Fault Isolator Module

                                                                                                        Addressable Devices

General
The Fire•Lite I300(A) Fault Isolator Module is used with
Fire•Lite’s addressable fire alarm control panels (FACPs) to
protect the system against wire-to-wire short circuits on the
SLC loop. The I300(A) should be placed between each device
on the SLC loop to isolate a short-circuit problem between the
modules. It is required for true Style 7 operation so that other
devices can continue to operate normally in the event of a
short-circuit on the SLC.

Features
• Powered by SLC loop directly, no external power required.
• Mounts in standard junction boxes (4.0"/10.16 cm square,
  2.125"/5.398 cm deep).
• Integral LED blinks to indicate normal condition. Illuminates
  steady when short circuit condition is detected.
• High noise (EMF/RFI) immunity.

Applications
The Fault Isolator Modules should be spaced between groups
of sensors in a loop to protect the rest of the loop. Use to iso-
late short circuit problems within a section of a loop so that
other sections can continue to operate normally. The I300(A)                                  I300(A)
supports a maximum of 25 devices in-between isolators,
except when using relay bases.                                       • Dimensions: 4.5”H x 4.5”W x 0.25” D (11.43 cm H x
NOTE: LOADS PER RELAY BASE AND ISOLATORS/ISOLATOR                      11.43 cm W x 0.635 cm D).
BASES: The maximum number of addressable devices between
isolators (or B224BIA isolator bases) is 25 devices.                 Construction
                          25 DEVICES                                 The face plate is made of off-white plastic. Module includes
                                                                     yellow LED indicator that pulses when normal and illuminates
 isolator                                               isolator
                                                                     steady when a short is detected.
 module                                                 module
 or base                                                or base
2243devices.wmf
                   detector               module
                                                                     Operation
                                                                     Automatically opens circuit when the line voltage drops below
                                                                     four volts. Fault Isolator Modules should be spaced between
B224RB relay bases draw more current than other intelligent          groups of addressable devices (maximum 25, see notes on
devices. When calculating the 25-device maximum, B224RB rep-
                                                                     page 1) in a loop to protect the rest of the loop. If a short
resents 2.5 DEVICES; see example on page 2.
                                                                     occurs between any two isolators, then both isolators immedi-
NOTE: ON MAXIMUM NUMBER OF DEVICES: See the SLC                      ately switch to an open circuit state and isolate the groups of
Manual (51309) for information on loss of addresses due to current   sensors between them. The remaining units on the loop con-
limitations. Each module or base added reduces the capacity of       tinue to fully operate.
address positions in an SLC. All SLC field devices must have been
purchased after February 1995 to meet the aforementioned             In Style 4 loops, the I300(A) is generally used at each T-tap
requirements. If the SLC field devices were purchased prior to       branch, to limit the effect of short circuits on a branch to the
February 1995, each isolator used reduces the capacity of an SLC     devices on that branch. The LED indicator is on continuously
by two address positions. Requirements differ as applied to relay    during a short circuit condition.
bases; see note above.
                                                                     The I300(A) Fault Isolator Module automatically restores the
                                                                     shorted portion of the communications loop to normal.
Specifications
• Operating voltage: 15 – 32 VDC (peak).                             Installation
• Maximum current upon activation due to short circuit:              • Mount on a standard junction box (4.0"/10.16 cm square)
  refer to the manual for the main FACP.                               which is at least 2.125"/5.398 cm deep.
• Standby current: 450 μA maximum; I300(A) is not isolating          • Terminal screws are provided for “in and out” wiring.
  – relay closed.
                                                                     • Installation instructions are provided with each module.
• Temperature range: 32°F to 120°F (0°C to 49°C).
                                                                     • Surface-mount box is available as an option.
• Relative humidity: 10% to 93%.
• Weight: 5 oz. (150 grams).

