Alarm System
Performance Metrics
FPID Symposium, Cork
March 2016
2
Presenter
Kim Van Camp is the Emerson Process
Management DeltaV Marketing Product
Manager for Alarm Management. He joined
Emerson in 1976 and has held senior
assignments in Manufacturing, Technology,
Field Service, Customer Service, Service
Marketing and Product Marketing. Kim is a
voting member of the ISA-18.2 committee
on Management of Alarm Systems for the
Process Industries and has published
multiple papers on alarm management. Kim
holds a BS degree in Electrical Engineering
from the University of Nebraska.
Presentation Abstract
This presentation centers on the primary metrics commonly
used to quantify alarm system performance; how they are
constructed, benchmark performance targets, and typical
causes for under-performance.
The foundation of the presentation is Technical Report ISA-
TR18.2.5-2012 Alarm System Monitoring, Assessment, and
Auditing, supplemented by speaker insights gained from
reviewing hundreds of performance reports received from
process plants worldwide in multiple industries.
3
Reference Material
TECHNICAL REPORT
ISA-TR18.2.5-2012
Alarm System Monitoring, Assessment, and Auditing
Approved 26 October 2012
4
Performance Metrics
Performance metrics are usually targeted toward operations
management. These metrics are broad indicators of alarm
system performance, which should be assessed by
comparison to performance goals stated in the alarm
philosophy. These metrics may not identify specific problems.
• Average alarm rate
• Percent of time the system is in a flood condition
• Quantity and listing of out-of-service-alarms
• Alarm priority or type distribution
5
Diagnostic Metrics
Diagnostic metrics are usually targeted toward the alarm
system owner and personnel responsible to take action.
These metrics identify specific problems with specific alarms.
• Listing and quantity of the most frequent alarms
• Listing and quantity of chattering alarms
• Listing of stale alarms
• Listing of shelved alarms with shelving duration
• Listing of out-of-service alarms with durations
• Listing of alarms shown by analysis to be potentially
redundant
6
Deployment Metrics
Deployment metrics are usually targeted toward alarm
system owners and responsible personnel to measure
progress on implementing alarm management practices.
• Percent of alarms rationalized
• Percent of alarms monitored
• Priority distribution of rationalized alarms.
7
Scaling Metrics
Scaling metrics are measurements used to determine other
metrics. This includes such items as:
• Number of configured alarms for a particular system
• Number of alarm occurrences for a particular system or
group of systems.
Scaling metrics are not directly used or reported, but are
used in reporting other metrics.
8
Audit Metrics
Audit metrics include the data on alarm systems that have
been audited. These metrics include:
• Number and nature of unauthorized alarm changes;
• Number and nature of unauthorized alarm suppression.
Audit metrics are usually targeted toward alarm system
owners and operations personnel. These metrics can be
used to measure execution of alarm management
procedures stated in the alarm philosophy, e.g.,
management of change.
9
ISA-18.2 Suggested Target Values
10
Metric Target
Annunciated Alarms Per Day Per Operating Position 150 – 300
Annunciated Alarm Per Hour Per Operating Position 6 – 12
Annunciated Alarms Per 10 Minutes Per Operator Position 1 – 2
Percent of 10 minute periods containing > 10 alarms < 1%
Maximum number of alarms in a 10 minute period <=10
Percent of time the system is in flood < 1%
Annunciated Priority Distribution (Low Priority) ~80%
Annunciated Priority Distribution (Med Priority) ~15%
Annunciated Priority Distribution (High Priority) ~5%
Percent contribution of top 10 most frequent alarms < 1% to ~5%
Quantity of Chattering and Fleeting Alarms 0
Stale Alarms (Active for more than >24 hours) < 5 on any day
Alarm performance based upon at least 30 days of data.
Sample Data Sets
• Performance and diagnostic
metrics from 236 systems
collected in in 2014-2015
• Most are starting-point
metrics, prior to nuisance
alarm elimination and
rationalization
• These were whole-system
reports, nominalized by
system IO count and number
of operator positions for this
presentation.
11
Average Alarm Rate
A useful initial measure of the overall performance of the
alarm system. The average alarm rate is the most common
alarm system performance metric. Periods of unusually
high alarm activity are easily identified in trend charts.
12
Average Alarm Rate
Per Hour Per Operator Workstation
• 29.0 alarms/hr.
for all industries
• 8.1 alarm/hr.
For Food &
Pharma
13
Alarm Rate Per 1 Hour
Acceptable ~ 6 Alarms
Manageable ~12 Alarms
Demanding ~ 30 Alarms
Unacceptable > Alarms
What can we learn from
average alarm rates?
• If very low. Then probably good.
• If very high. Need to know more.
14
Alarm Rate By System
Per Hour Per Operator Workstation
Per individual system it varied from near zero to 1063 alarms / hour!
15
Averages and Alarm Floods
• Averages can be misleading, providing no sense of peaks
in the alarm rate, making it difficult to distinguish “alarm
floods” vs. steady-state “normal” operation.
• An alarm flood can be defined as beginning when the
alarm rate exceeds 10 or more alarms occurring in 10
minutes, and ending when the rate drops below 5 alarms
