Shenzhen Huayansheng Electron Co.,Ltd

 Description


 MPM8000 is a powerful multifunction power meter with
 modular design, which can be applied for monitoring and
 controlling of the electrical system. MPM8000 can measure
 and analyze real time data, such as U, I, P, Q, S, COSΦ, F,



                                                                                                       8000
 kWh, kVAr, etc. MPM8000 has the following functions:



                                                                                                    PM
 RS-485 communication port, 2 energy pulse output (include



                                                                        ter M
 active energy and reactive energy), Max/min data record,



                                                                     Me
 and SOE event record. MPM8000 can extend functions by



                                                wer
 choosing the external optional modules: harmonic analysis,



                                           n Po
 8 remote signals on/off mode, programmable 4 analog



               ctio
 outputs (0~5V or 4~20mA optional), data storage, Profibus



         tifun
 Com. protocol, Ethernet communication functions. The


      ul
 multi-tariff function allows the user to measure energy in


Many interval (the min. interval is 30min.), which can read the   Technical Data
 sum, sharp, peak, valley, flat energy data in 30 days, and
 measure 2nd to 63rd harmonics in statistics.                     Input Current
      All our instruments fulfill all important requirements      Input Current: 5A (Current value can be set up)
 and regulations concerning electromagnetic compatibility         Measurement scope: 0.5%~120%
 and safety isolation (IEC61000, IEC1010 standard and             Overload capacity: 2 X rated continuously, 100A/1s non
 EN61010 standard). The devices have been developed,              continuously
 manufactured and tested in accordance with Quality               Power consumption: ≤0.2VA per phase
 Assurance System ISO 9001.                                       Voltage Input
                                                                  Input Voltage: 400VAC (L-N), 693VAC (L-L) (Voltage
 Measured Scope                                                   value can be set up)
                                                                  System frequency: 45~65Hz
The meter MPM8000 can be applied in single phase, 3-Ph



                                                                 s.com
                                                                  Measurement scope: 3%~120%
3Wire, 3-Ph 4Wire system. It can be applied vastly in the
                                                                  Overload Capacity: 2 X rated continuous, 2500V/1s non


                                                            zhye
field of secondary measurement in high Voltage, low
                                                                  continuous


                                             w.s
Voltage system, or transmission of measured data.


                                           w
                                                                  Power consumption: ≤0.5VA per phase

 Parameter setup
                                     w                            Pulse output


                                                                  No. of outputs
                                                                                                        2 channels
                                                                                                        (active/reactive energy
The programmable parameters are: com. address, PT, CT,
baud rte, clock, demand cycle, user password, multi-tariff                                              each)
rate, etc. The user can set up relay output, analog output on     Serial com. port
PC.                                                               NO. of outputs                        1 RS-485 port
The parameters setup on meter and PC: com. address, PT,           Communication protocol                Modbus-RTU protocol
CT, baud rate, time, demand statistics, no. of remote signal,                                           2400/4800/9600/1920
                                                                  Baud rate
user password, multi-tariff, IO module detection, Ethernet                                              0/38400bps
setup.




           www.szhyes.com                  Email: export008@szhyes.com                 Tel: 86-755-33581652
Shenzhen Huayansheng Electron Co.,Ltd

Technical Data                                                       EMC and Safety Standard

Other parameters                                                         IEC61000-4-2 (GB/T17626.2)
Auxiliary Power                        85~265VAC/DC                      IEC61000-4-8 (GB/T17626.8)
                                       LCD Display                       IEC61000-4-4 (GB/T17626.4)
Display module                                                           IEC61010-1 (GB/T4793.1)
                                       76mmx66mm




                                                                                                      8000
Storage Capacity                       2GB                           Terminal Chart
Temp. drifting factor                  <100PPM/℃


                                                                                                   PM
                                                                         ter M
Withstand Voltage                      2500V/1 min



                                                                      Me
Total power consumption                <8VA



                                                wer
Operation temperature                    -20℃~60℃



                                           n Po
Storage temperature                      -40℃~85℃



                 ctio
Operation humidity                     5~95% RH



           tifun
Pollution Class                        Class 2


        ul
                                       Flammability acc. to

M
Material of Housing
                                       UL94V0
Size                                   96x99x78mm

