Air System Sizing Summary for syst1
Project Name: salma 06/07/2022
Prepared by: ADIL DAHMANI 12:56
Air System Information
Air System Name: syst1
Air System Type: Single Zone CAV
Number of zones: 1
Floor Area: 355,2 sqm
Location: Casablanca, Morocco
Sizing Calculation Information
Calculation Months: Jan to Dec Calculation method: Transfer Function Method
Central Cooling Coil Sizing Data
Total coil load: 37,2 kW
Total coil load: 37,2 kW
Sensible coil load: 30,0 kW
Coil airflow: 3302 L/s
Sensible heat ratio: 0,808
Area per unit load: 9,6 sqm/kW
Load per unit area: 104,6 W/sqm
Load occurs at: Aug 1800
OA DB / WB: 28,4/21,9
Entering DB / WB: 22,7/18,2
Leaving DB / WB: 15,1/14,9
Coil ADP: 14,7 C
Bypass Factor: 0,050
Resulting RH: 66 %
Design supply temp: 15,0 C
Central Heating Coil Sizing Data
Max coil load: 26,5 kW
Coil airflow: 3302 L/s
Load per unit area: 74,7 W/sqm
Load occurs at: Des Htg
Ent DB / Lvg DB: 18,3/25,0
Supply Fan Sizing Data
Actual max airflow: 3302 L/s
Standard airflow: 3278 L/s
Actual max airflow per unit area: 9,30 L/(s-sqm)
Fan motor BHP: 0,00 BHP
Fan motor kW: 0,00 kW
Fan static: 0,00 Pa
Outdoor Ventilation Air Data
Design airflow: 321 L/s
Airflow per unit floor area: 0,90 L/(s-sqm)
Airflow per person: 4,46 L/s/person
Space Sizing Data
Space Name Maximum
Cooling
Sensible kW
Design
Airflow
L/s
Time of Peak
Load
Maximum
Heating
Load kW
Space
Floor
Area
sqm
Space
L/(s-sqm)
Arriere comptoir RDC 1,6 210 Aug 1800 1,6 20,6 10,17
Arrière comptoir RDC 1,6 189 Jul 2000 1,4 22,2 8,51
Bureau adjoint RDC 1,8 218 Aug 1700 1,2 17,4 12,53
Bureau certificats RDC 2,9 349 Jul 1800 1,8 37,9 9,20
Bureau conservateur RDC 2,5 298 Aug 1600 2,1 31,7 9,40
Bureau d ordre RDC 1,1 126 Jul 1900 0,8 10,2 12,30
Bureau RDC 1,9 227 Jul 1700 1,3 24,6 9,25
BureauChefGestArchiveRDC 2,3 268 Jul 2000 1,6 31,6 8,49
Caisse cf RDC 1,6 186 Jul 2000 1,1 16,7 11,12
Caisse sc RDC 0,5 82 Jul 1900 0,6 9,1 9,03
Chef servicecadastre RDC 2,3 278 Jul 2000 1,8 32,7 8,51
Espace notaires c.f RDC 1,3 155 Aug 1800 1,2 18,4 8,41
Espaceconsgeometres.cRDC 1,3 152 Aug 1800 0,9 12,3 12,38
Local Securite RDC 0,6 104 Jul 1700 0,8 7,2 14,39
Salle Scannarisation RDC 1,8 214 Jul 1800 1,6 26,8 7,99
Secrétariat c.f RDC 1,4 164 Aug 1500 1,1 14,3 11,48
secretariat c.s RDC 1,8 218 Jul 1900 1,3 21,5 10,15
Zone 27,7 3302 Jul 1800 22,3 355,2 9,30
Note: Table contains data for all spaces controlled by a single thermostat:
Space sizing basis: Peak space load
Zone sizing basis: Peak zone load
Block Load 4.15 Page 1 of 3
System Design Load Summary for syst1
Project Name: salma 06/07/2022
Prepared by: ADIL DAHMANI 12:56
DESIGN COOLING DESIGN HEATING
Aug 1800
OA DB / WB 28,4 C / 21,9 C
Design Heating Day
OA DB / WB 5,6 C / 1,8 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 16 sqm 1747 - 16 sqm - -
Wall Transmission 552 sqm 10623 - 552 sqm 11230 -
Roof Transmission 367 sqm 3380 - 367 sqm 2742 -
Window Transmission 16 sqm 318 - 16 sqm 772 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 366 sqm -179 - 366 sqm 110 -
Partitions/Ceilings 325 sqm -860 - 325 sqm 7403 -
Overhead Lighting 7104 W 7104 - 0 W 0 -
Electric Equipment 0 W 0 - 0 W 0 -
People 72 5170 4326 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>>Total Zone Loads - 27303 4326 - 22256 0
Thermostat and Pulldown Adjustment - 313 0 - -1140 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 321 L/s 2422 2804 321 L/s 5416 0
Supply Fan Load 3303 L/s 0 - 3303 L/s 0 -
>> Total System Loads - 30039 7129 - 26531 0
Central Cooling Coil - 30039 7133 - 0 0
Central Heating Coil - 0 - - 26531 -
>> Total Coil Loads - 30039 7133 - 26531 0
Key: Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Block Load 4.15 Page 2 of 3
System Psychrometricsforsyst1
Project Name: salma 06/07/2022
Prepared by: ADIL DAHMANI 12:56
1.OutdoorAir
2.MixedAir
3.CentralCoolingCoilOutlet
4.SupplyFanOutlet
5.RoomAir
1
2
3
4
5
0,000
0,002
0,004
0,006
0,008
0,010
0,012
0,014
0,016
0,018
0,020
0 10 20 30
Location:Casablanca,Morocco
Altitude:61,9m
Datafor:AugDESIGNCOOLINGDAY,1800
Specific
Humidity
(
kg/kg
)
Temperature(C)
Block Load 4.15 Page 3 of 3

