Thermal Analysis of a Road on Permafrost
Source: http://simmakers.com/road-on-permafrost/
(Keywords: thermal analysis of a road on permafrost, thermal analysis of a road, simulation of a road in permafrost
area, thermal analysis of roadbed, thermal analysis of road surface)
Road maintenance in permafrost areas is connected with the problem of ensuring soil stability.
Roadbed deformations are the result of settlement and heave due to the respective thawing and
freezing of underlying moist permafrost soils. These processes cause large amounts of damage on
road surfaces.
It is therefore important to pay particular attention to the thermal analysis of soil bases and
roadbeds at the design stage to determine the road characteristics such as embankment height,
thermal insulation layer thickness, and so on.
Simple 2D thermal analysis cannot account for the changes in terrain and geological structure of the
soil throughout the simulated road segment and proper temperature distribution analysis also
requires consideration of the influence of solar radiation, road thermal radiation and convective heat
transfer due to groundwater filtration.
Thus, valid soil and roadbed temperature forecasts must be based on software that allows you to
carry out 3D analyses of soil thermal fields, taking into account the above factors. Frost 3D
Universal is the most convenient tool for such purposes.
An example 3D road section thermal analysis in Frost 3D Universal
For our computation, we model a 1.3 km road section located in the upper horizon of permafrost
soil.
The three-dimensional geometry of the geotechnical soil structure is reconstructed using geological
data interpolation to form the 3D geometry of the embankment, an insulation layer and concrete
slabs; all designed natively in the software with special tools for geometric constructions. The
computational domain encompasses an area of 1000x300x90 meters.
3D model of a road and geological structure of the soil in an area with complex terrain
Zoom of the 3D model
Roadway design and soils in a cross-section of the computational domain
Boundary conditions are set on the borders of the 3D geometry and the conditions regarding heat
exchange with the environment are defined.
The boundary conditions on the 3D hydrogeological model of the road section
In order to consider convective heat exchange with the atmosphere, third-type boundary conditions
at the soil/road boundary are set. Air temperature (Tв) is set as a periodic dependency on time over
an interval of 1 year:
Month I II III IV V VI VII VIII IX X XI XII
Air temperature, o
C -26.4 -26.4 -19.2 -10.3 -2.6 8.4 15.4 11.3 5.2 -6.3 -18.2 -24
The software bases convective heat transfer coefficient (αв) calculations on average wind speeds,
which in our example are given in the following table:
Month I II III IV V VI VII VIII IX X XI XII
Wind speed, m/s 2.3 2.3 2.6 3.2 3.2 3.4 3.1 2.6 2.7 2.8 2.4 2.4
To account for the influence of snow cover on heat transfer from soil to the atmosphere, the
following snow cover thickness dynamics are set:
Month I II III IV V VI VII VIII IX X XI XII
Snow cover thickness, m 0.47 0.49 0.51 0.47 0.16 0 0 0 0 0.18 0.25 0.38
The calculation assumes that there is no snow cover on the road surface. To consider heating by
solar radiation, the following radiation increment is set:
Month I II III IV V VI VII VIII IX X XI XII
Solar radiation, W/m2
1.9 21.2 84.1 157.8 247.7 310.6 296.3 205.6 121.9 39.4 9.3 1.9
For soil, albedo A is assumed to be 0.75; for a reinforced concrete slab, A = 0.2.
Surface infrared radiation is factored in via the Stefan – Boltzmann law, with the coefficient of
surface emissivity ε taken as 0.9, and the fraction of surface infrared radiation reflected by the
atmosphere back to the Earth’s surface, p = 0.9.
On the lower boundary, the first-type boundary condition is set: the temperature of the permafrost
soil, which is equal to -1.5 o
C.
On the lateral boundary of the computational domain, heat flow is equal to zero.
For construction materials (reinforced concrete slab and «penoplex» insulation material), the
following thermophysical properties are set:
Parameters
Material short text
Reinforced concrete
slab
Heat insulation
Volumetric heat capacity of material, kJ/(m3
∙о
С) 2500 62.1
Heat conductivity, W/(m∙о
С) 1.5 0.031
Total gravimetric moisture, % 0.0001 0
Density, Kg/m3
2500 45
Phase transition temperature, о
С 0 0
Filtration coefficient, µm/s 0.001 0.0000001
Thermophysical properties of some geological layers:
Parameters
Material short text
EmbankmentLayer 1 Layer 2 Layer 4
Layer
11
Layer
14
Volumetric heat capacity of
thawed ground, kJ/(m3
∙о
С)
2480 4000 3170 2310 2390 2160
Volumetric heat capacity of
frozen ground, kJ/(m3
∙о
С)
1890 2310 2410 2140 2080 1800
Heat conductivity of thawed
ground, W/(m∙о
С)
1.57 0.81 1.57 1.62 2.0 1.54
Heat conductivity of frozen
ground, W/(m∙о
С)
1.86 1.34 1.8 1.74 2.2 1.62
Total gravimetric soil moisture, % 0.2 3.47 0.29 0.18 0.21 0.21
Density of dry soil, Kg/m3
1400 80 1450 1710 1630 1550
Phase transition temperature, о
С 0 0 -0.31 -0.38 -0.32 0
Filtration coefficient, µm/s 0.01 0.01 0.01 10 10 10
The dependence of unfrozen water content on temperature is given for each soil type in compliance
with SNIP 2.02.04-88 «Bases and Foundations on Permafrost Soils».
To solve the heat-filtration equation numerically, the 3D geometry is discretized on the
