SAUDI ARAMCO INDUSTRIAL LIGHTING
USING DIALUX 4.11
Indoor, Emergency, Outdoor & Security
Lighting Applications based on SA...
INTRODUCTION
Saudi Aramco, a fully integrated, global petroleum
and chemicals enterprise, is the state-owned oil
company o...
A. THEORETICAL
 Basic Lighting Terminologies
 Fundamental Formulas
 Manual Calculation & DIALux Verification
 Photomet...
1. To refresh participants with the design recommendations
according to SAES P-123, IESNA and NFPA 70
2. To apply the desi...
1. Adherence to Standards
~ NFPA
~ IESNA
~ OTHER SAUDI REGIONS
2. All Indoor Lighting will be calculated without effect of...
(BIDDING) – SLC Gives Technical Offer – {We start here}
(PRICING) – Requests to Verify Quantity - {Procurement}
(REVISION)...
LUMEN METHOD
F . n . N . MF . Uf
E = ------------------------------
A
SYMBOL NAME DEFINITION PROVIDED BY
E Ave Lux Illumin...
SAMPLE: How many recessed fixture 5712A/236BF.2 to
use in an Office with a Dimension of 4m x 5m x 3m?
Given:
5712A/236BF.2...
DIALUX LIGHT (BLUE ICON)
SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
DIALux Light Wizard h...
DEFINITIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
DEFINITIONS
SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
RECOMMENDED MOUNTING TYPES:
Ceilin...
LLF = LLD x LDD
SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
Luminaire Dirt Depreciation (L...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
1. RELEVANT STANDARDS
~ NFPA - National Fire P...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
4. MINIMUM HEIGHTS
~ GIS Hall: 7.0 meters
~ Ho...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
5. LAMPS TO BE USED
a. Indoor – Normal Operati...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
5. LAMPS TO BE USED
a. Indoor – DC Operation
i...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. FIXTURES TO BE USED PER ROOM
a. Indoor – AC...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. FIXTURES TO BE USED PER ROOM
a. Indoor – AC...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
a. (4.2.1) Exit ...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
b. (4.2.2) DC ci...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
c. (4.2.3) Twins...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
d. (4.2.4) Porta...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
e. OTHER OPTIONS...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
e. OTHER OPTIONS...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
e. OTHER OPTIONS...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
e. OTHER OPTIONS...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. EXIT & EMERGENCY SOLUTIONS
e. OTHER OPTIONS...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. MAINTENANCE FACTOR
- Also called Light Loss...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. MAINTENANCE FACTOR
- For this reason, we as...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. MOUNTING HEIGHTS
- According to 4.1.11
a. M...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. MOUNTING HEIGHTS
- According to 4.1.11
b. E...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
APPLICATION of SAES-P-123
6. MOUNTING HEIGHTS
- According to 4.1.11
b. D...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
SLC PART NUMBER ODERING
5712A /414BF.2.E3
5712 – Product Code
A – Mounti...
INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR
SLC PART NUMBER ODERING
5712A /414BF.2.E3
5712 – Product Code
A – Mounti...
Upcoming SlideShare
Loading in...5
×

SAUDI ARAMCO INDUSTRIAL LIGHTING USING DIALUX 4.11 - DAY ONE

2,202

Published on

Indoor, Emergency, Outdoor & Security Lighting Applications based on SAES-P-123

Published in: Design
1 Comment
7 Likes
Statistics
Notes
  • dear Mr. Michael,
    I've found that all of your presentations is very good about lighting (about 8 presentations to date). Could you please send all of the files to boosterhidrogen@gmail.com , because I want to use as a reference of my undergraduate thesis.
    thank you
       Reply 
    Are you sure you want to  Yes  No
    Your message goes here
No Downloads
Views
Total Views
2,202
On Slideshare
0
From Embeds
0
Number of Embeds
4
Actions
Shares
0
Downloads
0
Comments
1
Likes
7
Embeds 0
No embeds