More Related Content

Similar to rdc.pdf

DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...
DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...
DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...grssieee
 
Original Mosfet L3705N L3705 3705 55V 75A TO-220 New
Original Mosfet L3705N L3705 3705 55V 75A TO-220 NewOriginal Mosfet L3705N L3705 3705 55V 75A TO-220 New
Original Mosfet L3705N L3705 3705 55V 75A TO-220 NewAUTHELECTRONIC
 
2013 1 arduino_datalogger
2013 1 arduino_datalogger2013 1 arduino_datalogger
2013 1 arduino_dataloggerDon Doerres
 
49700707 t9085-estimate-blank
49700707 t9085-estimate-blank49700707 t9085-estimate-blank
49700707 t9085-estimate-blankimaduddin91
 
Energy transfer and heat load analysis
Energy transfer and heat load analysisEnergy transfer and heat load analysis
Energy transfer and heat load analysisSatwinder Singh
 
Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...
Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...
Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...Stephane Meteodyn
 
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdfBaladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdfAbdulkadirHassanMoha
 
97fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate01
97fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate0197fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate01
97fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate01Vinoth Kanna
 
Chillers selection 640 gpm
Chillers selection 640 gpmChillers selection 640 gpm
Chillers selection 640 gpmJoseAlvitrez1
 
00_Abnormality Report_
00_Abnormality Report_00_Abnormality Report_
00_Abnormality Report_ankit shukla
 
Technical specification EEE
Technical specification EEETechnical specification EEE
Technical specification EEEAmit Kumar
 
1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmeters
1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmeters1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmeters
1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmetersKhang Trang
 
C&I July-2022.pptx
C&I July-2022.pptxC&I July-2022.pptx
C&I July-2022.pptxPowerMurugan
 

Similar to rdc.pdf (20)

DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...
DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...
DEVELOPMENT OF HIGH TEMPERATURE NOISE SOURCE (HTS) FOR ADVANCED MICROWAVE SCA...
 
10004239951
1000423995110004239951
10004239951
 
Ch 03-30 mpw060
Ch 03-30 mpw060Ch 03-30 mpw060
Ch 03-30 mpw060
 
Original Mosfet L3705N L3705 3705 55V 75A TO-220 New
Original Mosfet L3705N L3705 3705 55V 75A TO-220 NewOriginal Mosfet L3705N L3705 3705 55V 75A TO-220 New
Original Mosfet L3705N L3705 3705 55V 75A TO-220 New
 
2013 1 arduino_datalogger
2013 1 arduino_datalogger2013 1 arduino_datalogger
2013 1 arduino_datalogger
 
49700707 t9085-estimate-blank
49700707 t9085-estimate-blank49700707 t9085-estimate-blank
49700707 t9085-estimate-blank
 
Energy transfer and heat load analysis
Energy transfer and heat load analysisEnergy transfer and heat load analysis
Energy transfer and heat load analysis
 
Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...
Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...
Combined CFD-Mean energy balance methode to thermal comfort assessment of bui...
 