in 10 minutes (a short-term manageable rate).
16
Percent of Time In Alarm Flood
• xx
17
Average Alarm Rates Per Operator
Position Excluding Alarm Floods
• 1.6 alarms/hr.
for all industries
• 0.8 alarm/hr.
For Food &
Pharma
18
Alarm Rate Per 1 Hour
Acceptable ~ 6 Alarms
Manageable ~12 Alarms
Demanding ~ 30 Alarms
Unacceptable > Alarms
Average Alarm Rates Per Operator
Position During Alarm Floods
• 73.8 alarms/hr.
for all industries
• 18.0 alarm/hr.
For Food &
Pharma
19
Alarm Rate Per 1 Hour
Acceptable ~ 6 Alarms
Manageable ~12 Alarms
Demanding ~ 30 Alarms
Unacceptable > Alarms
Typical Problems Associated
With A High Alarm Rate Excluding Floods
• Chattering alarms
• System and device
maintenance alarms
• Non-alarm notifications
– Messages
– Prompts
– Alerts
• Metric calculations?
20
Typical Problems Associated
With A High Alarm Rate During Floods
• Redundant Alarms
• Cascading Alarms
• Process state transitions
where the alarm system
is not designed to “follow
the process”
21
Alarm Flood Severity
• Flood severity based on the most alarms received in a
single ten minute period:
– 10 to 20 alarms — minor flood
– 20 to 30 alarms — moderate flood
– > 30 alarms — severe alarm flood
• In a severe flood, the alarm system can become a
hindrance or distraction, rather than acting as a useful
tool to assist the operator. During such periods, alarms
are likely to be missed.
22
Most extreme alarm floods,
Max. count of alarms in a 10 minute period
XX
23
Alarm Priority Distribution
Prioritization of alarms provides a mechanism for placing a
qualitative value on the importance of the alarm. The priority
of an alarm determines its significance and how quickly the
operator should respond to an alarm. Proper guidelines for a
recommended three-priority system distribution are widely
known and reflected in ISA-18.2, namely:
• ~80% Low Priority
• ~15% Medium Priority
• ~5% High Priority
24
“High Priority” alarm
percentages
Average “High Priority” Alarm Percent of Total Alarms:
25
Typical Problems Associated
With A High Percent of High Priority Alarms
• Alarms based on ultimate (unmitigated)
consequences rather than direct
(proximate) consequences
• Priority used to classify alarms for
reasons other than guiding operator on
order of actions
• Chattering high priority alarms, often
system and device alarms
• Priorities left at vendor default settings
26
Top 10 Source Contribution
To Total Alarm Count
Relatively few alarms often produce large percentages of the
total system alarm load. Substantial performance improvement
can be made by addressing the most frequent alarms.
27
Top 10 Alarm Source Contribution
By Industry and World Area
Average Top 10 Alarm Percentage Per System:
28
Typical Problems Associated
With A High Top 10 Percentage
• Nuisance alarms — alarms that
operators have come to expect,
and in most cases, ignore or
consider to be informational
• The alarm system is being
misused to (frequently) generate
operator prompts based on
routine changes in process
conditions or operating states
29
Stale Alarms
• Alarms which remain in the alarm state continuously for a
substantial time period. (24 hours is a recommended value
for analysis) They often last for days, weeks, or months.
• Following their initial appearance, such alarms provide
little valuable information to the operators. They clutter the
alarm displays and interfere with the operator’s ability to
detect and respond to new and meaningful alarms.
30
Stale Alarm Quantification
Snapshot Method: Number present at a certain time of day.
• Takes into account any local operator alarm filtering which can be difficult or
impossible to discern in the event history, providing the truest indication of
actual operator experience
• Allows Direct comparison to ISA benchmark.
Tally Method: A count of the number of alarms annunciations
that reached an old age (e.g. 24 hours) during a fixed time
period (typically a week or month)
• Can be applied uniformly to the ubiquitous OPC accessible event data
available from multiple process control, safety and other systems
• Can generate ordered lists of the longest standing alarms for continuous
improvement efforts
31
Stale Alarm Tallies By
Industry and World Area
Stale Alarm Tally Per 30 Days Per Operator Position:
32
Typical Problems Associated
With Stale Alarms
• Not following one of the basic principles of alarm
management, that alarms should be produced only upon
abnormal conditions. For example, standby or other
equipment that is intentionally shut down should not
produce alarms simply because they are off.
• Alarms that persist beyond the called-for operator action,
waiting for maintenance action.
• Alarms that are essentially latched due to excessive
application of hysteresis.
33
Key Ideas and Thoughts
• Identify and resolve nuisance alarms, to get a more realistic
picture when reviewing subsequent alarm rate metrics.
• A substantial reduction in configured alarms is the usual
result of alarm rationalization, along with a resulting alarm
priority distribution close to recommended values.
• Stale alarms are usually addressed by examination of the
cause and application of logic or state-based techniques.
• Alarm floods are more difficult to address, often involving a
dynamic alarm management solution.
• ISA-TR18.2.5-2012 is an excellent resource for interpreting
alarm metrics and common causes.
Discussion
35

