-RU2 (FC 5732)
EBMs Supported                  1                        1                   -
U Space                         2                        2                   2
EPO Connection                 Yes                     Yes                   -
Power Factor                   1.0                     0.96                  -
UPS Type                 Line Interactive        Line Interactive            -
Supported Country or
                       North America, Japan        International             -
Region
Input                        100/120V                 230V                 EBM
Line Cord               Detachable 4.3m,
                                                    Selectable               -
                           NEMA 5-20P
Voltage Range           84-121V for 100V
                                               160V-286V for 230V            -
                        97-145V for 120V
Max Current                     16A                    10A                  -
Phase / Frequency       1ph / 50 or 60Hz.       1ph / 50 or 60Hz.           -
Surge Energy Rating         1200 joules           2400 joules               -
Output                       100/120V                 230V                 EBM
Watts                    1500W @ 100V
                              (Japan)
                                                     1920W                   -
                         1920W @ 120V
                         (North America)
Nominal Voltage            100V, 120V           220, 230, or 240V
                                                                             -
                          (Configurable)         (Configurable)
Maximum Amperage           16A @ 100V
                                                       9.6A
                           16A @ 120V
Receptacles             6 x NEMA 5-20R
                                                 2 x IEC 320 C19
                        2 x IEC 320 C19                                      -
                                                 8 x IEC 320 C13
                        2 x IEC 320 C13

Optional Accessories
Network Management Card (NMC)               Environmental Monitor Probe
P/N: 46M4110 FC: 6145                       P/N: 46M4113 FC: 6146




                                              P a g e | 23                       © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Selectable Line Cords – IBM UPS2200 RM
2.8m        4.3m
Line Cord   Line Cord   Plug Type            Country or Region
39Y7917     81Y2376     CEE7-VII             Europe
39Y7918     81Y2382     DK2-5a               Denmark
39Y7919     81Y2390     SEV 1011-S24507      Switzerland
39Y7920     81Y2381     SI 32                Israel
39Y7921     81Y2380     CEI 23-16            Italy
39Y7922     81Y2379     SABS 164             South Africa
39Y7923     81Y2377     BS 1363/A            United Kingdom
39Y7924     81Y2383     AS/NZS 3112          Australia / New Zealand
39Y7925     81Y2385     KSC 8305             South Korea
39Y7927     81Y2386     IS6538               India
39Y7928     81Y2378     GB 2099.1            China
    -       81Y2388     CNS 10917 (125V)     Taiwan
81Y2375     81Y2389     CNS 10917 (250V)     Taiwan
39Y7929     81Y2387     NBR 6147             Brazil
39Y7930     81Y2384     IRAM 2073            Argentina




                                            P a g e | 24               © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS2200 RM 100/120V
  Ground                         Optional           2 IEC 320 C13                    2 IEC 320 C19
  Screw                   USB    NMC Bay          (Load Segment 2)                 (Load Segment 1)




       Remote emergency      RS-232         Optional EBM         6 6 NEMA 5-20R
         power-off port     Connector        Connector          (Load Segment 1)

  Detachable
  Line Cord



Logical Layout – IBM UPS2200 RM 100/120V
   Outlet
Amperage                                Output = 16A Max @ 100-120V

                                10A         C13
                                10A         C13

                                20A       5-20
                                20A       5-20
                                20A       5-20             Outlet Type
                                20A       5-20
                                20A       5-20
                                20A       5-20
AC to DC                        16A       C19
    then                        16A       C19
DC to AC

                          Input Line
                                        Input = 16A Max @ 100-120V

       Note: Color Indicates Load Grouping




                                                    P a g e | 25                                 © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS2200 RM 230V
                                           Optional         2 IEC 320 C13                     2 IEC 320 C19
    Ground Screw                           NMC Bay        (Load Segment 2)                  (Load Segment 1)




           Remote emergency          USB       RS-232        Optional EBM          6 IEC 320 C13
             power-off port                   Connector       Connector          (Load Segment 1)

    Detachable
    Line Cord



Logical Layout – IBM UPS2200 RM 230V
   Outlet
Amperage                                      Output = 9.6A Max @ 200-240V

                                     10A         C13
                                     10A         C13

                                     10A         C13
                                     10A         C13
                                     10A         C13             Outlet Type
                                     10A         C13
                                     10A         C13
                                     10A         C13
 AC to DC                            16A         C19
     then                            16A         C19
 DC to AC

                               Input Line
                                              Input = 10A Max @ 220-240V

          Note: Color Indicates Load Grouping



Run Time – IBM UPS2200 RM – 100/120V
                                                      Number of EBM
                                                      (P/N 46M4108)
                                     Internal
     %             Load (W)         Batteries *                +1 *
    25%               500               42                     143
    50%               969               18                      66
    75%              1450               11                      43
   100%              1920                7                      28
* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes

                                                           P a g e | 26                                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)



Run Time – IBM UPS2200 RM – 230V
                                                      Number of EBM
                                                      (P/N 46M4108)
                                     Internal
     %             Load (W)         Batteries *                +1 *
    25%               500               41                     138
    50%               968               17                      64
    75%              1450               10                      40
   100%              1920                7                      28

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes




EBM Connections – IBM UPS2200 RM




                                                           P a g e | 27                                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS3000 – Rack Mounted (RM)
IBM UPS3000 Front                          53953JX (208V) Back                     IBM UPS3000 EBM Front




53953KX (230V) Back                        53953AX (100V, 120V) Back




                           UPS3000 100/120V               UPS3000 200/208V           UPS3000 230V          EBM
Part Number                   5395-3AX                       5395-3JX                  5395-3KX          69Y1982
                                                                                                        5395-RU3
Feature Code               5395-RU3 (FC 6657)             5395-RU3 (FC 6658) 5395-RU3 (FC 6659)
                                                                                                        (FC 5733)
EBMs Supported                      1                                 1                     1               -
U Space                             3                                 3                     3               3
EPO Connection                     Yes                               Yes                   Yes              -
Power Factor                       0.9                               0.9                   0.9              -
UPS Type                     Line Interactive                  Line Interactive      Line Interactive       -
Supported Country                                              North America,
                          North America, Japan                                        World Wide            -
or Region                                                           Japan
Input                           100/120V                          200/208V                230V             EBM
                             Attached 2.0m,                      Detachable
Line Cord                                                                              Selectable           -
                             NEMA L5-30P                       NEMA L6-20P
                            84-121V for 100V
Voltage Range                                              155-255V for 208V       160V-286V for 230V       -
                            97-145V for 120V
Max Current                        24A                                16A                  16A              -
Phase / Frequency           1ph / 50 or 60Hz.                  1ph / 50 or 60Hz.    1ph / 50 or 60Hz.       -
Surge Energy Rating            1200 joules                       2400 joules          2400 joules           -
Output                          100/120V                          200/208V                230V             EBM
Watts                    2300W @ 100V (Japan)
                                                                    2700W                2700W              -
                      2700W @ 120V (North America)
Nominal Voltage                100V, 120V                           208V            220, 230, or 240V
                                                                                                            -
                             (Configurable)                     (Configurable)       (Configurable)
Maximum Amperage             22.5A @ 100V
                                                                    13.5A                13.5A
                             22.5A @ 120V
Receptacles                1 x NEMA L5-20R
                                                           2 x NEMA L6-20R
                            2 x NEMA 5-20R                                          2 x IEC 320 C19
                                                            2 x IEC 320 C19                                 -
                            2 x IEC 320 C19                                         8 x IEC 320 C13
                                                            2 x IEC 320 C13
                            2 x IEC 320 C13

Optional Accessories
Network Management Card (NMC)             Environmental Monitor Probe
P/N: 46M4110 FC: 6145                     P/N: 46M4113 FC: 6146




                                                P a g e | 28                             © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Selectable Line Cords – IBM UPS3000 RM
Line Cord    Plug Type                  Country or Region
40K9766      CEE7-VII                   Europe
40K9767      BS 1363/A w/13A fuse       UK
40K9768      CEI 23-16                  Italy
40K9769      IEC 309-P+N+G              Dmk/Swiss
40K9770      SABS 164                   S Africa
40K9771      SI 32                      Israel
40K9772      NEMA L6-20P                North America & Japan
40K9773      AS/NZS 3112                Australia/NZ
40K9774      GB 2099.1                  China
40K9776      IS 6538                    India
40K9777      IRAM 2073                  Argentina
59Y2747      CNS 10917 (250V)           Taiwan
59Y2749      KSC 8305                   Korea
69Y1989      NBR 14136                  Brazil
81Y2391      SEV 1011 T23               Switzerland




                                            P a g e | 29        © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS3000 RM 100/120V
                                                                            2 IEC 320 C13
                                                                          (Load Segment 2)

                  Remote emergency                       Output Circuit                      Optional EBM
                    power-off port              USB        Breakers                           Connector




                                                       RS-232                       2 NEMA 5-20R
                               Ground                 Connector                   (Load Segment 1)
     Fixed 2.0m
    NEMA L5-30P                Screw
     Line Cord                                              Optional        1 NEMA L5-20R
                                                            NMC Bay         (Load Segment 1)

                                                                                         2 IEC 320 C19
                                                                                       (Load Segment 1)


Logical Layout – IBM UPS3000 RM 100/120V

                                     Output = 22.5A Max @ 100-120V
                    20A
                            10A         C13
   Outlet
                            10A         C13
Amperage

 Breaker                    20A         5-20       Outlet Type
Amperage            20A     20A         5-20
                            16A         C19
                            16A         C19
AC to DC                    20A        L5-20
    then
DC to AC