                                                                                                  DF-52389:B • 01/05/2012 — Page 1 of 2
Engineering Specifications                                                 Agency Approvals and Listings
Fault Isolator Modules shall be provided to automatically iso-             These listings and approvals apply to the modules specified in
late wire-to-wire short circuits on an SLC loop. The Fault Isola-          this document. In some cases, certain modules or applications
tor Module shall limit the number of modules or detectors that             may not be listed by certain approval agencies, or listing may
may be rendered inoperative by a short circuit fault on the SLC            be in progress. Consult factory for listing details.
Loop. If a wire-to-wire short occurs, the Fault Isolator Module            •   UL Listed: S2424 (I300 only).
shall automatically open-circuit (disconnect) the SLC loop.
When the short circuit condition is corrected, the Fault Isolator          •   ULC Listed: S2424 (I300A only).
Module shall automatically reconnect the isolated section of               •   CSFM: 7300-0075:0159.
the SLC loop. The Fault Isolator Module shall not require any              •   MEA: 3-94-E.
address-setting, and its operations shall be totally automatic. It
                                                                           •   FM Approved.
shall not be necessary to replace or reset an Fault Isolator
Module after its normal operation. The Fault Isolator Module
shall mount in a standard 4" (10.16 cm) deep electrical box, in            Product Line Information
a surface-mounted backbox, or in the Fire Alarm Control                    NOTE: “A” suffix indicates ULC Listed model.
Panel. It shall provide a single LED which shall flash to indi-
cate that the Isolator is operational and shall illuminate steadily        I300I300A: Same as I300 with ULC Listing.
to indicate that a short circuit condition has been detected and           SMB500: Optional surface-mount backbox.
isolated.

                           Examples of Device Counts
                           (see notes under Applications)                                             Starts
                                                                                                   Next Count




                                                                                                                       52389-2011g.wmf
                             isolator                                                                isolator
                             module                                                                  module
                             or base       detector with       detector with                         or base
                                          standard base         relay base        module

                              Counts as...
                                                                                             (less than 25 total)




                                                                           Fire·Lite® are registered trademarks of Honeywell International Inc.
                                                                           ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
                                                                           of this document is strictly prohibited.



                                         This document is not intended to be used for installation purposes.
                                           We try to keep our product information up-to-date and accurate.
                                        We cannot cover all specific applications or anticipate all requirements.
                                               All specifications are subject to change without notice.
                                                                                                                                         Made in the U.S. A.
                             For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
                                                                    www.firelite.com
Page 2 of 2 — DF-52389:B • 01/05/2012

More Related Content

What's hot

01. hrc din fuses 3 na
01. hrc din fuses  3 na01. hrc din fuses  3 na
01. hrc din fuses 3 na
angelochintu
 
Acb2
Acb2Acb2
Sd355
Sd355Sd355
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Maxpromotion
 
Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!
Kristen_Barbour_PF
 
E2S warning signals - intrinsically safe solutions
E2S warning signals - intrinsically safe solutionsE2S warning signals - intrinsically safe solutions
E2S warning signals - intrinsically safe solutions
E2S Warning Signals
 
Pepperl fuchs 2011 Emerson Global Users Exchange Intrinsically Safe CHARMS S...
Pepperl fuchs 2011 Emerson Global Users Exchange  Intrinsically Safe CHARMS S...Pepperl fuchs 2011 Emerson Global Users Exchange  Intrinsically Safe CHARMS S...
Pepperl fuchs 2011 Emerson Global Users Exchange Intrinsically Safe CHARMS S...
Kristen_Barbour_PF
 
01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fuses01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fuses
angelochintu
 
Dn 6724
Dn 6724Dn 6724
Dn 6724
venvetty3
 
CM4 Four-Point Continuous Monitor
CM4 Four-Point Continuous MonitorCM4 Four-Point Continuous Monitor
CM4 Four-Point Continuous Monitor
ro19hit
 
Vlfvic010
Vlfvic010Vlfvic010
Rc 500射频芯片
Rc 500射频芯片Rc 500射频芯片
Rc 500射频芯片
guestb549bc
 
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side AccessLayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Power Systems, Inc.
 
Bg12 lx
Bg12 lxBg12 lx
Sr
SrSr
Denon+avc 3808,+avr-3808,+avr-3808 ci
Denon+avc 3808,+avr-3808,+avr-3808 ciDenon+avc 3808,+avr-3808,+avr-3808 ci
Denon+avc 3808,+avr-3808,+avr-3808 ci
BatistaBR
 
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power PanelLayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Power Systems, Inc.
 
Aeon labs micro motor controller manual us
Aeon labs micro motor controller manual usAeon labs micro motor controller manual us
Aeon labs micro motor controller manual us
Domotica daVinci
 
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentationPepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Kristen_Barbour_PF
 
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power PanelLayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Power Systems, Inc.
 

