Current carrying capacity
Single core cables with copper conductor,
PVC 70 ° C Insulated and PVC sheathed, 0.6/1 K V
ﺍﻟﺘﺤﻤﻴﻞ ﺗﻴﺎﺭﺍﺕ ﻗﻴﻢﻟﻜﺒﻼﺕﺑﺎﻟـ ﻣﻌﺰﻭﻟﺔ ﺍﻟﻨﻮﺍﺓ ﺃﺣﺎﺩﻳﺔ ﳓﺎﺳﻴﺔPVC
ﺣﺮﺍﺭﺓ ﺩﺭﺟﺔ70º Cﺑﺎﻟـ ﹼﻔﺔﻠﻭﻣﻐPVC،ﺗﻮﺗﺮ/1 kv٠,٦
8. ٨ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺭﻗﻢ ﺟﺪﻭﻝ)٢(
Current carrying capacity
Three and four core cables with copper conductor,
PVC 70 ° C Insulated and PVC sheathed, 0.6/1 K V
ﺍﻟﺘﺤﻤﻴﻞ ﺗﻴﺎﺭﺍﺕ ﻗﻴﻢﻟﻜﺒﻼﺕﺑﺎﻟـ ﻣﻌﺰﻭﻟﺔ ﺍﻟﻨﻮﺍﺓ ﻭﺭﺑﺎﻋﻴﺔ ﺛﻼﺛﻴﺔ ﳓﺎﺳﻴﺔpvc
ﺣﺮﺍﺭﺓ ﺩﺭﺟﺔ70º Cﺑﺎﻟـ ﹼﻔﺔﻠﻭﻣﻐPVCﺗﻮﺗﺮ ،/1 kv٠٫٦
9. ٩ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺍﳉﺪﻭﻝﺭﻗﻢ(3)
Current carrying capacity
Single core cables with copper conductors,
PVC 85 ° C Insulated and PVC sheathed, 0.6/1 K V
ﻗﻴﻢﺍﻟﺘﺤﻤﻴﻞ ﺗﻴﺎﺭﺍﺕﻟﻜﺒﻼﺕﺑﺎﻟـ ﻣﻌﺰﻭﻟﺔ ﺍﻟﻨﻮﺍﺓ ﺃﺣﺎﺩﻳﺔ ﳓﺎﺳﻴﺔPVC
ﺣﺮﺍﺭﺓ ﺩﺭﺟﺔ85º Cﺑﺎﻟـ ﹼﻔﺔﻠﻭﻣﻐPVC،ﺗﻮﺗﺮ/1 kv٠,٦
10. ١٠ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺍﳉﺪﻭﻝﺭﻗﻢ(4)
Current carrying capacity
Three and four core cables with copper conductors,
PVC 85 ° C Insulated and PVC sheathed, 0.6/1 K V
ﺍﻟﺘﺤﻤﻴﻞ ﺗﻴﺎﺭﺍﺕ ﻗﻴﻢﻟﻜﺒﻼﺕﺑﺎﻟـ ﻣﻌﺰﻭﻟﺔ ﺍﻟﻨﻮﺍﺓ ﻭﺭﺑﺎﻋﻴﺔ ﺛﻼﺛﻴﺔ ﳓﺎﺳﻴﺔPVC
ﺣﺮﺍﺭﺓ ﺩﺭﺟﺔ85º Cﺑﺎﻟـ ﹼﻔﺔﻠﻭﻣﻐPVC،ﺗﻮﺗﺮ/1 kv٠,٦
11. ١١ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺭﻗﻢ ﺍﳉﺪﻭﻝ(5)
Current carrying capacity
Single core cables with copper conductors,
of XLPE Insulated and PVC sheathed, 0.6/1 K V
ﻗﻴﻢﺍﻟﺘﺤﻤﻴﻞ ﺗﻴﺎﺭﺍﺕﻟﻜﺒﻼﺕﺑﺎﻟـ ﻣﻌﺰﻭﻟﺔ ﺍﻟﻨﻮﺍﺓ ﺃﺣﺎﺩﻳﺔ ﳓﺎﺳﻴﺔXLPE
ﺑﺎﻟـ ﻭﻣﻐﻠﻔﺔPVC،ﺗﻮﺗﺮ/1 kv٠,٦
12. ١٢ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺍﳉﺪﻭﻝﺭﻗﻢ(6)
Current carrying capacity
Three and four core cables with copper conductors,
XLPE Insulated and PVC sheathed, 0.6/1 K V
ﻗﻴﻢﺍﻟﺘﺤﻤﻴﻞ ﺗﻴﺎﺭﺍﺕﻟﻜﺒﻼﺕﺑﺎﻟـ ﻣﻌﺰﻭﻟﺔ ﺍﻟﻨﻮﺍﺓ ﻭﺭﺑﺎﻋﻴﺔ ﺛﻼﺛﻴﺔ ﳓﺎﺳﻴﺔXLPE
ﺑﺎﻟـ ﻭﻣﻐﻠﻔﺔPVC،ﺗﻮﺗﺮ/1 kv٠,٦
13. ١٣ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺍﳉﺪﻭﻝﺭﻗﻢ(7)
Cables laid direct in ground
Rating factors for variation in ground temperature
