This document provides submittal information for a water-cooled screw chiller unit with the following key details:
- Model number: 30XW-V308
- Cooling capacity: 306.6 tons
- Located in Shanghai, China
- Dimensions: 164 inches long, 56 inches wide, 91 inches tall
- Efficiency ratings, electrical information, accessories, and performance data are included for specifications.
2. Table Of Contents
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
Detailed Performance Report 3
CH 270 30XWV308 7
Unit Report 8
Performance Report 9
Acoustic Summary 11
Packaged Chiller Builder China Export 3.39R Page 2 of 11
3. Detailed Performance Summary For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
DetailedPerformanceReport
PackagedChillerReport:DoNotEdit
AquaForce Greenspeed
Water Cooled Screw Chiller
Unit Information
Tag Name: CH 270 30XWV308
Model Number: 30XW-V308
Condenser Type: Water Cooled
Nameplate Voltage: 380-3-60 V-Ph-Hz
Quantity: 1
Manufacturing Source: Shanghai, China
Refrigerant: R134a
Minimum Capacity: 20.00 %
Shipping Weight: 14427 lb
Operating Weight: 14074 lb
Unit Length: 164 in
Unit Width: 56 in
Unit Height: 91 in
Performance Information
Cooling Capacity: 306.6 Tons
Heating Capacity: 354.7 Tons
Total Unit Power: 179.3 kW
Cooling Efficiency (EER): 20.51 BTU/Wh
Heating Efficiency (COPH): 6.956 kW/kW
Acoustics Information
A-Weighted Sound Pressure Level: 84 dBA
Evaporator Information
Fluid Type: Fresh Water
Fouling Factor: 0.000102 (hr-sqft-F)/BTU
Leaving Temperature: 44.00 °F
Entering Temperature: 55.46 °F
Fluid Flow: 640.0 gpm
Pressure Drop: 17.9 ft H2O
Condenser Information
Fluid Type: Fresh Water
Fouling Factor: 0.000102 (hr-sqft-F)/BTU
Leaving Temperature: 94.30 °F
Entering Temperature: 85.00 °F
Fluid Flow: 920.5 gpm
Pressure Drop: 19.0 ft H2O
Packaged Chiller Builder China Export 3.39R Page 3 of 11
4. Detailed Performance Summary For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
Electrical Information
Unit Voltage: 380-3-60 V-Ph-Hz
Standby Power: 0.05000 kW
Minimum Voltage: 342 Volts
Maximum Voltage: 418 Volts
Power Factor: 0.92
Electrical Electrical
Amps (Un) Circuit 1 Circuit 2
Max Unit Current
Draw (RLA)
406.0 ---
Nominal Start Up
Current (ICF)
302.0 ---
Nominal Unit
Current Draw (A)
302.0 ---
Accessories and Installed Options
Opt. 314C Condenser Flanged Connections
Opt. 321 Discharge Shut Off Valve
Opt. 314E Evaporator Flanged Connections
Opt. 158A 7" Touch Screen Interface
Standard Single Power Connection
Opt. 61 380V-3-60Hz Power
Packaged Chiller Builder China Export 3.39R Page 4 of 11
5. Detailed Performance Summary For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
Integrated Part Load Value (AHRI)
IPLV.IP: 34.13 BTU/Wh
Unit Performance
Percent Full Load Cooling Capacity, % 100.00 75.00 50.00 25.00
Percent of Full Load Power, % 100.00 54.06 26.21 12.88
Unloading Sequence Default Default Default Default
Cooling Capacity, Tons 305.3 229.0 152.7 76.33
Total Unit Power, kW 180.8 97.75 47.39 23.28
Nominal Unit Current Draw (RLA) --- --- --- ---
Efficiency, BTU/Wh 20.26 28.11 38.66 39.35
Evaporator Data
Fluid Entering Temperature, °F 54.00 51.49 48.99 46.50
Fluid Leaving Temperature, °F 44.00 44.00 44.00 44.00
Fluid Flow Rate, gpm 730.3 730.3 730.3 730.3
Fouling Factor, (hr-sqft-F)/BTU 0.000100 0.000100 0.000100 0.000100
Condenser Data
Fluid Entering Temperature, °F 85.00 75.00 65.00 65.00
Fluid Leaving Temperature, °F 94.30 81.70 69.33 67.16
Fluid Flow Rate, gpm 918.3 918.3 918.3 918.3
Fouling Factor, (hr-sqft-F)/BTU 0.000250 0.000250 0.000250 0.000250