No notes for slide

Transcript of "SAUDI ARAMCO INDUSTRIAL LIGHTING USING DIALUX 4.11 - DAY ONE"

  1. 1. SAUDI ARAMCO INDUSTRIAL LIGHTING USING DIALUX 4.11 Indoor, Emergency, Outdoor & Security Lighting Applications based on SAES-P-123 Engr. Michael T. Santiago | REE.AILP.MIES DIALux Accredited Trainer, ID 2013029 Supervisor, Lighting Applications Design Department Day One – Indoor & Emergency Lighting 3rd day of March, 2014 SNC Lavalin Fayez Engineering Office Auto Moto Complex, Al-Khobar, KSA
  2. 2. INTRODUCTION Saudi Aramco, a fully integrated, global petroleum and chemicals enterprise, is the state-owned oil company of the Kingdom of Saudi Arabia. Through our 80-year history we have become a world leader in hydrocarbons exploration, production, refining, distribution, shipping and marketing, and the world’s top exporter of crude oil and natural gas liquids (NGLs). COURSE DEFINITION: A two day seminar & hands-on training for engineering design employees of SNC-Lavalin Fayez Engineering for the application of SAES-P-123 (Saudi Aramco Engineering Standards) in indoor, emergency, outdoor & security lighting of Saudi Aramco Industrial Projects with the use of DIALux 4.11 as the lighting calculation software. SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications SOURCE: http://www.roadsaudi.com/Event.aspx?id=487844
  3. 3. A. THEORETICAL  Basic Lighting Terminologies  Fundamental Formulas  Manual Calculation & DIALux Verification  Photometric Data & Maintenance Factors  Room Applications & Considerations B. PRACTICAL  Indoor Lighting Calculation in DIALux  Emergency Lighting Calculation in DIALux  Print-output & CAD LAyouts WIFM – What’s in it for me? SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
  4. 4. 1. To refresh participants with the design recommendations according to SAES P-123, IESNA and NFPA 70 2. To apply the design recommendations using SLC Products in future Saudi ARAMCO Substation Projects 3. To build a strong foundation where participant can design, calculate and estimate lighting for any given task, room or area in a ARAMCO substation project. OBJECTIVES SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
  5. 5. 1. Adherence to Standards ~ NFPA ~ IESNA ~ OTHER SAUDI REGIONS 2. All Indoor Lighting will be calculated without effect of obstructions/objects but if future projects will provide a detailed furniture/equipment/cable tray/HVAC ducts layout, they should be included in the planning and calculation 3. DIALux, a leading lighting planning/calculation/rendering software from Germany will be used for evaluation and print output CONSIDERATIONS SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
  6. 6. (BIDDING) – SLC Gives Technical Offer – {We start here} (PRICING) – Requests to Verify Quantity - {Procurement} (REVISION) – Changes due to updated CAD layouts – {Design} {AS-BUILT} - Changes due to actual equipment, cable tray, HVAC ducting installations – {Site} {COMMISSIONING} – Possible issues arising after materials are supplied or lux levels are tested {Site} We would appreciate a request containing all relevant, detailed and updated information so we can minimize design rebounds. IMPORTANCE SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
