IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 54
ENERGY AND EXERGY ANALYSIS OF A 250MW COAL FIRED
THERMAL POWER PLANT AT DIFFERENT LOADS
Soupayan Mitra1
, Joydip Ghosh2
1
Associate Professor, Mechanical Engineering Department, Jalpaiguri Government Engineering College, Jalpaiguri-
735102, West Bengal,India
2
Post Graduate Scholar, Mechanical Engineering Department, Jalpaiguri Government Engineering College,
Jalpaiguri-735102, West Bengal,India
Abstract
In this present investigation exergy and energy efficiencies of a coal fired 250 MW thermal power plant operating in eastern part
of India are determined both for 100% and 90% load based on actual operating data. The efficiencies are evaluated for the
overall plant as well as for different equipments like boiler, turbine, all feed water heaters and condenser. Similarly effectiveness
of the feed water heaters is evaluated for both the loads. Exergy destruction % for each of the equipment are also given for clear
understandingof the loss of available energy due to irreversibilities involved in the processes for each equipment and the whole
plant.
It is observed that a major irreversibility or, exergy destruction takes place at boiler though 1st law energy efficiency is quite
high. This signifies that there might have further scope of improvement in this equipment. Similar analyses are carried out for
other equipments. The results obtained in present analysis are compared with those of other investigators.
Keywords: Energy, Exergy, Efficiency, Effectiveness, Exergy destruction, Power plant
--------------------------------------------------------------------***------------------------------------------------------------------
1. INTRODUCTION
Exergy or, availability of a system signifies the part of the
system energy that can be converted into maximum useful
or desired work with respect to immediate surrounding
condition, referred to as ‘dead state’. The term Exergy was
used for the first time by Rant, Z. in 1956. According to 1st
law of thermodynamics energy is conserved, but energy is
conserved only quantitatively and not qualitatively. But
exergy is a manifestation of quality of energy and unlike
energy, exergy is not conserved and in fact, get destroyed
due to irreversibility during a process. The energy efficiency
or, 1st law efficiency merely implies the ratio of desired or,
useful work output against total energy input for a system.
But this does not consider the true capability of the system
by considering the thermodynamic limitations for which the
system is not responsible. Efficiency based on exergy for
any system like whole thermal power plant or, say, a turbine
reflect the true capability of the concerned system i.e., their
actual working capability against their maximum possible
capability due to irreversibility present in the system
process. Thus unlike, energy efficiency, exergy efficiency
gives more insight into the problem and help design, analyse
and performance improvement of the energy conversion
systems more effectively by identifying the locations and
associated irreversibilities. A relationship between energy
and exergy is pictorially shown in Fig-1.Of late, many
researchers are using exergy methodology for analysing
different types of energy conversion systems [1– 6] and in
fact, some good books are now available in this arena [8 –
10].
In the present investigation, for a 250 MW thermal power
plant energy, exergy efficiency and effectiveness of different
equipments as well as for the whole plant are determined
based on plant operating data at 100% and 90% load. The
results for the loads are compared, analysed and discussed.
The present results obtained are compared with those of
other investigators. It is believed that present investigation
will help understanding the possible improvement locations
for a power plant as well as will indicate the priority areas of