More Related Content

Similar to Alarm System Performance Metrics

Alarms structured management systems
Alarms structured management systemsAlarms structured management systems
Alarms structured management systemsEnrico QUERCI
 
White paper - Actionable Alarming - Wonderware-Schneider Electric
White paper - Actionable Alarming - Wonderware-Schneider ElectricWhite paper - Actionable Alarming - Wonderware-Schneider Electric
White paper - Actionable Alarming - Wonderware-Schneider ElectricSuman Singh
 
Alarm Rationalization Workshop - Tips, Tricks and Traps
Alarm Rationalization Workshop - Tips, Tricks and Traps Alarm Rationalization Workshop - Tips, Tricks and Traps
Alarm Rationalization Workshop - Tips, Tricks and Traps Mary Claire Simoneaux
 
2-03.pdf
2-03.pdf2-03.pdf
2-03.pdfkhans21
 
A method to remove chattering alarms using median filters
A method to remove chattering alarms using median filtersA method to remove chattering alarms using median filters
A method to remove chattering alarms using median filtersISA Interchange
 
Management of control room alarms
Management of control room alarmsManagement of control room alarms
Management of control room alarmsAndy Brazier
 
20111117 WAM reporting for end customers
20111117 WAM reporting for end customers20111117 WAM reporting for end customers
20111117 WAM reporting for end customersUReasonChannel
 
Design of alarm using pir sensor for
Design of alarm using pir sensor forDesign of alarm using pir sensor for
Design of alarm using pir sensor forAkshay Dhole
 
