LSV:
Vibrating Fork Level
Limit Switch for Solids
Instruction Manual
39 Mangal Nagar, Behind Sai Ram Plaza, Near Rajiv Gandhi
Circle, AB Road, Indore, MP 452 001, India
Phone: +91-731-497 2065
Trumen Technologies Pvt. Ltd. Customer Support
Phone: +91-731-656 2425
email: sales@trumen.in
email: support@trumen.in
web:www.trumen.in
®
sensing matters
List of content
Introduction - LSV-UD-D1/D2/D3 (Order code EIUD / ERUD)....................................
controls & indicators, connection terminals, configuration switches.........................
Electrical Connections - LSV-UD-D1/D2/D3 (EIUD / ERUD)........................................
Operating Principle.....................................................................................................................
Technical Specification................................................................................................................
Do's and Don'ts............................................................................................................................
Troubleshooting...........................................................................................................................
Maintenance & Spares...............................................................................................
Operation Matrix - LSV-UD-D1/D2/D3 (EIUD / ERUD)................................................
1
Page1
2
3
4
4
Page
Annexure-1
Page1
Page2
Page3
Introduction - LSV-DP-D1/D2/D3 (Order code EIDP / ERDP)......................................
controls & indicators, connection terminals, configuration switches.........................
Electrical Connections - LSV-DP-D1/D2/D3 (EIDP / ERDP).........................................
Operation Matrix - LSV-DP-D1/D2/D3 (EIDP / ERDP).................................................
Page1
Annexure-2
Page1
Page2
Page3
Introduction - LSV-U(S+P)-D1/D2/D3 (Order code EIUSP / ERUSP)..........................
controls & indicators, connection terminals, configuration switches.........................
Electrical Connections - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP)..............................
Operation Matrix - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP)......................................
Page1
Annexure-3
Page1
Page2
Page3
Introduction - LSV-AR-D1/D2/D3 (Order code EIAR)..................................................
controls & indicators, connection terminals, configuration switches.........................
Electrical Connections - LSV-AR-D1/D2/D3 (EIAR)......................................................
Operation Matrix - LSV-AR-D1/D2/D3 (EIAR)..............................................................
Page1
Annexure-4
Page1
Page2
Page3
Introduction - LSV-DL-D1/D2/D3 (Order code EIDL)...................................................
controls & indicators, connection terminals, configuration switches.........................
Electrical Connections - LSV-DL-D1/D2/D3 (EIDL).......................................................
Operation Matrix - LSV-DL-D1/D2/D3 (EIDL)..............................................................
Page1
Annexure-5
Page1
Page2
Page3
®
sensing matters
Operating Principle
Electronics of LSV excites the piezo-electric-crystals inside the tuning fork, which makes the fork
tines vibrate at their natural resonance frequency in free air.
When material touches the fork tines, vibration stops as the resonance gets disturbed.
Amplitudes of vibration are above threshold when the tines are free to vibrate.
Amplitudes of vibration, as sensed by electronics falls below the threshold strength and material
presence is thus detected.
www.trumen.in
lsv-manual-page01 1
Technical Specification
Features Specifications
Applications
Specifications are subject to change without prior notice
1. Free flowing powders and granules (size max. 10mm)
2. Suitable for side as well as top mounting
3. Minimum and maximum failsafe field selectable
4. Process temperature max 250°C
5. Process pressure max. 15 bar
Typical Mountings
1. Fast Switching Response 2 sec
(0.8 sec and 1.5 sec available on demand)
2. 1" screw mountings available
3. High pressure 15 bar forks
4. High Tempreture up-to 250°C available
5. Calibration-less operation
6. Remote electronics with std 10 meters cable length
7. Tropicalized & potted electronics module
8. Threaded & Flanged Mountings
9. Electronic Inserts support all requirements
10. Ingress protection : IP 68/66 (as per IS-13947)
11. Ex-proof (Ex d T6 IP-66 IIC )
- Flameproof as per IS/IEC 60079-1:2007
- Weatherproof (IP-66) as per IS/IEC 60529:2001
- Suitable for Gas Group : IIC
- Suitable for Zone 1 & 2 atmospheres
12. Compact size
13. Low power consumption (0.5 to 0.7VA)
Integral / Remote Electronics
Universal Power Supply, DPDT Relay Output
15 to 80 VDC and 15 to 260 VAC 50/60Hz
Potential Free DPDT Relay Output
5 A each @ 24VDC or 220VAC
Integral / Remote Electronics for PNP Output
12 to 60 VDC, PNP
250mA max. Short Circuit Safe
Integral / Remote Electronics SPDT + PNP Output
Universal Supply for SPDT Output
15 to 80 VDC
15 to 260 VAC 50/60Hz
DC Supply for PNP Output
15 to 60 VDC
Potential Free DPDT Relay Output
5 A each @ 24VDC or 220VAC
250mA max. Short Circuit Safe
Integral Electronics AC series relay
Two Wire 18 to 260 VAC, Series Relay
not less than 4mA to release external relay
maximum 150mA to magnetize relay
Use relays/contactors will more than
4mA holding current
Integral Electronics 4-20mA Loop Powered
Two Wire DC 8 / 16 mA
12 to 60 VDC
8mA (±1mA max) / 16mA (±1mA max)
Remote electronics require special cable from fork to
controller.
10 meter standard length
more available on demand
15 gram/litre for D1 (Fork length 150mm)
75 gram/litre for D2 (Fork length 125mm)
500 gram/litre for D3 (Fork length 100mm)
-20°C ... 70°C (-4°F ... 158 °F)
-20°C ... 80°C (-4°F ... 176 °F)
-30°C ... 200°C (-22°F ... 392 °F)
{250°C available on request}
(extensions & heat sinks required)
absolute / max. 15 bar
SS 316 or SS 316L
NPT / BSP 1", 1¼", 1½", 2" etc
Flanged : ANSI/JIS/DIN/ASA/custom
SS 304, SS 316, SS 316L
125mm to 3,000mm
EIUD / ERUD
Supply & Output
Relay Type and Rating
EIDP / ERDP
Supply & Output
Output Limit
EIUSP / ERUSP
Supply & Output
Relay Type and Rating
PNP Output
EIAR
Supply & Output
Output Limit
EIDL
Supply & Output
Output Limit
Sensor Cable
Min. Density
Ambient Temp.
Process Temp.
Extended Process
Temperature
Process Pressure
Wetted Parts
Mountings
Extensions Tube
Material & Length
lsv-manual-page02 www.trumen.in 2
wall/pipe
mounting
remote
electronics
special
interconnection
cable
Do's and Don'ts
Features
Installation Precaution
1. Always connect the "Earth" to the external "Earthing" screw
2. Tighten the cable entries & glands properly
3. Secure the top aluminium cover at its place properly once the
electrical connections and other settings are completed
4. Always tighten the process connection using proper wrench
never try to tight by rotating the aluminium housing
5. Make sure process connection is same as that in hopper/tank
6. Vibrating fork tines:-
6.1 Should never be bent closer
6.2 Should never be bent apart
6.3 Should never be cut or machined in any way
6.4 Should never be extended by welding or machining
7. Cable entries must face downwards only
8. Nozzles should never be longer than the fork extension
9. If mounted directly under the material entry, always install
a cannopy of suitable strength at proper height from the fork
10. Never climb either by gripping or stepping over either the
fork tines or its aluminium housing
11. Obeserve other safety precautions as required at the place
of application
3
2
4
5
1
6
lsv-manual-page03 www.trumen.in 3
Troubleshooting
Maintenance and Spares
Top Cover
Electronic Insert
connection terminals
electronic insert fixing screw
4-way male connector for sensor (fork)
4-way female connector from sensor (fork)
Cable glands
Thermal spacer (where needed)
Process connection
Fork extension (longer for low level)
Fork tines
Device enclosure
Shown on the left are various parts of LSV level switch.
Separatable parts are
1. Electronic insert in short called 'electronics'
2. Fork + Enclosure + Cover + Glands collectively called 'mechanical'
For maintenance issues involving replacement of 'electronics', just a
single fixing screw is needed to be released.
Lift the electronics slowly by holding electronics with one hand and
mechanical with other, as wires are connected using rigid 4-way
connectors to it.
Disconnect 4-way connector by holding electronics with one hand and
female of connector by other hand, while the rest of the device is at rest.
Connect the new replaced sensor. 4-way connector is unidirectional
and only connects in proper direction.
Set the electronics properly to its position.
Match the mounting screw hole of electronics with that of enclosure
and fix the screw.
For mechanical issues please send the entire device back to Trumen.
Applications
Indication Probable cause Work-around Solution
No switching output or
sensor is permanently in alarm
Proper voltage is available but 'power'
LED is still OFF
Power is not available
Power section of sensor electronic
insert is failed
See if 'power' LED is ON
If power LED is OFF check voltage on
terminal 1 and 2
Sensor electronic insert is needed to be replaced.
Abrupt switching Material is agitated Set time delay to 5 second in both dry and
wet condition (turn switch 2, 3 ON)
Time delay solves switching issues in agitated
materials.
Make necessary arrangements to filter the
noise in power-line before being fed to the
device
Provide an exclusive earthing to terminal#
3, fork enclosure earthing screw and
fork process connection (device mounting
screw or flange)
Device contains sufficient filtering of power supply
noise inside, but sometimes external earth is
needed to make filters sink the extra power supply
noise back to earth.
Device worked for few months / years
but now fails to switch with respect to
material while power conditions are
all same
Device senses fork frequency and
amplitude to ascertain presence/absense
of material. Possible reasons are