computational mesh consisting of 45.27 million nodes.
3D model computational mesh of the road on permafrost
Computational mesh with decorations of trees and houses
Soil thermal regime forecast can be developed in Frost 3D Universal for any simulation period. Let’s
conduct the forecast of soil temperature regime and roadbed for a 3-year period.
As a result of the model computation, we obtain the temperature distribution over different points in
time.
The temperature distribution (o
C) in the second layer of the ground in the winter after 2.5 years. Top
layer of soil (Layer 1) is disabled
The temperature distribution in the second layer of the ground in summer after 3 years
The temperature distribution on the surface of the ground and the road in the summer after 3 years
The analysis of temperature field dynamics may be performed in a cross-section of the
computational domain. The heat distribution in the cross-section may be performed in the form of
isolines in addition to color filling. Asymmetrical distribution of temperature isolines is caused by
convective heat transfer due to filtration.
The temperature distribution in the cross section of computational domain (winter after 2 years)
The temperature distribution in the form of isolines in the computational domain cross section (winter
after 2 years)
The temperature distribution in the summer after 2 years in the cross section of the computational
domain
The next figure shows that ground located directly beneath the roadbed is thawing up to the
embankment basement (see isoline 0 o
C position).
The temperature distribution in the cross section of the computational domain in isolines (summer
after 2 years)
A more accurate analysis of the soil thaw depth can be performed in the unfrozen water content
view in the program postprocessor.
Relative unfrozen water content distribution (ratio of the unfrozen water content to the total
gravimetric soil moisture: Ww/Wtot) during summer after 2 years
Since the value of the total gravimetric soil moisture (Wtot), is known for each soil type, in order to
more accurately represent fully thawed sections, the resulting distribution of unfrozen water content
is derived as the ratio of unfrozen water to the total gravimetric soil moisture: Ww/ Wtot(for thawing
soil, the unfrozen water content Ww is almost equal to the total gravimetric soil moisture Wtot). The
unfrozen water content distribution is hence expressed in the range from zero to one, where one
represents fully thawed soil as the unfrozen water content is equal to total gravimetric soil moisture.
When soil temperatures is below the initial temperature of the phase transition, the value of the
unfrozen water content decreases, and the ratio Ww/Wtot tends towards zero. However, according to
the dependence of unfrozen water content on temperature established by SNIP 2.02.04-88 «Bases
and Foundations on Permafrost Soils», only sand can have zero unfrozen water when temperatures
are below zero degrees Celsius. For other soils at negative temperatures, there is always some
nonzero quantity of unfrozen water. Distribution analysis of the relative unfrozen water content is
more conveniently performed on the cross-section of the computational domain.
Relative unfrozen water content distribution after 2 years in summer (computational domain cross
section)
In Frost 3D Universal, the groundwater flow process is simulated based on the Darcy differential
equation. For groundwater filtration simulation, the corresponding hydraulic head levels (from 40 to
100 m above sea level) are specified on the side boundaries of the computational domain. For a
«headless» ground layer, the value of the hydraulic head is equal to the groundwater level. When
considering seasonal changes in groundwater filtration, the value of the hydraulic head on the
boundaries is set as a time dependency (e.g., a specific value for each month).
The resulting groundwater filtration velocity simulations in winter and summer in the x-axis direction
are shown below.
Filtration velocity along x-axis (micrometers per second) in winter after 2 years
Filtration velocity along x-axis (micrometers per second) in summer after 2 years
The different values of groundwater filtration velocity in summer and winter are due to the filtration
coefficient value decrease with soil freezing. Since there is a certain amount of unfrozen water
content in some soils at negative temperature, the filtration coefficient for these is nonzero at
temperatures below 0 °C.
When the filtration coefficient of top layers changes from 0.01 to 50 µm/s, the groundwater filtration
velocity increases.
Filtration velocity along x-axis (micrometers per second) for larger filtration coefficient in summer
after 2 years
When the groundwater flow rate increases due to convective heat transfer, a large thaw depth is
formed beneath the road.
The temperature distribution (o
C) in the cross section of the computational domain for increased
filtration velocity (summer after 2 years)
Relative unfrozen water content distribution after 2 years in summer for increased filtration velocity
(computational domain cross section)
You will be also interested in:
Thermosyphon Technology for Ground Freezing
Computer Simulation of Artificial Ground Freezing
Simulation of Groundwater Flow in Saturated Soil