action for better performance and operation of the plant.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 55
Fig-1: Relationship between Energy and Exergy
2. A BRIEF NOTE ABOUT THE POWER PLANT
SELECTED FOR PRESENT ANALYSIS
For the present analysis operating data of a 250 MW thermal
power plant located in India are collected. The plant was
commissioned about six years back and running smoothly.
The plant is based on cornered fired firing technology. The
prevailing ambient temperature varies from 0 to 450
C,
normal being about 300
C. At the time of collecting data
temperature was 300
C. It’s a condensing steam plant and
like other steam power plant it runs on Rankine cycle. Water
from river is chemically treated and demineralised at D.M
(Demineralised) plant. Water enters into boiler through
economiser and ultimately converted into superheated
steam. The superheated steam passes through HP, IP, LP
turbines and turbine shafts are coupled with generator to
produce electric power. Exhaust two-phase steam from LP
turbine then enters into condenser and get condensed by
circulating cooling water. The condensate then passes
through low pressure (LP) heaters and deaerator. After
deaerator by feed pump pressure of the water is raised
considering the pressure required for boiler and then water
passes through high pressure (HP) feed water heaters and
enters into boiler through economiser and the cycle repeats.
The LP, HP and deaerator are continuously supplied with
bled or, extracted steam from CRH ( Cold ReHeat ) line, IP
and LP turbines at selective points. The details of the plant
layout including extraction of steams, heater drips etc. are
shown in Fig-2.
The plant normally runs on E-grade coal. The ultimate
analysis of operating coal is given by C = 34.20%, H =
5.00%, N = 1.80%, O = 10.70%, M (moisture) = 8.00%, S=
0.30 %. Ash = 40.00% . Coal GCV is 3700 KCal/kg
i.e.15490 KJ/kg.
3. REFERENCE OR DEAD STATE
In any exergy analysis proper selection of reference or Dead
state is of extreme importance. The exergy value of any
system, flow or equipment depends on the reference or Dead
state. In our exergy analysis the dead state pressure(po)and
temperature(To)are considered as 1 bar and 303 K i.e., 300
C
respectively.In fact, this corresponds to plant operating
ambient condition. Dead state enthalpy ( ho) and entropy (
so) are given by 125.83 KJ/kg and 0.437 KJ/kg-K
respectively.
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 56
4. FLOW LAYOUT DIAGRAM OF THE POWER PLANT
Total flow layout of the power plant is shown in Fig.-2
Fig-2: Plant flow layout diagram
5. METHODOLOGY OF ANALYSIS :
In this present investigation following methodology and
equations are used to determine energy, exergy efficiencies,
and effectiveness of different equipments like boiler,
turbine, heaters, and condenser of the plant. We note that all
the flow processes through different equipments of the
thermal power plant individually and also through the whole
power plant are steady and hence no energy or exergy is
stored within any system or equipment.
 Mass balance equation :
𝑚𝑖𝑛 = 𝑚 𝑜𝑢𝑡 1
 Energy balance equation :
𝐸𝑖𝑛
𝑖𝑛
+ 𝑄 = 𝐸𝑜𝑢𝑡
𝑜𝑢𝑡
+ 𝑊 (2)
 General Exergy balance equation :
𝑚𝑖𝑛 𝑥𝑖𝑛
𝑖𝑛
+ 𝑋 𝑄 + 𝑋 𝐶𝐻
= 𝑚 𝑜𝑢𝑡 𝑥 𝑜𝑢𝑡
𝑜𝑢𝑡
+ 𝑊 + 𝑋 𝑑𝑒𝑠 3
 Energy efficiency equation or, 1st Law efficiency :
η1 =
Useful i.e.desired energy output
Total energy input
(4)
But, for condenser,
η1=
Actual temperature rise of the cold fluid
Maximum possible temperature rise of the cold fluid
For example, overall power plant,
η1 =
Total Power output
Total Energy supplied by fuel
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 57
 Exergy efficiency equation or, 2nd Law efficiency :
η2=
Exergy recovered
Total exergy input or,supplied
or, may be given by,
=
Actual thermal efficiency
Maximum possible reversible thermal efficiency
(5)
 Effectiveness ( for heaters) :
ϵ=
Actual temperature rise of the cold fluid
Maximum possible temperature rise of the cold fluid
(6)