  7. 7. LUMEN METHOD F . n . N . MF . Uf E = ------------------------------ A SYMBOL NAME DEFINITION PROVIDED BY E Ave Lux Illuminance Level Required CIE / IESNA Standards F Lamp Lumens Design Lumen Package per Lamp Lamp Manufacturer Datasheet n No. of Lamps Pieces or Combination of Lamps in a Luminaire Lighting Specification/Legend N No. of Luminaires To be calculated as the required no. of fittings that will meet required lux level. To be calculated MF Maintenance Factor a.k.a Light Loss Factor is factor used to calculate to maintain light level even after luminaire dirt accumulation & lamp depreciation Specified by SAES Uf Utilization Factor Factor that depends on the luminous flux distribution of the luminaire, the geometry of the room and the reflectance of room surfaces. Photometric Testing from Luminaire Manufacturer A Area Dimension of the room CAD Plan View & Section View Consultant Architectural Drawings MANUAL CALCULATION SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
  8. 8. SAMPLE: How many recessed fixture 5712A/236BF.2 to use in an Office with a Dimension of 4m x 5m x 3m? Given: 5712A/236BF.2, Office, 5x4x3 F = 3350 lumens n = 2 lamps MF = 0.8 E = 500 lux, target ave A = 5 x 4, Ch = Mh = 3m Reflectances CWF: 70-50-20 MANUAL CALCULATION SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications To get the Uf, find the Room Index L x W 4 x 5 RI = --------------- = ------------------- (L + W) Hw (4 + 5)(3.0-0.76) RI = 0.992 Replacing the Values: E x A (500) x (20) N = --------------------- = ----------------------------- F x n x MF x Uf 3350 x 2 x 0.8 x 0.4 N = 4.664 ≈ 5.0 fixtures To Verify this, we use Dialux Light software
  9. 9. DIALUX LIGHT (BLUE ICON) SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications DIALux Light Wizard has been available since DIALux version 3.1. With the help of this wizard it is possible to complete lighting designs quickly and simply. This means that infrequent users of DIALux can readily use the program without having to train themselves fully in using the software.
  10. 10. DEFINITIONS SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications
  11. 11. DEFINITIONS SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications RECOMMENDED MOUNTING TYPES: Ceiling Slabs – Surface Mounted Recessed with 60x60 grid Pendant Mounted with Rod Hibay Applications
  12. 12. LLF = LLD x LDD SAUDI ARAMCO INDUSTRIAL LIGHTING| Day One - Indoor & Emergency Applications Luminaire Dirt Depreciation (LDD) – is determined by estimating from the appropriate dirt condition curve and the proper elapsed time in years of the assumed cleaning cycle. GE LUCALOX Tubular HPS Lamp INITIAL LUMENS MEAN LUMENS LLD LU 70/90/MO/T/E27 1/25 6,473 6,000 92.69% LU100/100/MO/T/40 9,880 9,600 97.17% LU150/100/40 15,490 15,000 96.84% LU250/T/40 28,750 28,500 99.13% LU400/T/40 48,300 48,000 99.38% LU1000/110/T/40 4pk 133,340 130,000 97.50% Lamp Lumen Depreciation (LLD) – Information about the chosen lamp and its lumen depreciation and mortality are available from lamp manufacturers’ tables and graphs. ANSI/IESNA RP-8- 00 Annex A4 LAMP LUMEN DEPTRECIATION (LLD) LUMINAIRE DIRT DEPRECIATION (LDD) HPS 0.90 Outdoor Industrial 0.71 MH (above 400W) 0.83 Indoor Non-Industrial 0.86 MH (400W & Below) 0.77 Indoor Industrial 0.79 Fluorescent 0.86 Outdoor Residential 0.77 LED 0.70 SAES-P-123 Art. 5.8.1.
  13. 13. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 1. RELEVANT STANDARDS ~ NFPA - National Fire Protection Association ~ NEC – National Electrical Code ~ IESNA – Illumination Engineering Society of North America 2. VOLTAGE RATINGS: ~ Outdoor: 220 Vac ~ Indoor (Normal): 127Vac ~ Indoor (Emergency): 125 Vdc 3. As a Rule, all Saudi Lighting Photometric data used can be used interchangeably in any voltage rating. Part Numbers are critical only during ordering.