1. Fork frequency shift due to fork wear/
errosion by service material
2. Material deposition on fork leads
3. Over temperature of service material
causing fork drive damage
Select proper fork surface while ordering
as per service material to mitigate fork
errosion as well as deposition
Order device of proper thermal grade for
proper service life of device
Clean up deposited materials on fork tines
as a part of maintenance schedule
Care is needed to be taken while ordering.
Scheduled cleaning of fork tines in sticky material
application is recommended.
In case of fork tine wear or temperature stress, fork
sensor is needed to be replaced.
Fork is not vibrating when fork tines
are touched by hand
Sensor electronic insert fork oscillator
failed
Fork settings are all OK but fork fails
to switch to 'no material' at random
times
Power supply carrying extra noise and
fork amplifier picking the noise
Device shows no material after some
time even when fork is inside the
material
Material fluffy or fork rate-holes the
material due to its own vibrations
Set device in sensitive mode (turn switch
1 ON)
Sensitive setting reduces vibrational strength and
makes switching point at lower amplitude.
Fork is vibrating but no switching
output when fork tines are touched
by hand
Sensor electronic insert evaluation
section failure
lsv-manual-page04 www.trumen.in 4
1 sensitivity control
sensitive setting for low density materials
(turn-on for fluffy/low density powders etc)
(keep turned-off for normal density materials)
2 “dry” (or uncovered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork out of material confirmation)
3 “wet” (or covered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork dipped in the material confirmation)
4 minimum failsafe select
Failsafe means alarm is same as power failure.
Turn on for underflow detection (min. failsafe)
Keep turned off for overflow detection
(max. failsafe)
configuration switches
Example of Switch in On and Off Positions
OFF Position ON Position
1 + of DC or Live of AC Supply input
2 - of DC or Neutral of AC Supply input
Supply:
15 to 80VDC or 15 to 260VAC 50/60Hz
3 Earth terminal for safety
4 Normally connected terminal of contact 1
5 Common terminal of contact 1
6 Normally open terminal of contact 1
7 Normally connected terminal of contact 2
8 Common terminal of contact 2
9 Normally open terminal of contact 2
A Alarm Indicating LED
B Configuration Switches
C Power ON LED Indicator
D Connecting Terminals
E External Earthing Terminal
controls & indicators
connection terminals
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-UD-D1/D2/D3
5 sec
ON Position
OFF Position
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-UD
5 sec status
power
L1 N
U 15... 80 VDC
15... 260 VAC
1 2 3 4 5 6 7 8 9
D
B
C
A
ON
E
lsv-manual-annexure-1 www.trumen.in
Annexure-1
Introduction - LSV-UD-D1/D2/D3 (EIUD / ERUD)
Page 1
LSV-UD-D1
LSV-UD-D2
LSV-UD-D3
Failsafe defines that the alarm and power failure / device failure conditions are same to
the external system. Failsafe operation is best understood with the type of installation
and following matrix.
lsv-manual-annexure-1 www.trumen.in
Off
Off
On
On
Failsafe
Setting
Material &
Installation
Status
LED Power ON
1 2 3 4
ON
min failsafe
1 2 3 4
ON
min failsafe
4 5 6 7 8 9
Material
Status
No material
at high level.
DPDT Relay Contacts
Power OFF
Switch no. 4
is off, failsafe
high/maximum
Indicating
normal or
healthy
status.
4 5 6 7 8 9
Relay ON
normal or healthy
contacts.
Relay OFF
alarm contacts.
(due to power
failure)
No material
at low level.
Indicating
alarm
status.
4 5 6 7 8 9
Relay OFF
alarm contacts.
4 5 6 7 8 9
1 2 3 4
ON
min failsafe Indicating
alarm
status.
4 5 6 7 8 9
Relay OFF
alarm contacts.
4 5 6 7 8 9
Relay OFF
alarm contacts.
(as it is)
Material is
above the low
level or fork
is covered
with material.
1 2 3 4
ON
min failsafe
4 5 6 7 8 9 4 5 6 7 8 9
Material is
above the high
level or fork
is covered
with material.
Indicating
normal or
healthy
status.
Relay ON
normal or healthy
contacts.
High
level
/
overflow
detection
Low
level
/
underflow
detection Annexure-1
Operation Matrix - LSV-UD-D1/D2/D3 (EIUD / ERUD)
Switch no. 4
is off, failsafe
high/maximum
Switch no. 4
is on, failsafe
low/minimum
Switch no. 4
is on, failsafe
low/minimum
Relay OFF
alarm contacts.
(due to power
failure)
Page 2
Relay OFF
alarm contacts.
(as it is)
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
electrical connections (AC)
lsv-manual-annexure-1 www.trumen.in
electrical connections (DC)
DC
15 to 80 VDC
output
contact 1
output
contact 2
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-UD
status
power
L1 N
U 15... 80V DC
15... 260V AC
1 2 3 4 5 6 7 8 9
ON
output
contact 1
output
contact 2
Live
Neutral
15 to 260 VAC
50/60 Hz
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-UD
status
power
L1 N
U 15... 80V DC
15... 260V AC
1 2 3 4 5 6 7 8 9
ON
Electrical Connections - LSV-UD-D1/D2/D3 (EIUD / ERUD)
Annexure-1
Page 3
Remote probe connections for
LSV-UD-D3 (ERUD)
LSV-UD-D1/D2 (ERUD)
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-UD
5 sec
status
power
L1 N
U 15... 80 VDC
15... 260 VAC
1 2 3 4 5 6 7 8 9
ON
Red
White
Black
1 2 3 4
LSV-D3
Green
1 2 3
Red
White
Black
LSV-D1/D2
1 sensitivity control
sensitive setting for low density materials
(turn-on for fluffy/ low density powders etc)
(keep turned-off for normal density materials)
2 “dry” (or uncovered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork out of material confirmation)
3 “wet” (or covered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork dipped in the material confirmation)
4 minimum failsafe select
Failsafe means alarm is same as power failure.
Turn on for underflow detection (min. failsafe)
Keep turned off for overflow detection (max. failsafe)
configuration switches
OFF Position ON Position
Example of Switch in On and Off Positions
1 + of DC Supply input
2 - of DC Supply input
Supply:
12 to 60VDC
3 Earth terminal for safety
4 PNP output is supplied with voltage
12 to 60VDC
A Alarm Indicating LED
B Configuration Switches
C Power ON LED Indicator
D Connecting Terminals
E External Earthing Terminal
controls & indicators
connection terminals
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-DP-D1/D2/D3
5 sec
ON Position
OFF Position
sensitive
dry delay
wet delay
min
failsafe
to set
turn-on
LSV-DP
5 sec status
power
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
D
B
C
A
PNP (alarm=float)
ON
E
lsv-manual-annexure-2 www.trumen.in
Annexure-2
Introduction - LSV-DP-D1/D2/D3 (EIDP / ERDP)
Page 1
LSV-DP-D1
LSV-DP-D2
LSV-DP-D3
Vibrating fork is a single element tuned mechanical element type level sensing device.
Failsafe defines that the alarm and power failure / device failure conditions are same to
the external system. Failsafe operation is best understood with the type of installation
and following matrix.
Off
Off
On
On
Failsafe
Setting
Material &
Installation
Status
LED Power ON
1 2 3 4
ON
min failsafe
1 2 3 4
ON
min failsafe
Material
Status
No material
at high level.
PNP Output
Power OFF
Switch no. 4
is off, failsafe
high/maximum.
Indicating
normal or
healthy
status.
Normal or healthy
output.
Alarm output.
(due to power
failure)
No material
at low level.
Switch no. 4
is on, failsafe
low/minimum.
Indicating
alarm
status.
1 2 3 4
ON
min failsafe Indicating
alarm
status.
Material is
above the low
level or fork
is covered
with material.
1 2 3 4
ON
min failsafe
Material is
above the high
level or fork
is covered
with material.
Indicating
normal or
healthy
status.
High
level
/
overflow
detection
Low
level
/
underflow
detection
1 2 3 4
IL
IL(max) = 250mA
1 2 3 4
Ileak ≤ 0.1mA
Ileak
1 2 3 4
Ileak ≤ 0.1mA
Ileak
1 2 3 4
Ileak ≤ 0.1mA
Ileak
1 2 3 4
Ileak ≤ 0.1mA
Ileak
1 2 3 4
Ileak ≤ 0.1mA
Ileak
1 2 3 4
IL
IL(max) = 250mA
1 2 3 4
Ileak ≤ 0.1mA
Ileak
Alarm output.
(as it is)
Alarm output.
Alarm output.
Normal or healthy
output.
lsv-manual-annexure-2 www.trumen.in
Annexure-2
Operation Matrix - LSV-DP-D1/D2/D3 (EIDP / ERDP)
Page 2
Switch no. 4
is off, failsafe
high/maximum.
Alarm output.
(as it is)
Switch no. 4
is on, failsafe
low/minimum.
Alarm output.
(due to power
failure)
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lsv-manual-annexure-2 www.trumen.in
electrical connections (DC)
sensitive
dry delay
wet delay
min
failsafe
to set
turn-on
LSV-DP
5 sec
status
power
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
PNP (alarm=float)
output unused terminals
DC
12 to 60 VDC
ON
Electrical Connections - LSV-DP-D1/D2/D3 (EIDP / ERDP)
Annexure-2
Page 3
Remote probe connections for
LSV-DP-D3 (ERDP)
LSV-DP-D1/D2 (ERDP)
sensitive
dry delay
wet delay
min
failsafe
to set
turn-on
LSV-DP
5 sec
status
power
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
PNP (alarm=float)
ON
Red
White
Black
1 2 3 4
LSV-D3
Green
1 2 3
Red
White
Black
LSV-D1/D2
Introduction - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP)
1 sensitivity control
sensitive setting for low density materials
(turn-on for fluffy/low density materials)
(keep turned-off for normal materials)
2 “dry” (or uncovered) delay (5 second delay)
(turn-on when 5 second more time is needed for
fork out of material confirmation)
3 “wet” (or covered) delay (5 second delay)
(turn-on when 5 second more time is needed for
fork dipped in the material confirmation)
4 minimum failsafe select
Failsafe means alarm is same as power failure.
Turn on for underflow detection (min. failsafe)
Keep turned off for overflow detection
(max. failsafe)
configuration switches
OFF Position ON Position
Example of Switch in On and Off Positions
1 (+) of DC or Live of AC Supply input
2 (-) of DC or Neutral of AC Supply input
Supply:
15 to 80VDC or 15 to 260VAC 50/60Hz
3 Earth terminal for safety
4 Normally connected terminal of SPDT
contact
5 Common terminal of SPDT contact
6 Normally open terminal of SPDT contact
7 (-) of DC for PNP output
8 (+) of DC for PNP output
9 DC PNP output with respect to -ve of DC
Supply should be within 15 to 60VDC for
PNP output
A Alarm Indicating LED
B Configuration Switches
C Power ON LED Indicator
D Connecting Terminals