ﺍﻟﺘﺮﺑﺔ ﺣﺮﺍﺭﺓ ﺩﺭﺟﺔ ﺍﺧﺘﻼﻑ ﻋﻨﺪ ﺍﻟﺘﺼﺤﻴﺢ ﻋﺎﻣﻞ
ﻟﻜﺒﻼﺕﺍﻟﺘﺮﺑﺔ ﰲ ﻣﺒﺎﺷﺮﺓ ﻣﻨﻔﺬﺓ
ﺍﳉﺪﻭﻝﺭﻗﻢ(8)
Cables laid direct in ground
Rating factors for variation in depth of burial
(to centre of cable in the trefoil group of cables)
ﻋﻦ ﺍﻟﺘﺮﺑﺔ ﰲ ﺍﻟﻜﺒﻞ ﻋﻤﻖ ﺍﺯﺩﻳﺎﺩ ﻟﺪﻯ ﺍﻟﺘﺼﺤﻴﺢ ﻋﺎﻣﻞ0.5m
)ﺠﻤﻟﻤﻮﻋﺔ ﺍﻟﻜﺒﻞ ﻣﺮﻛﺰ ﺇﱃ ﺍﻟﻘﻴﺎﺱ ﳚﺮﻱﻛﺒﻼﺕﺷﻜﻞ ﻋﻠﻰ(
14. ١٤ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺍﳉﺪﻭﻝﺭﻗﻢ(9)
Cables laid direct in ground
Rating factors for variation in thermal resitivity of soil (average values)
ﻟﻠﺘﺮﺑﺔ ﺍﻟﻨﻮﻋﻴﺔ ﺍﳌﻘﺎﻭﻣﺔ ﺍﺧﺘﻼﻑ ﻋﻨﺪ ﺍﻟﺘﺼﺤﻴﺢ ﺟﺪﻭﻝ
ﺍﳉﺪﻭﻝﺭﻗﻢ(11)
Cables installed in air
Group rating factors for multicore cables in flat formation
ﺗﻨﻔﻴﺬ ﻋﻨﺪ ﺍﻟﺘﺼﺤﻴﺢ ﺟﺪﻭﻝﻛﺒﻼﺕﺍﳍﻮﺍﺀ ﰲ ﻣﺘﺠﺎﻭﺭﺓ ﺍﻟﻨﻮﺍﺓ ﻣﺘﻌﺪﺩﺓFlat
30. ٣٠ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺟﺪﻭﻝ)٢٥(،ﺍﻟﻘﺼﺮ ﺗﻴﺎﺭ ﻋﻨﺪﻫﺎ ﻣﻌﻄﻰ ﻧﻘﻄﺔ ﲢﺖ ﺗﻘﻊ ﻧﻘﻄﺔ ﻋﻨﺪ ﺍﻟﻘﺼﺮ ﺗﻴﺎﺭ ﺣﺴﺎﺏ
ISC at a point downstream, in terms of a known upstream fault-current value and the length and c.s.a.
of the intervening conductors, in 230/400 v 3-phase system.
Note: for a 3-phase system having 230 v between phases, divide the above lengths by √3 = 1.732
33. ٣٣ اﻟﻤﺼﺮي ﺻﺒﺤﻲ ﻣﺤﻤﺪ
آﻬﺮﺏﺎﺋﻴﺔ ﻋﻠﻮم هﻨﺪﺳﺔ ﻣﺎﺟﺴﺘﻴﺮ
00963 94 571281
ﺍﻟﻜ ﺍﳊﺴﺎﺑﺎﺕ ﰲ ﺍﳌﺴﺘﺨﺪﻣﺔ ﺍﻷﺳﺎﺳﻴﺔ ﺍﻟﻌﻼﻗﺎﺕ ﻷﻫﻢ ﻣﻠﺨﺺ ﻳﻠﻲ ﻭﻓﻴﻤﺎﳐﺘﻠﻔﺔ ﺗﻮﺗﺮﺍﺕ ﻋﻨﺪ ﻬﺮﺑﺎﺋﻴﺔ:
* I= P/ UL cos ϕ for 2 phases
S : The apparent power measured by [kVA]
P : The active power measured by [kW]
ρ : The resistivity measured by [Ω.mm2
/m] = 1/54 for Copper, 1/34 for Aluminum at 20o
C
L : Length of conductor [m]
s : conductor cross section [mm2
]
∆V: Voltage drop [V] also = r.L.I/1000 for single phase,
=√٣.r.L.I/1000 for three phase = 9.5 v for 2.5%
r : approx. cable resistance [Ω/km]
ε %: Percentage of a voltage drop. 3% max for lighting load, 6% max for power load
UL : Line voltage; phase to phase voltage [V]
Uph: Phase to neutral voltage [V]
cos ϕ : power factor = 0.8
I : Load current [A]