  14. 14. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 4. MINIMUM HEIGHTS ~ GIS Hall: 7.0 meters ~ Hook Height 5.0 meters (overhead crane) ~ Rooms with False Ceiling 3.5 meters (Control Room, Telecomm, Workshop, Office, etc.) ~ Rooms without False Ceiling 4.5 meters (Battery, Valve Rooms, Switchgears, Toilet, etc ) ~ Cable Cellars / Basement 2.5 meters (Mandatory for all GIS and Switchgear Halls)
  15. 15. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 5. LAMPS TO BE USED a. Indoor – Normal Operation i. MAX 40W, T5 fluorescent lamps, 220vac, electronic ~ 14w T5 (60cm) = 16w, 1200 lumens / lamp ~ 28w T5 (120 cm) = 30.5w, 2600 lumens / lamp ~ 35w T5 (150 cm) = 38.5w, 3300 lumens / lamp ii. HID LAMPS ~ If color is not an Issue, use HPS lamps because: - high luminous efficacy: up to 150 lm / w - long life, longer maintenance ~ for Mounting Heights higher > 6 meter - start using 250w (CWA) and up
  16. 16. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 5. LAMPS TO BE USED a. Indoor – DC Operation i. 60w incandescent lamp , 125 Vdc 6. FIXTURES TO BE USED PER ROOM a. Indoor – DC (Emergency) Operation i. If there is a false ceiling, use: ~ 5770/11-60 ii. If there are no false ceiling, use: ~ 8513S/11-60 (surface) ~ 8513W/11-60 (wall)
  17. 17. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. FIXTURES TO BE USED PER ROOM a. Indoor – AC (Normal) Operation i. ALL ROOMS with false ceiling, use: ~ 5712/414XF.2 ii. GIS Halls ~ 2 x 40 FL wall mounted (7295/228) ~ HPS Hi-bay (6323/5-250) iii. Switchgear Rooms ~ Max 40w CFL wall-mounted fixture (8513W/2CDE18) ~ 2 x 40 FL wall mounted (7295/228)
  18. 18. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. FIXTURES TO BE USED PER ROOM a. Indoor – AC (Normal) Operation iv. General Areas (Stairs, Corridors, Toilets, etc) ~ 2 x 40w wrap-around acrylic diffuser (7266/228XF.2) v. Basement (cable cellars, trenches) ~ IP54 2 x 40w FL fixture (7295/228XF) vi. Battery / Fuel Rooms ~ Explosion Protected (ellK92/228XF) vii. Other areas ~ IP54 2 x 40w FL fixture (7295/228XF)
  19. 19. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS a. (4.2.1) Exit Light ~ without presence of flammable materials: - 8w FL with electronic ballast, charged from 127Vac ~ with presence of flammable materials: battery & fuel - 8w FL with electronic ballast, charged from 127Vac - explosion protected fixture (SLC EE11PL/CSE11) Note: • Exit Signs to be installed above doors, intersections • Ideal Maximum Viewing Distance of 30 meters • Greater than 30 m, use 1x18, 2x08, 2x18 FL lamps
  20. 20. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS b. (4.2.2) DC circuit fed ~ Automatically turns on when AC circuit fails ~ Fed from 125 Vdc emergency lighting panel ~ 60w incandescent fixture for all rooms ~ Explosion-proof fixture, 60w inc lamp for Battery Room ~ TARGETS: - Average: 10 lux - Minimum: 1 lux any point within 1m of escape path
  21. 21. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS c. (4.2.3) Twinspot ~ 2 x 25w PAR36 (SLC VX-CTL/NM3 2x20.B) ~ Stairs, Corridors, Toilets, Control Rooms ~ TARGETS: - Minimum: 1 lux along center line of escape path ~ Typical Mounting:
  22. 22. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS d. (4.2.4) Portable Twinspot ~ 2 x 35w PAR36 ~ Control Rooms
  23. 23. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS e. OTHER OPTIONS i. SELF-CONTAINED - Emergency battery packs installed inside fixture that automatically will energize lamp/lamps when AC power fails - Types: a. Non-Maintained (EN) ~ Normal: Off, Emergency: On b. Maintained (E) ~ Normal: On, Emergency: On