                       Input Line
                                     Input = 24A Max @ 100-120V


       Note: Color Indicates Load Grouping




                                               P a g e | 30                                    © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS3000 RM 200/208V
   Remote emergency                                       2 IEC 320 C13     Optional EBM
     power-off port                        USB          (Load Segment 2)     Connector




   Detachable   Ground                    RS-232       2 NEMA L6-20R         2 IEC 320 C19
   Line Cord    Screw                    Connector     (Load Segment 1)    (Load Segment 1)



Logical Layout – IBM UPS3000 RM 200/208V
   Outlet
Amperage                              Output = 13.5A @ Max 200-240V

                              10A       C13
                              10A       C13          Outlet Type

                              16A        C19
                              16A        C19
AC to DC                      20A       L6-20
    then                      20A       L6-20
DC to AC

                         Input Line
                                      Input = 16A Max @ 200-240V

       Note: Color Indicates Load Grouping




                                                 P a g e | 31                              © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS3000 RM 230V
    Remote emergency                                                    2 IEC 320 C13         Optional EBM
      power-off port                                 USB              (Load Segment 2)         Connector




      Detachable      Ground                       RS-232                  6 IEC 320 C13        2 IEC 320 C19
      Line Cord       Screw                       Connector              (Load Segment 1)     (Load Segment 1)



Logical Layout – IBM UPS3000 RM 230V
   Outlet
Amperage                                      Output = 13.5A Max @ 200-240V

                                     10A         C13
                                     10A         C13

                                     10A         C13
                                     10A         C13
                                     10A         C13             Outlet Type
                                     10A         C13
                                     10A         C13
                                     10A         C13
 AC to DC                            16A         C19
     then                            16A         C19
 DC to AC

                               Input Line
                                             Input = 16A Max @ 220-240V

          Note: Color Indicates Load Grouping


Run Time – IBM UPS3000 RM 100/120V
                                                      Number of EBM
                                                      (P/N 69Y1982)
                                     Internal
     %             Load (W)         Batteries *                +1 *
    25%               678               42                     156
    50%              1350               16                      62
    75%              2060               10                      42
   100%              2700                7                      27
* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.




                                                           P a g e | 32                                      © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

          Note: Run times are in minutes


Run Time – IBM UPS3000 RM 200/208V
                                                      Number of EBM
                                                      (P/N 69Y1982)
                                     Internal
     %             Load (W)         Batteries *                +1 *
    25%               660               41                     153
    50%              1340               17                      68
    75%              2040               10                      43
   100%              2680                6                      29

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes


Run Time – IBM UPS3000 RM 230V
                                                      Number of EBM
                                                      (P/N 69Y1982)
                                     Internal
     %             Load (W)         Batteries *                +1 *
    25%               670               41                     156
    50%              1350               17                      81
    75%              2020               10                      41
   100%              2680                7                      27

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes




                                                           P a g e | 33                                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

EBM Connections – IBM UPS3000 RM




                                            P a g e | 34     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)


IBM UPS5000 – Rack Mounted
IBM UPS5000 Front     IBM UPS5000 Back




IBM UPS5000 EBM Back




Model                             UPS5000XHV                EBM
Part Number                         2419-5KX              39Y8857
Feature Code                  2419-RU1 (FC 7618)     2419-RU1 (FC 5743)
EBMs Supported                           4                   -
EPO Connection                          Yes                  -
Power Factor                            0.9                  -
UPS Type                       Double Conversion             -
Supported Country or Region        World Wide                -
Input                             UPS5000XHV                EBM
Line Cord                           Selectable               -
Voltage                             200-240V                 -
VA                                     5000                  -
Max Current                             30A                  -
Phase / Frequency               1ph / 50 or 60Hz.            -
Output                            UPS5000XHV                EBM
Watts                                  4500                  -
Nominal voltage                     200-240V                 -
Maximum Amperage                       22.5A                 -
Receptacles                      8 x IEC320 C13
                                                              -
                                 2 x IEC320 C19



Selectable Line Cords – IBM UPS5000
Line Cord     Plug Type             Country or Region
40K9612       IEC 309 P+N+G         International
40K9614       NEMA L6-30P           North America
40K9617       AUS/NZ 3112 32A       Australia / New Zealand
40K9618       KSC 8305 30A          South Korea




                                            P a g e | 35                  © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Outlet Diagram – IBM UPS5000
                          Input Connector




15A Circuit Breaker
  / Load Segment


                                                             Load Segemnt 2
                                                             Load Segemnt 1


Logical Layout – IBM UPS5000
   Outlet
Amperage                            Output = 22.5A Max 200-240V

                            10A       C13
                    15A     10A       C13
                            10A       C13
                            10A       C13
                            16A       C19
 Breaker                                          Outlet Type
Amperage                    10A       C13
                    15A     10A       C13
                            10A       C13
AC to DC                    10A       C13
    then                    16A       C19
DC to AC

                       Input Line
                                    Input = 30A 200-240V




                                             P a g e | 36                     © IBM Corporation 2011
A Guide To IBM System x Uninterruptible Power Supply (UPS)

Run Time – IBM UPS5000
                  Number of EBM (P/N 39Y8857)
Load (W)          +0 *        +1 *        +2 *                          +3 *              +4 *
50                409         1083        1892                          2733              3596
100               290         771         1349                          1950              2566
200               180         483         846                           1223              1610
300               129         347         610                           882               1162
400               99          270         474                           686               904
500               80          219         366                           559               737
600               67          184         324                           470               620
700               57          158         279                           405               534
800               50          138         244                           355               468
900               44          122         217                           315               416
1000              39          110         195                           283               374
1200              32          90          161                           235               311
1400              26          76          137                           200               265
1600              22          66          119                           174               230
1800              19          58          105                           153               203
2000              17          52          93                            137               181
2500              12          40          73                            107               142
3000              9           32          60                            88                117
3400              7           25          50                            72                100
4000              6           23          43                            60                85
4500              5           20          38                            54                75

* Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

          Note: Run times are in minutes


EBM Connections – IBM UPS5000




                                                           P a g e | 37                                     © IBM Corporation 2011
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0
Ibm system x_ups_guide_v1.6.0

More Related Content

What's hot

Pipe coating system
Pipe coating systemPipe coating system
Pipe coating system
Malai Kavya
 
MEMS microphone Patent Infringement April 2015 report published by Yole Devel...
MEMS microphone Patent Infringement April 2015 report published by Yole Devel...MEMS microphone Patent Infringement April 2015 report published by Yole Devel...
MEMS microphone Patent Infringement April 2015 report published by Yole Devel...
Yole Developpement
 
Carbon Disclosure Project: Reducing Risk and Driving Business Value
Carbon Disclosure Project: Reducing Risk and Driving Business ValueCarbon Disclosure Project: Reducing Risk and Driving Business Value
Carbon Disclosure Project: Reducing Risk and Driving Business Value
Sustainable Brands
 

What's hot (20)

Green bonds
Green bonds Green bonds
Green bonds
 
Gas Storage
Gas StorageGas Storage
Gas Storage
 
An Introduction to Carbon Offsets, Markets and Projects
An Introduction to Carbon Offsets, Markets and ProjectsAn Introduction to Carbon Offsets, Markets and Projects
An Introduction to Carbon Offsets, Markets and Projects
 
Finance for renewable energy
Finance for renewable energyFinance for renewable energy
Finance for renewable energy
 
presentation on voluntary carbon market.pptx
presentation on voluntary carbon market.pptxpresentation on voluntary carbon market.pptx
presentation on voluntary carbon market.pptx
 
HOW UL STANDARDS SUPPORT THE SAFETY LIFECYCLE OF EV BATTERIES
HOW UL STANDARDS SUPPORT THE SAFETY LIFECYCLE OF EV BATTERIESHOW UL STANDARDS SUPPORT THE SAFETY LIFECYCLE OF EV BATTERIES
HOW UL STANDARDS SUPPORT THE SAFETY LIFECYCLE OF EV BATTERIES
 
Pipe coating system
Pipe coating systemPipe coating system
Pipe coating system
 
The role of Direct Air Capture and Carbon Dioxide Removal in well below 2C sc...
The role of Direct Air Capture and Carbon Dioxide Removal in well below 2C sc...The role of Direct Air Capture and Carbon Dioxide Removal in well below 2C sc...
The role of Direct Air Capture and Carbon Dioxide Removal in well below 2C sc...
 
Long Duration Energy Storage - Eclipse Ventures.pdf
Long Duration Energy Storage - Eclipse Ventures.pdfLong Duration Energy Storage - Eclipse Ventures.pdf
Long Duration Energy Storage - Eclipse Ventures.pdf
 
Understanding Underground Storage Tanks
Understanding Underground Storage Tanks   Understanding Underground Storage Tanks
Understanding Underground Storage Tanks
 
MEMS microphone Patent Infringement April 2015 report published by Yole Devel...
MEMS microphone Patent Infringement April 2015 report published by Yole Devel...MEMS microphone Patent Infringement April 2015 report published by Yole Devel...
MEMS microphone Patent Infringement April 2015 report published by Yole Devel...
 