More Related Content

What's hot

UECT_2014_Poster_Leverett
UECT_2014_Poster_LeverettUECT_2014_Poster_Leverett
UECT_2014_Poster_LeverettMehmet Ender
 
Groundwater Modelling Application for Waterworks
Groundwater Modelling Application for WaterworksGroundwater Modelling Application for Waterworks
Groundwater Modelling Application for WaterworksTapesh Ajmera
 
JIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperJIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperAhmed Sohail Izhar
 
Atlantic multidecadal overterning cirrulation presentation
Atlantic multidecadal overterning cirrulation presentationAtlantic multidecadal overterning cirrulation presentation
Atlantic multidecadal overterning cirrulation presentationShubham Pachpor
 
Gt2008 51300-final-paper
Gt2008 51300-final-paperGt2008 51300-final-paper
Gt2008 51300-final-paperssusercf6d0e
 
1.1 power plant module1 batch3
1.1 power plant module1 batch31.1 power plant module1 batch3
1.1 power plant module1 batch3daisydhei
 
1 s2.0-s0306261910005465-main
1 s2.0-s0306261910005465-main1 s2.0-s0306261910005465-main
1 s2.0-s0306261910005465-mainLuis Calderon
 
Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...
Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...
Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...Agriculture Journal IJOEAR
 
Air Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat ExchangerAir Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat ExchangerIOSR Journals
 
IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...
IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...
IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...IRJET Journal
 
Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...
Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...
Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...InfoAndina CONDESAN
 
StreamFlow Variability of 21 Watersheds, Oregon
StreamFlow Variability of 21 Watersheds, OregonStreamFlow Variability of 21 Watersheds, Oregon
StreamFlow Variability of 21 Watersheds, OregonDonnych Diaz
 

What's hot (15)

UECT_2014_Poster_Leverett
UECT_2014_Poster_LeverettUECT_2014_Poster_Leverett
UECT_2014_Poster_Leverett
 
PAPER2
PAPER2PAPER2
PAPER2
 
Groundwater Modelling Application for Waterworks
Groundwater Modelling Application for WaterworksGroundwater Modelling Application for Waterworks
Groundwater Modelling Application for Waterworks
 
JIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperJIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference Paper
 
Atlantic multidecadal overterning cirrulation presentation
Atlantic multidecadal overterning cirrulation presentationAtlantic multidecadal overterning cirrulation presentation
Atlantic multidecadal overterning cirrulation presentation
 
Gt2008 51300-final-paper
Gt2008 51300-final-paperGt2008 51300-final-paper
Gt2008 51300-final-paper
 
1.1 power plant module1 batch3
1.1 power plant module1 batch31.1 power plant module1 batch3
1.1 power plant module1 batch3
 
1 s2.0-s0306261910005465-main
1 s2.0-s0306261910005465-main1 s2.0-s0306261910005465-main
1 s2.0-s0306261910005465-main
 
Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...
Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...
Simulated versus Satellite Retrieval Distribution Patterns of the Snow Water ...
 
Air Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat ExchangerAir Conditioning System with Ground Source Heat Exchanger
Air Conditioning System with Ground Source Heat Exchanger
 
IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...
IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...
IRJET- Numerical Investigation of Heat Transfer Enhancement in Circular Pipe ...
 
E351923
E351923E351923
E351923
 
Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...
Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...
Applications and Limitations of Sustaining a Cost-Effective Embedded Sensor N...
 
30120140503007
3012014050300730120140503007
30120140503007
 
StreamFlow Variability of 21 Watersheds, Oregon
StreamFlow Variability of 21 Watersheds, OregonStreamFlow Variability of 21 Watersheds, Oregon
StreamFlow Variability of 21 Watersheds, Oregon
 

Viewers also liked (7)

Final Presentation
Final Presentation Final Presentation
Final Presentation
 
11. periglaciation areas
11. periglaciation areas11. periglaciation areas
11. periglaciation areas
 
Permafrost
PermafrostPermafrost
Permafrost
 
Periglaciation
PeriglaciationPeriglaciation
Periglaciation
 
What are periglacial processes?
What are periglacial processes?What are periglacial processes?
What are periglacial processes?
 