 Total exergy flow rate into a control volume or, an
equipment is given by :
𝑋𝑖𝑛 = 𝑚𝑖𝑛 𝑥𝑖𝑛 (7)
Similarly, exergy outlet flow rate can be determined.
 Specific exergyis given by :
x= ( h – ho) – To ( s – so ) (8)
6. ENERGY AND EXERGY FLOW RATES
THROUGHOUT THE POWER PLANT
In Table-1, at 100% load operating pressure, temperature
and flow of the working fluid are given in each node of the
plant corresponding to Fig-2. Based on this in the same
Table-1, at 100% load corresponding specific enthalpy,
specific entropy, total energy flow rate and total exergy flow
rate are given. For 90% load corresponding operating
parameters are not tabulated here, but all relevant
calculations are carried out and results are shown.
Table-1: Operational Data For 100% Load at Each Node Shown in Fig.-2
Node [Pr, bar] [Temp,0
C] [Flow, TPH] [h, kJ/kg] [s, kJ/kg-K] [𝐸, MW ] [𝑋, MW ]
1 147.00 549.00 785.00 3450.940 6.532 752.497 322.357
2 40.50 549.00 715.00 3557.460 7.226 706.551 273.003
3 41.53 360.00 785.00 3114.730 6.602 679.184 244.420
4 41.53 360.00 715.00 3114.730 6.602 618.620 222.624
5 41.53 360.00 70.00 3114.730 6.602 60.564 21.795
6 20.00 437.00 68.00 3329.510 7.247 62.891 21.538
7 10.00 348.00 647.00 3153.920 7.296 566.830 170.703
8 10.00 348.00 627.20 3153.920 7.296 549.483 165.479
9 10.00 348.00 19.80 3153.920 7.296 17.347 5.224
10 1.82 216.00 30.00 2903.710 7.620 24.198 5.012
11 1.64 120.00 38.00 2709.810 7.226 28.604 5.562
12 0.10 45.800 559.20 2414.000 7.575 374.975 19.472
13 0.10 45.800 559.20 199.660 0.649 31.014 1.490
14 0.10 45.80 635.20 199.660 0.649 35.229 1.693
15 12.00 51.000 635.20 214.540 0.716 37.854 0.736
16 10.00 76.00 635.20 318.940 1.027 56.275 2.530
17 8.00 98.00 635.20 411.200 1.284 72.554 5.069
18 6.00 158.80 795.00 670.500 1.931 148.069 20.314
19 20.00 167.00 795.00 706.790 2.011 156.083 22.975
20 190.00 171.00 795.00 733.740 2.029 162.034 27.722
21 189.00 207.00 795.00 890.810 2.369 196.721 39.658
22 185.00 242.00 795.00 1049.070 2.688 231.670 53.262
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 58
23 175.00 253.00 795.00 1100.440 2.789 243.014 57.848
24 8.00 170.40 138.00 721.020 2.046 27.639 4.127
25 26.00 215.00 70.000 920.760 2.471 17.904 3.473
26 10.00 210.00 2.000 2852.200 6.746 1.585 0.453
27 0.80 93.40 38.000 391.640 1.232 4.134 0.263
28 1.00 99.60 30.000 417.440 1.302 3.479 0.246
29 6.00 30.00 33000.00 126.29 0.437 1157.650 4.216
30 5.00 38.90 33000.00 163.380 0.558 1497.650 8.131
7. SOME SAMPLE CALCULATIONS
Some sample calculations are carried out hereunder to
illustrate the use of the above equations.
(1) Energy efficiency (η1) of overall plant at 100 % load :
Total gross power output from the power plant at 100% load
= 250 MW.
Energy supplied by coal to the plant at 100% load = Coal
GCV ( 15490kJ/kg) × Coal firing rate (158 TPH i.e.43.88
kg/s ) = 679.7012 MW.
η1= ( 250/679.7012 ) × 100 % = 36.78 %
Similarly,at 90% load with coal firing rate 151 TPH, η1 =
(225 MW /651.90 MW)× 100% = 34.51 %
(2)Efficiency (η1) of Condenser at 100% load
η1=
Actual temperature rise of the cooling water
saturated steam inlet temp .to condenser − Cooling water inlet temp
= [( 38.90 – 30 ) /(45.8 – 30 ) ] × 100% = 56.32 %
(3) Exergy efficiency (η2)of L.P. Heater (LPH) No.-2 at
100% load
Total Exergysuppliedto the heater = 𝑋16 + 𝑋10 = 2.53 +
5.012 = 7.542 MW
Total Exergyrecovered from the heater = 𝑋17 + 𝑋27= 5.069
+ 0.246 = 5.315 MW
Therefore, η2 = ( 5.315/ 7.542 ) × 100% = 70.47 %
(4) Exergy efficiency (η2) of Boiler at 100% load :
Exergy supply by coal= Coal GCV(15490 kJ/kg ) × Coal
firing rate (158 TPH i.e., 43.8888 kg/s) × 1.06= 720.4832
MW
where 1.06 is the Exergy Grade Function( f )for coal [ 7 , 8
].
Exergy flow into boiler = 𝑋23 + 𝑋4 + Coal exergy=
1000.95 MW
Exergy flow out from the boiler = 𝑋1 + 𝑋2= 595.36 MW.
η2= (595.36 /1000.95) × 100% = 59.47 %
(5) Effectiveness (ϵ) of HPH No.-1 at 100% load :
Actual temperature rise of cold fluid = ( 207 – 171 ) 0
C = 36
0
C
