Installation instructions for slip-on indoor termination
1. This product should be installed only by competent personnel trained in good safety practices involving high voltage
electrical equipment. These instructions are not intended as a substitute for adequate training or experience in such
safety practices. These instructions do not attempt to provide for every possible contingency.
Failure to follow these instructions could result in damage to the product and serious or fatal injury.
IMPORTANT : Cable and associated apparatus must be de-energised, locked out, and tagged prior to product
installation.
a Nexans company
Optionally supplied :
CAUTION: Read instructions thoroughly and completely prior to beginning installation.
Installation instructions for slip-on indoor termination
AIN 30U max. 36 kV
Contents :
Installation
instructions
3 x Stress control
mastic strips, type
MFC (Hi-K)
Glove
Roll adhesive
tape Emery cloth
WiperSilicone grease
3 x Tinned
copper wire
3 x Earth braid
3 x Semi-
conductive tape
3 x Conductor
cable lug
or
3 x Termination
housing
Table 1
Termination
size
1 50 - 70
95 - 240
240 - 400
23,5
27,0
32,0
29,0
38,0
43,0
2
3
Conductor
cross section
(mm²)
[for information only]
Cable core
insulation
diameter
(mm)
min. max.
For copper tape screened cable with:
- extruded easy strip semi-conductive screen
- bonded extruded semi-conductive screen
Page 1 of 6
IS94018-ENG - AIN 30-26
18 September 2013 - Revision 5 - Supersedes edition of 18 March 2013IS94018-ENG-AIN30-26-Revision5
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
2. B
A
1 Temporarily install the cable lug on to the equipment and hold the
cable next to it.
2 Mark the bottom of the cable lug on the cable (reference point A).
3 Measure the depth of the cable lug bore (length L) and mark this
distance above the reference point A on the cable
(reference point B).
4 Cut the cable at the reference point B.
EQUIPMENT
L
cable
temporarily
fixed cable lug
IS94018-ENG-AIN30-26-Revision5
Page 2 of 6
3. extruded semi-
conductive
screen
outer
sheath
core
insulation
20
CABLE PREPARATION
1 Remove the outer cable sheath for a distance X + L + 30 mm.
L = depth of the cable lug bore
X = see table 2
2 Remove the copper tape screen to a point 20 mm above the cut
edge of the outer sheath.
3 Remove the semi-conductive screen up to 45 - 50 mm above
the cut edge of the outer sheath.
Check if the cable insulation diameter is in accordance with the
termination range. See table 2.
4 Bare the conductor for a distance L + 30 mm.
IMPORTANT : To ensure the termination slips on easily, the
edge of the core insulation should be rounded and
slightly roughened using the supplied emery cloth.
L
!
!
Table 2
L + 30
X+L+30
copper tape
screen
45 - 50
conductor
bevelled
and
rounded
!
remove
all sharp
edges
1
23,5 - 26
26 - 29
27 - 30,6
30,6 - 34,1
34,1 - 38
32 - 38
38 - 43
255
250
250
245
240
255
245
2
3
Termination
size
Cable core
insulation
diameter
(mm)
X
(mm)
Page 3 of 6
IS94018-ENG-AIN30-26-Revision5
4. 5 Using a tinned copper wire, cleat the earth braid onto the copper tape screen.
6 Using adhesive tape, secure the earth braid approx. 60 mm below the edge of the outer sheath.
7 Completely overtape the cleating with semi-conductive tape. All sharp edges must be covered. Make a step at
20 mm from the edge of the outer sheath.
8 For cables with extruded easy strip semi-conductive screen (see detail)
- Apply one layer of field control mastic, type MFC (Hi-K) on the core insulation, flush with the extruded semi-
conductive screen.
- Squeeze it tightly in place using the coated side of the paper.
!
extruded semi-
conductive screen
extruded semi-
conductive screen
cleating
adhesive
tape
!
60
semi-conductive
tape
cleating
!
20
20
field control mastic,
type MFC (Hi-K)
semi-conductive
tape
DETAIL
For cables with extruded easy strip
semi-conductive screen
earth braid
earth braid
earth braid
IS94018-ENG-AIN30-26-Revision5
Page 4 of 6
5. !
1 Remove burrs from the conductor and as a protection, wrap a few turns of adhesive tape around
the conductor end.
2 Remove any traces of conductive residue from the core insulation.
3 Lubricate core insulation and the inner surface of the termination (use only the silicone lubricant
supplied).
4 Push the termination on the cable, until the internal step in the bottom part of the termination butts against the
step made by the cleating and taping. Remove protective tape from the conductor.
5 - Crimp contacts : crimp according specification.
- Bolted contacts : tighten the screws, refer to the installation instruction included with the contact.
6 Remove any burrs after crimping/tightening and wipe off excess inhibitor.
!
!
INSTALLATION OF THE TERMINATION HOUSING AND CABLE LUG
Hexagonal
cable lug
deep indent
cable lug
bolted
cable lug
protective
adhesive
tape
termination
housing
internal
step
Page 5 of 6
IS94018-ENG-AIN30-26-Revision5
6. a Nexans company
Nexans Network Solutions NV - div. EUROMOLD
Zuid III - Industrielaan 12
B-9320 EREMBODEGEM-AALST – BELGIUM
Tel: +32 (0)53/85 02 11 – Telefax: +32 (0)53/83 10 13
sales.euromold@nexans.com
1 Connect earth braid to the system earth.
2 Clamp the cable as close as possible to the termination.
CABLE SCREEN EARTHING
to the
system
earth
cable lug
cable
clamp
IS94018-ENG-AIN30-26-Revision5
Page 6 of 6