E External Earthing Terminal
controls & indicators
connection terminals
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-U(S+P)-D1/D2/D3
5 Sec
ON Position
OFF Position
lsv-manual-annexure-3 www.trumen.in Page 1
Annexure-3
!
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-U(S+P)
5 Sec
status
power
L1 N
U 15... 80V DC
15... 260V AC
1 2 3 4 5 6 7 8 9
D
B
C
A
E
ON
U
15... 60V DC
PNP o/p
!
less than
60VDC only
LSV-U(S+P)-D1
LSV-U(S+P)-D2
LSV-U(S+P)-D3
lsv-manual-annexure-3 www.trumen.in
Annexure-3
Page 2
Failsafe defines that the alarm and power failure / device failure conditions are same to
the external system. Failsafe operation is best understood with the type of installation and
following matrix.
Operation Matrix - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP)
Off
Off
On
On
Failsafe
Setting
Material &
Installation
Status
LED
1 2 3 4
ON
min failsafe
1 2 3 4
ON
min failsafe
4 5 6 4 5 6
Material
Status
No material at
high level.
Switch no. 4
is off, failsafe
high/maximum
Relay Contacts & PNP Output
Indicating
normal or
healthy
status.
Power ON Power OFF
Relay ON normal
or healthy contacts.
Relay OFF alarm
contacts. (due to
power failure)
1 2 3 4
ON
min failsafe
Switch no. 4
is off, failsafe
high/maximum
Material is
above the high
level or fork is
covered with
material.
Indicating
alarm
status.
Relay OFF alarm
contacts.
Relay OFF alarm
contacts. (as it is)
No material at
low level.
Switch no. 4
is on, failsafe
low/minimum
Indicating
alarm
status.
Material is
above the low
level or fork is
covered with
material.
1 2 3 4
ON
min failsafe
Switch no. 4
is on, failsafe
low/minimum
Indicating
normal or
healthy
status.
High
level
/
overflow
detection
Low
level
/
underflow
detection
Ileak ≤ 0.1mA
7 8 9
Ileak
7 8 9
IL
IL(max) = 250mA
7 8 9
Ileak
Ileak ≤ 0.1mA
7 8 9
Ileak
Ileak ≤ 0.1mA
7 8 9
Ileak
Ileak ≤ 0.1mA
7 8 9
Ileak
Ileak ≤ 0.1mA
4 5 6
4 5 6
Relay OFF alarm
contacts.
Relay OFF alarm
contacts. (as it is)
4 5 6
4 5 6
4 5 6 4 5 6
Relay ON normal
or healthy contacts.
Relay OFF alarm
contacts. (due to
power failure)
Ileak ≤ 0.1mA
7 8 9
Ileak
7 8 9
IL
IL(max) = 250mA
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lsv-manual-annexure-3 www.trumen.in
Electrical Connections - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP)
Annexure-3
Page 3
output
contact
Live
Neutral
15 to 260 VAC
50/60 Hz
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-U(S+P)
5 Sec
status
power
L1 N
U 15... 80V DC
15... 260V AC
1 2 3 4 5 6 7 8 9
ON
U
15... 60V DC
PNP o/p
!
less than
60VDC only
PNP
output DC
15 to 60 VDC
output
contact
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-U(S+P)
5 Sec
status
power
L1 N
U 15... 80V DC
15... 260V AC
1 2 3 4 5 6 7 8 9
ON
U
15... 60V DC
PNP o/p
!
less than
60VDC only
PNP
output
electrical connections (AC) electrical connections (DC)
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-U(S+P)
5 Sec
status
power
L1 N
U 15... 80V DC
15... 260V AC
1 2 3 4 5 6 7 8 9
ON
U
15... 60V DC
PNP o/p
!
less than
60VDC only
Red
White
Black
1 2 3 4
LSV-D3
Green
1 2 3
Red
White
Black
LSV-D1/D2
Remote probe connections for
LSV-U(S+P)-D3 (ERUSP)
LSV-U(S+P)-D1/D2 (ERUSP)
1 Not used
2 “dry” (or uncovered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork out of material confirmation)
3 “wet” (or covered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork dipped in the material confirmation)
4 minimum failsafe select
Failsafe means alarm is same as power failure.
Turn on for underflow detection (min. failsafe)
Keep turned off for overflow detection (max. failsafe)
configuration switches
OFF Position ON Position
Example of Switch in On and Off Positions
1 Live of AC Supply through fuse
2 Neutral of AC Supply input through
specified series relay
18 to 260VAC 50/60 Hz series
3 Earth terminal for safety
4,5,6,7,8,9 Not used
A Alarm Indicating LED
B Configuration Switches
C Normal LED Indicator
D Connecting Terminals
E External Earthing Terminal
controls & indicators
connection terminals
x
dry delay
wet delay
min failsafe
to set
turn-on
LSV-AR-D1/D2/D3
5 sec
ON Position
OFF Position
lsv-manual-annexure-4 www.trumen.in
Annexure-4
Introduction - LSV-AR-D1/D2/D3 (EIAR)
Page 1
x
dry delay
wet delay
to set
turn-on
LSV-AR
5 sec alarm
normal
U 18... 260V AC
1 2 3 4 5 6 7 8 9
D
B
C
A
E
ON
min failsafe
2 wire AC series Relay
(<5mA holding current)
LSV-AR-D1
LSV-AR-D2
LSV-AR-D3
Series relay will be energized in normal or healthy condition. Series relay will be de-
energized in alarm condition. Failsafe defines that the alarm and power failure / device
failure conditions are same to the external system. Failsafe operation is best understood
with the type of installation and following matrix.
Normal
or
healthy
Off
Alarm
Alarm
On
Failsafe
Setting
Material &
Installation
Status
LED
1 2 3 4
ON
min failsafe
1 2 3 4
ON
min failsafe
Switching
Operation
When switch no. 4
is off (failsafe high /
maximum).
output status shows
normal when there
is no material at high
switch point or fork
is out of the material.
When switch no. 4
is off (failsafe high /
maximum).
output status shows
alarm if fork is
dipped in material at
high switch point.
When switch no. 4
is on (failsafe low /
minimum).
output status shows
alarm when there is
no material at low
switch point or fork
is out of the material.
When switch no. 4
is on (failsafe low /
minimum).
output status shows
normal if fork is
dipped in material at
low switch point.
Series Relay Status
Alarm/
Normal
lsv-manual-annexure-4 www.trumen.in Page 2
Annexure-4
Operation Matrix - LSV-AR-D1/D2/D3 (EIAR)
High
level
/
overflow
detection
Low
level
/
underflow
detection
Power ON Power OFF
1 2 3 4
ON
min failsafe
Series relay
on
Series relay
off (due to
power
failure)
Red
Green
On
Red
Off
Green
1 2 3 4
ON
min failsafe
Normal
or
healthy
Off
On
Red
Green
On
Red
Off
Green
Series relay
off
Series relay
off
(as it is)
Series relay
off
Series relay
off
(as it is)
Series relay
on
Series relay
off (due to
power
failure)
1 2
L N
1 2
L N
1 2
L N
1 2
L N
1 2
L N
1 2
L N
1 2
L N
1 2
L N
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lsv-manual-annexure-4 www.trumen.in
Annexure-4
Electrical Connections - LSV-AR-D1/D2/D3 (EIAR)
electrical connections (AC)
Page 3
x
dry delay
wet delay
to set
turn-on
LSV-AR
5 sec
alarm
normal
U 18... 260V AC
1 2 3 4 5 6 7 8 9
ON
min failsafe
2 wire AC series Relay
(<5mA holding current)
x
dry delay
wet delay
to set
turn-on
LSV-AR
5 sec
alarm
normal
U 18... 260V AC
1 2 3 4 5 6 7 8 9
ON
min failsafe
2 wire AC series Relay
(<5mA holding current)
Not Used
L
N
AC Supply
18 to 260 VAC
Specified AC Series Relay
Use AC relay / contactor having maximum 150mA to
magnetize and holding current should not be less than 4mA.
Voltage rating of AC relay should be as per input supply voltage.
1 sensitivity control
sensitive setting for low density materials
(turn-on for fluffy / low density materials etc.)
(keep turned-off for normal density materials)
2 “dry” (or uncovered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork out of material confirmation)
3 “wet” (or covered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork dipped in the material confirmation)
4 minimum failsafe select
Failsafe means alarm is same as power failure.
Turn on for underflow detection (min. failsafe)
Keep turned off for overflow detection
(max. failsafe)
configuration switches
OFF Position ON Position
Example of Switch in On and Off Positions
1 (+) of DC Supply input
2 (-) of DC Supply input
DC Supply: 12 to 60VDC
3 Earth terminal for safety
4,5,6,7,8,9 Not used
A Alarm Indicating LED
B Configuration Switches
C Power ON LED Indicator
D Connecting Terminals
E External Earthing Terminal
controls & indicators
connection terminals
sensitive
dry delay
wet delay
min failsafe
to set
turn-on
LSV-DL-8/16
5 sec
ON Position
OFF Position
lsv-manual-annexure-5 www.trumen.in
Annexure-5
Introduction - LSV-DL-D1/D2/D3 (EIDL)
8/16 mA Output
Page 1
sensitive
dry delay
wet delay
min
failsafe
to set
turn-on
LSV-DL-
5 sec
alarm
power
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
D
B
C
A
E
ON
Loop powered
8mA ± 1mA (alarm)
16mA ± 1mA (normal)
8/16
LSV-DL-D1
LSV-DL-D2
LSV-DL-D3
Miliampere output 16 is supplied in normal or healthy condition. Miliampere output
8 is supplied in alarm condition. Failsafe defines that the alarm and power failure /
device failure conditions are same to the external system. Failsafe operation is best
understood with the type of installation and following matrix.
Normal
Off
Off
Alarm
On
On
Failsafe
Setting
Material &
Installation
Status
LED
1 2 3 4
ON
min failsafe
1 2 3 4
ON
min failsafe
Switching
Operation
When switch no. 4
is off (failsafe high /
maximum).
output status shows
normal when there
is no material at high
switch point or fork
is out of the material.
When switch no. 4
is off (failsafe high /
maximum).
output status shows
alarm if fork is
dipped in material
at high switch point.
When switch no. 4
is on (failsafe low /
minimum).
output status shows
alarm when there is
no material at low
switch point or fork
is out of the material.
When switch no. 4
is on (failsafe low /
minimum).
output status shows
normal if fork is
dipped in material
at low switch point.
Miliampere Output
Status
lsv-manual-annexure-5 www.trumen.in Page 2
Annexure-5
Operation Matrix - LSV-DL-D1/D2/D3 (EIDL)
High
level
/
overflow
detection
Low
level
/
underflow
detection
1 2 3 4
ON
min failsafe
1 2 3 4
ON
min failsafe
1 2
DC
IL IL
IL = 16mA
1 2
DC
IL IL
IL = 8mA
1 2
DC
IL IL
IL = 8mA
1 2
DC
IL IL
IL = 16mA
Normal
Alarm
Electrical Connections - LSV-DL-D1/D2/D3 (EIDL)
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
electrical connections (DC)
lsv-manual-annexure-5 www.trumen.in Page 3
Annexure-5
sensitive
dry delay
wet delay
min
failsafe
to set
turn-on
LSV-DL-
5 sec
alarm
power
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
ON
Loop powered
8mA ± 1mA (alarm)
16mA ± 1mA (normal)
8/16
Supply
12 to 60 VDC
Not used
1 2 3 4 5 6 7 8 9
sensitive
dry delay
wet delay
min
failsafe
to set
turn-on
LSV-DL-
5 sec
alarm
power
U 12 to 60V DC
ON
Loop powered
8mA ±1mA (alarm)
16mA ±1mA (normal)
8/16
mA
Meter/Indicator/PLC/SCADA