13. landforms
13. landforms13. landforms
13. landforms
 
Construction equipments
Construction equipmentsConstruction equipments
Construction equipments
 

Similar to Thermal analysis of a road on permafrost

Prediction of ground thaw formations around an oil well
Prediction of ground thaw formations around an oil wellPrediction of ground thaw formations around an oil well
Prediction of ground thaw formations around an oil wellNikolai F.
 
The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...
The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...
The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...IDES Editor
 
Methods for assessment of a cooling tower plume size
Methods for assessment of a cooling tower plume sizeMethods for assessment of a cooling tower plume size
Methods for assessment of a cooling tower plume sizeIJERA Editor
 
Sachpazis: Geomorphological investigation of the drainage networks and calcul...
Sachpazis: Geomorphological investigation of the drainage networks and calcul...Sachpazis: Geomorphological investigation of the drainage networks and calcul...
Sachpazis: Geomorphological investigation of the drainage networks and calcul...Dr.Costas Sachpazis
 
Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses
 Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses  Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses
Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses BREEZE Software
 
SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...
SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...
SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...IAEME Publication
 
The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...
The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...
The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...AI Publications
 
Micro cold traps on the Moon
Micro cold traps on the MoonMicro cold traps on the Moon
Micro cold traps on the MoonSérgio Sacani
 
Quantifying the Stability of Summer Temperatures for Different Thermal Climat...
Quantifying the Stability of Summer Temperatures for Different Thermal Climat...Quantifying the Stability of Summer Temperatures for Different Thermal Climat...
Quantifying the Stability of Summer Temperatures for Different Thermal Climat...Manat Srivanit
 
Numerical Analysis of Inverted Notched Fin Array Using Natural Convection
Numerical Analysis of Inverted Notched Fin Array Using Natural ConvectionNumerical Analysis of Inverted Notched Fin Array Using Natural Convection
Numerical Analysis of Inverted Notched Fin Array Using Natural ConvectionIOSR Journals
 
Geothermal Heat Exchenger
Geothermal Heat ExchengerGeothermal Heat Exchenger
Geothermal Heat ExchengerRaji Panicker
 
EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...
EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...
EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...Barhm Mohamad
 
Icuc2
Icuc2Icuc2
Icuc2epfl
 
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...IAEME Publication
 
forced convection heat transfer chapter 3.ppt
forced convection heat transfer chapter 3.pptforced convection heat transfer chapter 3.ppt
forced convection heat transfer chapter 3.pptAmentiDEmiru
 
1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.ppt1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.pptRasakumar Raj
 
1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.ppt1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.pptlakshmi sirisha
 
Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...
Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...
Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...IJSRED
 

Similar to Thermal analysis of a road on permafrost (20)

Prediction of ground thaw formations around an oil well
Prediction of ground thaw formations around an oil wellPrediction of ground thaw formations around an oil well
Prediction of ground thaw formations around an oil well
 
The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...
The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...
The Effect of Climatic Conditions of Various Regions of Iran on Pavement Fati...
 
Methods for assessment of a cooling tower plume size
Methods for assessment of a cooling tower plume sizeMethods for assessment of a cooling tower plume size
Methods for assessment of a cooling tower plume size
 
Sachpazis: Geomorphological investigation of the drainage networks and calcul...
Sachpazis: Geomorphological investigation of the drainage networks and calcul...Sachpazis: Geomorphological investigation of the drainage networks and calcul...
Sachpazis: Geomorphological investigation of the drainage networks and calcul...
 
Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses
 Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses  Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses
Utilizing CALPUFF for Offshore and Nearshore Dispersion Modeling Analyses
 
SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...
SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...
SIMULATION OF VAPOR AND HEAT FLUXES OVER WET AND DRY REGIME IN PADDY FIELD EN...
 
The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...
The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...
The Effects of Nanofluids on Forced Convection Heat Transfer Inside Parallel ...
 
Micro cold traps on the Moon
Micro cold traps on the MoonMicro cold traps on the Moon
Micro cold traps on the Moon
 
Quantifying the Stability of Summer Temperatures for Different Thermal Climat...
Quantifying the Stability of Summer Temperatures for Different Thermal Climat...Quantifying the Stability of Summer Temperatures for Different Thermal Climat...
Quantifying the Stability of Summer Temperatures for Different Thermal Climat...
 
Numerical Analysis of Inverted Notched Fin Array Using Natural Convection
Numerical Analysis of Inverted Notched Fin Array Using Natural ConvectionNumerical Analysis of Inverted Notched Fin Array Using Natural Convection
Numerical Analysis of Inverted Notched Fin Array Using Natural Convection
 
Geothermal Heat Exchenger
Geothermal Heat ExchengerGeothermal Heat Exchenger
Geothermal Heat Exchenger
 
EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...
EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...
EXPERIMENTAL AND NUMERICAL INVESTIGATIONS OF A TURBULENT BOUNDARY LAYER UNDER...
 