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdfBaladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
 
HVAC CAPSULEEMERSON EDUARDO RODRIGUES
HVAC CAPSULEEMERSON EDUARDO RODRIGUESHVAC CAPSULEEMERSON EDUARDO RODRIGUES
HVAC CAPSULEEMERSON EDUARDO RODRIGUES
 
11 mn01 review 2
11 mn01 review 211 mn01 review 2
11 mn01 review 2
 
97fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate01
97fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate0197fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate01
97fd01fe-d033-40ce-964b-f2b030a90d30-150210013729-conversion-gate01
 
Chillers selection 640 gpm
Chillers selection 640 gpmChillers selection 640 gpm
Chillers selection 640 gpm
 
Sn5414 7414
Sn5414 7414Sn5414 7414
Sn5414 7414
 
00_Abnormality Report_
00_Abnormality Report_00_Abnormality Report_
00_Abnormality Report_
 
Technical specification EEE
Technical specification EEETechnical specification EEE
Technical specification EEE
 
1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmeters
1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmeters1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmeters
1. va1 lici-00 eg-i-m4d-das-0001.positive displacement flowmeters
 
12.3 inch Automotive TFT the CDS123WU01
12.3 inch Automotive TFT the CDS123WU0112.3 inch Automotive TFT the CDS123WU01
12.3 inch Automotive TFT the CDS123WU01
 
All hvac calculation
All hvac calculationAll hvac calculation
All hvac calculation
 
C&I July-2022.pptx
C&I July-2022.pptxC&I July-2022.pptx
C&I July-2022.pptx
 

Recently uploaded

Class 11 Legal Studies Ch-1 Concept of State .pdf
Class 11 Legal Studies Ch-1 Concept of State .pdfClass 11 Legal Studies Ch-1 Concept of State .pdf
Class 11 Legal Studies Ch-1 Concept of State .pdfakmcokerachita
 
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTiammrhaywood
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13Steve Thomason
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptxVS Mahajan Coaching Centre
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxpboyjonauth
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityGeoBlogs
 
How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17Celine George
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Celine George
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application ) Sakshi Ghasle
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docxPoojaSen20
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsanshu789521
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting DataJhengPantaleon
 
Employee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxEmployee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxNirmalaLoungPoorunde1
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxiammrhaywood
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 

Recently uploaded (20)

Class 11 Legal Studies Ch-1 Concept of State .pdf
Class 11 Legal Studies Ch-1 Concept of State .pdfClass 11 Legal Studies Ch-1 Concept of State .pdf
Class 11 Legal Studies Ch-1 Concept of State .pdf
 
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
 
Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1
 
9953330565 Low Rate Call Girls In Rohini Delhi NCR
9953330565 Low Rate Call Girls In Rohini  Delhi NCR9953330565 Low Rate Call Girls In Rohini  Delhi NCR
9953330565 Low Rate Call Girls In Rohini Delhi NCR
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptx
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 
How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
 
Staff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSDStaff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSD
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application )
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docx
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha elections
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
 
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
 
Employee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxEmployee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptx
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdfTataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
 