More Related Content

Similar to Vibrating Fork Level Limit Switch for Solids.pdf

Vfd l m-en_20030522
Vfd l m-en_20030522Vfd l m-en_20030522
Vfd l m-en_20030522
Toàn Huỳnh
 
FTW360 compact pump protector
FTW360 compact pump protectorFTW360 compact pump protector
Catalog biến tần Inovance MD310
Catalog biến tần Inovance MD310Catalog biến tần Inovance MD310
Catalog biến tần Inovance MD310
CTY TNHH HẠO PHƯƠNG
 
Catalog FR-D700 instruction manual (basic)-Beeteco.com
Catalog FR-D700 instruction manual (basic)-Beeteco.comCatalog FR-D700 instruction manual (basic)-Beeteco.com
Catalog FR-D700 instruction manual (basic)-Beeteco.com
Beeteco
 
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec SheetDrager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
Thorne & Derrick UK
 
Ct2000 f manual_english
Ct2000 f manual_englishCt2000 f manual_english
Ct2000 f manual_english
Toàn Huỳnh
 
Magnetic Flowmeter Selection Model Zero Instrument.pdf
Magnetic Flowmeter Selection Model Zero Instrument.pdfMagnetic Flowmeter Selection Model Zero Instrument.pdf
Magnetic Flowmeter Selection Model Zero Instrument.pdf
Dalian Zero Instrument Technology Co., Ltd China
 
Catalog FR-D700 Instruction manual (applied)-Beeteco.com
Catalog FR-D700 Instruction manual (applied)-Beeteco.comCatalog FR-D700 Instruction manual (applied)-Beeteco.com
Catalog FR-D700 Instruction manual (applied)-Beeteco.com
Beeteco
 
Catalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.com
Catalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.comCatalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.com
Catalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.com
Beeteco
 
ARTECHE_CT_LATCHING-RELAYS_EN
ARTECHE_CT_LATCHING-RELAYS_ENARTECHE_CT_LATCHING-RELAYS_EN
ARTECHE_CT_LATCHING-RELAYS_ENMarius Spamers
 
Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]
Toàn Huỳnh
 
V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08Cara Bereck Levy
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices Catalogue
Thorne & Derrick International
 
single-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdfsingle-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdf
acrelenergy
 
Deeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec Sheet
Deeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec SheetDeeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec Sheet
Deeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec SheetThorne & Derrick UK
 
14269179.pdf
14269179.pdf14269179.pdf
14269179.pdf
ErikAntonioTiconipaQ1
 
Intro to Ellman Part 1/5 (RF vs. ESU)
Intro to Ellman Part 1/5 (RF vs. ESU)Intro to Ellman Part 1/5 (RF vs. ESU)
Intro to Ellman Part 1/5 (RF vs. ESU)
Marc Weiser
 
I s7 eng_101201
I s7 eng_101201I s7 eng_101201
I s7 eng_101201
Chan Suk
 
I s7 eng_101201
I s7 eng_101201I s7 eng_101201
I s7 eng_101201
Toàn Huỳnh
 
Moisture, Hydrogen, and Temperature Measurement in Electrical Transformers
Moisture, Hydrogen, and Temperature Measurement in Electrical TransformersMoisture, Hydrogen, and Temperature Measurement in Electrical Transformers
Moisture, Hydrogen, and Temperature Measurement in Electrical Transformers
Alliance Technical Sales, Inc.
 

Similar to Vibrating Fork Level Limit Switch for Solids.pdf (20)

Vfd l m-en_20030522
Vfd l m-en_20030522Vfd l m-en_20030522
Vfd l m-en_20030522
 
FTW360 compact pump protector
FTW360 compact pump protectorFTW360 compact pump protector
FTW360 compact pump protector
 
Catalog biến tần Inovance MD310
Catalog biến tần Inovance MD310Catalog biến tần Inovance MD310
Catalog biến tần Inovance MD310
 
Catalog FR-D700 instruction manual (basic)-Beeteco.com
Catalog FR-D700 instruction manual (basic)-Beeteco.comCatalog FR-D700 instruction manual (basic)-Beeteco.com
Catalog FR-D700 instruction manual (basic)-Beeteco.com
 
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec SheetDrager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
 
Ct2000 f manual_english
Ct2000 f manual_englishCt2000 f manual_english
Ct2000 f manual_english
 
Magnetic Flowmeter Selection Model Zero Instrument.pdf
Magnetic Flowmeter Selection Model Zero Instrument.pdfMagnetic Flowmeter Selection Model Zero Instrument.pdf
Magnetic Flowmeter Selection Model Zero Instrument.pdf
 
Catalog FR-D700 Instruction manual (applied)-Beeteco.com
Catalog FR-D700 Instruction manual (applied)-Beeteco.comCatalog FR-D700 Instruction manual (applied)-Beeteco.com
Catalog FR-D700 Instruction manual (applied)-Beeteco.com
 
Catalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.com
Catalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.comCatalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.com
Catalog Inverter FR-E700 instruction manual (basic) Mitsubishi-Beeteco.com
 
ARTECHE_CT_LATCHING-RELAYS_EN
ARTECHE_CT_LATCHING-RELAYS_ENARTECHE_CT_LATCHING-RELAYS_EN
ARTECHE_CT_LATCHING-RELAYS_EN
 
Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]
 
V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices Catalogue
 
single-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdfsingle-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdf
 
Deeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec Sheet
Deeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec SheetDeeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec Sheet
Deeter LVCS FP Flameproof Liquid Vertical Continuous Sensor - Spec Sheet
 
14269179.pdf
14269179.pdf14269179.pdf
14269179.pdf
 
Intro to Ellman Part 1/5 (RF vs. ESU)
Intro to Ellman Part 1/5 (RF vs. ESU)Intro to Ellman Part 1/5 (RF vs. ESU)
Intro to Ellman Part 1/5 (RF vs. ESU)
 
I s7 eng_101201
I s7 eng_101201I s7 eng_101201
I s7 eng_101201
 
I s7 eng_101201
I s7 eng_101201I s7 eng_101201
I s7 eng_101201
 
Moisture, Hydrogen, and Temperature Measurement in Electrical Transformers
Moisture, Hydrogen, and Temperature Measurement in Electrical TransformersMoisture, Hydrogen, and Temperature Measurement in Electrical Transformers
Moisture, Hydrogen, and Temperature Measurement in Electrical Transformers
 

More from Trumen Technologies Pvt. Ltd. India

Frequency Sweep Level Switch LMFS.pdf
Frequency Sweep Level Switch LMFS.pdfFrequency Sweep Level Switch LMFS.pdf
Frequency Sweep Level Switch LMFS.pdf
Trumen Technologies Pvt. Ltd. India
 
Flush Diaphragm Pressure Transmitter in India.pdf
Flush Diaphragm Pressure Transmitter in India.pdfFlush Diaphragm Pressure Transmitter in India.pdf
Flush Diaphragm Pressure Transmitter in India.pdf
Trumen Technologies Pvt. Ltd. India
 
Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...
Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...
Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...
Trumen Technologies Pvt. Ltd. India
 
Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...
Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...
Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...
Trumen Technologies Pvt. Ltd. India
 
Instruction-Manual-ICT India.pdf
Instruction-Manual-ICT India.pdfInstruction-Manual-ICT India.pdf
Instruction-Manual-ICT India.pdf
Trumen Technologies Pvt. Ltd. India
 
Indicator Controller Cum Transmitter.pdf
Indicator Controller Cum Transmitter.pdfIndicator Controller Cum Transmitter.pdf
Indicator Controller Cum Transmitter.pdf
Trumen Technologies Pvt. Ltd. India
 
Vibrating Rod Point Level Switch for Solids
Vibrating Rod Point Level Switch for SolidsVibrating Rod Point Level Switch for Solids
Vibrating Rod Point Level Switch for Solids
Trumen Technologies Pvt. Ltd. India
 
Vibrating Rod Level Switch | Trumen Technologies Pvt Ltd
Vibrating Rod Level Switch | Trumen Technologies Pvt LtdVibrating Rod Level Switch | Trumen Technologies Pvt Ltd
Vibrating Rod Level Switch | Trumen Technologies Pvt Ltd
Trumen Technologies Pvt. Ltd. India
 
Vibrating Fork Level Switch | Trumen Technologies Pvt Ltd
Vibrating Fork Level Switch | Trumen Technologies Pvt LtdVibrating Fork Level Switch | Trumen Technologies Pvt Ltd
Vibrating Fork Level Switch | Trumen Technologies Pvt Ltd
Trumen Technologies Pvt. Ltd. India
 
Ultrasonic Level Transmitter
Ultrasonic Level TransmitterUltrasonic Level Transmitter
Ultrasonic Level Transmitter
Trumen Technologies Pvt. Ltd. India
 
Rotating Paddle Level Switch for Solids & Powders
Rotating Paddle Level Switch for Solids & PowdersRotating Paddle Level Switch for Solids & Powders
Rotating Paddle Level Switch for Solids & Powders
Trumen Technologies Pvt. Ltd. India
 
Capacitance Type Level Switch Manufacturers in Indiia
Capacitance Type Level Switch Manufacturers in IndiiaCapacitance Type Level Switch Manufacturers in Indiia
Capacitance Type Level Switch Manufacturers in Indiia
Trumen Technologies Pvt. Ltd. India
 
Capacitance Continuous Level Transmitter.pdf
Capacitance Continuous Level Transmitter.pdfCapacitance Continuous Level Transmitter.pdf
Capacitance Continuous Level Transmitter.pdf
Trumen Technologies Pvt. Ltd. India
 
Trumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in India
Trumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in IndiaTrumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in India
Trumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in India
Trumen Technologies Pvt. Ltd. India
 
Trumen vibrating fork point level switch in India | LFV
Trumen vibrating fork point level switch in India | LFV Trumen vibrating fork point level switch in India | LFV
Trumen vibrating fork point level switch in India | LFV
Trumen Technologies Pvt. Ltd. India
 

More from Trumen Technologies Pvt. Ltd. India (15)

Frequency Sweep Level Switch LMFS.pdf
Frequency Sweep Level Switch LMFS.pdfFrequency Sweep Level Switch LMFS.pdf
Frequency Sweep Level Switch LMFS.pdf
 
Flush Diaphragm Pressure Transmitter in India.pdf
Flush Diaphragm Pressure Transmitter in India.pdfFlush Diaphragm Pressure Transmitter in India.pdf
Flush Diaphragm Pressure Transmitter in India.pdf
 
Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...
Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...
Capacitance Head Level Sensor Type Rate of Flow Calculator, Indicator, Contro...
 
Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...
Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...
Capacitance Head Level Sensor Type Loss of Head Indicator, Controller, and Tr...
 