Technical Data

   Parameters                Display                  Accuracy
Voltage                 0~9999.9kV               Class 0.2
                                                 scope:5%~100%V
                                                 Class 0.2
                                                 scope: 5%~100%A
       Current              0~9999.9kA           Zero sequence
                                                 current Class 0.5




                                                                    s.com
Power factor            -1~+1                    Class 1




                                          w.s                  zhye
Frequency               45~65Hz                  ±0.01Hz
                                                                         Terminal 1, 2, 3, 4 are Voltage In, marked as L1, L2,


                                       ww
Active Power            -9999~9999MW             Class 0.5
                                                                         L3, N.
Reactive Power          -9999~9999MVAr           Class 0.5
                                                                         Terminal 5, 6 , 7, 8, 9, 10are Current In, marked as
Apparent Power        0~9999MVA                  Class 0.5
                                                                         I1*,I1, I2*, I2, I3*, I3.
Active Demand           -9999~9999MW             Class 1.0
                                                                         Terminal 11, 12, 13 as auxiliary power input, 12 as L
Reactive Demand         -9999~9999MVAr           Class 1.0               end, 11 as N end, 13 as ground line. It is
Active Energy         0~9999999.99Mwh            Class 1.0               recommended to connect the ground line.
Reactive Energy       0~9999999.99MVArh          Class 2.0               Terminal 15, 16 are RS 485 com. 15 as A+, 16 as B-.
Phase Angle             0.0°~359.9°              Class 2.0               Terminal 17, 18,19 are a pair of active and reactive
Current                 0~100%                   Class 2.0               energy pulse output, 17 as active positive end, 18 as
total harmonic %                                                         reactive positive end, and 12 as COM negative end.
Voltage    total        0~100%                   Class 2.0               Terminal 14,20, 21,22,23,24 are standby ends.
harmonic %


             www.szhyes.com                Email: export008@szhyes.com                Tel: 86-755-33581652
Shenzhen Huayansheng Electron Co.,Ltd

                                                 Function Description
            Real time measurement
                                       Phase Voltage            Phase Voltage, average phase Voltage

                                       Line Voltage             Line Voltage, average line Voltage
                                                                Phase Current, average phase Current, zero sequence
                                       Current
                                                                Current



                                                                                                        8000
                                       Active Power             Phase active power, 3 phase active total power


                                                                                                     PM
                                       Reactive Power           Phase reactive power, 3 phase reactive total power



                                                                          ter M
                                       Apparent Power           Phase apparent power, 3 phase apparent total power


                                                                       Me
                                       Power 4 quadrant         Power 4 quadrant



                                            Po wer
                                       Frequency                System frequency
  Main



                 ction
                                       Power Factor             Phase power factor, 3 phase total power factor
  unit


             fun
                                                                3 phase active/reactive demand power, demand apparent


  ulti
               Demand statistic        Demand
                                                                power


M              Energy Reading          Active energy
                                                                Imported, exported and net active energy, 1 channel active
                                                                energy pulse output
                                                                Imported, exported and net reactive energy, 1 channel
                                       Reactive energy
                                                                reactive energy pulse output
                                       Multi tariff billing     Multi tariff setup
                 Time display          Real time display        Year/month/day/hour/minute/second
                                       RS-485
             Data communication                                 1 Modbus-RTU protocol
                                       communication


                                                       Installation

            1. Exterior size: 91 mm×91 mm×72mm



                                                            s.com
            2. Installation size: 91 mm×91mm




                                     w.s               zhye
                                                      Supporting comp.


                                  ww
                            Hole



                                                 Buckle up position.