Icuc2
Icuc2Icuc2
Icuc2
 
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
STUDY OF HEAT TRANSFER ON BROKEN ARC ROUGHNESS ELEMENTS ON THE ABSORBER PLATE...
 
X10709 (me8693)
X10709 (me8693)X10709 (me8693)
X10709 (me8693)
 
forced convection heat transfer chapter 3.ppt
forced convection heat transfer chapter 3.pptforced convection heat transfer chapter 3.ppt
forced convection heat transfer chapter 3.ppt
 
1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.ppt1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.ppt
 
1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.ppt1.Solar-Radiation.Energy.Temp-09.ppt
1.Solar-Radiation.Energy.Temp-09.ppt
 
ThermoFluid Final 2
ThermoFluid Final 2ThermoFluid Final 2
ThermoFluid Final 2
 
Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...
Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...
Extinction of Millimeter wave on Two Dimensional Slices of Foam-Covered Sea-s...
 

More from Nikolai F.

Agile Manifesto Values
Agile Manifesto ValuesAgile Manifesto Values
Agile Manifesto ValuesNikolai F.
 
Thermal Analysis of a Road on Permafrost
Thermal Analysis of a Road on PermafrostThermal Analysis of a Road on Permafrost
Thermal Analysis of a Road on PermafrostNikolai F.
 
Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...
Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...
Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...Nikolai F.
 
Моделирование искусственного замораживания грунта при строительстве тоннеля
Моделирование искусственного замораживания грунта при строительстве тоннеляМоделирование искусственного замораживания грунта при строительстве тоннеля
Моделирование искусственного замораживания грунта при строительстве тоннеляNikolai F.
 
Теплотехнический расчет трубопровода в условиях вечной мерзлоты
Теплотехнический расчет трубопровода в условиях вечной мерзлотыТеплотехнический расчет трубопровода в условиях вечной мерзлоты
Теплотехнический расчет трубопровода в условиях вечной мерзлотыNikolai F.
 
Моделирование термостабилизации грунта под резервуаром с нефтью
Моделирование термостабилизации грунта под резервуаром с нефтьюМоделирование термостабилизации грунта под резервуаром с нефтью
Моделирование термостабилизации грунта под резервуаром с нефтьюNikolai F.
 
Расчет дороги в вечной мерзлоте
Расчет дороги в вечной мерзлотеРасчет дороги в вечной мерзлоте
Расчет дороги в вечной мерзлотеNikolai F.
 
Прогноз оттаивания грунта вокруг нефтегазовых скважин
Прогноз оттаивания грунта вокруг нефтегазовых скважинПрогноз оттаивания грунта вокруг нефтегазовых скважин
Прогноз оттаивания грунта вокруг нефтегазовых скважинNikolai F.
 
Доклад компании Simmakers - Технология GPGPU в высокопроизводительных вычисл...
Доклад компании Simmakers  - Технология GPGPU в высокопроизводительных вычисл...Доклад компании Simmakers  - Технология GPGPU в высокопроизводительных вычисл...
Доклад компании Simmakers - Технология GPGPU в высокопроизводительных вычисл...Nikolai F.
 

More from Nikolai F. (9)

Agile Manifesto Values
Agile Manifesto ValuesAgile Manifesto Values
Agile Manifesto Values
 
Thermal Analysis of a Road on Permafrost
Thermal Analysis of a Road on PermafrostThermal Analysis of a Road on Permafrost
Thermal Analysis of a Road on Permafrost
 
Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...
Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...
Моделирование заморозки грунтов по периметру атомной электростанции «Фукусима...
 
Моделирование искусственного замораживания грунта при строительстве тоннеля
Моделирование искусственного замораживания грунта при строительстве тоннеляМоделирование искусственного замораживания грунта при строительстве тоннеля
Моделирование искусственного замораживания грунта при строительстве тоннеля
 
Теплотехнический расчет трубопровода в условиях вечной мерзлоты
Теплотехнический расчет трубопровода в условиях вечной мерзлотыТеплотехнический расчет трубопровода в условиях вечной мерзлоты
Теплотехнический расчет трубопровода в условиях вечной мерзлоты
 
Моделирование термостабилизации грунта под резервуаром с нефтью
Моделирование термостабилизации грунта под резервуаром с нефтьюМоделирование термостабилизации грунта под резервуаром с нефтью
Моделирование термостабилизации грунта под резервуаром с нефтью
 
Расчет дороги в вечной мерзлоте
Расчет дороги в вечной мерзлотеРасчет дороги в вечной мерзлоте
Расчет дороги в вечной мерзлоте
 
Прогноз оттаивания грунта вокруг нефтегазовых скважин
Прогноз оттаивания грунта вокруг нефтегазовых скважинПрогноз оттаивания грунта вокруг нефтегазовых скважин
Прогноз оттаивания грунта вокруг нефтегазовых скважин
 
Доклад компании Simmakers - Технология GPGPU в высокопроизводительных вычисл...
Доклад компании Simmakers  - Технология GPGPU в высокопроизводительных вычисл...Доклад компании Simmakers  - Технология GPGPU в высокопроизводительных вычисл...
Доклад компании Simmakers - Технология GPGPU в высокопроизводительных вычисл...
 