Une Communaute d'Energie sur le parc des Hauts-Sarts - 02/04/2021
Une Communaute d'Energie sur le parc des Hauts-Sarts - 02/04/2021Une Communaute d'Energie sur le parc des Hauts-Sarts - 02/04/2021
Une Communaute d'Energie sur le parc des Hauts-Sarts - 02/04/2021
 
Carbon Capture and Storage breakfast seminar
Carbon Capture and Storage breakfast seminarCarbon Capture and Storage breakfast seminar
Carbon Capture and Storage breakfast seminar
 
Tod's group slideshare version
Tod's group slideshare versionTod's group slideshare version
Tod's group slideshare version
 
The Why, What, and How of Innovation Management - ISO TC 279
The Why, What, and How of Innovation Management - ISO TC 279The Why, What, and How of Innovation Management - ISO TC 279
The Why, What, and How of Innovation Management - ISO TC 279
 
Energy Transition and CO2 Emission Fact Sheet.pptx
Energy Transition and CO2 Emission Fact Sheet.pptxEnergy Transition and CO2 Emission Fact Sheet.pptx
Energy Transition and CO2 Emission Fact Sheet.pptx
 
Carbon Disclosure Project: Reducing Risk and Driving Business Value
Carbon Disclosure Project: Reducing Risk and Driving Business ValueCarbon Disclosure Project: Reducing Risk and Driving Business Value
Carbon Disclosure Project: Reducing Risk and Driving Business Value
 
Adsorption Materials and Processes for Carbon Capture from Gas-Fired Power Pl...
Adsorption Materials and Processes for Carbon Capture from Gas-Fired Power Pl...Adsorption Materials and Processes for Carbon Capture from Gas-Fired Power Pl...
Adsorption Materials and Processes for Carbon Capture from Gas-Fired Power Pl...
 
IEA Net Zero Emissions 2050 - UNEP-FI version
IEA Net Zero Emissions 2050 - UNEP-FI versionIEA Net Zero Emissions 2050 - UNEP-FI version
IEA Net Zero Emissions 2050 - UNEP-FI version
 
UNDERSTANDING THE IMPLEMENTATION OF CCUS BUSINESS CASE
UNDERSTANDING THE IMPLEMENTATION OF CCUS BUSINESS CASEUNDERSTANDING THE IMPLEMENTATION OF CCUS BUSINESS CASE
UNDERSTANDING THE IMPLEMENTATION OF CCUS BUSINESS CASE
 

Viewers also liked

"high tension generator", "high tension","tension generator", "generator", ...
"high tension generator",  "high tension","tension generator",  "generator", ..."high tension generator",  "high tension","tension generator",  "generator", ...
"high tension generator", "high tension","tension generator", "generator", ...
Prem Murti
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 

Viewers also liked (20)

Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)
 
Huawei Modular UPS Systems UPS5000E Sereis
Huawei Modular UPS Systems UPS5000E SereisHuawei Modular UPS Systems UPS5000E Sereis
Huawei Modular UPS Systems UPS5000E Sereis
 
Engineered Custom Motor Controls
Engineered Custom Motor ControlsEngineered Custom Motor Controls
Engineered Custom Motor Controls
 
Summer training at NTPC Badarpur ppt
Summer training at NTPC Badarpur ppt Summer training at NTPC Badarpur ppt
Summer training at NTPC Badarpur ppt
 
Shoaib khan ntpc
Shoaib khan ntpcShoaib khan ntpc
Shoaib khan ntpc
 
Ntpc(btps) report
Ntpc(btps) reportNtpc(btps) report
Ntpc(btps) report
 
Protection settings calculation
Protection settings calculationProtection settings calculation
Protection settings calculation
 
UPS Batteries By BatteryClerk
UPS Batteries By BatteryClerkUPS Batteries By BatteryClerk
UPS Batteries By BatteryClerk
 
Protection settings calculation
Protection settings calculationProtection settings calculation
Protection settings calculation
 
40 MVA TX
40 MVA TX40 MVA TX
40 MVA TX
 
Srimedha Institute for CA - Fraud Institute
Srimedha Institute for CA - Fraud InstituteSrimedha Institute for CA - Fraud Institute
Srimedha Institute for CA - Fraud Institute
 
Electrical Design calculations
Electrical Design calculationsElectrical Design calculations
Electrical Design calculations
 
"high tension generator", "high tension","tension generator", "generator", ...
"high tension generator",  "high tension","tension generator",  "generator", ..."high tension generator",  "high tension","tension generator",  "generator", ...
"high tension generator", "high tension","tension generator", "generator", ...
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
ABB Software tools - DOC 2
ABB Software tools - DOC 2ABB Software tools - DOC 2
ABB Software tools - DOC 2
 
Top 10 bariatric interview questions with answers
Top 10 bariatric interview questions with answersTop 10 bariatric interview questions with answers
Top 10 bariatric interview questions with answers
 
Practical Motor Protection, Control and Maintenance Technologies
Practical Motor Protection, Control and Maintenance TechnologiesPractical Motor Protection, Control and Maintenance Technologies
Practical Motor Protection, Control and Maintenance Technologies
 
Ntpc badarpur training ppt
Ntpc badarpur training pptNtpc badarpur training ppt
Ntpc badarpur training ppt
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 

Similar to Ibm system x_ups_guide_v1.6.0

Cathodic protection dc voltage
Cathodic protection   dc voltageCathodic protection   dc voltage
Cathodic protection dc voltage
Asif Sheriff
 
Datavideo PD-1
Datavideo PD-1Datavideo PD-1
Datavideo PD-1
AVNed
 
Base unit dc actuator
Base unit dc actuatorBase unit dc actuator
Base unit dc actuator
Asif Sheriff
 
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)
Sarah Krystelle
 
ee2259-lab-manual
 ee2259-lab-manual ee2259-lab-manual
ee2259-lab-manual
surya721327
 
Multiple well cathodic protection
Multiple well cathodic protectionMultiple well cathodic protection
Multiple well cathodic protection
Asif Sheriff
 
Pump control.with base radio
Pump control.with base radioPump control.with base radio
Pump control.with base radio
Asif Sheriff
 
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)
Sarah Krystelle
 

Similar to Ibm system x_ups_guide_v1.6.0 (20)

Tle 2426
Tle 2426Tle 2426
Tle 2426
 
Base Unit AC CP
Base Unit AC CPBase Unit AC CP
Base Unit AC CP
 
Cathodic protection dc voltage
Cathodic protection   dc voltageCathodic protection   dc voltage
Cathodic protection dc voltage
 
Datavideo PD-1
Datavideo PD-1Datavideo PD-1
Datavideo PD-1
 
Base unit dc actuator
Base unit dc actuatorBase unit dc actuator
Base unit dc actuator
 
1k
1k1k
1k
 
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for PULA)
 
Tda8511 j
Tda8511 jTda8511 j
Tda8511 j
 
電流臨界モード方式PFC制御回路の解説書
電流臨界モード方式PFC制御回路の解説書電流臨界モード方式PFC制御回路の解説書
電流臨界モード方式PFC制御回路の解説書
 
Evaluation Report of TL431BILP
Evaluation Report of TL431BILPEvaluation Report of TL431BILP
Evaluation Report of TL431BILP
 
ee2259-lab-manual
 ee2259-lab-manual ee2259-lab-manual
ee2259-lab-manual
 
Ee2259 lab-manual
Ee2259 lab-manualEe2259 lab-manual
Ee2259 lab-manual
 
Multiple well cathodic protection
Multiple well cathodic protectionMultiple well cathodic protection
Multiple well cathodic protection
 
Pump control.with base radio
Pump control.with base radioPump control.with base radio
Pump control.with base radio
 
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)
SIGNAL SPECTRA EXPERIMENT 2 - FINALS (for CAUAN)
 
SPICE MODEL of AN1431T in SPICE PARK
SPICE MODEL of AN1431T in SPICE PARKSPICE MODEL of AN1431T in SPICE PARK
SPICE MODEL of AN1431T in SPICE PARK
 
SPICE MODEL of uPC24M18A in SPICE PARK
SPICE MODEL of uPC24M18A in SPICE PARKSPICE MODEL of uPC24M18A in SPICE PARK
SPICE MODEL of uPC24M18A in SPICE PARK
 
SPICE MODEL of uPC78M06A in SPICE PARK
SPICE MODEL of uPC78M06A in SPICE PARKSPICE MODEL of uPC78M06A in SPICE PARK
SPICE MODEL of uPC78M06A in SPICE PARK
 
Dvd D204
Dvd D204Dvd D204
Dvd D204
 
SPICE MODEL of uPC24M10A in SPICE PARK
SPICE MODEL of uPC24M10A in SPICE PARKSPICE MODEL of uPC24M10A in SPICE PARK
SPICE MODEL of uPC24M10A in SPICE PARK
 

Recently uploaded

Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
?#DUbAI#??##{{(☎️+971_581248768%)**%*]'#abortion pills for sale in dubai@
 

Recently uploaded (20)

A Beginners Guide to Building a RAG App Using Open Source Milvus
A Beginners Guide to Building a RAG App Using Open Source MilvusA Beginners Guide to Building a RAG App Using Open Source Milvus
A Beginners Guide to Building a RAG App Using Open Source Milvus
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
+971581248768>> SAFE AND ORIGINAL ABORTION PILLS FOR SALE IN DUBAI AND ABUDHA...
 
Manulife - Insurer Transformation Award 2024
Manulife - Insurer Transformation Award 2024Manulife - Insurer Transformation Award 2024
Manulife - Insurer Transformation Award 2024
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
Apidays New York 2024 - Accelerating FinTech Innovation by Vasa Krishnan, Fin...
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
"I see eyes in my soup": How Delivery Hero implemented the safety system for ...
"I see eyes in my soup": How Delivery Hero implemented the safety system for ..."I see eyes in my soup": How Delivery Hero implemented the safety system for ...
"I see eyes in my soup": How Delivery Hero implemented the safety system for ...
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challenges
 
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost SavingRepurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
 
AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024
 
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
 
Web Form Automation for Bonterra Impact Management (fka Social Solutions Apri...
Web Form Automation for Bonterra Impact Management (fka Social Solutions Apri...Web Form Automation for Bonterra Impact Management (fka Social Solutions Apri...
Web Form Automation for Bonterra Impact Management (fka Social Solutions Apri...
 
Ransomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdfRansomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdf
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
MS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectorsMS Copilot expands with MS Graph connectors
MS Copilot expands with MS Graph connectors
 

Ibm system x_ups_guide_v1.6.0

  • 1. A Guide to IBM System x Uninterruptible Power Supply (UPS) Remote emergency power-off port Line-interactive UPS Technology Optional RS-232 Optional EBM Ground NMC Bay Connector USB Connector Screw INPUT AVR OUTPUT FILTER FILTER AC SOURCE LOAD INVERTER BATTERY CHARGER DC LINK BATTERY NORMAL POWER FLOW Output Circuit Output Circuit Output Circuit Output Circuit Input Terminal Breaker (20A) Breaker (20A) Breaker (20A) Breaker (20A) Block w/ Cover STORED ENERGY POWER FLOW RECHARGE ENERGY FLOW 4 IEC 320 C19 4 IEC 320 C19 (Load Segment 1) (Load Segment 2) UPS Logical Layout 4 IEC 320 C19 Remote emergency (Load Segment 1) power-off port Output = 28A Max @ 200-240V Output Circuit Output Circuit RS-232 Breaker (20A) Breaker (20A) Optional Breaker 10A C13 NMC Bay USB Connector Amperage 10A C13 15A 10A C13 10A C13 10A C13 Outlet Amperage 10A C13 Outlet Type 20A 16A C19 16A C19 20A 16A C19 AC to DC 16A C19 then DC to AC Optional EBM Output Circuit 6 IEC 320 C13 Input Terminal Ground Input Line Connector Breaker (15A) (Load Segment 2) Block w/ Cover Screw Input = 30A Max @ 200-240V Authors: William S. Champion wchamp@us.ibm.com Matthew R. Archibald archibam@us.ibm.com Version: 1.6.0 Date: December 23, 2010 The user of this document is responsible for obtaining the latest copy prior to use. Obsolete copies may be archived and used for reference purposes only. The latest version of this document is located at: http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655
  • 2. A Guide To IBM System x Uninterruptible Power Supply (UPS) © IBM Corporation 2011 Revision History 1.0.0 – March 25, 2010 Initial Release 1.1.0 – May 17, 2010 Updated sections Introduction, How To Use This Guide, Input Connection Block for IBM UPS7500/10000, IBM System x Server Label Rating, IBM Storage Label Rating, IEC 309 Pin & Sleeve Plug Decode, and IEC 320 Connectors. Modified run times to be all in minutes. Added Some Background on Power Factor and UPS Sizing section. 1.2.0 – July 20, 2010 Added new rack mounted IBM UPS1500, IBM UPS2200, and IBM UPS3000, new line cords 1.3.0 – September 28, 2010 Update Helpful Links section. Updated Line Cords and Plugs section. Added new rack mounted IBM UPS6000. 1.4.0 – October 26, 2010 Add new IBM UPS1000/1500 tower models. 1.5.0 – January 19, 2011 Add new IBM UPS11000. Updated IEC 309 Pin & Sleeve Plug Decode section and document title to the more common spelling of uninterruptible. 1.5.1 – February 2, 2011 Updated System x server label ratings section. 1.6.0 – December 23, 2011 Remove old UPS1000/1500 Tower models. Updated Label Rating sections and cover page image. Contributors Marc Hollingsworth MarcHHollingsworth@Eaton.com Manager, Global Accounts – Eaton http://www.eaton.com/ibm David Walker dgwalker@us.ibm.com System x World Wide Options Marketing Manager Ben Hilmus bhilmus@us.ibm.com Worldwide System x Channel Enablement Preston Miller prmiller@apcc.com Global Program Manager – American Power Conversion (APC) http://www.apc.com Notices: This paper is intended to provide information regarding IBM® System x™ Power Uninterruptible Power Supply (UPS). It discusses findings based on configurations that were created and tested under laboratory conditions. These findings may not be realized in all customer environments, and implementation in such environments may require additional steps, configurations and performance analysis. The information herein is provided “AS IS” with no warranties, express or implied. This information does not constitute a specification or form part of the warranty for any IBM or non-IBM products. Information in this document was developed in conjunction with the use of the equipment specified and is limited in application to those specific hardware and software products and levels. The information contained in this document has not been submitted to any formal IBM test and is distributed as is. The use of this information or the implementation of these techniques is a customer responsibility and depends on the customer’s ability to evaluate and integrate them into the customer’s operational environment. While each item may have been reviewed by IBM for accuracy in a specific situation, there is no guarantee that the same or similar results will be obtained elsewhere. Customers attempting to adapt these techniques to their own environments do so at their own risk. IBM may not officially support techniques mentioned in this document. For questions regarding officially supported techniques, please refer to the product documentation, announcement letters or contact the IBM Support Line at 1-800-IBM-SERV. This document makes references to vendor-acquired applications or utilities. It is the customer responsibility to obtain licenses of these utilities prior to their usage. © Copyright International Business Machines Corporation 2011. All rights reserved. U.S. Government Users Restricted Rights – Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp. Page |2 © IBM Corporation 2011
  • 3. A Guide To IBM System x Uninterruptible Power Supply (UPS) Table of Contents TABLE OF CONTENTS ........................................................................................................................................................... 3 INTRODUCTION ................................................................................................................................................................... 6 HOW TO USE THIS GUIDE .............................................................................................................................................................. 6 IBM UPS QUICK VIEW .......................................................................................................................................................... 7 IBM UPS1000 TOWER .......................................................................................................................................................... 8 Optional Accessories ........................................................................................................................................................... 8 SELECTABLE LINE CORDS – IBM UPS1000 TOWER (230V) ................................................................................................................ 9 OUTLET DIAGRAM – IBM UPS1000 TOWER (100/120V) ............................................................................................................... 10 Logical Layout – IBM UPS1000 Tower (100/120V)............................................................................................................ 10 OUTLET DIAGRAM – IBM UPS1000 TOWER (230V)....................................................................................................................... 11 Logical Layout – IBM UPS1000 Tower (230V) ................................................................................................................... 11 RUN TIME – IBM UPS1000 TOWER ............................................................................................................................................. 11 IBM UPS1500 TOWER ........................................................................................................................................................ 12 Optional Accessories ......................................................................................................................................................... 12 SELECTABLE LINE CORDS – IBM UPS1500 TOWER .......................................................................................................................... 13 OUTLET DIAGRAM – IBM UPS1500 TOWER (120V)....................................................................................................................... 14 Logical Layout – IBM UPS1500 Tower (120V) ................................................................................................................... 14 OUTLET DIAGRAM – IBM UPS1500 TOWER (100V)....................................................................................................................... 15 Logical Layout – IBM UPS1500 Tower (100V) ................................................................................................................... 15 OUTLET DIAGRAM – IBM UPS1500 TOWER (230V)....................................................................................................................... 16 Logical Layout – IBM UPS1500 Tower (230V) ................................................................................................................... 16 RUN TIME – IBM UPS1500 TOWER ............................................................................................................................................. 17 IBM UPS1500THV TOWER .................................................................................................................................................. 18 SELECTABLE LINE CORDS – UPS1500THV ..................................................................................................................................... 18 OUTLET DIAGRAM – IBM UPS1500THV ...................................................................................................................................... 19 Logical Layout – IBM UPS1500THV ................................................................................................................................... 19 RUN TIME – IBM UPS1500THV ................................................................................................................................................. 19 IBM UPS1500 – RACK MOUNTED (RM) .............................................................................................................................. 20 Optional Accessories ......................................................................................................................................................... 20 SELECTABLE LINE CORDS – IBM UPS1500 RM .............................................................................................................................. 21 OUTLET DIAGRAM – IBM UPS1500 RM 100/120V ...................................................................................................................... 