rdc.pdf

  • 1. Air System Sizing Summary for syst1 Project Name: salma 06/07/2022 Prepared by: ADIL DAHMANI 12:56 Air System Information Air System Name: syst1 Air System Type: Single Zone CAV Number of zones: 1 Floor Area: 355,2 sqm Location: Casablanca, Morocco Sizing Calculation Information Calculation Months: Jan to Dec Calculation method: Transfer Function Method Central Cooling Coil Sizing Data Total coil load: 37,2 kW Total coil load: 37,2 kW Sensible coil load: 30,0 kW Coil airflow: 3302 L/s Sensible heat ratio: 0,808 Area per unit load: 9,6 sqm/kW Load per unit area: 104,6 W/sqm Load occurs at: Aug 1800 OA DB / WB: 28,4/21,9 Entering DB / WB: 22,7/18,2 Leaving DB / WB: 15,1/14,9 Coil ADP: 14,7 C Bypass Factor: 0,050 Resulting RH: 66 % Design supply temp: 15,0 C Central Heating Coil Sizing Data Max coil load: 26,5 kW Coil airflow: 3302 L/s Load per unit area: 74,7 W/sqm Load occurs at: Des Htg Ent DB / Lvg DB: 18,3/25,0 Supply Fan Sizing Data Actual max airflow: 3302 L/s Standard airflow: 3278 L/s Actual max airflow per unit area: 9,30 L/(s-sqm) Fan motor BHP: 0,00 BHP Fan motor kW: 0,00 kW Fan static: 0,00 Pa Outdoor Ventilation Air Data Design airflow: 321 L/s Airflow per unit floor area: 0,90 L/(s-sqm) Airflow per person: 4,46 L/s/person Space Sizing Data Space Name Maximum Cooling Sensible kW Design Airflow L/s Time of Peak Load Maximum Heating Load kW Space Floor Area sqm Space L/(s-sqm) Arriere comptoir RDC 1,6 210 Aug 1800 1,6 20,6 10,17 Arrière comptoir RDC 1,6 189 Jul 2000 1,4 22,2 8,51 Bureau adjoint RDC 1,8 218 Aug 1700 1,2 17,4 12,53 Bureau certificats RDC 2,9 349 Jul 1800 1,8 37,9 9,20 Bureau conservateur RDC 2,5 298 Aug 1600 2,1 31,7 9,40 Bureau d ordre RDC 1,1 126 Jul 1900 0,8 10,2 12,30 Bureau RDC 1,9 227 Jul 1700 1,3 24,6 9,25 BureauChefGestArchiveRDC 2,3 268 Jul 2000 1,6 31,6 8,49 Caisse cf RDC 1,6 186 Jul 2000 1,1 16,7 11,12 Caisse sc RDC 0,5 82 Jul 1900 0,6 9,1 9,03 Chef servicecadastre RDC 2,3 278 Jul 2000 1,8 32,7 8,51 Espace notaires c.f RDC 1,3 155 Aug 1800 1,2 18,4 8,41 Espaceconsgeometres.cRDC 1,3 152 Aug 1800 0,9 12,3 12,38 Local Securite RDC 0,6 104 Jul 1700 0,8 7,2 14,39 Salle Scannarisation RDC 1,8 214 Jul 1800 1,6 26,8 7,99 Secrétariat c.f RDC 1,4 164 Aug 1500 1,1 14,3 11,48 secretariat c.s RDC 1,8 218 Jul 1900 1,3 21,5 10,15 Zone 27,7 3302 Jul 1800 22,3 355,2 9,30 Note: Table contains data for all spaces controlled by a single thermostat: Space sizing basis: Peak space load Zone sizing basis: Peak zone load Block Load 4.15 Page 1 of 3
  • 2. System Design Load Summary for syst1 Project Name: salma 06/07/2022 Prepared by: ADIL DAHMANI 12:56 DESIGN COOLING DESIGN HEATING Aug 1800 OA DB / WB 28,4 C / 21,9 C Design Heating Day OA DB / WB 5,6 C / 1,8 C Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W Window and Skylight Solar Loads 16 sqm 1747 - 16 sqm - - Wall Transmission 552 sqm 10623 - 552 sqm 11230 - Roof Transmission 367 sqm 3380 - 367 sqm 2742 - Window Transmission 16 sqm 318 - 16 sqm 772 - Skylight Transmission 0 sqm 0 - 0 sqm 0 - Door Loads 0 sqm 0 - 0 sqm 0 - Floor Transmission 366 sqm -179 - 366 sqm 110 - Partitions/Ceilings 325 sqm -860 - 325 sqm 7403 - Overhead Lighting 7104 W 7104 - 0 W 0 - Electric Equipment 0 W 0 - 0 W 0 - People 72 5170 4326 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >>Total Zone Loads - 27303 4326 - 22256 0 Thermostat and Pulldown Adjustment - 313 0 - -1140 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Ventilation Load 321 L/s 2422 2804 321 L/s 5416 0 Supply Fan Load 3303 L/s 0 - 3303 L/s 0 - >> Total System Loads - 30039 7129 - 26531 0 Central Cooling Coil - 30039 7133 - 0 0 Central Heating Coil - 0 - - 26531 - >> Total Coil Loads - 30039 7133 - 26531 0 Key: Positive values are clg loads Negative values are htg loads Positive values are htg loads Negative values are clg loads Block Load 4.15 Page 2 of 3
  • 3. System Psychrometricsforsyst1 Project Name: salma 06/07/2022 Prepared by: ADIL DAHMANI 12:56 1.OutdoorAir 2.MixedAir 3.CentralCoolingCoilOutlet 4.SupplyFanOutlet 5.RoomAir 1 2 3 4 5 0,000 0,002 0,004 0,006 0,008 0,010 0,012 0,014 0,016 0,018 0,020 0 10 20 30 Location:Casablanca,Morocco Altitude:61,9m Datafor:AugDESIGNCOOLINGDAY,1800 Specific Humidity ( kg/kg ) Temperature(C) Block Load 4.15 Page 3 of 3