Understanding ISO/IEC 14763-3 Cabling Standards
-Seymour Goldstein
17-01-2018 1www.flukenetworks.com| 2006-2017 Fluke Corporation
Understanding ISO/IEC 14763-3 Cabling Standards
17-01-2018 2
ISO/IEC 14763-3 edition 2 was published in 2014. This standard supports the
implementation and operation of customer premises cabling by specifying systems and methods for
inspecting and testing optical fiber cabling. In 2015, a corrigendum was published. Currently, an
amendment is under review to make further corrections. Also, a supplement to the amendment was
added.
The corrigendum made changes to connecting hardware attenuation values and modified
the equations for test limits. The amendment made corrections to end face inspection, test
methods, and uncertainty. The supplement to the amendment fixed errors within the uncertainties.
Details of the changes are described herein.
Standards are constantly changing in response to commercial changes, and are intended to
align with customer needs. Sometimes the changes may appear confusing, as in this case, so it is a
good idea to pay closer attention to developments in standards.
www.flukenetworks.com| 2006-2017 Fluke Corporation
Understanding ISO/IEC 14763-3 Cabling Standards
17-01-2018 3
• Single-mode connecting hardware attenuation for “random mated” (mating two reference-grade
connectors) was changed from 0.30 dB maximum to 0.25 dB maximum1
• Single-mode connecting hardware attenuation for “mated against reference” (mating an unknown
connector to a reference grade connector) was changed from 0.65 dB maximum to 0.75 dB
maximum2
This correction was made to align actual data to the standard. The IEC connector standard
referenced in the footnotes uses the attenuation values for an LC/APC connector. Since an APC polish
single-mode connector typically has higher attenuation than a PC connector, it is used to represent the
worst case.
www.flukenetworks.com| 2006-2017 Fluke Corporation
Corrigendum 1
Understanding ISO/IEC 14763-3 Cabling Standards
17-01-2018 4
Regarding the change for the treatment of permanent link test limits, these equations are now used:
• Multimode: (2 x 0.50 dB) + (sum cable attenuation) + (sum embedded connection attenuation)
• Single-mode: (2 x 0.75 dB) + (sum cable attenuation) + (sum embedded connection attenuation)
These equations use the connector attenuation values for “mated against reference”. For the
multimode value of 0.50 dB, a Grade B performance for an LC/PC is used. For the single-mode value of
0.75 dB, a Grade C performance is used for an LC/APC.
1 For 50% as defined by a Grade C connector performance standard.
2 For all cases as defined by a Grade C connector performance standard.
www.flukenetworks.com| 2006-2017 Fluke Corporation
Corrigendum 1
Understanding ISO/IEC 14763-3 Cabling Standards
17-01-2018 5
Amendment 1 is in committee draft and contains information about inspecting connector end
faces used in installed cabling and test cords. The connectors are types with a single fiber, such as an LC
connector, or with multiple fibers, such as an MPO connector. Recommendations for cleaning these
interfaces are included. The amendment replaces the previously required inspection annex with a
now recommended annex. The reason is that during a 2015 subcommittee meeting, it was reported
that automated analysis of connector end faces is not consistent among suppliers - results vary.
Pending investigation by a task group asked to develop a calibration process, end face inspection will
remain informative (recommended).
Amendment 1 contains three tables for inspection requirements. Each table has information
on allowable scratches and defects for a given return loss.
• Multimode 20 dB for cylindrical (e.g. LC) and rectangular ferrules (e.g. MPO).
• Single-mode 35 dB for a PC cylindrical ferrules only (e.g. LC).
• Single-mode 60 dB APC for cylindrical (e.g. LC) or rectangular ferrules (e.g. MPO).
www.flukenetworks.com| 2006-2017 Fluke Corporation
Amendment 1
Understanding ISO/IEC 14763-3 Cabling Standards
17-01-2018 6
The tables for inspection are copied from IEC 61300-3-35, the standard used by manufacturers
of inspection equipment. One issue that is under investigation is the difference in requirements for
single-mode PC connectors. IEC 61300-3-35 specifies a 45 dB return loss and ISO/IEC 14763-3 requires
a 35 dB return loss. As a workable solution, the information from IEC 61300-3-35 for 45 dB return loss
with minor modifications may be used. This will be discussed at the February 2016 meeting.
www.flukenetworks.com| 2006-2017 Fluke Corporation
Amendment 1
Understanding ISO/IEC 14763-3 Cabling Standards
17-01-2018 7
The supplement to Amendment 1 simply corrects uncertainty values for the test methods. The
uncertainty assigned to various test methods is a separate topic.
www.flukenetworks.com| 2006-2017 Fluke Corporation
Supplement to Amendment 1
Understanding ISO/IEC 14763-3 Cabling Standards
17-01-2018 8
As mentioned earlier, standards are not stagnant and in today’s climate standards change
quicker than ever. It is sometimes difficult to keep up with complex standards. Fortunately, companies
such as Fluke Networks are paying close attention to these changes and providing guidance with
communications and with up to date test equipment used for compliance testing.
www.flukenetworks.com| 2006-2017 Fluke Corporation
Wrap up
Thank You!
17-01-2018 9www.flukenetworks.com| 2006-2017 Fluke Corporation