Packaged Chiller Builder China Export 3.39R Page 5 of 11
6. Detailed Performance Summary For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
Load Line
Unit Performance (1) (1)
Percent Full Load Cooling Capacity, % 100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00
Percent of Full Load Power, % 100.00 80.69 63.59 50.32 38.30 29.43 30.87 24.31 17.55 9.65
Unloading Sequence Default Default Default Default Default Default Default Default Default Default
Cooling Capacity, Tons 306.6 275.9 245.3 214.6 183.9 153.3 122.6 91.97 61.31 30.66
Heating Capacity, Tons 354.7 314.7 275.7 238.6 202.1 167.1 137.1 103.3 69.41 34.71
Total Unit Power, kW 179.3 144.7 114.0 90.24 68.68 52.77 55.36 43.59 31.47 17.31
Nominal Unit Current Draw (RLA) --- - - - - - - - - -
Cooling Efficiency BTU/Wh 20.51 22.88 25.81 28.54 32.14 34.86 26.58 25.32 23.38 21.25
Heating Efficiency, kW/kW 6.956 7.648 8.504 9.301 10.35 11.14 8.713 8.335 7.757 7.051
A-Weighted Sound Pressure Level,
dBA
84 86 80 81 80 78 78 78 - -
Evaporator Data
Fluid Entering Temperature, °F 55.46 54.29 53.15 52.01 50.86 49.72 48.58 47.43 46.29 45.14
Fluid Leaving Temperature, °F 44.00 44.00 44.00 44.00 44.00 44.00 44.00 44.00 44.00 44.00
Fluid Flow Rate, gpm 640.0 640.0 640.0 640.0 640.0 640.0 640.0 640.0 640.0 640.0
Pressure Drop, ft H2O 17.9 17.9 18.0 18.0 18.0 18.1 18.1 18.2 18.2 18.2
Fouling Factor, (hr-sqft-F)/BTU 0.000102 0.000102 0.000102 0.000102 0.000102 0.000102 0.000102 0.000102 0.000102 0.000102
Condenser Data
Fluid Entering Temperature, °F 85.00 82.00 79.00 76.00 73.00 70.00 81.00 81.00 81.00 81.00
Fluid Leaving Temperature, °F 94.30 90.25 86.23 82.25 78.30 74.38 84.59 83.71 82.82 81.91
Fluid Flow Rate, gpm 920.5 920.0 919.5 919.0 918.6 918.2 919.5 919.4 919.4 919.3
Pressure Drop, ft H2O 19.0 19.2 19.4 19.6 19.7 19.9 19.4 19.4 19.4 19.4
Fouling Factor, (hr-sqft-F)/BTU 0.000102 0.000102 0.000102 0.000102 0.000102 0.00010 0.00010 0.00010 0.00010 0.00010
(1) Compressor cycling is expected. Stated performances are average.
Sound pressure level measured in accordance with AHRI Standard 575-2008. Sound pressure level is the free field sound data (the unit is placed in free field over a reflecting
plane).
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on
AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org
Packaged Chiller Builder China Export 3.39R Page 6 of 11
7. CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
CH27030XWV308
CH 270 30XWV308
Detailed Performance Report
Tag Cover Sheet
Unit Report
Performance Report
Acoustic Summary
Packaged Chiller Builder China Export 3.39R Page 7 of 11
8. Unit Report For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
Unit Report
Unit Information
Tag Name: CH 270 30XWV308
Model Number: 30XW-V308
Condenser Type: Water Cooled
Nameplate Voltage: 380-3-60 V-Ph-Hz
Quantity: 1
Manufacturing Source: Shanghai, China
Refrigerant: R134a
Minimum Capacity: 20.0 %
Shipping Weight: 14427 lb
Operating Weight: 14074 lb
Unit Length: 164 in
Unit Width: 56 in
Unit Height: 91 in
Accessories and Installed Options
Opt. 314C Condenser Flanged Connections
Opt. 321 Discharge Shut Off Valve
Opt. 314E Evaporator Flanged Connections
Opt. 158A 7" Touch Screen Interface
Standard Single Power Connection
Opt. 61 380V-3-60Hz Power
Ordering Information
Part Number Description Quantity
30XW-V308 Packaged Chiller 1
Base Unit
Packaged Chiller Builder China Export 3.39R Page 8 of 11
9. Summary Performance Report For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
PerformanceReport