21 Logical Layout – IBM UPS1500 RM 100/120V .................................................................................................................. 21 OUTLET DIAGRAM – IBM UPS1500 RM 230V.............................................................................................................................. 22 Logical Layout – IBM UPS1500 RM 230V .......................................................................................................................... 22 RUN TIME – IBM UPS1500 RM ................................................................................................................................................. 22 IBM UPS2200 – RACK MOUNTED (RM) .............................................................................................................................. 23 Optional Accessories ......................................................................................................................................................... 23 SELECTABLE LINE CORDS – IBM UPS2200 RM .............................................................................................................................. 24 OUTLET DIAGRAM – IBM UPS2200 RM 100/120V ...................................................................................................................... 25 Logical Layout – IBM UPS2200 RM 100/120V .................................................................................................................. 25 OUTLET DIAGRAM – IBM UPS2200 RM 230V.............................................................................................................................. 26 Logical Layout – IBM UPS2200 RM 230V .......................................................................................................................... 26 RUN TIME – IBM UPS2200 RM – 100/120V .............................................................................................................................. 26 RUN TIME – IBM UPS2200 RM – 230V ...................................................................................................................................... 27 EBM CONNECTIONS – IBM UPS2200 RM.................................................................................................................................... 27 IBM UPS3000 – RACK MOUNTED (RM) .............................................................................................................................. 28 Optional Accessories ......................................................................................................................................................... 28 Page |3 © IBM Corporation 2011
  • 4. A Guide To IBM System x Uninterruptible Power Supply (UPS) SELECTABLE LINE CORDS – IBM UPS3000 RM .............................................................................................................................. 29 OUTLET DIAGRAM – IBM UPS3000 RM 100/120V ...................................................................................................................... 30 Logical Layout – IBM UPS3000 RM 100/120V .................................................................................................................. 30 OUTLET DIAGRAM – IBM UPS3000 RM 200/208V ...................................................................................................................... 31 Logical Layout – IBM UPS3000 RM 200/208V .................................................................................................................. 31 OUTLET DIAGRAM – IBM UPS3000 RM 230V.............................................................................................................................. 32 Logical Layout – IBM UPS3000 RM 230V .......................................................................................................................... 32 RUN TIME – IBM UPS3000 RM 100/120V ................................................................................................................................. 32 RUN TIME – IBM UPS3000 RM 200/208V ................................................................................................................................. 33 RUN TIME – IBM UPS3000 RM 230V ........................................................................................................................................ 33 EBM CONNECTIONS – IBM UPS3000 RM.................................................................................................................................... 34 IBM UPS5000 – RACK MOUNTED ....................................................................................................................................... 35 SELECTABLE LINE CORDS – IBM UPS5000 ..................................................................................................................................... 35 OUTLET DIAGRAM – IBM UPS5000 ............................................................................................................................................. 36 Logical Layout – IBM UPS5000 .......................................................................................................................................... 36 RUN TIME – IBM UPS5000 ........................................................................................................................................................ 37 EBM CONNECTIONS – IBM UPS5000 .......................................................................................................................................... 37 IBM UPS6000 – RACK MOUNTED ....................................................................................................................................... 38 Optional Accessories ......................................................................................................................................................... 38 OUTLET DIAGRAM – IBM UPS6000 200/208V ............................................................................................................................ 39 Logical Layout – IBM UPS6000 200/208V ......................................................................................................................... 39 OUTLET DIAGRAM – IBM UPS6000 230V .................................................................................................................................... 40 Logical Layout – IBM UPS6000 230V ................................................................................................................................ 40 RUN TIME – IBM UPS6000 ........................................................................................................................................................ 41 EBM CONNECTIONS – IBM UPS6000 .......................................................................................................................................... 41 INPUT CONNECTION BLOCK – IBM UPS6000 ................................................................................................................................. 42 IBM UPS7500/10000 – RACK MOUNTED ............................................................................................................................ 43 OUTLET DIAGRAM – IBM UPS7500/10000 ................................................................................................................................. 44 Logical Layout – IBM UPS7500/10000 .............................................................................................................................. 44 RUN TIME – IBM UPS7500/10000 ............................................................................................................................................ 45 EBM CONNECTIONS – IBM UPS7500/10000 .............................................................................................................................. 46 INPUT CONNECTION BLOCK – IBM UPS7500/10000 ..................................................................................................................... 47 International Connection Only .......................................................................................................................................... 47 North American Connection Only ...................................................................................................................................... 47 IBM UPS11000 – RACK MOUNTED ..................................................................................................................................... 48 Optional Accessories ......................................................................................................................................................... 48 OUTLET DIAGRAM – IBM UPS11000 ........................................................................................................................................... 49 Logical Layout – IBM UPS11000 ........................................................................................................................................ 49 RUN TIME – IBM UPS11000 ...................................................................................................................................................... 50 EBM CONNECTIONS – IBM UPS11000 ........................................................................................................................................ 50 INPUT CONNECTION BLOCK – IBM UPS11000 ............................................................................................................................... 51 LINE CORDS AND PLUGS .................................................................................................................................................... 52 100/120V NEMA 5-15P (NORTH AMERICA & JAPAN) UPS1500 RM & TOWER ............................................................................... 52 100/120V NEMA 5-20P (NORTH AMERICA & JAPAN) UPS2200 RM ............................................................................................. 52 100/120V NEMA L5-30P (NORTH AMERICA & JAPAN) UPS3000 RM ............................................................................................ 52 200/208V NEMA L6-20P (NORTH AMERICA & JAPAN) UPS3000 RM ............................................................................................ 53 CEE7-VII (EUROPE) ................................................................................................................................................................... 53 DK2-5A (DENMARK) .................................................................................................................................................................. 54 SEV 1011-S24507 (SWITZERLAND) ............................................................................................................................................. 54 SI 32 (ISRAEL) ........................................................................................................................................................................... 54 CEI 23-16 (ITALY) ..................................................................................................................................................................... 55 Page |4 © IBM Corporation 2011