More Related Content

Similar to Understanding isoiec 14763 3 cabling standards

Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...
Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...
Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...
Thorne & Derrick International
 
A solder joint reliability model for the philips lumileds luxeon rebel led c...
A solder joint reliability model for the philips lumileds luxeon rebel led  c...A solder joint reliability model for the philips lumileds luxeon rebel led  c...
A solder joint reliability model for the philips lumileds luxeon rebel led c...
Greg Caswell
 
Fiber optic test issues ¨c what to measure and why
Fiber optic test issues ¨c what to measure and whyFiber optic test issues ¨c what to measure and why
Fiber optic test issues ¨c what to measure and why
Md.Bellal Hossain
 

Similar to Understanding isoiec 14763 3 cabling standards (20)

Breaking the rules! bicsi
Breaking the rules! bicsi  Breaking the rules! bicsi
Breaking the rules! bicsi
 
Traxon Cove Light AC Data Injector Specification
Traxon Cove Light AC Data Injector SpecificationTraxon Cove Light AC Data Injector Specification
Traxon Cove Light AC Data Injector Specification
 
C011122428
C011122428C011122428
C011122428
 
Catalog busbar Legrand
Catalog busbar LegrandCatalog busbar Legrand
Catalog busbar Legrand
 
Premium Power Quality contracts and labeling
Premium Power Quality contracts and labelingPremium Power Quality contracts and labeling
Premium Power Quality contracts and labeling
 
Slide 1.pdf
Slide 1.pdfSlide 1.pdf
Slide 1.pdf
 
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdfSchneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
Schneider Harmonics abstract IEEE_STD_519_1992vs2014.pdf
 
Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...
Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...
Elastimold Connectors - Loadbreak & Deadbreak Elbow & Bolted Tee Connectors -...
 
A solder joint reliability model for the philips lumileds luxeon rebel led c...
A solder joint reliability model for the philips lumileds luxeon rebel led  c...A solder joint reliability model for the philips lumileds luxeon rebel led  c...
A solder joint reliability model for the philips lumileds luxeon rebel led c...
 
FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439
 
ABB Low Voltage LV Capacitors, ABB CLMD
ABB Low Voltage LV Capacitors, ABB CLMDABB Low Voltage LV Capacitors, ABB CLMD
ABB Low Voltage LV Capacitors, ABB CLMD
 
07 - ELCB - Fuji Electric
07 - ELCB - Fuji Electric07 - ELCB - Fuji Electric
07 - ELCB - Fuji Electric
 
Kaizenreport
KaizenreportKaizenreport
Kaizenreport
 
VLinkSys.ppt
VLinkSys.pptVLinkSys.ppt
VLinkSys.ppt
 
Datablad opa627 operasjonsforsterer sven åge eriksen fagskolen telemark opamp...
Datablad opa627 operasjonsforsterer sven åge eriksen fagskolen telemark opamp...Datablad opa627 operasjonsforsterer sven åge eriksen fagskolen telemark opamp...
Datablad opa627 operasjonsforsterer sven åge eriksen fagskolen telemark opamp...
 
Fiber optic test issues ¨c what to measure and why
Fiber optic test issues ¨c what to measure and whyFiber optic test issues ¨c what to measure and why
Fiber optic test issues ¨c what to measure and why
 
Arc flash example4
Arc flash example4Arc flash example4
Arc flash example4
 
Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...Results of 10 years after installation tests with partial discharge detection...
Results of 10 years after installation tests with partial discharge detection...
 
Elastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations CatalogueElastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations Catalogue
 
ABB Training Manual.pdf
ABB Training Manual.pdfABB Training Manual.pdf
ABB Training Manual.pdf
 

More from smithponting

More from smithponting (19)

Cable testing 101 how to read the link ware™ pc report
Cable testing 101 how to read the link ware™ pc reportCable testing 101 how to read the link ware™ pc report
Cable testing 101 how to read the link ware™ pc report
 
Standards update the four a’s of harmonization
Standards update the four a’s of harmonizationStandards update the four a’s of harmonization
Standards update the four a’s of harmonization
 
Standard update 25 gbase t joins the party!
Standard update 25 gbase t joins the party!Standard update 25 gbase t joins the party!
Standard update 25 gbase t joins the party!
 
Standard update 25 gbase t joins the party!
Standard update 25 gbase t joins the party!Standard update 25 gbase t joins the party!
Standard update 25 gbase t joins the party!
 
Benefits of fiber optic and passive optical lan test
Benefits of fiber optic and passive optical lan testBenefits of fiber optic and passive optical lan test
Benefits of fiber optic and passive optical lan test
 
Beauty isn’t skin deep
Beauty isn’t skin deepBeauty isn’t skin deep
Beauty isn’t skin deep
 
Beat the heat with versiv™ cool features
Beat the heat with versiv™ cool featuresBeat the heat with versiv™ cool features
Beat the heat with versiv™ cool features
 
All fiber roads divisible by 2 and 8
All fiber roads divisible by 2 and 8All fiber roads divisible by 2 and 8
All fiber roads divisible by 2 and 8
 
A closer look at 40 gig duplex multimode applications
A closer look at 40 gig duplex multimode applicationsA closer look at 40 gig duplex multimode applications
A closer look at 40 gig duplex multimode applications
 
How high speed fiber applications is impacting the networking arena
How high speed fiber applications is impacting the networking arenaHow high speed fiber applications is impacting the networking arena
How high speed fiber applications is impacting the networking arena
 
All about alien crosstalk measurement
All about alien crosstalk measurementAll about alien crosstalk measurement
All about alien crosstalk measurement
 
A closer look at 40 gig duplex multimode applications
A closer look at 40 gig duplex multimode applicationsA closer look at 40 gig duplex multimode applications
A closer look at 40 gig duplex multimode applications
 
Six reasons certification is essential white paper
Six reasons certification is essential white paperSix reasons certification is essential white paper
Six reasons certification is essential white paper
 
Certification vs. qualification a closer look
Certification vs. qualification a closer lookCertification vs. qualification a closer look
Certification vs. qualification a closer look
 
Certifying 10 gig sv white paper
Certifying 10 gig sv white paperCertifying 10 gig sv white paper
Certifying 10 gig sv white paper
 
101 series understanding copper cabling’s balancing act
101 series understanding copper cabling’s balancing act101 series understanding copper cabling’s balancing act
101 series understanding copper cabling’s balancing act
 
Encircled flux white paper
Encircled flux white paperEncircled flux white paper
Encircled flux white paper
 
Copper and glass securing the foundation of your 10 gigabit data center
Copper and glass securing the foundation of your 10 gigabit data centerCopper and glass securing the foundation of your 10 gigabit data center
Copper and glass securing the foundation of your 10 gigabit data center
 
Certifying 10 gig sv white paper
Certifying 10 gig sv white paperCertifying 10 gig sv white paper
Certifying 10 gig sv white paper
 

Recently uploaded

Harnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptx
Harnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptxHarnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptx
Harnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptx
FIDO Alliance
 
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc
 
Tales from a Passkey Provider Progress from Awareness to Implementation.pptx
Tales from a Passkey Provider  Progress from Awareness to Implementation.pptxTales from a Passkey Provider  Progress from Awareness to Implementation.pptx
Tales from a Passkey Provider Progress from Awareness to Implementation.pptx
FIDO Alliance
 
“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf
“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf
“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf
Muhammad Subhan
 

Recently uploaded (20)

Introduction to FIDO Authentication and Passkeys.pptx
Introduction to FIDO Authentication and Passkeys.pptxIntroduction to FIDO Authentication and Passkeys.pptx
Introduction to FIDO Authentication and Passkeys.pptx
 
Frisco Automating Purchase Orders with MuleSoft IDP- May 10th, 2024.pptx.pdf
Frisco Automating Purchase Orders with MuleSoft IDP- May 10th, 2024.pptx.pdfFrisco Automating Purchase Orders with MuleSoft IDP- May 10th, 2024.pptx.pdf
Frisco Automating Purchase Orders with MuleSoft IDP- May 10th, 2024.pptx.pdf
 
JohnPollard-hybrid-app-RailsConf2024.pptx
JohnPollard-hybrid-app-RailsConf2024.pptxJohnPollard-hybrid-app-RailsConf2024.pptx
JohnPollard-hybrid-app-RailsConf2024.pptx
 
Harnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptx
Harnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptxHarnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptx
Harnessing Passkeys in the Battle Against AI-Powered Cyber Threats.pptx
 
The Ultimate Prompt Engineering Guide for Generative AI: Get the Most Out of ...
The Ultimate Prompt Engineering Guide for Generative AI: Get the Most Out of ...The Ultimate Prompt Engineering Guide for Generative AI: Get the Most Out of ...
The Ultimate Prompt Engineering Guide for Generative AI: Get the Most Out of ...
 
Cyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptx
Cyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptxCyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptx
Cyber Insurance - RalphGilot - Embry-Riddle Aeronautical University.pptx
 
UiPath manufacturing technology benefits and AI overview
UiPath manufacturing technology benefits and AI overviewUiPath manufacturing technology benefits and AI overview
UiPath manufacturing technology benefits and AI overview
 
Generative AI Use Cases and Applications.pdf
Generative AI Use Cases and Applications.pdfGenerative AI Use Cases and Applications.pdf
Generative AI Use Cases and Applications.pdf
 
Introduction to use of FHIR Documents in ABDM
Introduction to use of FHIR Documents in ABDMIntroduction to use of FHIR Documents in ABDM
Introduction to use of FHIR Documents in ABDM
 
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
TrustArc Webinar - Unified Trust Center for Privacy, Security, Compliance, an...
 
The Zero-ETL Approach: Enhancing Data Agility and Insight
The Zero-ETL Approach: Enhancing Data Agility and InsightThe Zero-ETL Approach: Enhancing Data Agility and Insight
The Zero-ETL Approach: Enhancing Data Agility and Insight
 
الأمن السيبراني - ما لا يسع للمستخدم جهله
الأمن السيبراني - ما لا يسع للمستخدم جهلهالأمن السيبراني - ما لا يسع للمستخدم جهله
الأمن السيبراني - ما لا يسع للمستخدم جهله
 
AI mind or machine power point presentation
AI mind or machine power point presentationAI mind or machine power point presentation
AI mind or machine power point presentation
 
Event-Driven Architecture Masterclass: Integrating Distributed Data Stores Ac...
Event-Driven Architecture Masterclass: Integrating Distributed Data Stores Ac...Event-Driven Architecture Masterclass: Integrating Distributed Data Stores Ac...
Event-Driven Architecture Masterclass: Integrating Distributed Data Stores Ac...
 
Tales from a Passkey Provider Progress from Awareness to Implementation.pptx
Tales from a Passkey Provider  Progress from Awareness to Implementation.pptxTales from a Passkey Provider  Progress from Awareness to Implementation.pptx
Tales from a Passkey Provider Progress from Awareness to Implementation.pptx
 
How we scaled to 80K users by doing nothing!.pdf
How we scaled to 80K users by doing nothing!.pdfHow we scaled to 80K users by doing nothing!.pdf
How we scaled to 80K users by doing nothing!.pdf
 
“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf
“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf
“Iamnobody89757” Understanding the Mysterious of Digital Identity.pdf
 
Navigating the Large Language Model choices_Ravi Daparthi
Navigating the Large Language Model choices_Ravi DaparthiNavigating the Large Language Model choices_Ravi Daparthi
Navigating the Large Language Model choices_Ravi Daparthi
 
(Explainable) Data-Centric AI: what are you explaininhg, and to whom?
(Explainable) Data-Centric AI: what are you explaininhg, and to whom?(Explainable) Data-Centric AI: what are you explaininhg, and to whom?
(Explainable) Data-Centric AI: what are you explaininhg, and to whom?
 
Six Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal OntologySix Myths about Ontologies: The Basics of Formal Ontology
Six Myths about Ontologies: The Basics of Formal Ontology
 