Instruction-Manual-ICT India.pdf
Instruction-Manual-ICT India.pdfInstruction-Manual-ICT India.pdf
Instruction-Manual-ICT India.pdf
 
Indicator Controller Cum Transmitter.pdf
Indicator Controller Cum Transmitter.pdfIndicator Controller Cum Transmitter.pdf
Indicator Controller Cum Transmitter.pdf
 
Vibrating Rod Point Level Switch for Solids
Vibrating Rod Point Level Switch for SolidsVibrating Rod Point Level Switch for Solids
Vibrating Rod Point Level Switch for Solids
 
Vibrating Rod Level Switch | Trumen Technologies Pvt Ltd
Vibrating Rod Level Switch | Trumen Technologies Pvt LtdVibrating Rod Level Switch | Trumen Technologies Pvt Ltd
Vibrating Rod Level Switch | Trumen Technologies Pvt Ltd
 
Vibrating Fork Level Switch | Trumen Technologies Pvt Ltd
Vibrating Fork Level Switch | Trumen Technologies Pvt LtdVibrating Fork Level Switch | Trumen Technologies Pvt Ltd
Vibrating Fork Level Switch | Trumen Technologies Pvt Ltd
 
Ultrasonic Level Transmitter
Ultrasonic Level TransmitterUltrasonic Level Transmitter
Ultrasonic Level Transmitter
 
Rotating Paddle Level Switch for Solids & Powders
Rotating Paddle Level Switch for Solids & PowdersRotating Paddle Level Switch for Solids & Powders
Rotating Paddle Level Switch for Solids & Powders
 
Capacitance Type Level Switch Manufacturers in Indiia
Capacitance Type Level Switch Manufacturers in IndiiaCapacitance Type Level Switch Manufacturers in Indiia
Capacitance Type Level Switch Manufacturers in Indiia
 
Capacitance Continuous Level Transmitter.pdf
Capacitance Continuous Level Transmitter.pdfCapacitance Continuous Level Transmitter.pdf
Capacitance Continuous Level Transmitter.pdf
 
Trumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in India
Trumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in IndiaTrumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in India
Trumen Vibrating Rod Point Level Switch Supplier Manufacturer Exporter in India
 
Trumen vibrating fork point level switch in India | LFV
Trumen vibrating fork point level switch in India | LFV Trumen vibrating fork point level switch in India | LFV
Trumen vibrating fork point level switch in India | LFV
 

Recently uploaded

gtyccccccccccccccccccccccccccccccccccccccccccccccccccccccc
gtycccccccccccccccccccccccccccccccccccccccccccccccccccccccgtyccccccccccccccccccccccccccccccccccccccccccccccccccccccc
gtyccccccccccccccccccccccccccccccccccccccccccccccccccccccc
4thzenzstar
 
What Does the Active Steering Malfunction Warning Mean for Your BMW
What Does the Active Steering Malfunction Warning Mean for Your BMWWhat Does the Active Steering Malfunction Warning Mean for Your BMW
What Does the Active Steering Malfunction Warning Mean for Your BMW
Tanner Motors
 
Ec460b lc Excavator Volvo Service Repair.pdf
Ec460b lc Excavator Volvo Service Repair.pdfEc460b lc Excavator Volvo Service Repair.pdf
Ec460b lc Excavator Volvo Service Repair.pdf
Excavator
 
Ec330B Lc Excavator Volvo Service Repair.pdf
Ec330B Lc Excavator Volvo Service Repair.pdfEc330B Lc Excavator Volvo Service Repair.pdf
Ec330B Lc Excavator Volvo Service Repair.pdf
Excavator
 
Empowering Limpopo Entrepreneurs Consulting SMEs.pptx
Empowering Limpopo Entrepreneurs  Consulting SMEs.pptxEmpowering Limpopo Entrepreneurs  Consulting SMEs.pptx
Empowering Limpopo Entrepreneurs Consulting SMEs.pptx
Precious Mvulane CA (SA),RA
 
Why Is Your BMW X3 Hood Not Responding To Release Commands
Why Is Your BMW X3 Hood Not Responding To Release CommandsWhy Is Your BMW X3 Hood Not Responding To Release Commands
Why Is Your BMW X3 Hood Not Responding To Release Commands
Dart Auto
 
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
psavhef
 
Antique Plastic Traders Company Profile
Antique Plastic Traders Company ProfileAntique Plastic Traders Company Profile
Antique Plastic Traders Company Profile
Antique Plastic Traders
 
Things to remember while upgrading the brakes of your car
Things to remember while upgrading the brakes of your carThings to remember while upgrading the brakes of your car
Things to remember while upgrading the brakes of your car
jennifermiller8137
 
What Exactly Is The Common Rail Direct Injection System & How Does It Work
What Exactly Is The Common Rail Direct Injection System & How Does It WorkWhat Exactly Is The Common Rail Direct Injection System & How Does It Work
What Exactly Is The Common Rail Direct Injection System & How Does It Work
Motor Cars International
 
What Causes 'Trans Failsafe Prog' to Trigger in BMW X5
What Causes 'Trans Failsafe Prog' to Trigger in BMW X5What Causes 'Trans Failsafe Prog' to Trigger in BMW X5
What Causes 'Trans Failsafe Prog' to Trigger in BMW X5
European Service Center
 
Tyre Industrymarket overview with examples of CEAT
Tyre Industrymarket overview with examples of CEATTyre Industrymarket overview with examples of CEAT
Tyre Industrymarket overview with examples of CEAT
kshamashah95
 
一比一原版BC毕业证波士顿学院毕业证成绩单如何办理
一比一原版BC毕业证波士顿学院毕业证成绩单如何办理一比一原版BC毕业证波士顿学院毕业证成绩单如何办理
一比一原版BC毕业证波士顿学院毕业证成绩单如何办理
amvovau
 
Wondering if Your Mercedes EIS is at Fault Here’s How to Tell
Wondering if Your Mercedes EIS is at Fault Here’s How to TellWondering if Your Mercedes EIS is at Fault Here’s How to Tell
Wondering if Your Mercedes EIS is at Fault Here’s How to Tell
Vic Auto Collision & Repair
 
Why Isn't Your BMW X5's Comfort Access Functioning Properly Find Out Here
Why Isn't Your BMW X5's Comfort Access Functioning Properly Find Out HereWhy Isn't Your BMW X5's Comfort Access Functioning Properly Find Out Here
Why Isn't Your BMW X5's Comfort Access Functioning Properly Find Out Here
Masters European & Gapanese Auto Repair
 
Statistics5,c.xz,c.;c.;d.c;d;ssssss.pptx
Statistics5,c.xz,c.;c.;d.c;d;ssssss.pptxStatistics5,c.xz,c.;c.;d.c;d;ssssss.pptx
Statistics5,c.xz,c.;c.;d.c;d;ssssss.pptx
coc7987515756
 
Core technology of Hyundai Motor Group's EV platform 'E-GMP'
Core technology of Hyundai Motor Group's EV platform 'E-GMP'Core technology of Hyundai Motor Group's EV platform 'E-GMP'
Core technology of Hyundai Motor Group's EV platform 'E-GMP'
Hyundai Motor Group
 
5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention
5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention
5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention
Bertini's German Motors
 
What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...
What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...
What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...
Autohaus Service and Sales
 

Recently uploaded (19)

gtyccccccccccccccccccccccccccccccccccccccccccccccccccccccc
gtycccccccccccccccccccccccccccccccccccccccccccccccccccccccgtyccccccccccccccccccccccccccccccccccccccccccccccccccccccc
gtyccccccccccccccccccccccccccccccccccccccccccccccccccccccc
 
What Does the Active Steering Malfunction Warning Mean for Your BMW
What Does the Active Steering Malfunction Warning Mean for Your BMWWhat Does the Active Steering Malfunction Warning Mean for Your BMW
What Does the Active Steering Malfunction Warning Mean for Your BMW
 
Ec460b lc Excavator Volvo Service Repair.pdf
Ec460b lc Excavator Volvo Service Repair.pdfEc460b lc Excavator Volvo Service Repair.pdf
Ec460b lc Excavator Volvo Service Repair.pdf
 
Ec330B Lc Excavator Volvo Service Repair.pdf
Ec330B Lc Excavator Volvo Service Repair.pdfEc330B Lc Excavator Volvo Service Repair.pdf
Ec330B Lc Excavator Volvo Service Repair.pdf
 
Empowering Limpopo Entrepreneurs Consulting SMEs.pptx
Empowering Limpopo Entrepreneurs  Consulting SMEs.pptxEmpowering Limpopo Entrepreneurs  Consulting SMEs.pptx
Empowering Limpopo Entrepreneurs Consulting SMEs.pptx
 
Why Is Your BMW X3 Hood Not Responding To Release Commands
Why Is Your BMW X3 Hood Not Responding To Release CommandsWhy Is Your BMW X3 Hood Not Responding To Release Commands
Why Is Your BMW X3 Hood Not Responding To Release Commands
 
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
 
Antique Plastic Traders Company Profile
Antique Plastic Traders Company ProfileAntique Plastic Traders Company Profile
Antique Plastic Traders Company Profile
 
Things to remember while upgrading the brakes of your car
Things to remember while upgrading the brakes of your carThings to remember while upgrading the brakes of your car
Things to remember while upgrading the brakes of your car
 
What Exactly Is The Common Rail Direct Injection System & How Does It Work
What Exactly Is The Common Rail Direct Injection System & How Does It WorkWhat Exactly Is The Common Rail Direct Injection System & How Does It Work
What Exactly Is The Common Rail Direct Injection System & How Does It Work
 
What Causes 'Trans Failsafe Prog' to Trigger in BMW X5
What Causes 'Trans Failsafe Prog' to Trigger in BMW X5What Causes 'Trans Failsafe Prog' to Trigger in BMW X5
What Causes 'Trans Failsafe Prog' to Trigger in BMW X5
 
Tyre Industrymarket overview with examples of CEAT
Tyre Industrymarket overview with examples of CEATTyre Industrymarket overview with examples of CEAT
Tyre Industrymarket overview with examples of CEAT
 
一比一原版BC毕业证波士顿学院毕业证成绩单如何办理
一比一原版BC毕业证波士顿学院毕业证成绩单如何办理一比一原版BC毕业证波士顿学院毕业证成绩单如何办理
一比一原版BC毕业证波士顿学院毕业证成绩单如何办理
 
Wondering if Your Mercedes EIS is at Fault Here’s How to Tell
Wondering if Your Mercedes EIS is at Fault Here’s How to TellWondering if Your Mercedes EIS is at Fault Here’s How to Tell
Wondering if Your Mercedes EIS is at Fault Here’s How to Tell
 
Why Isn't Your BMW X5's Comfort Access Functioning Properly Find Out Here
Why Isn't Your BMW X5's Comfort Access Functioning Properly Find Out HereWhy Isn't Your BMW X5's Comfort Access Functioning Properly Find Out Here
Why Isn't Your BMW X5's Comfort Access Functioning Properly Find Out Here
 
Statistics5,c.xz,c.;c.;d.c;d;ssssss.pptx
Statistics5,c.xz,c.;c.;d.c;d;ssssss.pptxStatistics5,c.xz,c.;c.;d.c;d;ssssss.pptx
Statistics5,c.xz,c.;c.;d.c;d;ssssss.pptx
 
Core technology of Hyundai Motor Group's EV platform 'E-GMP'
Core technology of Hyundai Motor Group's EV platform 'E-GMP'Core technology of Hyundai Motor Group's EV platform 'E-GMP'
Core technology of Hyundai Motor Group's EV platform 'E-GMP'
 
5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention
5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention
5 Warning Signs Your BMW's Intelligent Battery Sensor Needs Attention
 
What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...
What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...
What Does the PARKTRONIC Inoperative, See Owner's Manual Message Mean for You...
 