What's hot (20)

01. hrc din fuses 3 na
01. hrc din fuses  3 na01. hrc din fuses  3 na
01. hrc din fuses 3 na
 
Acb2
Acb2Acb2
Acb2
 
Sd355
Sd355Sd355
Sd355
 
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
 
Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!
 
E2S warning signals - intrinsically safe solutions
E2S warning signals - intrinsically safe solutionsE2S warning signals - intrinsically safe solutions
E2S warning signals - intrinsically safe solutions
 
Pepperl fuchs 2011 Emerson Global Users Exchange Intrinsically Safe CHARMS S...
Pepperl fuchs 2011 Emerson Global Users Exchange  Intrinsically Safe CHARMS S...Pepperl fuchs 2011 Emerson Global Users Exchange  Intrinsically Safe CHARMS S...
Pepperl fuchs 2011 Emerson Global Users Exchange Intrinsically Safe CHARMS S...
 
01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fuses01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fuses
 
Dn 6724
Dn 6724Dn 6724
Dn 6724
 
CM4 Four-Point Continuous Monitor
CM4 Four-Point Continuous MonitorCM4 Four-Point Continuous Monitor
CM4 Four-Point Continuous Monitor
 
Vlfvic010
Vlfvic010Vlfvic010
Vlfvic010
 
Rc 500射频芯片
Rc 500射频芯片Rc 500射频芯片
Rc 500射频芯片
 
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side AccessLayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
LayerZero Series 70: eRDP-FS Remote Distribution Panel with Front/Side Access
 
Bg12 lx
Bg12 lxBg12 lx
Bg12 lx
 
Sr
SrSr
Sr
 
Denon+avc 3808,+avr-3808,+avr-3808 ci
Denon+avc 3808,+avr-3808,+avr-3808 ciDenon+avc 3808,+avr-3808,+avr-3808 ci
Denon+avc 3808,+avr-3808,+avr-3808 ci
 
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power PanelLayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
LayerZero Series 70: eRPP-SL2 Slim Remote Power Panel
 
Aeon labs micro motor controller manual us
Aeon labs micro motor controller manual usAeon labs micro motor controller manual us
Aeon labs micro motor controller manual us
 
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentationPepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
 
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power PanelLayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
LayerZero Series 70: ePanel-1 Wall-Mounted Power Panel
 

Similar to I300

Mmf300
Mmf300Mmf300
Ad355
Ad355Ad355
Mmf302
Mmf302Mmf302
01. sentron 3 wl brochure
01. sentron 3 wl brochure01. sentron 3 wl brochure
01. sentron 3 wl brochure
angelochintu
 
VLT micro drive FC51
VLT micro drive FC51VLT micro drive FC51
Vlt micro drive fc51
Vlt micro drive fc51Vlt micro drive fc51
Vlt micro drive fc51
Toàn Huỳnh
 
System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data Sheet
JMAC Supply
 
Edwards Signaling E-NAC Installation Manual
Edwards Signaling E-NAC Installation ManualEdwards Signaling E-NAC Installation Manual
Edwards Signaling E-NAC Installation Manual
JMAC Supply
 
Manual zxt 600
Manual zxt 600Manual zxt 600
Manual zxt 600
Domotica daVinci
 
Zxr10 introduction to 5928 e
Zxr10 introduction to 5928 eZxr10 introduction to 5928 e
Zxr10 introduction to 5928 e
Meshack Omingo
 
manual dimmer - Zipato
manual dimmer - Zipatomanual dimmer - Zipato
manual dimmer - Zipato
Domotica daVinci
 
H355
H355H355
Remotec ZXT120 manual
Remotec ZXT120 manualRemotec ZXT120 manual
Remotec ZXT120 manual
Domotica daVinci
 
2004 Product Guide
2004 Product Guide2004 Product Guide
2004 Product Guide
pmatas
 
Catalog acb dòng dw fuji electric mới nhất 2019
Catalog acb dòng dw fuji electric mới nhất 2019Catalog acb dòng dw fuji electric mới nhất 2019
Catalog acb dòng dw fuji electric mới nhất 2019
CTY TNHH HẠO PHƯƠNG
 
Track d more performance less power - freescale final
Track d   more performance less power  - freescale finalTrack d   more performance less power  - freescale final
Track d more performance less power - freescale final
chiportal
 
Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0
Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0
Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0
guest9595657
 