  • 5. A Guide To IBM System x Uninterruptible Power Supply (UPS) SABS 164 (SOUTH AFRICA) ......................................................................................................................................................... 55 BS 1363/A (UK) ...................................................................................................................................................................... 56 AS/NZS 3112 (AUS/NZ) ........................................................................................................................................................... 56 KSC 8305 (S. KOREA) ................................................................................................................................................................ 57 IS6538 (INDIA) ......................................................................................................................................................................... 57 GB 2099.1 (CHINA) .................................................................................................................................................................. 58 NBR 6147 (BRAZIL) ................................................................................................................................................................... 58 IRAM 2073 (ARGENTINA) .......................................................................................................................................................... 59 IEC 309 P+N+G (DENMARK/SWITZERLAND).................................................................................................................................. 59 NBR 14136 (BRAZIL)................................................................................................................................................................. 59 SEV 1011 T23 (SWITZERLAND) ................................................................................................................................................... 60 CNS 10917 – 125V (TAIWAN) ................................................................................................................................................... 60 CNS 10917 – 250V (TAIWAN) ................................................................................................................................................... 60 40K9612 - IBM DPI 32A CORD (IEC 309 P+N+G) ....................................................................................................................... 61 40K9614 - IBM DPI 30A CORD (NEMA L6-30P)......................................................................................................................... 61 40K9617 – IBM DPI 32A CORD (AUS/NZ 3112 32A) ................................................................................................................. 61 40K9618 – IBM DPI 30A CORD (KSC 8305 30A) ........................................................................................................................ 62 REFERENCE MATERIAL ....................................................................................................................................................... 63 IBM BLADECENTER CHASSIS LABEL RATING .................................................................................................................................... 63 IBM STORAGE LABEL RATING ....................................................................................................................................................... 63 IBM SYSTEM X SERVER LABEL RATING............................................................................................................................................ 64 IBM SYSTEM X SERVER LABEL RATING – CONTINUED ........................................................................................................................ 65 IBM SYSTEM X TOP OF RACK ETHERNET SWITCH LABEL RATING .......................................................................................................... 65 IBM XSERIES SERVER LABEL RATING .............................................................................................................................................. 65 IBM IDATAPLEX CHASSIS LABEL RATING......................................................................................................................................... 66 IBM IDATAPLEX CHASSIS LABEL RATING – CONTINUED ..................................................................................................................... 67 SOME BACKGROUND ON POWER FACTOR AND UPS SIZING ................................................................................................................ 68 IEC 309 PIN & SLEEVE PLUG DECODE ........................................................................................................................................... 69 INGRESS PROTECTION (IP) DECODE ............................................................................................................................................... 70 IEC 320 CONNECTORS ................................................................................................................................................................ 70 60A THREE PHASE DELTA POWER CALCULATIONS ............................................................................................................................ 71 32A THREE PHASE WYE POWER CALCULATIONS .............................................................................................................................. 71 UPS INSTALLATION MANUAL LINKS ............................................................................................................................................... 72 HELPFUL LINKS........................................................................................................................................................................... 72 Page |5 © IBM Corporation 2011
  • 6. A Guide To IBM System x Uninterruptible Power Supply (UPS) Introduction The Uninterruptible Power Supply (UPS) systems covered in this guide are those that are currently marketed worldwide. The intent of this guide is to provide UPS information when needed when planning power for System x and BladeCenter solutions. This guide is best used in softcopy form since it contains hyperlinks for navigation. This document can still be used in hardcopy as reference only. You can obtain the latest copy of this document by sending an email to wchamp@us.ibm.com or archibam@us.ibm.com (put “Latest UPS Guide” in the subject line). For more information about how to size and plan for UPS systems, see the “Background on Power Factor and UPS Sizing” section on page 68 of this document. How to Use This Guide In order to size a UPS properly, you need to know the total power requirements of what will be connected to the UPS. This information is available from the System x & BladeCenter Power Configurator: http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html When the total supported power is know, and appropriately sized UPS can be selected. Once a UPS is selected the solution wiring needs to be figured out. UPS systems have outlet and group limits, much like PDUs and the solution needs to be wired so as to not exceed the outlet and/or group rating of the UPS. The IT appliances and UPS systems need to be wired according to system nameplate rating for compliance with local electrical codes and product support documentation. In cases where a UPS fits the electrical load of a solution, but the UPS does not have sufficient C13 outlets, DPI Universal Rack PDUs (P/N: 39Y8951 F/C: 5950) may be able to be used to offer additional C13 outlets. When wiring the solution using PDUs, the same restrictions apply in that the outlet and group limitations of the UPS and PDUs are not exceeded. Page |6 © IBM Corporation 2011
  • 7. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS Quick View Option Input Max Input Output UPS Number Voltage Amperage Voltage Output W / Amperage Outlets Page 1 53961AX 120V 1ph 120V 1ph 8 / 5-15 UPS1000 7 12A 750W / 7.5A 1 53961JX 100V 1ph 100V 1ph 8 / 5-15 8 Tower 8 5 53961KX 230V 1ph 10A 230V 1ph 750W / 3.75A 8 / C13 1 53962AX 120V 1ph 12A 120V 1ph 8 / 5-15 UPS1500 7 1000W / 10A 2 53962JX 100V 1ph 16A 100V 1ph 8 / 5-20 12 Tower 8 5 53962KX 230V 1ph 10A 230V 1ph 1000W / 5A 8 / C13 UPS1500THV 200-240V 200-240V 5 2130R6X 7.5A 1050W / 5.25A 8 / C13 18 Tower 1ph 1ph 1 100-127V 120V 1ph 4 / 5-15 UPS1500 53951AX 13A 1000W / 10A 5 1ph 100V 1ph 2 / C13 20 Rack 5 53951KX 230V 1ph 7.5A 230V 1ph 1000W / 5A 4 / C13 2 6 / 5-20 100-127V 120V 1ph 1920W / 16A @ 120V 5 53952AX 16A 2 / C13 UPS2200 1ph 100V 1ph 1500W / 16A @ 100V 6 2 / C19 23 Rack 5 8 / C13 53952KX 230V 1ph 10A 230V 1ph 1920W / 9.6A 6 2 / C19 2 2 / 5-20 3 100-127V 120V 1ph 2700W / 22.5A @ 120V 1 / L5-20 53953AX 24A 5 1ph 100V 1ph 2300W / 22.5A @ 100V 2 / C13 6 2 / C19 UPS3000 4 1 / L6-20 28 Rack 200V 1ph 200V 1ph 5 53953JX 16A 2700W / 13.5A 2 / C13 208V 1ph 208V 1ph 6 2 / C19 5 8 / C13 53953KX 230V 1ph 16A 230V 1ph 2700W / 13.5A 6 2 / C19 5 UPS5000 200-240V 200-240V 8 / C13 24195KX 25A 4500W / 22.5A 6 35 Rack 1ph 1ph 2 / C19 9 200V 1ph 200V 1ph 2 / L6-30 53956AX 30A 6 UPS6000 208V 1ph 208V 1ph 4 / C19 5600W / 28A 5 38 Rack 6 / C13 53956KX 230V 1ph 30A 230V 1ph 6 4 / C19 200-240V 38A UPS7500 1ph 200-240V 6 21303RX 6000W / 30A 4 / C19 43 Rack 380-415V 1ph 8 14A 3ph Wye 200-240V 50A UPS10000 1ph 200-240V 6 21304RX 8000W / 40A 4 / C19 43 Rack 380-415V 1ph 8 18A 3ph Wye UPS11000 200-240V 69.96A 200- 6 53959KX 10000W / 50A 8 / C19 48 Rack 1ph 240V1ph 1 – “5-15” refers to NEMA 5-15 outlet 6 – “C19” refers to IEC320 C19 outlet 2 – “5-20” refers to NEMA 5-20 outlet 7 – Supported only in Japan 3 – “L5-20” refers to NEMA L5-20 outlet 8 – Not supported in North America or Japan 4 – “L6-20” refers to NEMA L6-20 outlet 9 – “L6-30” refers to NEMA L6-30 outlet 5 – “C13” refers to IEC320 C13 outlet Page |7 © IBM Corporation 2011