    During the installation, please insert the meter in the hole of the cabinet, then push and buckle up the meter with the
    installation accessories. It is strongly recommended there should be 20mm space around the surface of the meter for
    ventilation purpose.

         www.szhyes.com               Email: export008@szhyes.com                     Tel: 86-755-33581652
Shenzhen Huayansheng Electron Co.,Ltd
 Shenzhen Huayansheng Electron Co.,Ltd




www.szhyes.com   Email: export008@szhyes.com   Tel: 86-755-33581652
Shenzhen Huayansheng Electron Co.,Ltd

                                          Auxiliary module's function and usage
8 remote signals input module: This module has 8                Programmable 4 relay outputs module: This module has 4
sourcefree remote signals input channels, each channel can      separate electric relay output channels, which can be setted up
be setted up separately to check the outside on-off status.     separately to corresponding different electricity parameter’s
Detail setup can be finished through the key on the meter       automatic model and manual model which can be operated by
and upper computer. The function of upper read                  upper computer. Associated automatic alarm function can trigger


                                                                                                              8000
SOE(Sequence of events) by connecting the SOE interface         event to record the present power system status; without alarm,


                                                                                                           PM
which record accurately the status and detail time of events.   the 4 electric relay will normally keep open.


Programmable 4 analog outputs module: This module

                                                                            Me ter M
                                                                SD card data storage module: Adopted advanced high-capacity


                                                 wer
has 4 analog output, voltage or current model optional.         internal storage SD card to store electrical measurement



                                            n Po
Output adopts 4 channels same negative terminal format,         parameter at real time; and store the data for a given period of


                ctio
each channel corresponding separately to different              time. The data can be educed and analysed by upper computer,



          tifun
electricity parameter. Current is: (4--20) mA output, voltage   internal storage of SD card is optional.



M      ul
is: (0--5) V output.


Harmonic analysis module: It can display each measured          Data storage and harmonic analysis module: This module
information of the harmonic, and feedback the electric          combined SD card data storage and harmonic analysis function,
harmonic parameter, including (2~63 times) harmonic             which can store electrical measurement data and harmonic
content; phase angle etc. measured information.                 measurement data, including analysis and display (2~63times)
                                                                harmonic content; phase angle etc. measured information.
Ethernet communication module: It can connect to        Profibus communication module: The meter can Network
 Ethernet by RJ45, and read electrical measurement by through Profibus communication Protocol terminal, fully
remote access. Adopted 10M and 100M self-adaption complied with Profibus-DP Communication Protocol.
model. (Default IP address is:192.168.0.250; Local port
27011)




                                                                zhye s.com
Note: A max. of 4 modules can be applied to 1 main unit, and the same type of modules can’t be selected together. C and V



                                         w.s
can’t be selected at the same time; B can’t be selected with M or H.


                                      ww




            www.szhyes.com                   Email: export008@szhyes.com                     Tel: 86-755-33581652
Shenzhen Huayansheng Electron Co.,Ltd
                             Typical Wiring Diagram




                                                                 PM 8000
                                              Me ter M
                      n Po wer
    tifun ctio
Mul