Vibrating Fork Level Limit Switch for Solids.pdf

  • 1. LSV: Vibrating Fork Level Limit Switch for Solids Instruction Manual 39 Mangal Nagar, Behind Sai Ram Plaza, Near Rajiv Gandhi Circle, AB Road, Indore, MP 452 001, India Phone: +91-731-497 2065 Trumen Technologies Pvt. Ltd. Customer Support Phone: +91-731-656 2425 email: sales@trumen.in email: support@trumen.in web:www.trumen.in ® sensing matters
  • 2. List of content Introduction - LSV-UD-D1/D2/D3 (Order code EIUD / ERUD).................................... controls & indicators, connection terminals, configuration switches......................... Electrical Connections - LSV-UD-D1/D2/D3 (EIUD / ERUD)........................................ Operating Principle..................................................................................................................... Technical Specification................................................................................................................ Do's and Don'ts............................................................................................................................ Troubleshooting........................................................................................................................... Maintenance & Spares............................................................................................... Operation Matrix - LSV-UD-D1/D2/D3 (EIUD / ERUD)................................................ 1 Page1 2 3 4 4 Page Annexure-1 Page1 Page2 Page3 Introduction - LSV-DP-D1/D2/D3 (Order code EIDP / ERDP)...................................... controls & indicators, connection terminals, configuration switches......................... Electrical Connections - LSV-DP-D1/D2/D3 (EIDP / ERDP)......................................... Operation Matrix - LSV-DP-D1/D2/D3 (EIDP / ERDP)................................................. Page1 Annexure-2 Page1 Page2 Page3 Introduction - LSV-U(S+P)-D1/D2/D3 (Order code EIUSP / ERUSP).......................... controls & indicators, connection terminals, configuration switches......................... Electrical Connections - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP).............................. Operation Matrix - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP)...................................... Page1 Annexure-3 Page1 Page2 Page3 Introduction - LSV-AR-D1/D2/D3 (Order code EIAR).................................................. controls & indicators, connection terminals, configuration switches......................... Electrical Connections - LSV-AR-D1/D2/D3 (EIAR)...................................................... Operation Matrix - LSV-AR-D1/D2/D3 (EIAR).............................................................. Page1 Annexure-4 Page1 Page2 Page3 Introduction - LSV-DL-D1/D2/D3 (Order code EIDL)................................................... controls & indicators, connection terminals, configuration switches......................... Electrical Connections - LSV-DL-D1/D2/D3 (EIDL)....................................................... Operation Matrix - LSV-DL-D1/D2/D3 (EIDL).............................................................. Page1 Annexure-5 Page1 Page2 Page3 ® sensing matters
  • 3. Operating Principle Electronics of LSV excites the piezo-electric-crystals inside the tuning fork, which makes the fork tines vibrate at their natural resonance frequency in free air. When material touches the fork tines, vibration stops as the resonance gets disturbed. Amplitudes of vibration are above threshold when the tines are free to vibrate. Amplitudes of vibration, as sensed by electronics falls below the threshold strength and material presence is thus detected. www.trumen.in lsv-manual-page01 1
  • 4. Technical Specification Features Specifications Applications Specifications are subject to change without prior notice 1. Free flowing powders and granules (size max. 10mm) 2. Suitable for side as well as top mounting 3. Minimum and maximum failsafe field selectable 4. Process temperature max 250°C 5. Process pressure max. 15 bar Typical Mountings 1. Fast Switching Response 2 sec (0.8 sec and 1.5 sec available on demand) 2. 1" screw mountings available 3. High pressure 15 bar forks 4. High Tempreture up-to 250°C available 5. Calibration-less operation 6. Remote electronics with std 10 meters cable length 7. Tropicalized & potted electronics module 8. Threaded & Flanged Mountings 9. Electronic Inserts support all requirements 10. Ingress protection : IP 68/66 (as per IS-13947) 11. Ex-proof (Ex d T6 IP-66 IIC ) - Flameproof as per IS/IEC 60079-1:2007 - Weatherproof (IP-66) as per IS/IEC 60529:2001 - Suitable for Gas Group : IIC - Suitable for Zone 1 & 2 atmospheres 12. Compact size 13. Low power consumption (0.5 to 0.7VA) Integral / Remote Electronics Universal Power Supply, DPDT Relay Output 15 to 80 VDC and 15 to 260 VAC 50/60Hz Potential Free DPDT Relay Output 5 A each @ 24VDC or 220VAC Integral / Remote Electronics for PNP Output 12 to 60 VDC, PNP 250mA max. Short Circuit Safe Integral / Remote Electronics SPDT + PNP Output Universal Supply for SPDT Output 15 to 80 VDC 15 to 260 VAC 50/60Hz DC Supply for PNP Output 15 to 60 VDC Potential Free DPDT Relay Output 5 A each @ 24VDC or 220VAC 250mA max. Short Circuit Safe Integral Electronics AC series relay Two Wire 18 to 260 VAC, Series Relay not less than 4mA to release external relay maximum 150mA to magnetize relay Use relays/contactors will more than 4mA holding current Integral Electronics 4-20mA Loop Powered Two Wire DC 8 / 16 mA 12 to 60 VDC 8mA (±1mA max) / 16mA (±1mA max) Remote electronics require special cable from fork to controller. 10 meter standard length more available on demand 15 gram/litre for D1 (Fork length 150mm) 75 gram/litre for D2 (Fork length 125mm) 500 gram/litre for D3 (Fork length 100mm) -20°C ... 70°C (-4°F ... 158 °F) -20°C ... 80°C (-4°F ... 176 °F) -30°C ... 200°C (-22°F ... 392 °F) {250°C available on request} (extensions & heat sinks required) absolute / max. 15 bar SS 316 or SS 316L NPT / BSP 1", 1¼", 1½", 2" etc Flanged : ANSI/JIS/DIN/ASA/custom SS 304, SS 316, SS 316L 125mm to 3,000mm EIUD / ERUD Supply & Output Relay Type and Rating EIDP / ERDP Supply & Output Output Limit EIUSP / ERUSP Supply & Output Relay Type and Rating PNP Output EIAR Supply & Output Output Limit EIDL Supply & Output Output Limit Sensor Cable Min. Density Ambient Temp. Process Temp. Extended Process Temperature Process Pressure Wetted Parts Mountings Extensions Tube Material & Length lsv-manual-page02 www.trumen.in 2 wall/pipe mounting remote electronics special interconnection cable
  • 5. Do's and Don'ts Features Installation Precaution 1. Always connect the "Earth" to the external "Earthing" screw 2. Tighten the cable entries & glands properly 3. Secure the top aluminium cover at its place properly once the electrical connections and other settings are completed 4. Always tighten the process connection using proper wrench never try to tight by rotating the aluminium housing 5. Make sure process connection is same as that in hopper/tank 6. Vibrating fork tines:- 6.1 Should never be bent closer 6.2 Should never be bent apart 6.3 Should never be cut or machined in any way 6.4 Should never be extended by welding or machining 7. Cable entries must face downwards only 8. Nozzles should never be longer than the fork extension 9. If mounted directly under the material entry, always install a cannopy of suitable strength at proper height from the fork 10. Never climb either by gripping or stepping over either the fork tines or its aluminium housing 11. Obeserve other safety precautions as required at the place of application 3 2 4 5 1 6 lsv-manual-page03 www.trumen.in 3
  • 6. Troubleshooting Maintenance and Spares Top Cover Electronic Insert connection terminals electronic insert fixing screw 4-way male connector for sensor (fork) 4-way female connector from sensor (fork) Cable glands Thermal spacer (where needed) Process connection Fork extension (longer for low level) Fork tines Device enclosure Shown on the left are various parts of LSV level switch. Separatable parts are 1. Electronic insert in short called 'electronics' 2. Fork + Enclosure + Cover + Glands collectively called 'mechanical' For maintenance issues involving replacement of 'electronics', just a single fixing screw is needed to be released. Lift the electronics slowly by holding electronics with one hand and mechanical with other, as wires are connected using rigid 4-way connectors to it. Disconnect 4-way connector by holding electronics with one hand and female of connector by other hand, while the rest of the device is at rest. Connect the new replaced sensor. 4-way connector is unidirectional and only connects in proper direction. Set the electronics properly to its position. Match the mounting screw hole of electronics with that of enclosure and fix the screw. For mechanical issues please send the entire device back to Trumen. Applications Indication Probable cause Work-around Solution No switching output or sensor is permanently in alarm Proper voltage is available but 'power' LED is still OFF Power is not available Power section of sensor electronic insert is failed See if 'power' LED is ON If power LED is OFF check voltage on terminal 1 and 2 Sensor electronic insert is needed to be replaced. Abrupt switching Material is agitated Set time delay to 5 second in both dry and wet condition (turn switch 2, 3 ON) Time delay solves switching issues in agitated materials. Make necessary arrangements to filter the noise in power-line before being fed to the device Provide an exclusive earthing to terminal# 3, fork enclosure earthing screw and fork process connection (device mounting screw or flange) Device contains sufficient filtering of power supply noise inside, but sometimes external earth is needed to make filters sink the extra power supply noise back to earth. Device worked for few months / years but now fails to switch with respect to material while power conditions are all same Device senses fork frequency and amplitude to ascertain presence/absense of material. Possible reasons are 1. Fork frequency shift due to fork wear/ errosion by service material 2. Material deposition on fork leads 3. Over temperature of service material causing fork drive damage Select proper fork surface while ordering as per service material to mitigate fork errosion as well as deposition Order device of proper thermal grade for proper service life of device Clean up deposited materials on fork tines as a part of maintenance schedule Care is needed to be taken while ordering. Scheduled cleaning of fork tines in sticky material application is recommended. In case of fork tine wear or temperature stress, fork sensor is needed to be replaced. Fork is not vibrating when fork tines are touched by hand Sensor electronic insert fork oscillator failed Fork settings are all OK but fork fails to switch to 'no material' at random times Power supply carrying extra noise and fork amplifier picking the noise Device shows no material after some time even when fork is inside the material Material fluffy or fork rate-holes the material due to its own vibrations Set device in sensitive mode (turn switch 1 ON) Sensitive setting reduces vibrational strength and makes switching point at lower amplitude. Fork is vibrating but no switching output when fork tines are touched by hand Sensor electronic insert evaluation section failure lsv-manual-page04 www.trumen.in 4