20110204 alarm management seminar ureason v1 3
20110204 alarm management seminar ureason v1 320110204 alarm management seminar ureason v1 3
20110204 alarm management seminar ureason v1 3UReasonChannel
 
Threats to AI-Driven Industry 4.O From Neural Backdoors.pdf
Threats to AI-Driven Industry 4.O From Neural Backdoors.pdfThreats to AI-Driven Industry 4.O From Neural Backdoors.pdf
Threats to AI-Driven Industry 4.O From Neural Backdoors.pdfPentaTech
 
Practical Alarm Management for Engineers and Technicians
Practical Alarm Management for Engineers and TechniciansPractical Alarm Management for Engineers and Technicians
Practical Alarm Management for Engineers and TechniciansLiving Online
 
Importence of Vibration Transmitters.pptx
Importence of Vibration Transmitters.pptxImportence of Vibration Transmitters.pptx
Importence of Vibration Transmitters.pptxCentum Controls
 
3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...
3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...
3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...Sujith100785
 
Information Assurance Metrics: Practical Steps to Measurement
Information Assurance Metrics: Practical Steps to MeasurementInformation Assurance Metrics: Practical Steps to Measurement
Information Assurance Metrics: Practical Steps to MeasurementEnclaveSecurity
 
Software Reliability_CS-3059_VISHAL_PADME.pptx
Software Reliability_CS-3059_VISHAL_PADME.pptxSoftware Reliability_CS-3059_VISHAL_PADME.pptx
Software Reliability_CS-3059_VISHAL_PADME.pptxVishalPadme2
 
Intelligent instrumentation and power plant simulators
Intelligent instrumentation and power plant simulatorsIntelligent instrumentation and power plant simulators
Intelligent instrumentation and power plant simulatorsSelvam Sethurathinam
 
Problem management foundation - Lifecycle
Problem management foundation - Lifecycle Problem management foundation - Lifecycle
Problem management foundation - Lifecycle Ronald Bartels
 

Similar to Alarm System Performance Metrics (20)

Alarms structured management systems
Alarms structured management systemsAlarms structured management systems
Alarms structured management systems
 
Alarm process basics for dummies
Alarm process basics for dummiesAlarm process basics for dummies
Alarm process basics for dummies
 
Smart Alarming Management
Smart Alarming ManagementSmart Alarming Management
Smart Alarming Management
 
White paper - Actionable Alarming - Wonderware-Schneider Electric
White paper - Actionable Alarming - Wonderware-Schneider ElectricWhite paper - Actionable Alarming - Wonderware-Schneider Electric
White paper - Actionable Alarming - Wonderware-Schneider Electric
 
Alarm Rationalization Workshop - Tips, Tricks and Traps
Alarm Rationalization Workshop - Tips, Tricks and Traps Alarm Rationalization Workshop - Tips, Tricks and Traps
Alarm Rationalization Workshop - Tips, Tricks and Traps
 
2-03.pdf
2-03.pdf2-03.pdf
2-03.pdf
 
A method to remove chattering alarms using median filters
A method to remove chattering alarms using median filtersA method to remove chattering alarms using median filters
A method to remove chattering alarms using median filters
 
Management of control room alarms
Management of control room alarmsManagement of control room alarms
Management of control room alarms
 
20111117 WAM reporting for end customers
20111117 WAM reporting for end customers20111117 WAM reporting for end customers
20111117 WAM reporting for end customers
 
Design of alarm using pir sensor for
Design of alarm using pir sensor forDesign of alarm using pir sensor for
Design of alarm using pir sensor for
 
20110204 alarm management seminar ureason v1 3
20110204 alarm management seminar ureason v1 320110204 alarm management seminar ureason v1 3
20110204 alarm management seminar ureason v1 3
 
Threats to AI-Driven Industry 4.O From Neural Backdoors.pdf
Threats to AI-Driven Industry 4.O From Neural Backdoors.pdfThreats to AI-Driven Industry 4.O From Neural Backdoors.pdf
Threats to AI-Driven Industry 4.O From Neural Backdoors.pdf
 