Craig & Derricott Enclosed Switchgear Photovoltaic (PV) Isolators
Craig & Derricott Enclosed Switchgear Photovoltaic (PV) IsolatorsCraig & Derricott Enclosed Switchgear Photovoltaic (PV) Isolators
Craig & Derricott Enclosed Switchgear Photovoltaic (PV) Isolators
Thorne & Derrick International
 
Addressable system definition.pdf
Addressable system definition.pdfAddressable system definition.pdf
Addressable system definition.pdf
RicardoHernanGomezB
 
Catalog Inverter FR-E700 Mitsubishi Electric-Beeteco.com
Catalog Inverter FR-E700 Mitsubishi Electric-Beeteco.comCatalog Inverter FR-E700 Mitsubishi Electric-Beeteco.com
Catalog Inverter FR-E700 Mitsubishi Electric-Beeteco.com
Beeteco
 

Similar to I300 (20)

Mmf300
Mmf300Mmf300
Mmf300
 
Ad355
Ad355Ad355
Ad355
 
Mmf302
Mmf302Mmf302
Mmf302
 
01. sentron 3 wl brochure
01. sentron 3 wl brochure01. sentron 3 wl brochure
01. sentron 3 wl brochure
 
VLT micro drive FC51
VLT micro drive FC51VLT micro drive FC51
VLT micro drive FC51
 
Vlt micro drive fc51
Vlt micro drive fc51Vlt micro drive fc51
Vlt micro drive fc51
 
System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data Sheet
 
Edwards Signaling E-NAC Installation Manual
Edwards Signaling E-NAC Installation ManualEdwards Signaling E-NAC Installation Manual
Edwards Signaling E-NAC Installation Manual
 
Manual zxt 600
Manual zxt 600Manual zxt 600
Manual zxt 600
 
Zxr10 introduction to 5928 e
Zxr10 introduction to 5928 eZxr10 introduction to 5928 e
Zxr10 introduction to 5928 e
 
manual dimmer - Zipato
manual dimmer - Zipatomanual dimmer - Zipato
manual dimmer - Zipato
 
H355
H355H355
H355
 
Remotec ZXT120 manual
Remotec ZXT120 manualRemotec ZXT120 manual
Remotec ZXT120 manual
 
2004 Product Guide
2004 Product Guide2004 Product Guide
2004 Product Guide
 
Catalog acb dòng dw fuji electric mới nhất 2019
Catalog acb dòng dw fuji electric mới nhất 2019Catalog acb dòng dw fuji electric mới nhất 2019
Catalog acb dòng dw fuji electric mới nhất 2019
 
Track d more performance less power - freescale final
Track d   more performance less power  - freescale finalTrack d   more performance less power  - freescale final
Track d more performance less power - freescale final
 
Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0
Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0
Profibus Dp Interface Module Users Manual Qj71 Pb92 D Sh Na 0
 
Craig & Derricott Enclosed Switchgear Photovoltaic (PV) Isolators
Craig & Derricott Enclosed Switchgear Photovoltaic (PV) IsolatorsCraig & Derricott Enclosed Switchgear Photovoltaic (PV) Isolators
Craig & Derricott Enclosed Switchgear Photovoltaic (PV) Isolators
 
Addressable system definition.pdf
Addressable system definition.pdfAddressable system definition.pdf
Addressable system definition.pdf
 
Catalog Inverter FR-E700 Mitsubishi Electric-Beeteco.com
Catalog Inverter FR-E700 Mitsubishi Electric-Beeteco.comCatalog Inverter FR-E700 Mitsubishi Electric-Beeteco.com
Catalog Inverter FR-E700 Mitsubishi Electric-Beeteco.com
 

More from sanzen enterprises

Odyssey 3
Odyssey 3Odyssey 3
Vm3240va ce cb1e
Vm3240va ce cb1eVm3240va ce cb1e
Vm3240va ce cb1e
sanzen enterprises
 
Vm 3240 e
Vm 3240 eVm 3240 e
Sv200ma mi1e
Sv200ma mi1eSv200ma mi1e
Sv200ma mi1e
sanzen enterprises
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
sanzen enterprises
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
sanzen enterprises
 
Cs154 cs1e
Cs154 cs1eCs154 cs1e
Cs154 cs1e
sanzen enterprises
 
Bs678 cs1e tei rev1
Bs678 cs1e tei rev1Bs678 cs1e tei rev1
Bs678 cs1e tei rev1
sanzen enterprises
 