  • 7. 1 sensitivity control sensitive setting for low density materials (turn-on for fluffy/low density powders etc) (keep turned-off for normal density materials) 2 “dry” (or uncovered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork out of material confirmation) 3 “wet” (or covered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork dipped in the material confirmation) 4 minimum failsafe select Failsafe means alarm is same as power failure. Turn on for underflow detection (min. failsafe) Keep turned off for overflow detection (max. failsafe) configuration switches Example of Switch in On and Off Positions OFF Position ON Position 1 + of DC or Live of AC Supply input 2 - of DC or Neutral of AC Supply input Supply: 15 to 80VDC or 15 to 260VAC 50/60Hz 3 Earth terminal for safety 4 Normally connected terminal of contact 1 5 Common terminal of contact 1 6 Normally open terminal of contact 1 7 Normally connected terminal of contact 2 8 Common terminal of contact 2 9 Normally open terminal of contact 2 A Alarm Indicating LED B Configuration Switches C Power ON LED Indicator D Connecting Terminals E External Earthing Terminal controls & indicators connection terminals sensitive dry delay wet delay min failsafe to set turn-on LSV-UD-D1/D2/D3 5 sec ON Position OFF Position sensitive dry delay wet delay min failsafe to set turn-on LSV-UD 5 sec status power L1 N U 15... 80 VDC 15... 260 VAC 1 2 3 4 5 6 7 8 9 D B C A ON E lsv-manual-annexure-1 www.trumen.in Annexure-1 Introduction - LSV-UD-D1/D2/D3 (EIUD / ERUD) Page 1 LSV-UD-D1 LSV-UD-D2 LSV-UD-D3
  • 8. Failsafe defines that the alarm and power failure / device failure conditions are same to the external system. Failsafe operation is best understood with the type of installation and following matrix. lsv-manual-annexure-1 www.trumen.in Off Off On On Failsafe Setting Material & Installation Status LED Power ON 1 2 3 4 ON min failsafe 1 2 3 4 ON min failsafe 4 5 6 7 8 9 Material Status No material at high level. DPDT Relay Contacts Power OFF Switch no. 4 is off, failsafe high/maximum Indicating normal or healthy status. 4 5 6 7 8 9 Relay ON normal or healthy contacts. Relay OFF alarm contacts. (due to power failure) No material at low level. Indicating alarm status. 4 5 6 7 8 9 Relay OFF alarm contacts. 4 5 6 7 8 9 1 2 3 4 ON min failsafe Indicating alarm status. 4 5 6 7 8 9 Relay OFF alarm contacts. 4 5 6 7 8 9 Relay OFF alarm contacts. (as it is) Material is above the low level or fork is covered with material. 1 2 3 4 ON min failsafe 4 5 6 7 8 9 4 5 6 7 8 9 Material is above the high level or fork is covered with material. Indicating normal or healthy status. Relay ON normal or healthy contacts. High level / overflow detection Low level / underflow detection Annexure-1 Operation Matrix - LSV-UD-D1/D2/D3 (EIUD / ERUD) Switch no. 4 is off, failsafe high/maximum Switch no. 4 is on, failsafe low/minimum Switch no. 4 is on, failsafe low/minimum Relay OFF alarm contacts. (due to power failure) Page 2 Relay OFF alarm contacts. (as it is)
  • 9. Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must. electrical connections (AC) lsv-manual-annexure-1 www.trumen.in electrical connections (DC) DC 15 to 80 VDC output contact 1 output contact 2 sensitive dry delay wet delay min failsafe to set turn-on LSV-UD status power L1 N U 15... 80V DC 15... 260V AC 1 2 3 4 5 6 7 8 9 ON output contact 1 output contact 2 Live Neutral 15 to 260 VAC 50/60 Hz sensitive dry delay wet delay min failsafe to set turn-on LSV-UD status power L1 N U 15... 80V DC 15... 260V AC 1 2 3 4 5 6 7 8 9 ON Electrical Connections - LSV-UD-D1/D2/D3 (EIUD / ERUD) Annexure-1 Page 3 Remote probe connections for LSV-UD-D3 (ERUD) LSV-UD-D1/D2 (ERUD) sensitive dry delay wet delay min failsafe to set turn-on LSV-UD 5 sec status power L1 N U 15... 80 VDC 15... 260 VAC 1 2 3 4 5 6 7 8 9 ON Red White Black 1 2 3 4 LSV-D3 Green 1 2 3 Red White Black LSV-D1/D2
  • 10. 1 sensitivity control sensitive setting for low density materials (turn-on for fluffy/ low density powders etc) (keep turned-off for normal density materials) 2 “dry” (or uncovered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork out of material confirmation) 3 “wet” (or covered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork dipped in the material confirmation) 4 minimum failsafe select Failsafe means alarm is same as power failure. Turn on for underflow detection (min. failsafe) Keep turned off for overflow detection (max. failsafe) configuration switches OFF Position ON Position Example of Switch in On and Off Positions 1 + of DC Supply input 2 - of DC Supply input Supply: 12 to 60VDC 3 Earth terminal for safety 4 PNP output is supplied with voltage 12 to 60VDC A Alarm Indicating LED B Configuration Switches C Power ON LED Indicator D Connecting Terminals E External Earthing Terminal controls & indicators connection terminals sensitive dry delay wet delay min failsafe to set turn-on LSV-DP-D1/D2/D3 5 sec ON Position OFF Position sensitive dry delay wet delay min failsafe to set turn-on LSV-DP 5 sec status power U 12 to 60V DC 1 2 3 4 5 6 7 8 9 D B C A PNP (alarm=float) ON E lsv-manual-annexure-2 www.trumen.in Annexure-2 Introduction - LSV-DP-D1/D2/D3 (EIDP / ERDP) Page 1 LSV-DP-D1 LSV-DP-D2 LSV-DP-D3
  • 11. Vibrating fork is a single element tuned mechanical element type level sensing device. Failsafe defines that the alarm and power failure / device failure conditions are same to the external system. Failsafe operation is best understood with the type of installation and following matrix. Off Off On On Failsafe Setting Material & Installation Status LED Power ON 1 2 3 4 ON min failsafe 1 2 3 4 ON min failsafe Material Status No material at high level. PNP Output Power OFF Switch no. 4 is off, failsafe high/maximum. Indicating normal or healthy status. Normal or healthy output. Alarm output. (due to power failure) No material at low level. Switch no. 4 is on, failsafe low/minimum. Indicating alarm status. 1 2 3 4 ON min failsafe Indicating alarm status. Material is above the low level or fork is covered with material. 1 2 3 4 ON min failsafe Material is above the high level or fork is covered with material. Indicating normal or healthy status. High level / overflow detection Low level / underflow detection 1 2 3 4 IL IL(max) = 250mA 1 2 3 4 Ileak ≤ 0.1mA Ileak 1 2 3 4 Ileak ≤ 0.1mA Ileak 1 2 3 4 Ileak ≤ 0.1mA Ileak 1 2 3 4 Ileak ≤ 0.1mA Ileak 1 2 3 4 Ileak ≤ 0.1mA Ileak 1 2 3 4 IL IL(max) = 250mA 1 2 3 4 Ileak ≤ 0.1mA Ileak Alarm output. (as it is) Alarm output. Alarm output. Normal or healthy output. lsv-manual-annexure-2 www.trumen.in Annexure-2 Operation Matrix - LSV-DP-D1/D2/D3 (EIDP / ERDP) Page 2 Switch no. 4 is off, failsafe high/maximum. Alarm output. (as it is) Switch no. 4 is on, failsafe low/minimum. Alarm output. (due to power failure)
  • 12. Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must. lsv-manual-annexure-2 www.trumen.in electrical connections (DC) sensitive dry delay wet delay min failsafe to set turn-on LSV-DP 5 sec status power U 12 to 60V DC 1 2 3 4 5 6 7 8 9 PNP (alarm=float) output unused terminals DC 12 to 60 VDC ON Electrical Connections - LSV-DP-D1/D2/D3 (EIDP / ERDP) Annexure-2 Page 3 Remote probe connections for LSV-DP-D3 (ERDP) LSV-DP-D1/D2 (ERDP) sensitive dry delay wet delay min failsafe to set turn-on LSV-DP 5 sec status power U 12 to 60V DC 1 2 3 4 5 6 7 8 9 PNP (alarm=float) ON Red White Black 1 2 3 4 LSV-D3 Green 1 2 3 Red White Black LSV-D1/D2
  • 13. Introduction - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP) 1 sensitivity control sensitive setting for low density materials (turn-on for fluffy/low density materials) (keep turned-off for normal materials) 2 “dry” (or uncovered) delay (5 second delay) (turn-on when 5 second more time is needed for fork out of material confirmation) 3 “wet” (or covered) delay (5 second delay) (turn-on when 5 second more time is needed for fork dipped in the material confirmation) 4 minimum failsafe select Failsafe means alarm is same as power failure. Turn on for underflow detection (min. failsafe) Keep turned off for overflow detection (max. failsafe) configuration switches OFF Position ON Position Example of Switch in On and Off Positions 1 (+) of DC or Live of AC Supply input 2 (-) of DC or Neutral of AC Supply input Supply: 15 to 80VDC or 15 to 260VAC 50/60Hz 3 Earth terminal for safety 4 Normally connected terminal of SPDT contact 5 Common terminal of SPDT contact 6 Normally open terminal of SPDT contact 7 (-) of DC for PNP output 8 (+) of DC for PNP output 9 DC PNP output with respect to -ve of DC Supply should be within 15 to 60VDC for PNP output A Alarm Indicating LED B Configuration Switches C Power ON LED Indicator D Connecting Terminals E External Earthing Terminal controls & indicators connection terminals sensitive dry delay wet delay min failsafe to set turn-on LSV-U(S+P)-D1/D2/D3 5 Sec ON Position OFF Position lsv-manual-annexure-3 www.trumen.in Page 1 Annexure-3 ! sensitive dry delay wet delay min failsafe to set turn-on LSV-U(S+P) 5 Sec status power L1 N U 15... 80V DC 15... 260V AC 1 2 3 4 5 6 7 8 9 D B C A E ON U 15... 60V DC PNP o/p ! less than 60VDC only LSV-U(S+P)-D1 LSV-U(S+P)-D2 LSV-U(S+P)-D3