  • 8. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS1000 Tower Back IBM UPS1000 53961AX (120V) Back Tower Front 53961JX (100V) 53961KX (230V) UPS1000 120V UPS1000 100V UPS1000 230V Part Number 5396-1AX 5396-1JX 5396-1KX Feature Code 5396-TU1 (FC 6663) 5396-TU1 (FC 6664) 5396-TU1 (FC 6665) EBMs Supported None None None EPO Connection Yes Yes Yes Power Factor 0.75 0.75 0.75 UPS Type Line Interactive Line Interactive Line Interactive Supported Country or Region North America Japan International Input 120V 100V 230V Line Cord detachable 4.3m, detachable 4.3m, Selectable NEMA 5-15P NEMA 5-15P Voltage Range 84-121V for 100V 84-121V for 100V 160V-286V for 230V 97-145V for 120V 97-145V for 120V Max Current 12A 12A 10A Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. Surge Energy Rating 1200 joules 1200 joules 2400 joules Output 120V 100V 230V Watts 750W 750W 750W Nominal Voltage 220, 230, or 240V 120V (Configurable) 100V (Configurable) (Configurable) Maximum Amperage 7.5A 7.5A 3.75A Receptacles 8 x NEMA 5-15R 8 x NEMA 5-15R 8 x IEC 320 C13 Optional Accessories Network Management Card (NMC) Environmental Monitor Probe P/N: 46M4110 FC: 6145 P/N: 46M4113 FC: 6146 Page |8 © IBM Corporation 2011
  • 9. A Guide To IBM System x Uninterruptible Power Supply (UPS) Selectable Line Cords – IBM UPS1000 Tower (230V) 2.8m 4.3m Line Cord Line Cord Plug Type Country or Region 39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China 81Y2374 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina Page |9 © IBM Corporation 2011
  • 10. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS1000 Tower (100/120V) Optional Remote emergency NMC Bay power-off port RS-232 USB Connector 2 NEMA 5-15P (Load Segment 1) 6 NEMA 5-15P (Load Segment 2) Detachable Line Cord Logical Layout – IBM UPS1000 Tower (100/120V) Outlet Output = 7.5A Max 100-120V Amperage 15A 5-15 15A 5-15 15A 5-15 Outlet Type 15A 5-15 15A 5-15 15A 5-15 AC to DC 15A 5-15 then 15A 5-15 DC to AC Input Line Input = 12A 100-120V P a g e | 10 © IBM Corporation 2011
  • 11. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS1000 Tower (230V) Optional Remote emergency NMC Bay power-off port RS-232 USB Connector 2 IEC 320 C13 (Load Segment 1) 6 IEC 320 C13 (Load Segment 2) Detachable Line Cord Logical Layout – IBM UPS1000 Tower (230V) Outlet Output = 3.75A Max 200-240V Amperage 10A C13 10A C13 10A C13 Outlet Type 10A C13 10A C13 10A C13 AC to DC 10A C13 then 10A C13 DC to AC Input Line Input = 10A 200-240V Run Time – IBM UPS1000 Tower Internal % Load (W) Batteries * 25% 188 25 50% 375 15 75% 573 7 100% 750 6 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes P a g e | 11 © IBM Corporation 2011
  • 12. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS1500 Tower IBM UPS1500 Back Back Back Tower Front 53962AX (120V) 53962JX (100V) 53962KX (230V) UPS1500 120V UPS1500 100V UPS1500 230V Part Number 5396-2AX 5396-2JX 5396-2KX Feature Code 5396-TU2 (FC 6666) 5396-TU2 (FC 6667) 5396-TU2 (FC 6668) EBMs Supported None None None EPO Connection Yes Yes Yes Power Factor 0.7 0.7 0.7 UPS Type Line Interactive Line Interactive Line Interactive Supported Country or Region North America Japan International Input 120V 100V 230V Line Cord detachable 2.8m, detachable 2.5m, Selectable NEMA 5-15P NEMA 5-20P Voltage Range 97-145V 84-121V 160V-286V Max Current 12A 16A 10A Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. Surge Energy Rating 1200 joules 1200 joules 2400 joules Output 120V 100V 230V Watts 1000W 1000W 1000W Nominal Voltage 220, 230, or 240V 120V (Configurable) 100V (Configurable) (Configurable) Maximum Amperage 10A 10A 5A Receptacles 8 x NEMA 5-15R 8 x NEMA 5-15R 8 x IEC 320 C13 Optional Accessories Network Management Card (NMC) Environmental Monitor Probe P/N: 46M4110 FC: 6145 P/N: 46M4113 FC: 6146 P a g e | 12 © IBM Corporation 2011
  • 13. A Guide To IBM System x Uninterruptible Power Supply (UPS) Selectable Line Cords – IBM UPS1500 Tower 2.8m 4.3m Line Cord Line Cord Plug Type Country or Region 39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China 81Y2374 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina P a g e | 13 © IBM Corporation 2011
  • 14. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS1500 Tower (120V) Optional Remote emergency NMC Bay power-off port RS-232 USB Connector 2 NEMA 5-15P (Load Segment 1) 6 NEMA 5-15P (Load Segment 2) Detachable Line Cord Logical Layout – IBM UPS1500 Tower (120V) Outlet Output = 10A Max 100-120V Amperage 15A 5-15 15A 5-15 15A 5-15 Outlet Type 15A 5-15 15A 5-15 15A 5-15 AC to DC 15A 5-15 then 15A 5-15 DC to AC Input Line Input = 12A 100-120V P a g e | 14 © IBM Corporation 2011
  • 15. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS1500 Tower (100V) Optional Remote emergency NMC Bay power-off port RS-232 USB Connector 2 NEMA 5-20P (Load Segment 1) 6 NEMA 5-20P (Load Segment 2) Detachable Line Cord Logical Layout – IBM UPS1500 Tower (100V) IBM UPS1500LV 100V Outlet Output = 10A Max 100V Amperage 20A 5-20 20A 5-20 20A 5-20 Outlet Type 20A 5-20 20A 5-20 20A 5-20 AC to DC 20A 5-20 then 20A 5-20 DC to AC Input Line Input = 16A 100V P a g e | 15 © IBM Corporation 2011
  • 16. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS1500 Tower (230V) Optional Remote emergency NMC Bay power-off port RS-232 USB Connector 2 IEC 320 C13 (Load Segment 1) 6 IEC 320 C13 (Load Segment 2) Detachable Line Cord Logical Layout – IBM UPS1500 Tower (230V) IBM UPS1500LV 230V Outlet Output = 5A Max 200-240V Amperage 10A C13 10A C13 10A C13 Outlet Type 10A C13 10A C13 10A C13 AC to DC 10A C13 then 10A C13 DC to AC Input Line Input = 10A 200-240V P a g e | 16 © IBM Corporation 2011
  • 17. A Guide To IBM System x Uninterruptible Power Supply (UPS) Run Time – IBM UPS1500 Tower Internal % Load (W) Batteries * 25% 255 36 50% 510 15 75% 750 9 100% 970 6 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes P a g e | 17 © IBM Corporation 2011
  • 18. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS1500THV Tower UPS1500THV Back UPS1500THV Part Number 2130R6X EBMs Supported None EPO Connection None Power Factor 0.7 UPS Type Double Conversion Input High Voltage 1 Supported Region International Line Cord Selectable Voltage 200-240V VA 1500 VA Max Current 7.5A Phase / Frequency 1ph / 50 or 60Hz. Output High Voltage Watts 1050 W Nominal voltage 200-240V Max Current 5.25A Receptacles 8 / C13 1 – Does not include support for North America or Japan Selectable Line Cords – UPS1500THV Line Cord Plug Type Country or Region 39Y7917 CEE7-VII Europe 39Y7918 DK2-5a Denmark 39Y7919 SEV 1011-S24507 Switzerland 39Y7920 SI 32 Israel 39Y7921 CEI 23-16 Italy 39Y7922 SABS 164 South Africa 39Y7923 BS 1363/A United Kingdom 39Y7924 AS/NZS 3112 Australia / New Zealand 39Y7925 KSC 8305 South Korea 39Y7927 IS6538 India 39Y7928 GB 2099.1 China 39Y7929 NBR 6147 Brazil 39Y7930 IRAM 2073 Argentina P a g e | 18 © IBM Corporation 2011
  • 19. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS1500THV Battery Connector * 15A Circuit Breaker Outlets Input Line Cord Connector Logical Layout – IBM UPS1500THV Outlet Output = 5.25A Max 200-240V Amperage 10A C13 10A C13 Breaker 10A C13 Outlet Type Amperage 15A 10A C13 10A C13 10A C13 AC to DC 10A C13 then 10A C13 DC to AC Input Line Input = 7.5A 200-240V Run Time – IBM UPS1500THV Runtime (minutes) Load (W) UPS1000T * UPS1500T * 30 224 269 60 127 157 122 64 80 184 41 51 247 29 37 311 23 28 377 18 22 447 15 18 500 13.5 16.5 511 12 15 579 11 13 700 8 11 790 - 9 936 - 7.4 1050 - 6.7 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes P a g e | 19 © IBM Corporation 2011
  • 20. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS1500 – Rack Mounted (RM) IBM UPS1500 RM Front 53951AX (100V, 120V) Back 53951KX (230V) Back UPS1500 100/120V UPS1500 230V Part Number 5395-1AX 5395-1KX Feature Code 5395-RU1 (FC 6653) 5395-RU1 (FC 6654) EBMs Supported None None U Space 2 2 EPO Connection Yes Yes Power Factor 0.7 0.7 UPS Type Line Interactive Line Interactive Supported Country or Region North America, Japan International Input 100/120V 230V Line Cord detachable 4.3m, Selectable NEMA 5-15P Voltage Range 84-121V for 100V 160V-286V for 230V 97-145V for 120V Max Current 13A 7.5A Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. Surge Energy Rating 1200 joules 2400 joules Output 100/120V 230V Watts 1000W 1000W Nominal Voltage 100V, 120V 220, 230, or 240V (Configurable) (Configurable) Maximum Amperage 10A 5A Receptacles 4 x NEMA 5-15R 4 x IEC 320 C13 2 x IEC 320 C13 Optional Accessories Network Management Card (NMC) Environmental Monitor Probe P/N: 46M4110 FC: 6145 P/N: 46M4113 FC: 6146 P a g e | 20 © IBM Corporation 2011
  • 21. A Guide To IBM System x Uninterruptible Power Supply (UPS) Selectable Line Cords – IBM UPS1500 RM 2.8m 4.3m Line Cord Line Cord Plug Type Country or Region 39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China 81Y2374 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina Outlet Diagram – IBM UPS1500 RM 100/120V Detachable Optional 4 NEMA 5-15R Line Cord NMC Bay USB (Load Segment 1) Ground Screw Remote emergency RS-232 2 IEC 320 C13 power-off port Connector (Load Segment 2) Logical Layout – IBM UPS1500 RM 100/120V Outlet Amperage Output = 10A Max @ 100-120V 10A C13 10A C13 Outlet Type 15A 5-15 15A 5-15 AC to DC 15A 5-15 then 15A 5-15 DC to AC Input Line Input = 13A Max @ 100-120V Note: Color Indicates Load Grouping P a g e | 21 © IBM Corporation 2011
  • 22. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS1500 RM 230V Detachable Optional 2 IEC320 C13 Line Cord NMC Bay USB (Load Segment 1) Ground Remote emergency RS-232 2 IEC320 C13 Screw power-off port (Load Segment 2) Logical Layout – IBM UPS1500 RM 230V Outlet Amperage Output = 5A Max @ 220-240V 10A C13 10A C13 Outlet Type 15A C13 15A C13 AC to DC then DC to AC Input Line Input = 7.5A Max @ 220-240V Note: Color Indicates Load Grouping Run Time – IBM UPS1500 RM Internal % Load (W) Batteries * 25% 250 14 50% 500 11 75% 750 7 100% 1000 5 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes P a g e | 22 © IBM Corporation 2011