                                  zhye s.com
                     ww w.s




    www.szhyes.com    Email: export008@szhyes.com     Tel: 86-755-33581652

LCD Multifunction Power Analyzer with Data Logger

  • 1.
    Shenzhen Huayansheng ElectronCo.,Ltd Description MPM8000 is a powerful multifunction power meter with modular design, which can be applied for monitoring and controlling of the electrical system. MPM8000 can measure and analyze real time data, such as U, I, P, Q, S, COSΦ, F, 8000 kWh, kVAr, etc. MPM8000 has the following functions: PM RS-485 communication port, 2 energy pulse output (include ter M active energy and reactive energy), Max/min data record, Me and SOE event record. MPM8000 can extend functions by wer choosing the external optional modules: harmonic analysis, n Po 8 remote signals on/off mode, programmable 4 analog ctio outputs (0~5V or 4~20mA optional), data storage, Profibus tifun Com. protocol, Ethernet communication functions. The ul multi-tariff function allows the user to measure energy in Many interval (the min. interval is 30min.), which can read the Technical Data sum, sharp, peak, valley, flat energy data in 30 days, and measure 2nd to 63rd harmonics in statistics. Input Current All our instruments fulfill all important requirements Input Current: 5A (Current value can be set up) and regulations concerning electromagnetic compatibility Measurement scope: 0.5%~120% and safety isolation (IEC61000, IEC1010 standard and Overload capacity: 2 X rated continuously, 100A/1s non EN61010 standard). The devices have been developed, continuously manufactured and tested in accordance with Quality Power consumption: ≤0.2VA per phase Assurance System ISO 9001. Voltage Input Input Voltage: 400VAC (L-N), 693VAC (L-L) (Voltage Measured Scope value can be set up) System frequency: 45~65Hz The meter MPM8000 can be applied in single phase, 3-Ph s.com Measurement scope: 3%~120% 3Wire, 3-Ph 4Wire system. It can be applied vastly in the Overload Capacity: 2 X rated continuous, 2500V/1s non zhye field of secondary measurement in high Voltage, low continuous w.s Voltage system, or transmission of measured data. w Power consumption: ≤0.5VA per phase Parameter setup w Pulse output No. of outputs 2 channels (active/reactive energy The programmable parameters are: com. address, PT, CT, baud rte, clock, demand cycle, user password, multi-tariff each) rate, etc. The user can set up relay output, analog output on Serial com. port PC. NO. of outputs 1 RS-485 port The parameters setup on meter and PC: com. address, PT, Communication protocol Modbus-RTU protocol CT, baud rate, time, demand statistics, no. of remote signal, 2400/4800/9600/1920 Baud rate user password, multi-tariff, IO module detection, Ethernet 0/38400bps setup. www.szhyes.com Email: export008@szhyes.com Tel: 86-755-33581652
  • 2.
    Shenzhen Huayansheng ElectronCo.,Ltd Technical Data EMC and Safety Standard Other parameters IEC61000-4-2 (GB/T17626.2) Auxiliary Power 85~265VAC/DC IEC61000-4-8 (GB/T17626.8) LCD Display IEC61000-4-4 (GB/T17626.4) Display module IEC61010-1 (GB/T4793.1) 76mmx66mm 8000 Storage Capacity 2GB Terminal Chart Temp. drifting factor <100PPM/℃ PM ter M Withstand Voltage 2500V/1 min Me Total power consumption <8VA wer Operation temperature -20℃~60℃ n Po Storage temperature -40℃~85℃ ctio Operation humidity 5~95% RH tifun Pollution Class Class 2 ul Flammability acc. to M Material of Housing UL94V0 Size 96x99x78mm Technical Data Parameters Display Accuracy Voltage 0~9999.9kV Class 0.2 scope:5%~100%V Class 0.2 scope: 5%~100%A Current 0~9999.9kA Zero sequence current Class 0.5 s.com Power factor -1~+1 Class 1 w.s zhye Frequency 45~65Hz ±0.01Hz Terminal 1, 2, 3, 4 are Voltage In, marked as L1, L2, ww Active Power -9999~9999MW Class 0.5 L3, N. Reactive Power -9999~9999MVAr Class 0.5 Terminal 5, 6 , 7, 8, 9, 10are Current In, marked as Apparent Power 0~9999MVA Class 0.5 I1*,I1, I2*, I2, I3*, I3. Active Demand -9999~9999MW Class 1.0 Terminal 11, 12, 13 as auxiliary power input, 12 as L Reactive Demand -9999~9999MVAr Class 1.0 end, 11 as N end, 13 as ground line. It is Active Energy 0~9999999.99Mwh Class 1.0 recommended to connect the ground line. Reactive Energy 0~9999999.99MVArh Class 2.0 Terminal 15, 16 are RS 485 com. 15 as A+, 16 as B-. Phase Angle 0.0°~359.9° Class 2.0 Terminal 17, 18,19 are a pair of active and reactive Current 0~100% Class 2.0 energy pulse output, 17 as active positive end, 18 as total harmonic % reactive positive end, and 12 as COM negative end. Voltage total 0~100% Class 2.0 Terminal 14,20, 21,22,23,24 are standby ends. harmonic % www.szhyes.com Email: export008@szhyes.com Tel: 86-755-33581652