Maximum possible temperature rise = ( hotfluid inlet
temperature, 437 0
C)– ( 1710
C ) = 266 0
C
Effectiveness (ϵ)= 36 0
C/266 0
C = 0.135
8. RESULTS AND DISCUSSION
All relevant calculations are done based on above stated
methodology for both 100% and 90% load at different
equipment level as well as considering the whole power
plant. The results obtained are given in both tabular and
graphical forms for ease of comparison and understanding.
In Table-2,η1 and η2for 90% and 100% load are given side
by side.
Table-2: Energy and Exergy efficiencies for 100% and 90% load
Equipment 100% Load 90% Load
η1 ( % ) η2 ( % ) η1 ( % ) η2 ( % )
Boiler 94.52 59.47 94.38 58.05
Turbine 91.96 84.99 87.05 79.55
Condenser 56.32 40.61 69.04 43.93
Overall Plant 36.78 32.15 34.51 30.34
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 59
Table-3: Exergy efficiency and effectiveness for 100% and 90% load
Equipment 100% Load 90% Load
η2 ( % ) ϵ η2 ( % ) ϵ
LPH-1 44.35 0.36 43.82 0.33
LPH-2 70.47 0.15 71.56 0.14
HPH-1 83.03 0.13 81.42 0.12
HPH-2 92.32 0.22 93.78 0.25
Fig.-3: Energy Efficiency(η1 , % )
Fig.-4: Exergy Efficiency (η2, % )
0 10 20 30 40 50 60 70 80 90 100
Boiler
Turbine
Condenser
Overall Plant
Energy Efficiency ( % )
90% Load
100% Load
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
LPH-1
LPH-2
HPH-1
HPH-2
Boiler
Turbine
Condenser
Overall Plant
Exergy Efficiency ( % )
90% Load
100% Load
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 60
Fig.-5: Effectiveness of Heaters (ϵ)
Fig.-6: Exergy destruction ( % ) for equipment & overall plant at 100% load
We searched literatures to compare our results to those
obtained by other investigators. But not much data are
available for energy and exergy efficiency and for
effectiveness of individual component and for the overall
power plant of 250 MW capacity under more or less similar
conditions to ours. In some cases only some scattered data
are available. Based on the available data, we have
compared our results which are given in Table-4 and Table-
5.
Table – 4: Comparison of Energy efficiency ( η1 in % )and effectiveness (ϵ )at 100% load
Sl No. Parameter Present Investigation Ref [3]
1. Boiler η1 94.52 85.23
2. Condenser η1 56.32 53.33
3. Overall Plantη1 36.78 36.74
4. LPH-1 ϵ 0.36 0.46
5. LPH-2 ϵ 0.15 0.14
6. HPH-1 ϵ 0.13 0.13
7. HPH-2 ϵ 0.22 0.29
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
LPH-1
LPH-2
HPH-1
HPH-2
90% Load
100% Load
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 61
Table-5: Comparison of Exergy efficiency (η2 in % ) at 100% load
Sl No. Parameter
Present
Investigation
Ref [4 ] Ref[5] Ref [6]
1. Boiler η2 59.47 46.24 53.00 48.55
2. Turbine η2 84.99 87.78 92.25 92.71
3. Overall Plant η2 32.15 NA 36.80 44.07
4. LPH-1 η2 44.35 89.71 NA NA
5. LPH-2 η2 70.47 96.46 NA NA
6. HPH-1 η2 83.03 97.64 NA NA
7. HPH-2 η2 92.32
93.52
NA NA
From the above results and comparison, it is clear that our
obtained results compare reasonably well with other
available results of similar category power plant. Of course,
the energy and exergy efficiency and effectiveness of
heaters in a plant depend on many other factors apart from
size of the plant. For example, ultimate composition of coal,
coal GCV, coal burning mechanism and associated
irresversibilities in the combustion process and
irreversibility for large temperature gradient heat transfer
from flue gas to water & steam, individual equipment
irreversibility, prevailing ambient condition are some of the
factors to name which effect the performance of the plant
and the plant equipments. Finally, our results along with
other available results can generate a data pool and by
analysing this type of data pool more insights about the
performance of the power plant and its equipments can be
obtained. This definitely will boil down to more effective
design and operation of the power plant and thereby will
save our precious energy resources and help reduce
pollution effects.
9. CONCLUSION