Bs633a data sheet
Bs633a data sheetBs633a data sheet
Bs633a data sheet
sanzen enterprises
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
sanzen enterprises
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
sanzen enterprises
 
Data sheet en_us_1911721995
Data sheet en_us_1911721995Data sheet en_us_1911721995
Data sheet en_us_1911721995
sanzen enterprises
 
La1 uw24 x column loudspeakers
La1 uw24 x column loudspeakersLa1 uw24 x column loudspeakers
La1 uw24 x column loudspeakers
sanzen enterprises
 
Bgt 4139 ts
Bgt 4139 tsBgt 4139 ts
Bgt 4139 ts
sanzen enterprises
 
Bgt 5504 a
Bgt 5504 aBgt 5504 a
Bgt 5504 a
sanzen enterprises
 
Bgt 5140 a
Bgt 5140 aBgt 5140 a
Bgt 5140 a
sanzen enterprises
 
Bgt 9120 ts
Bgt 9120 tsBgt 9120 ts
Bgt 9120 ts
sanzen enterprises
 
Bgt 9119 as
Bgt 9119 asBgt 9119 as
Bgt 9119 as
sanzen enterprises
 
Bgt 720 tos
Bgt 720 tosBgt 720 tos
Bgt 720 tos
sanzen enterprises
 
Bgt 5221 as
Bgt 5221 asBgt 5221 as
Bgt 5221 as
sanzen enterprises
 

More from sanzen enterprises (20)

Odyssey 3
Odyssey 3Odyssey 3
Odyssey 3
 
Vm3240va ce cb1e
Vm3240va ce cb1eVm3240va ce cb1e
Vm3240va ce cb1e
 
Vm 3240 e
Vm 3240 eVm 3240 e
Vm 3240 e
 
Sv200ma mi1e
Sv200ma mi1eSv200ma mi1e
Sv200ma mi1e
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
 
Cs154 cs1e
Cs154 cs1eCs154 cs1e
Cs154 cs1e
 
Bs678 cs1e tei rev1
Bs678 cs1e tei rev1Bs678 cs1e tei rev1
Bs678 cs1e tei rev1
 
Bs633a data sheet
Bs633a data sheetBs633a data sheet
Bs633a data sheet
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
 
Data sheet en_us_1911721995
Data sheet en_us_1911721995Data sheet en_us_1911721995
Data sheet en_us_1911721995
 
La1 uw24 x column loudspeakers
La1 uw24 x column loudspeakersLa1 uw24 x column loudspeakers
La1 uw24 x column loudspeakers
 