PackagedChillerReport:DoNotEdit
AquaForce Greenspeed
Water Cooled Screw Chiller
Unit Information
Tag Name: CH 270 30XWV308
Model Number: 30XW-V308
Quantity: 1
Manufacturing Source: Shanghai, China
Refrigerant: R134a
Shipping Weight: 14427 lb
Operating Weight: 14074 lb
Unit Length: 164 in
Unit Width: 56 in
Unit Height: 91 in
Evaporator Information
Fluid Type: Fresh Water
Fouling Factor: 0.000102 (hr-sqft-F)/BTU
Leaving Temperature: 44.00 °F
Entering Temperature: 55.46 °F
Fluid Flow: 640.0 gpm
Pressure Drop: 17.9 ft H2O
Condenser Information
Fluid Type: Fresh Water
Fouling Factor: 0.000102 (hr-sqft-F)/BTU
Leaving Temperature: 94.30 °F
Entering Temperature: 85.00 °F
Fluid Flow: 920.5 gpm
Pressure Drop: 19.0 ft H2O
Performance Information
Cooling Capacity: 306.6 Tons
Heating Capacity: 354.7 Tons
Total Unit Power: 179.3 kW
Cooling Efficiency (EER): 20.51 BTU/Wh
Heating Efficiency (COPH): 6.956 kW/kW
IPLV.IP: 34.13 BTU/Wh
A-Weighted Sound Pressure Level: 84 dBA
Accessories and Installed Options
Opt. 314C Condenser Flanged Connections
Opt. 321 Discharge Shut Off Valve
Opt. 314E Evaporator Flanged Connections
Opt. 158A 7" Touch Screen Interface
Standard Single Power Connection
Opt. 61 380V-3-60Hz Power
Electrical Information
Unit Voltage: 380-3-60 V-Ph-Hz
Standby Power: 0.05000 kW
Minimum Voltage: 342 Volts
Maximum Voltage: 418 Volts
Power Factor: 0.92
Electrical Electrical
Amps (Un) Circuit 1 Circuit 2
Max Unit Current
Draw (RLA)
406.0 ---
Nominal Start Up
Current (ICF)
302.0 ---
Nominal Unit
Current Draw (A)
302.0 ---
Sound pressure level measured in accordance with AHRIStandard 575-2008. Sound pressure level is the free field sound data (the
unit isplaced in free field over a reflecting plane).
Packaged Chiller Builder China Export 3.39R Page 9 of 11
10. Summary Performance Report For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating
Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may
be found in the AHRI Directory at www.ahridirectory.org
Packaged Chiller Builder China Export 3.39R Page 10 of 11
11. Acoustic Summary For CH 270 30XWV308
Project: Engie-Centro Empresarial Santa Cruz 2-Alpina 11/13/2020
Prepared By: 10:35AM
AcousticSummary
PackagedChillerReport:DoNotEdit
Unit Parameters
Tag Name: CH 270 30XWV308
Model Number: 30XW-V308
Condenser Type: Water Cooled
Chiller Nameplate Voltage: 380-3-60 V-Ph-Hz
Quantity: 1
Manufacturing Source: Shanghai, China
Refrigerant: R134a
Shipping Weight: 14427 lb
Operating Weight: 14074 lb
Unit Length: 164 in
Unit Width: 56 in
Unit Height: 91 in 1 - Chiller Height Above Ground
2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
Accessories and Installed Options
Opt. 314C Condenser Flanged Connections
Opt. 321 Discharge Shut Off Valve
Opt. 314E Evaporator Flanged Connections
Opt. 158A 7" Touch Screen Interface
Standard Single Power Connection
Opt. 61 380V-3-60Hz Power
Acoustic Information (Full Load)
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k Total
Sound Power at Chiller Acoustic Center, dB 85 108 99 97 92 84 77 109
A-Weighted Sound Power, dBA 69 100 96 97 94 85 76 103
Sound pressure at specified distance in a free field, dB 66 89 80 78 73 64 57 90
A-Weighted Sound Pressure Level, dBA 49 80 76 78 74 65 56 84
Notes
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 3.3 ft
3 - Receiver Height Above Ground = 4.9 ft
Sound pressure level measured in accordance with AHRI575. Sound pressure level is the free field sound data (the unit is placed in
free field over a reflecting plane).
Packaged Chiller Builder China Export 3.39R Page 11 of 11