In this present study energy, exergy efficiencies and
effectiveness of different relevant equipments as well as for
the overall plant are carried out both at 100 % and 90% load
for a 250 MW coal fired power plant based on plant
operating data. The energy and exergy flow rates at each of
the nodal points of the whole plant are calculated and
tabulated. All relevant equations for performance
calculations are illustrated by carrying out some sample
calculations for each of the different situation. From the
analysis it is found that major energy loss in the plant occurs
at the condenser due to phase conversion of working fluid.
Similarly major exergy loss occurs at the boiler and the
condenser. Our results are compared reasonably well with
other available investigators results for similar type of power
plants; of course there are certain deviations. It is expected
that all these data will form a pool of plant performance data
which may ultimately results in better understanding of the
plantand thereby possibly help improvement in plant design
and operation.
NOMENCLATURE
E : Energy [MW ]
h : Specific enthalpy [kJ/kg]
m : Mass [Ton]
s : Specific entropy [kJ/kg-K]
X : Total exergy [MW]
x : Specific Exergy [kW]
ECO : Economizer
GCV : Gross Calorific Value [kJ/kg]
HPH : High Pressure Heater
HPT : High Pressure Turbine
IPT : Intermediate Pressure Turbine
LPH : Low Pressure Heater
LPT : Low Pressure Turbine
NA : Not available
Q : Heat input [MW]
TPH : Ton per hour
W : Work output [MW]
ϵ : Effectiveness [unit less ]
η1 : Energy efficiency or, 1st law efficiency [ % ]
η2 : Exergyefficiency or, 2nd law efficiency [% ]
Subscripts
des : destruction
in : at inlet condition
out : at outlet condition
0 : reference or, dead state
.(dot) : ‘dot’ over any parameter implies corresponding flow
rate
REFERENCES
[1] Dincer and H. Al-Muslim ; ‘Thermodynamics
analysis of reheat cycle steam power plant’, Int. J.
Energy Research, vol :25(8), 2001
[2] S. C. Kaushik, V. S. Reddy and S. K. Tyagi ; ‘Energy
and exergy analyses of thermal power plants : A
review’, J. of Renewable and Sustainable Energy
Reviews (RESR), Elsevier, vol :15, 2011
[3] M. Bajwa and P. Gulati ; ‘Comparing the thermal
power plant performance at various output loads by
energy auditing ( a statistical analysing tool )’, Int. J.
Mechanical Engg & Tech. (IJMET), vol :2, issue :2,
May-July2011
[4] K. Maghsoudi, A. Mehrpanahi and M. Tabaraki ;
‘Energy and exergy analysis of 250 MW steam
power plant’, Switzerland Research Park Journal, vol
:102, no. :11, Nov2013.
[5] M. Ameri, P. Ahmadi and A. Hamidi ; ‘Energy,
exergy and exergoeconomic analysis of a steam
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 62
power plant : a case study’, Int. Journal of Exergy
Research, vol :33, 2009
[6] H. Zhao and Y. Chai ; ‘Exergy analysis of a power
cycle system with 300 MW capacity’, Proc. Int.
Conf. on ‘Advances in energy engineering’, Beijing,
Chain, June 2010, IEEE
[7] G. Reistad ; ‘Available energy conversion &
utilization in the United States’. Journal of Energy
Power,Vol :9, 1975
[8] Dincer & M. A. Rosen ; ‘Exergy Energy,
Environment and sustainable development’, Elsevier
publication, 2007
[9] T. J. Kotas ; ‘The Exergy method of thermal plant
analysis’, Butterwards Pub., 1995
[10] J. Szargut, D.R. Morris and F.R Steward ; ‘Exergy
Analysis of thermal, chemical and metallurgical
process’, Hemisphere, NewYork, 1988.
BIOGRAPHIES
Dr. Soupayan Mitra, (B.E) From North
Bengal University, (M.M.E) From
Jadavpur University, [Ph.D(Engg.)]
From Jadavpur University. Associate
Professor, Department of Mechanical
Engineering Jalpaiguri Government
Engineering College Jalpaiguri -735102,
West Bengal, India
Joydip Ghosh, (B.Tech) from West
Bengal University of Technology
(M.Tech) from Jalpaiguri Government
Engineering College. Post Graduate
Scholar, Department of Mechanical
Engineering, Jalpaiguri Government
Engineering College Jalpaiguri -735102,
West Bengal, India