  • 3.
    Shenzhen Huayansheng ElectronCo.,Ltd Function Description Real time measurement Phase Voltage Phase Voltage, average phase Voltage Line Voltage Line Voltage, average line Voltage Phase Current, average phase Current, zero sequence Current Current 8000 Active Power Phase active power, 3 phase active total power PM Reactive Power Phase reactive power, 3 phase reactive total power ter M Apparent Power Phase apparent power, 3 phase apparent total power Me Power 4 quadrant Power 4 quadrant Po wer Frequency System frequency Main ction Power Factor Phase power factor, 3 phase total power factor unit fun 3 phase active/reactive demand power, demand apparent ulti Demand statistic Demand power M Energy Reading Active energy Imported, exported and net active energy, 1 channel active energy pulse output Imported, exported and net reactive energy, 1 channel Reactive energy reactive energy pulse output Multi tariff billing Multi tariff setup Time display Real time display Year/month/day/hour/minute/second RS-485 Data communication 1 Modbus-RTU protocol communication Installation 1. Exterior size: 91 mm×91 mm×72mm s.com 2. Installation size: 91 mm×91mm w.s zhye Supporting comp. ww Hole Buckle up position. During the installation, please insert the meter in the hole of the cabinet, then push and buckle up the meter with the installation accessories. It is strongly recommended there should be 20mm space around the surface of the meter for ventilation purpose. www.szhyes.com Email: export008@szhyes.com Tel: 86-755-33581652
  • 4.
    Shenzhen Huayansheng ElectronCo.,Ltd Shenzhen Huayansheng Electron Co.,Ltd www.szhyes.com Email: export008@szhyes.com Tel: 86-755-33581652
  • 5.
    Shenzhen Huayansheng ElectronCo.,Ltd Auxiliary module's function and usage 8 remote signals input module: This module has 8 Programmable 4 relay outputs module: This module has 4 sourcefree remote signals input channels, each channel can separate electric relay output channels, which can be setted up be setted up separately to check the outside on-off status. separately to corresponding different electricity parameter’s Detail setup can be finished through the key on the meter automatic model and manual model which can be operated by and upper computer. The function of upper read upper computer. Associated automatic alarm function can trigger 8000 SOE(Sequence of events) by connecting the SOE interface event to record the present power system status; without alarm, PM which record accurately the status and detail time of events. the 4 electric relay will normally keep open. Programmable 4 analog outputs module: This module Me ter M SD card data storage module: Adopted advanced high-capacity wer has 4 analog output, voltage or current model optional. internal storage SD card to store electrical measurement n Po Output adopts 4 channels same negative terminal format, parameter at real time; and store the data for a given period of ctio each channel corresponding separately to different time. The data can be educed and analysed by upper computer, tifun electricity parameter. Current is: (4--20) mA output, voltage internal storage of SD card is optional. M ul is: (0--5) V output. Harmonic analysis module: It can display each measured Data storage and harmonic analysis module: This module information of the harmonic, and feedback the electric combined SD card data storage and harmonic analysis function, harmonic parameter, including (2~63 times) harmonic which can store electrical measurement data and harmonic content; phase angle etc. measured information. measurement data, including analysis and display (2~63times) harmonic content; phase angle etc. measured information. Ethernet communication module: It can connect to Profibus communication module: The meter can Network Ethernet by RJ45, and read electrical measurement by through Profibus communication Protocol terminal, fully remote access. Adopted 10M and 100M self-adaption complied with Profibus-DP Communication Protocol. model. (Default IP address is:192.168.0.250; Local port 27011) zhye s.com Note: A max. of 4 modules can be applied to 1 main unit, and the same type of modules can’t be selected together. C and V w.s can’t be selected at the same time; B can’t be selected with M or H. ww www.szhyes.com Email: export008@szhyes.com Tel: 86-755-33581652
  • 6.
    Shenzhen Huayansheng ElectronCo.,Ltd Typical Wiring Diagram PM 8000 Me ter M n Po wer tifun ctio Mul zhye s.com ww w.s www.szhyes.com Email: export008@szhyes.com Tel: 86-755-33581652