Recently uploaded

Low Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service Bikaner
Low Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service BikanerLow Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service Bikaner
Low Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service BikanerSuhani Kapoor
 
The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...ranjana rawat
 
Call Girls South Delhi Delhi reach out to us at ☎ 9711199012
Call Girls South Delhi Delhi reach out to us at ☎ 9711199012Call Girls South Delhi Delhi reach out to us at ☎ 9711199012
Call Girls South Delhi Delhi reach out to us at ☎ 9711199012sapnasaifi408
 
(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Service
(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Service(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Service
(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Freegle User Survey as visual display - BH
Freegle User Survey as visual display - BHFreegle User Survey as visual display - BH
Freegle User Survey as visual display - BHbill846304
 
VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...
VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...
VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...Suhani Kapoor
 
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...Call Girls in Nagpur High Profile
 
VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130
VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130
VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130Suhani Kapoor
 
(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Service
(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Service(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Service
(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Call Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance Bookingtanu pandey
 
VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130
VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130
VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130Suhani Kapoor
 
VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...
VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...
VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...Suhani Kapoor
 
(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Service(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Service
(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Service(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Service
(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...
NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...
NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...Amil baba
 
(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

Low Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service Bikaner
Low Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service BikanerLow Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service Bikaner
Low Rate Call Girls Bikaner Anika 8250192130 Independent Escort Service Bikaner
 
The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Shirwal 8250192130 Will You Miss This Cha...
 
Call Girls South Delhi Delhi reach out to us at ☎ 9711199012
Call Girls South Delhi Delhi reach out to us at ☎ 9711199012Call Girls South Delhi Delhi reach out to us at ☎ 9711199012
Call Girls South Delhi Delhi reach out to us at ☎ 9711199012
 
(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Service
(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Service(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Service
(DIYA) Call Girls Sinhagad Road ( 7001035870 ) HI-Fi Pune Escorts Service
 
Freegle User Survey as visual display - BH
Freegle User Survey as visual display - BHFreegle User Survey as visual display - BH
Freegle User Survey as visual display - BH
 
VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...
VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...
VIP Call Girls Moti Ganpur ( Hyderabad ) Phone 8250192130 | ₹5k To 25k With R...
 
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
 
Sustainable Packaging
Sustainable PackagingSustainable Packaging
Sustainable Packaging
 
VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130
VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130
VIP Call Girls Service Tolichowki Hyderabad Call +91-8250192130
 
(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Service
(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Service(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Service
(ZARA) Call Girls Talegaon Dabhade ( 7001035870 ) HI-Fi Pune Escorts Service
 
Call Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Pune Airport Call Me 7737669865 Budget Friendly No Advance Booking
 
young Whatsapp Call Girls in Delhi Cantt🔝 9953056974 🔝 escort service
young Whatsapp Call Girls in Delhi Cantt🔝 9953056974 🔝 escort serviceyoung Whatsapp Call Girls in Delhi Cantt🔝 9953056974 🔝 escort service
young Whatsapp Call Girls in Delhi Cantt🔝 9953056974 🔝 escort service
 
VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130
VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130
VIP Call Girls Service Bandlaguda Hyderabad Call +91-8250192130
 
VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...
VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...
VIP Call Girls Mahadevpur Colony ( Hyderabad ) Phone 8250192130 | ₹5k To 25k ...
 
(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Service(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Service
(ANIKA) Call Girls Wagholi ( 7001035870 ) HI-Fi Pune Escorts Service
 
(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Service
(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Service(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Service
(ANAYA) Call Girls Hadapsar ( 7001035870 ) HI-Fi Pune Escorts Service
 
NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...
NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...
NO1 Verified kala jadu karne wale ka contact number kala jadu karne wale baba...
 