Bgt 4139 ts
Bgt 4139 tsBgt 4139 ts
Bgt 4139 ts
 
Bgt 5504 a
Bgt 5504 aBgt 5504 a
Bgt 5504 a
 
Bgt 5140 a
Bgt 5140 aBgt 5140 a
Bgt 5140 a
 
Bgt 9120 ts
Bgt 9120 tsBgt 9120 ts
Bgt 9120 ts
 
Bgt 9119 as
Bgt 9119 asBgt 9119 as
Bgt 9119 as
 
Bgt 720 tos
Bgt 720 tosBgt 720 tos
Bgt 720 tos
 
Bgt 5221 as
Bgt 5221 asBgt 5221 as
Bgt 5221 as
 

I300

  • 1. DF-52389:B • E-940 I300(A) Fault Isolator Module Addressable Devices General The Fire•Lite I300(A) Fault Isolator Module is used with Fire•Lite’s addressable fire alarm control panels (FACPs) to protect the system against wire-to-wire short circuits on the SLC loop. The I300(A) should be placed between each device on the SLC loop to isolate a short-circuit problem between the modules. It is required for true Style 7 operation so that other devices can continue to operate normally in the event of a short-circuit on the SLC. Features • Powered by SLC loop directly, no external power required. • Mounts in standard junction boxes (4.0"/10.16 cm square, 2.125"/5.398 cm deep). • Integral LED blinks to indicate normal condition. Illuminates steady when short circuit condition is detected. • High noise (EMF/RFI) immunity. Applications The Fault Isolator Modules should be spaced between groups of sensors in a loop to protect the rest of the loop. Use to iso- late short circuit problems within a section of a loop so that other sections can continue to operate normally. The I300(A) I300(A) supports a maximum of 25 devices in-between isolators, except when using relay bases. • Dimensions: 4.5”H x 4.5”W x 0.25” D (11.43 cm H x NOTE: LOADS PER RELAY BASE AND ISOLATORS/ISOLATOR 11.43 cm W x 0.635 cm D). BASES: The maximum number of addressable devices between isolators (or B224BIA isolator bases) is 25 devices. Construction 25 DEVICES The face plate is made of off-white plastic. Module includes yellow LED indicator that pulses when normal and illuminates isolator isolator steady when a short is detected. module module or base or base 2243devices.wmf detector module Operation Automatically opens circuit when the line voltage drops below four volts. Fault Isolator Modules should be spaced between B224RB relay bases draw more current than other intelligent groups of addressable devices (maximum 25, see notes on devices. When calculating the 25-device maximum, B224RB rep- page 1) in a loop to protect the rest of the loop. If a short resents 2.5 DEVICES; see example on page 2. occurs between any two isolators, then both isolators immedi- NOTE: ON MAXIMUM NUMBER OF DEVICES: See the SLC ately switch to an open circuit state and isolate the groups of Manual (51309) for information on loss of addresses due to current sensors between them. The remaining units on the loop con- limitations. Each module or base added reduces the capacity of tinue to fully operate. address positions in an SLC. All SLC field devices must have been purchased after February 1995 to meet the aforementioned In Style 4 loops, the I300(A) is generally used at each T-tap requirements. If the SLC field devices were purchased prior to branch, to limit the effect of short circuits on a branch to the February 1995, each isolator used reduces the capacity of an SLC devices on that branch. The LED indicator is on continuously by two address positions. Requirements differ as applied to relay during a short circuit condition. bases; see note above. The I300(A) Fault Isolator Module automatically restores the shorted portion of the communications loop to normal. Specifications • Operating voltage: 15 – 32 VDC (peak). Installation • Maximum current upon activation due to short circuit: • Mount on a standard junction box (4.0"/10.16 cm square) refer to the manual for the main FACP. which is at least 2.125"/5.398 cm deep. • Standby current: 450 μA maximum; I300(A) is not isolating • Terminal screws are provided for “in and out” wiring. – relay closed. • Installation instructions are provided with each module. • Temperature range: 32°F to 120°F (0°C to 49°C). • Surface-mount box is available as an option. • Relative humidity: 10% to 93%. • Weight: 5 oz. (150 grams). DF-52389:B • 01/05/2012 — Page 1 of 2
  • 2. Engineering Specifications Agency Approvals and Listings Fault Isolator Modules shall be provided to automatically iso- These listings and approvals apply to the modules specified in late wire-to-wire short circuits on an SLC loop. The Fault Isola- this document. In some cases, certain modules or applications tor Module shall limit the number of modules or detectors that may not be listed by certain approval agencies, or listing may may be rendered inoperative by a short circuit fault on the SLC be in progress. Consult factory for listing details. Loop. If a wire-to-wire short occurs, the Fault Isolator Module • UL Listed: S2424 (I300 only). shall automatically open-circuit (disconnect) the SLC loop. When the short circuit condition is corrected, the Fault Isolator • ULC Listed: S2424 (I300A only). Module shall automatically reconnect the isolated section of • CSFM: 7300-0075:0159. the SLC loop. The Fault Isolator Module shall not require any • MEA: 3-94-E. address-setting, and its operations shall be totally automatic. It • FM Approved. shall not be necessary to replace or reset an Fault Isolator Module after its normal operation. The Fault Isolator Module shall mount in a standard 4" (10.16 cm) deep electrical box, in Product Line Information a surface-mounted backbox, or in the Fire Alarm Control NOTE: “A” suffix indicates ULC Listed model. Panel. It shall provide a single LED which shall flash to indi- cate that the Isolator is operational and shall illuminate steadily I300I300A: Same as I300 with ULC Listing. to indicate that a short circuit condition has been detected and SMB500: Optional surface-mount backbox. isolated. Examples of Device Counts (see notes under Applications) Starts Next Count 52389-2011g.wmf isolator isolator module module or base detector with detector with or base standard base relay base module Counts as... (less than 25 total) Fire·Lite® are registered trademarks of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2 — DF-52389:B • 01/05/2012