  • 23. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS2200 – Rack Mounted (RM) IBM UPS2200 RM Front 53952AX (100V, 120V) Back 53952KX (230V) Back IBM UPS2200 EBM Front UPS2200 100/120V UPS2200 230V EBM Part Number 5395-2AX 5395-2KX 46M4108 Feature Code 5395-RU2 (FC 6655) 5395-RU2 (FC 6656) 5395-RU2 (FC 5732) EBMs Supported 1 1 - U Space 2 2 2 EPO Connection Yes Yes - Power Factor 1.0 0.96 - UPS Type Line Interactive Line Interactive - Supported Country or North America, Japan International - Region Input 100/120V 230V EBM Line Cord Detachable 4.3m, Selectable - NEMA 5-20P Voltage Range 84-121V for 100V 160V-286V for 230V - 97-145V for 120V Max Current 16A 10A - Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. - Surge Energy Rating 1200 joules 2400 joules - Output 100/120V 230V EBM Watts 1500W @ 100V (Japan) 1920W - 1920W @ 120V (North America) Nominal Voltage 100V, 120V 220, 230, or 240V - (Configurable) (Configurable) Maximum Amperage 16A @ 100V 9.6A 16A @ 120V Receptacles 6 x NEMA 5-20R 2 x IEC 320 C19 2 x IEC 320 C19 - 8 x IEC 320 C13 2 x IEC 320 C13 Optional Accessories Network Management Card (NMC) Environmental Monitor Probe P/N: 46M4110 FC: 6145 P/N: 46M4113 FC: 6146 P a g e | 23 © IBM Corporation 2011
  • 24. A Guide To IBM System x Uninterruptible Power Supply (UPS) Selectable Line Cords – IBM UPS2200 RM 2.8m 4.3m Line Cord Line Cord Plug Type Country or Region 39Y7917 81Y2376 CEE7-VII Europe 39Y7918 81Y2382 DK2-5a Denmark 39Y7919 81Y2390 SEV 1011-S24507 Switzerland 39Y7920 81Y2381 SI 32 Israel 39Y7921 81Y2380 CEI 23-16 Italy 39Y7922 81Y2379 SABS 164 South Africa 39Y7923 81Y2377 BS 1363/A United Kingdom 39Y7924 81Y2383 AS/NZS 3112 Australia / New Zealand 39Y7925 81Y2385 KSC 8305 South Korea 39Y7927 81Y2386 IS6538 India 39Y7928 81Y2378 GB 2099.1 China - 81Y2388 CNS 10917 (125V) Taiwan 81Y2375 81Y2389 CNS 10917 (250V) Taiwan 39Y7929 81Y2387 NBR 6147 Brazil 39Y7930 81Y2384 IRAM 2073 Argentina P a g e | 24 © IBM Corporation 2011
  • 25. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS2200 RM 100/120V Ground Optional 2 IEC 320 C13 2 IEC 320 C19 Screw USB NMC Bay (Load Segment 2) (Load Segment 1) Remote emergency RS-232 Optional EBM 6 6 NEMA 5-20R power-off port Connector Connector (Load Segment 1) Detachable Line Cord Logical Layout – IBM UPS2200 RM 100/120V Outlet Amperage Output = 16A Max @ 100-120V 10A C13 10A C13 20A 5-20 20A 5-20 20A 5-20 Outlet Type 20A 5-20 20A 5-20 20A 5-20 AC to DC 16A C19 then 16A C19 DC to AC Input Line Input = 16A Max @ 100-120V Note: Color Indicates Load Grouping P a g e | 25 © IBM Corporation 2011
  • 26. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS2200 RM 230V Optional 2 IEC 320 C13 2 IEC 320 C19 Ground Screw NMC Bay (Load Segment 2) (Load Segment 1) Remote emergency USB RS-232 Optional EBM 6 IEC 320 C13 power-off port Connector Connector (Load Segment 1) Detachable Line Cord Logical Layout – IBM UPS2200 RM 230V Outlet Amperage Output = 9.6A Max @ 200-240V 10A C13 10A C13 10A C13 10A C13 10A C13 Outlet Type 10A C13 10A C13 10A C13 AC to DC 16A C19 then 16A C19 DC to AC Input Line Input = 10A Max @ 220-240V Note: Color Indicates Load Grouping Run Time – IBM UPS2200 RM – 100/120V Number of EBM (P/N 46M4108) Internal % Load (W) Batteries * +1 * 25% 500 42 143 50% 969 18 66 75% 1450 11 43 100% 1920 7 28 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes P a g e | 26 © IBM Corporation 2011
  • 27. A Guide To IBM System x Uninterruptible Power Supply (UPS) Run Time – IBM UPS2200 RM – 230V Number of EBM (P/N 46M4108) Internal % Load (W) Batteries * +1 * 25% 500 41 138 50% 968 17 64 75% 1450 10 40 100% 1920 7 28 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes EBM Connections – IBM UPS2200 RM P a g e | 27 © IBM Corporation 2011
  • 28. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS3000 – Rack Mounted (RM) IBM UPS3000 Front 53953JX (208V) Back IBM UPS3000 EBM Front 53953KX (230V) Back 53953AX (100V, 120V) Back UPS3000 100/120V UPS3000 200/208V UPS3000 230V EBM Part Number 5395-3AX 5395-3JX 5395-3KX 69Y1982 5395-RU3 Feature Code 5395-RU3 (FC 6657) 5395-RU3 (FC 6658) 5395-RU3 (FC 6659) (FC 5733) EBMs Supported 1 1 1 - U Space 3 3 3 3 EPO Connection Yes Yes Yes - Power Factor 0.9 0.9 0.9 - UPS Type Line Interactive Line Interactive Line Interactive - Supported Country North America, North America, Japan World Wide - or Region Japan Input 100/120V 200/208V 230V EBM Attached 2.0m, Detachable Line Cord Selectable - NEMA L5-30P NEMA L6-20P 84-121V for 100V Voltage Range 155-255V for 208V 160V-286V for 230V - 97-145V for 120V Max Current 24A 16A 16A - Phase / Frequency 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. 1ph / 50 or 60Hz. - Surge Energy Rating 1200 joules 2400 joules 2400 joules - Output 100/120V 200/208V 230V EBM Watts 2300W @ 100V (Japan) 2700W 2700W - 2700W @ 120V (North America) Nominal Voltage 100V, 120V 208V 220, 230, or 240V - (Configurable) (Configurable) (Configurable) Maximum Amperage 22.5A @ 100V 13.5A 13.5A 22.5A @ 120V Receptacles 1 x NEMA L5-20R 2 x NEMA L6-20R 2 x NEMA 5-20R 2 x IEC 320 C19 2 x IEC 320 C19 - 2 x IEC 320 C19 8 x IEC 320 C13 2 x IEC 320 C13 2 x IEC 320 C13 Optional Accessories Network Management Card (NMC) Environmental Monitor Probe P/N: 46M4110 FC: 6145 P/N: 46M4113 FC: 6146 P a g e | 28 © IBM Corporation 2011
  • 29. A Guide To IBM System x Uninterruptible Power Supply (UPS) Selectable Line Cords – IBM UPS3000 RM Line Cord Plug Type Country or Region 40K9766 CEE7-VII Europe 40K9767 BS 1363/A w/13A fuse UK 40K9768 CEI 23-16 Italy 40K9769 IEC 309-P+N+G Dmk/Swiss 40K9770 SABS 164 S Africa 40K9771 SI 32 Israel 40K9772 NEMA L6-20P North America & Japan 40K9773 AS/NZS 3112 Australia/NZ 40K9774 GB 2099.1 China 40K9776 IS 6538 India 40K9777 IRAM 2073 Argentina 59Y2747 CNS 10917 (250V) Taiwan 59Y2749 KSC 8305 Korea 69Y1989 NBR 14136 Brazil 81Y2391 SEV 1011 T23 Switzerland P a g e | 29 © IBM Corporation 2011
  • 30. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS3000 RM 100/120V 2 IEC 320 C13 (Load Segment 2) Remote emergency Output Circuit Optional EBM power-off port USB Breakers Connector RS-232 2 NEMA 5-20R Ground Connector (Load Segment 1) Fixed 2.0m NEMA L5-30P Screw Line Cord Optional 1 NEMA L5-20R NMC Bay (Load Segment 1) 2 IEC 320 C19 (Load Segment 1) Logical Layout – IBM UPS3000 RM 100/120V Output = 22.5A Max @ 100-120V 20A 10A C13 Outlet 10A C13 Amperage Breaker 20A 5-20 Outlet Type Amperage 20A 20A 5-20 16A C19 16A C19 AC to DC 20A L5-20 then DC to AC Input Line Input = 24A Max @ 100-120V Note: Color Indicates Load Grouping P a g e | 30 © IBM Corporation 2011
  • 31. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS3000 RM 200/208V Remote emergency 2 IEC 320 C13 Optional EBM power-off port USB (Load Segment 2) Connector Detachable Ground RS-232 2 NEMA L6-20R 2 IEC 320 C19 Line Cord Screw Connector (Load Segment 1) (Load Segment 1) Logical Layout – IBM UPS3000 RM 200/208V Outlet Amperage Output = 13.5A @ Max 200-240V 10A C13 10A C13 Outlet Type 16A C19 16A C19 AC to DC 20A L6-20 then 20A L6-20 DC to AC Input Line Input = 16A Max @ 200-240V Note: Color Indicates Load Grouping P a g e | 31 © IBM Corporation 2011
  • 32. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS3000 RM 230V Remote emergency 2 IEC 320 C13 Optional EBM power-off port USB (Load Segment 2) Connector Detachable Ground RS-232 6 IEC 320 C13 2 IEC 320 C19 Line Cord Screw Connector (Load Segment 1) (Load Segment 1) Logical Layout – IBM UPS3000 RM 230V Outlet Amperage Output = 13.5A Max @ 200-240V 10A C13 10A C13 10A C13 10A C13 10A C13 Outlet Type 10A C13 10A C13 10A C13 AC to DC 16A C19 then 16A C19 DC to AC Input Line Input = 16A Max @ 220-240V Note: Color Indicates Load Grouping Run Time – IBM UPS3000 RM 100/120V Number of EBM (P/N 69Y1982) Internal % Load (W) Batteries * +1 * 25% 678 42 156 50% 1350 16 62 75% 2060 10 42 100% 2700 7 27 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. P a g e | 32 © IBM Corporation 2011
  • 33. A Guide To IBM System x Uninterruptible Power Supply (UPS) Note: Run times are in minutes Run Time – IBM UPS3000 RM 200/208V Number of EBM (P/N 69Y1982) Internal % Load (W) Batteries * +1 * 25% 660 41 153 50% 1340 17 68 75% 2040 10 43 100% 2680 6 29 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes Run Time – IBM UPS3000 RM 230V Number of EBM (P/N 69Y1982) Internal % Load (W) Batteries * +1 * 25% 670 41 156 50% 1350 17 81 75% 2020 10 41 100% 2680 7 27 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes P a g e | 33 © IBM Corporation 2011
  • 34. A Guide To IBM System x Uninterruptible Power Supply (UPS) EBM Connections – IBM UPS3000 RM P a g e | 34 © IBM Corporation 2011
  • 35. A Guide To IBM System x Uninterruptible Power Supply (UPS) IBM UPS5000 – Rack Mounted IBM UPS5000 Front IBM UPS5000 Back IBM UPS5000 EBM Back Model UPS5000XHV EBM Part Number 2419-5KX 39Y8857 Feature Code 2419-RU1 (FC 7618) 2419-RU1 (FC 5743) EBMs Supported 4 - EPO Connection Yes - Power Factor 0.9 - UPS Type Double Conversion - Supported Country or Region World Wide - Input UPS5000XHV EBM Line Cord Selectable - Voltage 200-240V - VA 5000 - Max Current 30A - Phase / Frequency 1ph / 50 or 60Hz. - Output UPS5000XHV EBM Watts 4500 - Nominal voltage 200-240V - Maximum Amperage 22.5A - Receptacles 8 x IEC320 C13 - 2 x IEC320 C19 Selectable Line Cords – IBM UPS5000 Line Cord Plug Type Country or Region 40K9612 IEC 309 P+N+G International 40K9614 NEMA L6-30P North America 40K9617 AUS/NZ 3112 32A Australia / New Zealand 40K9618 KSC 8305 30A South Korea P a g e | 35 © IBM Corporation 2011
  • 36. A Guide To IBM System x Uninterruptible Power Supply (UPS) Outlet Diagram – IBM UPS5000 Input Connector 15A Circuit Breaker / Load Segment Load Segemnt 2 Load Segemnt 1 Logical Layout – IBM UPS5000 Outlet Amperage Output = 22.5A Max 200-240V 10A C13 15A 10A C13 10A C13 10A C13 16A C19 Breaker Outlet Type Amperage 10A C13 15A 10A C13 10A C13 AC to DC 10A C13 then 16A C19 DC to AC Input Line Input = 30A 200-240V P a g e | 36 © IBM Corporation 2011
  • 37. A Guide To IBM System x Uninterruptible Power Supply (UPS) Run Time – IBM UPS5000 Number of EBM (P/N 39Y8857) Load (W) +0 * +1 * +2 * +3 * +4 * 50 409 1083 1892 2733 3596 100 290 771 1349 1950 2566 200 180 483 846 1223 1610 300 129 347 610 882 1162 400 99 270 474 686 904 500 80 219 366 559 737 600 67 184 324 470 620 700 57 158 279 405 534 800 50 138 244 355 468 900 44 122 217 315 416 1000 39 110 195 283 374 1200 32 90 161 235 311 1400 26 76 137 200 265 1600 22 66 119 174 230 1800 19 58 105 153 203 2000 17 52 93 137 181 2500 12 40 73 107 142 3000 9 32 60 88 117 3400 7 25 50 72 100 4000 6 23 43 60 85 4500 5 20 38 54 75 * Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. Note: Run times are in minutes EBM Connections – IBM UPS5000 P a g e | 37 © IBM Corporation 2011