(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(RIYA) Kalyani Nagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Model Call Girl in Rajiv Chowk Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Rajiv Chowk Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Rajiv Chowk Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Rajiv Chowk Delhi reach out to us at 🔝9953056974🔝
 
Green Marketing
Green MarketingGreen Marketing
Green Marketing
 

Thermal analysis of a road on permafrost

  • 1. Thermal Analysis of a Road on Permafrost Source: http://simmakers.com/road-on-permafrost/ (Keywords: thermal analysis of a road on permafrost, thermal analysis of a road, simulation of a road in permafrost area, thermal analysis of roadbed, thermal analysis of road surface) Road maintenance in permafrost areas is connected with the problem of ensuring soil stability. Roadbed deformations are the result of settlement and heave due to the respective thawing and freezing of underlying moist permafrost soils. These processes cause large amounts of damage on road surfaces. It is therefore important to pay particular attention to the thermal analysis of soil bases and roadbeds at the design stage to determine the road characteristics such as embankment height, thermal insulation layer thickness, and so on. Simple 2D thermal analysis cannot account for the changes in terrain and geological structure of the soil throughout the simulated road segment and proper temperature distribution analysis also requires consideration of the influence of solar radiation, road thermal radiation and convective heat transfer due to groundwater filtration. Thus, valid soil and roadbed temperature forecasts must be based on software that allows you to carry out 3D analyses of soil thermal fields, taking into account the above factors. Frost 3D Universal is the most convenient tool for such purposes. An example 3D road section thermal analysis in Frost 3D Universal For our computation, we model a 1.3 km road section located in the upper horizon of permafrost soil. The three-dimensional geometry of the geotechnical soil structure is reconstructed using geological data interpolation to form the 3D geometry of the embankment, an insulation layer and concrete slabs; all designed natively in the software with special tools for geometric constructions. The computational domain encompasses an area of 1000x300x90 meters. 3D model of a road and geological structure of the soil in an area with complex terrain
  • 2. Zoom of the 3D model Roadway design and soils in a cross-section of the computational domain Boundary conditions are set on the borders of the 3D geometry and the conditions regarding heat exchange with the environment are defined.
  • 3. The boundary conditions on the 3D hydrogeological model of the road section In order to consider convective heat exchange with the atmosphere, third-type boundary conditions at the soil/road boundary are set. Air temperature (Tв) is set as a periodic dependency on time over an interval of 1 year: Month I II III IV V VI VII VIII IX X XI XII Air temperature, o C -26.4 -26.4 -19.2 -10.3 -2.6 8.4 15.4 11.3 5.2 -6.3 -18.2 -24 The software bases convective heat transfer coefficient (αв) calculations on average wind speeds, which in our example are given in the following table: Month I II III IV V VI VII VIII IX X XI XII Wind speed, m/s 2.3 2.3 2.6 3.2 3.2 3.4 3.1 2.6 2.7 2.8 2.4 2.4 To account for the influence of snow cover on heat transfer from soil to the atmosphere, the following snow cover thickness dynamics are set: Month I II III IV V VI VII VIII IX X XI XII Snow cover thickness, m 0.47 0.49 0.51 0.47 0.16 0 0 0 0 0.18 0.25 0.38 The calculation assumes that there is no snow cover on the road surface. To consider heating by solar radiation, the following radiation increment is set: Month I II III IV V VI VII VIII IX X XI XII Solar radiation, W/m2 1.9 21.2 84.1 157.8 247.7 310.6 296.3 205.6 121.9 39.4 9.3 1.9 For soil, albedo A is assumed to be 0.75; for a reinforced concrete slab, A = 0.2. Surface infrared radiation is factored in via the Stefan – Boltzmann law, with the coefficient of surface emissivity ε taken as 0.9, and the fraction of surface infrared radiation reflected by the atmosphere back to the Earth’s surface, p = 0.9. On the lower boundary, the first-type boundary condition is set: the temperature of the permafrost soil, which is equal to -1.5 o C. On the lateral boundary of the computational domain, heat flow is equal to zero.
  • 4. For construction materials (reinforced concrete slab and «penoplex» insulation material), the following thermophysical properties are set: Parameters Material short text Reinforced concrete slab Heat insulation Volumetric heat capacity of material, kJ/(m3 ∙о С) 2500 62.1 Heat conductivity, W/(m∙о С) 1.5 0.031 Total gravimetric moisture, % 0.0001 0 Density, Kg/m3 2500 45 Phase transition temperature, о С 0 0 Filtration coefficient, µm/s 0.001 0.0000001 Thermophysical properties of some geological layers: Parameters Material short text EmbankmentLayer 1 Layer 2 Layer 4 Layer 11 Layer 14 Volumetric heat capacity of thawed ground, kJ/(m3 ∙о С) 2480 4000 3170 2310 2390 2160 Volumetric heat capacity of frozen ground, kJ/(m3 ∙о С) 1890 2310 2410 2140 2080 1800 Heat conductivity of thawed ground, W/(m∙о С) 1.57 0.81 1.57 1.62 2.0 1.54 Heat conductivity of frozen ground, W/(m∙о С) 1.86 1.34 1.8 1.74 2.2 1.62 Total gravimetric soil moisture, % 0.2 3.47 0.29 0.18 0.21 0.21 Density of dry soil, Kg/m3 1400 80 1450 1710 1630 1550 Phase transition temperature, о С 0 0 -0.31 -0.38 -0.32 0 Filtration coefficient, µm/s 0.01 0.01 0.01 10 10 10 The dependence of unfrozen water content on temperature is given for each soil type in compliance with SNIP 2.02.04-88 «Bases and Foundations on Permafrost Soils». To solve the heat-filtration equation numerically, the 3D geometry is discretized on the computational mesh consisting of 45.27 million nodes.