  24. 24. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS e. OTHER OPTIONS i. SELF-CONTAINED - Duration: a. E or EN: 1.5 hours b. E3 or EN3: 3.0 hours - Configuration: a. 1-lamp connected (typical): E or E3, EN or EN3 b. 2-lamps connected: 2E or 2E3, 2EN or 2EN3 c. etc.
  25. 25. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS e. OTHER OPTIONS i. SELF-CONTAINED - BALLAST LUMEN FACTOR (BLF) ~ Normal 100% Lamp output WILL DECREASE to about 20% Light output during emergency mode Example: Normal: 36w T8 lamp: 3350 lumens output BLF according to Ventilux KPHFM-4-58: 0.09 Emergency: 36w T8 lamp: 301.5 lumens output
  26. 26. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS e. OTHER OPTIONS ii. AUXILLARY Incandescent Lamps - Particularly used on High bay applications a. using Remotely Installed Battery Pack ~ outside gear box or fixture housing ~ Maximum 2m cable ~ charged via AC and is Non-Maintained ~ Max 100w Quartz Lamp, 12Vdc b. DC fed ~ maximum 250W incandescent lamp ~ E27 lamp socket
  27. 27. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. EXIT & EMERGENCY SOLUTIONS e. OTHER OPTIONS iii. CENTRAL BATTERY SYSTEMS - can give off 100% Output - Addressable fixture, lamp, gears and circuit - Fluorescent Lamps need to use electronic ballast - Demand is according to Ampere-Hour (Ah) - For more information and training: Refer to Saudi Lighting Central Battery Systems CBS Department
  28. 28. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. MAINTENANCE FACTOR - Also called Light Loss Factor - Demand to meet target lux level after time and dirt has taken its toll on the fixture - Combination of Recoverable and Non-Recoverable Factors that will affect the light output of fixture in time: - Some of these factors can be computed and some are intelligently assumed values
  29. 29. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. MAINTENANCE FACTOR - For this reason, we assign practice-tested values to use when doing lighting design thus, we have come up with: a. Indoor ~ Clean (cleanroom application, laboratory, etc): 0.9 ~ Normal (office, library, living room, etc): 0.8 ~ Dirty (workshops, maintenance, etc): 0.7 ~ Wet or dusty (laundry, meatshops, saw mills) 0.5 c. Outdoor ~ All exterior areas 0.7 ~ Extremely Dusty or Wet 0.5 (marina areas, foggy or dusty sites)
  30. 30. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. MOUNTING HEIGHTS - According to 4.1.11 a. MH over battery workbenches: 2.44 Example: Ch: 3.5m Mh: 2.44m Wh = Ch - Mh = 3.5m - 2.44m = 1.06 m ≈ 1.0 m
  31. 31. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. MOUNTING HEIGHTS - According to 4.1.11 b. Elsewhere: 2.7 Example: Ch: 3.5m Mh: 2.7m Wh = Ch - Mh = 3.5m - 2.7m = 0.7m ≈ 0.76 m
  32. 32. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR APPLICATION of SAES-P-123 6. MOUNTING HEIGHTS - According to 4.1.11 b. During Emergency: on ground or 0.0 m
  33. 33. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR SLC PART NUMBER ODERING 5712A /414BF.2.E3 5712 – Product Code A – Mounting Type 4 – Number of Lamps 14 – Type of Lamps B – Voltage Rating F – Type of Ballast 2 – Type of Optical Controller E3 – Emergency Option
  34. 34. INDUSTRIAL LIGHTING USING DIALUX – DAY 1 - INDOOR SLC PART NUMBER ODERING 5712A /414BF.2.E3 5712 – Product Code A – Mounting Type 4 – Number of Lamps 14 – Type of Lamps B – Voltage Rating F – Type of Ballast 2 – Type of Optical Controller E3 – Emergency Option

×