Practical Alarm Management for Engineers and Technicians
Practical Alarm Management for Engineers and TechniciansPractical Alarm Management for Engineers and Technicians
Practical Alarm Management for Engineers and Technicians
 
Importence of Vibration Transmitters.pptx
Importence of Vibration Transmitters.pptxImportence of Vibration Transmitters.pptx
Importence of Vibration Transmitters.pptx
 
ETD featurespdf
ETD featurespdfETD featurespdf
ETD featurespdf
 
3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...
3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...
3-5927_Rezabek-3-5927 Rezabek - Stauffer N-Space Visualization Assists Alarm ...
 
Information Assurance Metrics: Practical Steps to Measurement
Information Assurance Metrics: Practical Steps to MeasurementInformation Assurance Metrics: Practical Steps to Measurement
Information Assurance Metrics: Practical Steps to Measurement
 
Software Reliability_CS-3059_VISHAL_PADME.pptx
Software Reliability_CS-3059_VISHAL_PADME.pptxSoftware Reliability_CS-3059_VISHAL_PADME.pptx
Software Reliability_CS-3059_VISHAL_PADME.pptx
 
Intelligent instrumentation and power plant simulators
Intelligent instrumentation and power plant simulatorsIntelligent instrumentation and power plant simulators
Intelligent instrumentation and power plant simulators
 
Problem management foundation - Lifecycle
Problem management foundation - Lifecycle Problem management foundation - Lifecycle
Problem management foundation - Lifecycle
 

Recently uploaded

Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 

Recently uploaded (20)

Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 

Alarm System Performance Metrics

  • 1. Standards Certification Education & Training Publishing Conferences & Exhibits Alarm System Performance Metrics FPID Symposium, Cork March 2016
  • 2. 2 Presenter Kim Van Camp is the Emerson Process Management DeltaV Marketing Product Manager for Alarm Management. He joined Emerson in 1976 and has held senior assignments in Manufacturing, Technology, Field Service, Customer Service, Service Marketing and Product Marketing. Kim is a voting member of the ISA-18.2 committee on Management of Alarm Systems for the Process Industries and has published multiple papers on alarm management. Kim holds a BS degree in Electrical Engineering from the University of Nebraska.
  • 3. Presentation Abstract This presentation centers on the primary metrics commonly used to quantify alarm system performance; how they are constructed, benchmark performance targets, and typical causes for under-performance. The foundation of the presentation is Technical Report ISA- TR18.2.5-2012 Alarm System Monitoring, Assessment, and Auditing, supplemented by speaker insights gained from reviewing hundreds of performance reports received from process plants worldwide in multiple industries. 3
  • 4. Reference Material TECHNICAL REPORT ISA-TR18.2.5-2012 Alarm System Monitoring, Assessment, and Auditing Approved 26 October 2012 4
  • 5. Performance Metrics Performance metrics are usually targeted toward operations management. These metrics are broad indicators of alarm system performance, which should be assessed by comparison to performance goals stated in the alarm philosophy. These metrics may not identify specific problems. • Average alarm rate • Percent of time the system is in a flood condition • Quantity and listing of out-of-service-alarms • Alarm priority or type distribution 5
  • 6. Diagnostic Metrics Diagnostic metrics are usually targeted toward the alarm system owner and personnel responsible to take action. These metrics identify specific problems with specific alarms. • Listing and quantity of the most frequent alarms • Listing and quantity of chattering alarms • Listing of stale alarms • Listing of shelved alarms with shelving duration • Listing of out-of-service alarms with durations • Listing of alarms shown by analysis to be potentially redundant 6
  • 7. Deployment Metrics Deployment metrics are usually targeted toward alarm system owners and responsible personnel to measure progress on implementing alarm management practices. • Percent of alarms rationalized • Percent of alarms monitored • Priority distribution of rationalized alarms. 7
  • 8. Scaling Metrics Scaling metrics are measurements used to determine other metrics. This includes such items as: • Number of configured alarms for a particular system • Number of alarm occurrences for a particular system or group of systems. Scaling metrics are not directly used or reported, but are used in reporting other metrics. 8
  • 9. Audit Metrics Audit metrics include the data on alarm systems that have been audited. These metrics include: • Number and nature of unauthorized alarm changes; • Number and nature of unauthorized alarm suppression. Audit metrics are usually targeted toward alarm system owners and operations personnel. These metrics can be used to measure execution of alarm management procedures stated in the alarm philosophy, e.g., management of change. 9
  • 10. ISA-18.2 Suggested Target Values 10 Metric Target Annunciated Alarms Per Day Per Operating Position 150 – 300 Annunciated Alarm Per Hour Per Operating Position 6 – 12 Annunciated Alarms Per 10 Minutes Per Operator Position 1 – 2 Percent of 10 minute periods containing > 10 alarms < 1% Maximum number of alarms in a 10 minute period <=10 Percent of time the system is in flood < 1% Annunciated Priority Distribution (Low Priority) ~80% Annunciated Priority Distribution (Med Priority) ~15% Annunciated Priority Distribution (High Priority) ~5% Percent contribution of top 10 most frequent alarms < 1% to ~5% Quantity of Chattering and Fleeting Alarms 0 Stale Alarms (Active for more than >24 hours) < 5 on any day Alarm performance based upon at least 30 days of data.
  • 11. Sample Data Sets • Performance and diagnostic metrics from 236 systems collected in in 2014-2015 • Most are starting-point metrics, prior to nuisance alarm elimination and rationalization • These were whole-system reports, nominalized by system IO count and number of operator positions for this presentation. 11
  • 12. Average Alarm Rate A useful initial measure of the overall performance of the alarm system. The average alarm rate is the most common alarm system performance metric. Periods of unusually high alarm activity are easily identified in trend charts. 12
  • 13. Average Alarm Rate Per Hour Per Operator Workstation • 29.0 alarms/hr. for all industries • 8.1 alarm/hr. For Food & Pharma 13 Alarm Rate Per 1 Hour Acceptable ~ 6 Alarms Manageable ~12 Alarms Demanding ~ 30 Alarms Unacceptable > Alarms
  • 14. What can we learn from average alarm rates? • If very low. Then probably good. • If very high. Need to know more. 14
  • 15. Alarm Rate By System Per Hour Per Operator Workstation Per individual system it varied from near zero to 1063 alarms / hour! 15
  • 16. Averages and Alarm Floods • Averages can be misleading, providing no sense of peaks in the alarm rate, making it difficult to distinguish “alarm floods” vs. steady-state “normal” operation. • An alarm flood can be defined as beginning when the alarm rate exceeds 10 or more alarms occurring in 10 minutes, and ending when the rate drops below 5 alarms in 10 minutes (a short-term manageable rate). 16