  • 5. 3D model computational mesh of the road on permafrost Computational mesh with decorations of trees and houses Soil thermal regime forecast can be developed in Frost 3D Universal for any simulation period. Let’s conduct the forecast of soil temperature regime and roadbed for a 3-year period. As a result of the model computation, we obtain the temperature distribution over different points in time.
  • 6. The temperature distribution (o C) in the second layer of the ground in the winter after 2.5 years. Top layer of soil (Layer 1) is disabled The temperature distribution in the second layer of the ground in summer after 3 years
  • 7. The temperature distribution on the surface of the ground and the road in the summer after 3 years The analysis of temperature field dynamics may be performed in a cross-section of the computational domain. The heat distribution in the cross-section may be performed in the form of isolines in addition to color filling. Asymmetrical distribution of temperature isolines is caused by convective heat transfer due to filtration. The temperature distribution in the cross section of computational domain (winter after 2 years)
  • 8. The temperature distribution in the form of isolines in the computational domain cross section (winter after 2 years) The temperature distribution in the summer after 2 years in the cross section of the computational domain The next figure shows that ground located directly beneath the roadbed is thawing up to the embankment basement (see isoline 0 o C position).
  • 9. The temperature distribution in the cross section of the computational domain in isolines (summer after 2 years) A more accurate analysis of the soil thaw depth can be performed in the unfrozen water content view in the program postprocessor. Relative unfrozen water content distribution (ratio of the unfrozen water content to the total gravimetric soil moisture: Ww/Wtot) during summer after 2 years Since the value of the total gravimetric soil moisture (Wtot), is known for each soil type, in order to more accurately represent fully thawed sections, the resulting distribution of unfrozen water content is derived as the ratio of unfrozen water to the total gravimetric soil moisture: Ww/ Wtot(for thawing soil, the unfrozen water content Ww is almost equal to the total gravimetric soil moisture Wtot). The unfrozen water content distribution is hence expressed in the range from zero to one, where one represents fully thawed soil as the unfrozen water content is equal to total gravimetric soil moisture. When soil temperatures is below the initial temperature of the phase transition, the value of the unfrozen water content decreases, and the ratio Ww/Wtot tends towards zero. However, according to the dependence of unfrozen water content on temperature established by SNIP 2.02.04-88 «Bases and Foundations on Permafrost Soils», only sand can have zero unfrozen water when temperatures are below zero degrees Celsius. For other soils at negative temperatures, there is always some
  • 10. nonzero quantity of unfrozen water. Distribution analysis of the relative unfrozen water content is more conveniently performed on the cross-section of the computational domain. Relative unfrozen water content distribution after 2 years in summer (computational domain cross section) In Frost 3D Universal, the groundwater flow process is simulated based on the Darcy differential equation. For groundwater filtration simulation, the corresponding hydraulic head levels (from 40 to 100 m above sea level) are specified on the side boundaries of the computational domain. For a «headless» ground layer, the value of the hydraulic head is equal to the groundwater level. When considering seasonal changes in groundwater filtration, the value of the hydraulic head on the boundaries is set as a time dependency (e.g., a specific value for each month). The resulting groundwater filtration velocity simulations in winter and summer in the x-axis direction are shown below. Filtration velocity along x-axis (micrometers per second) in winter after 2 years
  • 11. Filtration velocity along x-axis (micrometers per second) in summer after 2 years The different values of groundwater filtration velocity in summer and winter are due to the filtration coefficient value decrease with soil freezing. Since there is a certain amount of unfrozen water content in some soils at negative temperature, the filtration coefficient for these is nonzero at temperatures below 0 °C. When the filtration coefficient of top layers changes from 0.01 to 50 µm/s, the groundwater filtration velocity increases. Filtration velocity along x-axis (micrometers per second) for larger filtration coefficient in summer after 2 years When the groundwater flow rate increases due to convective heat transfer, a large thaw depth is formed beneath the road.
  • 12. The temperature distribution (o C) in the cross section of the computational domain for increased filtration velocity (summer after 2 years) Relative unfrozen water content distribution after 2 years in summer for increased filtration velocity (computational domain cross section) You will be also interested in: Thermosyphon Technology for Ground Freezing Computer Simulation of Artificial Ground Freezing Simulation of Groundwater Flow in Saturated Soil