  • 14. lsv-manual-annexure-3 www.trumen.in Annexure-3 Page 2 Failsafe defines that the alarm and power failure / device failure conditions are same to the external system. Failsafe operation is best understood with the type of installation and following matrix. Operation Matrix - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP) Off Off On On Failsafe Setting Material & Installation Status LED 1 2 3 4 ON min failsafe 1 2 3 4 ON min failsafe 4 5 6 4 5 6 Material Status No material at high level. Switch no. 4 is off, failsafe high/maximum Relay Contacts & PNP Output Indicating normal or healthy status. Power ON Power OFF Relay ON normal or healthy contacts. Relay OFF alarm contacts. (due to power failure) 1 2 3 4 ON min failsafe Switch no. 4 is off, failsafe high/maximum Material is above the high level or fork is covered with material. Indicating alarm status. Relay OFF alarm contacts. Relay OFF alarm contacts. (as it is) No material at low level. Switch no. 4 is on, failsafe low/minimum Indicating alarm status. Material is above the low level or fork is covered with material. 1 2 3 4 ON min failsafe Switch no. 4 is on, failsafe low/minimum Indicating normal or healthy status. High level / overflow detection Low level / underflow detection Ileak ≤ 0.1mA 7 8 9 Ileak 7 8 9 IL IL(max) = 250mA 7 8 9 Ileak Ileak ≤ 0.1mA 7 8 9 Ileak Ileak ≤ 0.1mA 7 8 9 Ileak Ileak ≤ 0.1mA 7 8 9 Ileak Ileak ≤ 0.1mA 4 5 6 4 5 6 Relay OFF alarm contacts. Relay OFF alarm contacts. (as it is) 4 5 6 4 5 6 4 5 6 4 5 6 Relay ON normal or healthy contacts. Relay OFF alarm contacts. (due to power failure) Ileak ≤ 0.1mA 7 8 9 Ileak 7 8 9 IL IL(max) = 250mA
  • 15. Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must. lsv-manual-annexure-3 www.trumen.in Electrical Connections - LSV-U(S+P)-D1/D2/D3 (EIUSP / ERUSP) Annexure-3 Page 3 output contact Live Neutral 15 to 260 VAC 50/60 Hz sensitive dry delay wet delay min failsafe to set turn-on LSV-U(S+P) 5 Sec status power L1 N U 15... 80V DC 15... 260V AC 1 2 3 4 5 6 7 8 9 ON U 15... 60V DC PNP o/p ! less than 60VDC only PNP output DC 15 to 60 VDC output contact sensitive dry delay wet delay min failsafe to set turn-on LSV-U(S+P) 5 Sec status power L1 N U 15... 80V DC 15... 260V AC 1 2 3 4 5 6 7 8 9 ON U 15... 60V DC PNP o/p ! less than 60VDC only PNP output electrical connections (AC) electrical connections (DC) sensitive dry delay wet delay min failsafe to set turn-on LSV-U(S+P) 5 Sec status power L1 N U 15... 80V DC 15... 260V AC 1 2 3 4 5 6 7 8 9 ON U 15... 60V DC PNP o/p ! less than 60VDC only Red White Black 1 2 3 4 LSV-D3 Green 1 2 3 Red White Black LSV-D1/D2 Remote probe connections for LSV-U(S+P)-D3 (ERUSP) LSV-U(S+P)-D1/D2 (ERUSP)
  • 16. 1 Not used 2 “dry” (or uncovered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork out of material confirmation) 3 “wet” (or covered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork dipped in the material confirmation) 4 minimum failsafe select Failsafe means alarm is same as power failure. Turn on for underflow detection (min. failsafe) Keep turned off for overflow detection (max. failsafe) configuration switches OFF Position ON Position Example of Switch in On and Off Positions 1 Live of AC Supply through fuse 2 Neutral of AC Supply input through specified series relay 18 to 260VAC 50/60 Hz series 3 Earth terminal for safety 4,5,6,7,8,9 Not used A Alarm Indicating LED B Configuration Switches C Normal LED Indicator D Connecting Terminals E External Earthing Terminal controls & indicators connection terminals x dry delay wet delay min failsafe to set turn-on LSV-AR-D1/D2/D3 5 sec ON Position OFF Position lsv-manual-annexure-4 www.trumen.in Annexure-4 Introduction - LSV-AR-D1/D2/D3 (EIAR) Page 1 x dry delay wet delay to set turn-on LSV-AR 5 sec alarm normal U 18... 260V AC 1 2 3 4 5 6 7 8 9 D B C A E ON min failsafe 2 wire AC series Relay (<5mA holding current) LSV-AR-D1 LSV-AR-D2 LSV-AR-D3
  • 17. Series relay will be energized in normal or healthy condition. Series relay will be de- energized in alarm condition. Failsafe defines that the alarm and power failure / device failure conditions are same to the external system. Failsafe operation is best understood with the type of installation and following matrix. Normal or healthy Off Alarm Alarm On Failsafe Setting Material & Installation Status LED 1 2 3 4 ON min failsafe 1 2 3 4 ON min failsafe Switching Operation When switch no. 4 is off (failsafe high / maximum). output status shows normal when there is no material at high switch point or fork is out of the material. When switch no. 4 is off (failsafe high / maximum). output status shows alarm if fork is dipped in material at high switch point. When switch no. 4 is on (failsafe low / minimum). output status shows alarm when there is no material at low switch point or fork is out of the material. When switch no. 4 is on (failsafe low / minimum). output status shows normal if fork is dipped in material at low switch point. Series Relay Status Alarm/ Normal lsv-manual-annexure-4 www.trumen.in Page 2 Annexure-4 Operation Matrix - LSV-AR-D1/D2/D3 (EIAR) High level / overflow detection Low level / underflow detection Power ON Power OFF 1 2 3 4 ON min failsafe Series relay on Series relay off (due to power failure) Red Green On Red Off Green 1 2 3 4 ON min failsafe Normal or healthy Off On Red Green On Red Off Green Series relay off Series relay off (as it is) Series relay off Series relay off (as it is) Series relay on Series relay off (due to power failure) 1 2 L N 1 2 L N 1 2 L N 1 2 L N 1 2 L N 1 2 L N 1 2 L N 1 2 L N
  • 18. Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must. lsv-manual-annexure-4 www.trumen.in Annexure-4 Electrical Connections - LSV-AR-D1/D2/D3 (EIAR) electrical connections (AC) Page 3 x dry delay wet delay to set turn-on LSV-AR 5 sec alarm normal U 18... 260V AC 1 2 3 4 5 6 7 8 9 ON min failsafe 2 wire AC series Relay (<5mA holding current) x dry delay wet delay to set turn-on LSV-AR 5 sec alarm normal U 18... 260V AC 1 2 3 4 5 6 7 8 9 ON min failsafe 2 wire AC series Relay (<5mA holding current) Not Used L N AC Supply 18 to 260 VAC Specified AC Series Relay Use AC relay / contactor having maximum 150mA to magnetize and holding current should not be less than 4mA. Voltage rating of AC relay should be as per input supply voltage.
  • 19. 1 sensitivity control sensitive setting for low density materials (turn-on for fluffy / low density materials etc.) (keep turned-off for normal density materials) 2 “dry” (or uncovered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork out of material confirmation) 3 “wet” (or covered) delay (5 second delay) setting (turn-on when 5 second more time is needed for fork dipped in the material confirmation) 4 minimum failsafe select Failsafe means alarm is same as power failure. Turn on for underflow detection (min. failsafe) Keep turned off for overflow detection (max. failsafe) configuration switches OFF Position ON Position Example of Switch in On and Off Positions 1 (+) of DC Supply input 2 (-) of DC Supply input DC Supply: 12 to 60VDC 3 Earth terminal for safety 4,5,6,7,8,9 Not used A Alarm Indicating LED B Configuration Switches C Power ON LED Indicator D Connecting Terminals E External Earthing Terminal controls & indicators connection terminals sensitive dry delay wet delay min failsafe to set turn-on LSV-DL-8/16 5 sec ON Position OFF Position lsv-manual-annexure-5 www.trumen.in Annexure-5 Introduction - LSV-DL-D1/D2/D3 (EIDL) 8/16 mA Output Page 1 sensitive dry delay wet delay min failsafe to set turn-on LSV-DL- 5 sec alarm power U 12 to 60V DC 1 2 3 4 5 6 7 8 9 D B C A E ON Loop powered 8mA ± 1mA (alarm) 16mA ± 1mA (normal) 8/16 LSV-DL-D1 LSV-DL-D2 LSV-DL-D3
  • 20. Miliampere output 16 is supplied in normal or healthy condition. Miliampere output 8 is supplied in alarm condition. Failsafe defines that the alarm and power failure / device failure conditions are same to the external system. Failsafe operation is best understood with the type of installation and following matrix. Normal Off Off Alarm On On Failsafe Setting Material & Installation Status LED 1 2 3 4 ON min failsafe 1 2 3 4 ON min failsafe Switching Operation When switch no. 4 is off (failsafe high / maximum). output status shows normal when there is no material at high switch point or fork is out of the material. When switch no. 4 is off (failsafe high / maximum). output status shows alarm if fork is dipped in material at high switch point. When switch no. 4 is on (failsafe low / minimum). output status shows alarm when there is no material at low switch point or fork is out of the material. When switch no. 4 is on (failsafe low / minimum). output status shows normal if fork is dipped in material at low switch point. Miliampere Output Status lsv-manual-annexure-5 www.trumen.in Page 2 Annexure-5 Operation Matrix - LSV-DL-D1/D2/D3 (EIDL) High level / overflow detection Low level / underflow detection 1 2 3 4 ON min failsafe 1 2 3 4 ON min failsafe 1 2 DC IL IL IL = 16mA 1 2 DC IL IL IL = 8mA 1 2 DC IL IL IL = 8mA 1 2 DC IL IL IL = 16mA Normal Alarm
  • 21. Electrical Connections - LSV-DL-D1/D2/D3 (EIDL) Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must. electrical connections (DC) lsv-manual-annexure-5 www.trumen.in Page 3 Annexure-5 sensitive dry delay wet delay min failsafe to set turn-on LSV-DL- 5 sec alarm power U 12 to 60V DC 1 2 3 4 5 6 7 8 9 ON Loop powered 8mA ± 1mA (alarm) 16mA ± 1mA (normal) 8/16 Supply 12 to 60 VDC Not used 1 2 3 4 5 6 7 8 9 sensitive dry delay wet delay min failsafe to set turn-on LSV-DL- 5 sec alarm power U 12 to 60V DC ON Loop powered 8mA ±1mA (alarm) 16mA ±1mA (normal) 8/16 mA Meter/Indicator/PLC/SCADA