3. Legend Power
Introduc0on
• Legend Power is Energy Conserva0on
Company
• Target Commercial & Light Industrial
• Completed R&D in January 2009
• Completed 20+ pilot project in BC, Ontario
and California
• Dr. William Dunford – CTO and inventor of the
AVR
• Mark Petersen – P.Eng, Lead Engineer
6. What is Voltage Op0miza0on
Conserva0on Voltage Regula0on
• All Electrical Equipment is design to operate
+/‐ 5% of rated value
• Voltage op0miza0on ensures equipment is opera0ng
near the lower limit
• Reduce Energy Consump0on by 6‐10%
• Real Power Reduc0on ‐ kW
• Reac0ve Power Reduc0on KVar
• Energy Consump0on Reduc0on kWh
• Increase the life of Electrical Equipment
• Science World doubled life expectancy of exterior bulbs
10. Effects on Resis0ve Loads
Ligh0ng Loads
• Responsive Ligh0ng Loads:
• Incandescent
• T8 and T12 Fluorescent
• Compact Fluorescent
• Metal Halide
• High Pressure Sodium
• Front End Regulated Ballast
• Electronically regulated loads do not respond to voltage
op0miza0on
11. Effects on Motor Loads
• Real power ‐ kW
• Mechanical output
• iron and copper losses
• Reac0ve power drawn to maintain the
magne0c flux ‐ kVar
• Power factor
• Harmonics
• Effects of voltage op0miza0on is complex
12. Effects on Motor Loads
• Nameplate condi0ons do not represent the
most efficient point for motor opera0on
• higher voltage results in:
• Increased reac0ve power demand
• Increased harmonic current flow.
• Increased losses in the iron core
• Overall motor efficiency and power factor are
usually increased by reducing the motor
voltage to its rated value or below
15. Measurement & Verifica0on
• Instantaneous effects of voltage change can easily be
measured
• Sooware installed in the AVR forces a tap change
• executed every 30 minutes for one week
• 48 samples per day for one week
• Measurements are taken before and aoer each tap change
• kWh for the week determined by summing the 30
minute samples which will yield the actual kWh used
and the kWh which would have been used without
the AVR
16. Case Study
Honda Canada
Facility Profile Results
• 45% Ligh0ng • Annual kWh Savings: 76,271
• Average kW Reduc0on: 8.73
• 40% Motor & HVAC
• Percent Savings: 5.98%
• 10% Office Equipment
• Annual Dollar Savings: $4,400 ($8,800 Ontario)
• 5% Bapery Chargers • Op0mized Voltage : 575 Volts
• Average Voltage : 610 Volts