  • 17. Percent of Time In Alarm Flood • xx 17
  • 18. Average Alarm Rates Per Operator Position Excluding Alarm Floods • 1.6 alarms/hr. for all industries • 0.8 alarm/hr. For Food & Pharma 18 Alarm Rate Per 1 Hour Acceptable ~ 6 Alarms Manageable ~12 Alarms Demanding ~ 30 Alarms Unacceptable > Alarms
  • 19. Average Alarm Rates Per Operator Position During Alarm Floods • 73.8 alarms/hr. for all industries • 18.0 alarm/hr. For Food & Pharma 19 Alarm Rate Per 1 Hour Acceptable ~ 6 Alarms Manageable ~12 Alarms Demanding ~ 30 Alarms Unacceptable > Alarms
  • 20. Typical Problems Associated With A High Alarm Rate Excluding Floods • Chattering alarms • System and device maintenance alarms • Non-alarm notifications – Messages – Prompts – Alerts • Metric calculations? 20
  • 21. Typical Problems Associated With A High Alarm Rate During Floods • Redundant Alarms • Cascading Alarms • Process state transitions where the alarm system is not designed to “follow the process” 21
  • 22. Alarm Flood Severity • Flood severity based on the most alarms received in a single ten minute period: – 10 to 20 alarms — minor flood – 20 to 30 alarms — moderate flood – > 30 alarms — severe alarm flood • In a severe flood, the alarm system can become a hindrance or distraction, rather than acting as a useful tool to assist the operator. During such periods, alarms are likely to be missed. 22
  • 23. Most extreme alarm floods, Max. count of alarms in a 10 minute period XX 23
  • 24. Alarm Priority Distribution Prioritization of alarms provides a mechanism for placing a qualitative value on the importance of the alarm. The priority of an alarm determines its significance and how quickly the operator should respond to an alarm. Proper guidelines for a recommended three-priority system distribution are widely known and reflected in ISA-18.2, namely: • ~80% Low Priority • ~15% Medium Priority • ~5% High Priority 24
  • 25. “High Priority” alarm percentages Average “High Priority” Alarm Percent of Total Alarms: 25
  • 26. Typical Problems Associated With A High Percent of High Priority Alarms • Alarms based on ultimate (unmitigated) consequences rather than direct (proximate) consequences • Priority used to classify alarms for reasons other than guiding operator on order of actions • Chattering high priority alarms, often system and device alarms • Priorities left at vendor default settings 26
  • 27. Top 10 Source Contribution To Total Alarm Count Relatively few alarms often produce large percentages of the total system alarm load. Substantial performance improvement can be made by addressing the most frequent alarms. 27
  • 28. Top 10 Alarm Source Contribution By Industry and World Area Average Top 10 Alarm Percentage Per System: 28
  • 29. Typical Problems Associated With A High Top 10 Percentage • Nuisance alarms — alarms that operators have come to expect, and in most cases, ignore or consider to be informational • The alarm system is being misused to (frequently) generate operator prompts based on routine changes in process conditions or operating states 29
  • 30. Stale Alarms • Alarms which remain in the alarm state continuously for a substantial time period. (24 hours is a recommended value for analysis) They often last for days, weeks, or months. • Following their initial appearance, such alarms provide little valuable information to the operators. They clutter the alarm displays and interfere with the operator’s ability to detect and respond to new and meaningful alarms. 30
  • 31. Stale Alarm Quantification Snapshot Method: Number present at a certain time of day. • Takes into account any local operator alarm filtering which can be difficult or impossible to discern in the event history, providing the truest indication of actual operator experience • Allows Direct comparison to ISA benchmark. Tally Method: A count of the number of alarms annunciations that reached an old age (e.g. 24 hours) during a fixed time period (typically a week or month) • Can be applied uniformly to the ubiquitous OPC accessible event data available from multiple process control, safety and other systems • Can generate ordered lists of the longest standing alarms for continuous improvement efforts 31
  • 32. Stale Alarm Tallies By Industry and World Area Stale Alarm Tally Per 30 Days Per Operator Position: 32
  • 33. Typical Problems Associated With Stale Alarms • Not following one of the basic principles of alarm management, that alarms should be produced only upon abnormal conditions. For example, standby or other equipment that is intentionally shut down should not produce alarms simply because they are off. • Alarms that persist beyond the called-for operator action, waiting for maintenance action. • Alarms that are essentially latched due to excessive application of hysteresis. 33
  • 34. Key Ideas and Thoughts • Identify and resolve nuisance alarms, to get a more realistic picture when reviewing subsequent alarm rate metrics. • A substantial reduction in configured alarms is the usual result of alarm rationalization, along with a resulting alarm priority distribution close to recommended values. • Stale alarms are usually addressed by examination of the cause and application of logic or state-based techniques. • Alarm floods are more difficult to address, often involving a dynamic alarm management solution. • ISA-TR18.2.5-2012 is an excellent resource for interpreting alarm metrics and common causes.