Understanding isoiec 14763 3 cabling standards

  • 1. Understanding ISO/IEC 14763-3 Cabling Standards -Seymour Goldstein 17-01-2018 1www.flukenetworks.com| 2006-2017 Fluke Corporation
  • 2. Understanding ISO/IEC 14763-3 Cabling Standards 17-01-2018 2 ISO/IEC 14763-3 edition 2 was published in 2014. This standard supports the implementation and operation of customer premises cabling by specifying systems and methods for inspecting and testing optical fiber cabling. In 2015, a corrigendum was published. Currently, an amendment is under review to make further corrections. Also, a supplement to the amendment was added. The corrigendum made changes to connecting hardware attenuation values and modified the equations for test limits. The amendment made corrections to end face inspection, test methods, and uncertainty. The supplement to the amendment fixed errors within the uncertainties. Details of the changes are described herein. Standards are constantly changing in response to commercial changes, and are intended to align with customer needs. Sometimes the changes may appear confusing, as in this case, so it is a good idea to pay closer attention to developments in standards. www.flukenetworks.com| 2006-2017 Fluke Corporation
  • 3. Understanding ISO/IEC 14763-3 Cabling Standards 17-01-2018 3 • Single-mode connecting hardware attenuation for “random mated” (mating two reference-grade connectors) was changed from 0.30 dB maximum to 0.25 dB maximum1 • Single-mode connecting hardware attenuation for “mated against reference” (mating an unknown connector to a reference grade connector) was changed from 0.65 dB maximum to 0.75 dB maximum2 This correction was made to align actual data to the standard. The IEC connector standard referenced in the footnotes uses the attenuation values for an LC/APC connector. Since an APC polish single-mode connector typically has higher attenuation than a PC connector, it is used to represent the worst case. www.flukenetworks.com| 2006-2017 Fluke Corporation Corrigendum 1
  • 4. Understanding ISO/IEC 14763-3 Cabling Standards 17-01-2018 4 Regarding the change for the treatment of permanent link test limits, these equations are now used: • Multimode: (2 x 0.50 dB) + (sum cable attenuation) + (sum embedded connection attenuation) • Single-mode: (2 x 0.75 dB) + (sum cable attenuation) + (sum embedded connection attenuation) These equations use the connector attenuation values for “mated against reference”. For the multimode value of 0.50 dB, a Grade B performance for an LC/PC is used. For the single-mode value of 0.75 dB, a Grade C performance is used for an LC/APC. 1 For 50% as defined by a Grade C connector performance standard. 2 For all cases as defined by a Grade C connector performance standard. www.flukenetworks.com| 2006-2017 Fluke Corporation Corrigendum 1
  • 5. Understanding ISO/IEC 14763-3 Cabling Standards 17-01-2018 5 Amendment 1 is in committee draft and contains information about inspecting connector end faces used in installed cabling and test cords. The connectors are types with a single fiber, such as an LC connector, or with multiple fibers, such as an MPO connector. Recommendations for cleaning these interfaces are included. The amendment replaces the previously required inspection annex with a now recommended annex. The reason is that during a 2015 subcommittee meeting, it was reported that automated analysis of connector end faces is not consistent among suppliers - results vary. Pending investigation by a task group asked to develop a calibration process, end face inspection will remain informative (recommended). Amendment 1 contains three tables for inspection requirements. Each table has information on allowable scratches and defects for a given return loss. • Multimode 20 dB for cylindrical (e.g. LC) and rectangular ferrules (e.g. MPO). • Single-mode 35 dB for a PC cylindrical ferrules only (e.g. LC). • Single-mode 60 dB APC for cylindrical (e.g. LC) or rectangular ferrules (e.g. MPO). www.flukenetworks.com| 2006-2017 Fluke Corporation Amendment 1
  • 6. Understanding ISO/IEC 14763-3 Cabling Standards 17-01-2018 6 The tables for inspection are copied from IEC 61300-3-35, the standard used by manufacturers of inspection equipment. One issue that is under investigation is the difference in requirements for single-mode PC connectors. IEC 61300-3-35 specifies a 45 dB return loss and ISO/IEC 14763-3 requires a 35 dB return loss. As a workable solution, the information from IEC 61300-3-35 for 45 dB return loss with minor modifications may be used. This will be discussed at the February 2016 meeting. www.flukenetworks.com| 2006-2017 Fluke Corporation Amendment 1
  • 7. Understanding ISO/IEC 14763-3 Cabling Standards 17-01-2018 7 The supplement to Amendment 1 simply corrects uncertainty values for the test methods. The uncertainty assigned to various test methods is a separate topic. www.flukenetworks.com| 2006-2017 Fluke Corporation Supplement to Amendment 1
  • 8. Understanding ISO/IEC 14763-3 Cabling Standards 17-01-2018 8 As mentioned earlier, standards are not stagnant and in today’s climate standards change quicker than ever. It is sometimes difficult to keep up with complex standards. Fortunately, companies such as Fluke Networks are paying close attention to these changes and providing guidance with communications and with up to date test equipment used for compliance testing. www.flukenetworks.com| 2006-2017 Fluke Corporation Wrap up
  • 9. Thank You! 17-01-2018 9www.flukenetworks.com| 2006-2017 Fluke Corporation