More Related Content

What's hot

Simulation of the effects of turbine exhaust recirculation
Simulation of the effects of turbine exhaust recirculationSimulation of the effects of turbine exhaust recirculation
Simulation of the effects of turbine exhaust recirculationZin Eddine Dadach
 
Lecture 3-4: Exergy, Heating and Cooling, Solar Thermal
Lecture 3-4: Exergy, Heating and Cooling, Solar ThermalLecture 3-4: Exergy, Heating and Cooling, Solar Thermal
Lecture 3-4: Exergy, Heating and Cooling, Solar Thermalcdtpv
 
Energy and Exergy Analysis of a Country Sectors - Advanced Thermodynamics
Energy and Exergy Analysis of a Country Sectors - Advanced ThermodynamicsEnergy and Exergy Analysis of a Country Sectors - Advanced Thermodynamics
Energy and Exergy Analysis of a Country Sectors - Advanced ThermodynamicsMostafa Ghadamyari
 
available energy ,irreversibility,exchargy
available energy ,irreversibility,exchargyavailable energy ,irreversibility,exchargy
available energy ,irreversibility,exchargypaneliya sagar
 
2007 PROJECT DOCUMENT ON EXERGY
2007  PROJECT DOCUMENT ON EXERGY 2007  PROJECT DOCUMENT ON EXERGY
2007 PROJECT DOCUMENT ON EXERGY Alekhya Madisetty
 
Exergy notes
Exergy notesExergy notes
Exergy notesSafeer Mt
 
First law of thermodynamics
First law of thermodynamicsFirst law of thermodynamics
First law of thermodynamicsKapil Goyal
 
Depc A Abusoglu
Depc A AbusogluDepc A Abusoglu
Depc A AbusogluAbusoglu
 
The first law of thermodynamics
The first law of thermodynamicsThe first law of thermodynamics
The first law of thermodynamicspaneliya sagar
 
2nd law of thermodynamics, entropy
2nd law of thermodynamics, entropy2nd law of thermodynamics, entropy
2nd law of thermodynamics, entropyposhiyabhavin
 
THE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial Engineerig
THE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial EngineerigTHE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial Engineerig
THE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial EngineerigKum Visal
 
Laws of thermodynamics
Laws of thermodynamicsLaws of thermodynamics
Laws of thermodynamicsFaraz Ahmed
 
Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...
Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...
Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...Varun Pratap Singh
 
Impact of solar radiation and temperature levels on the variation of the seri...
Impact of solar radiation and temperature levels on the variation of the seri...Impact of solar radiation and temperature levels on the variation of the seri...
Impact of solar radiation and temperature levels on the variation of the seri...eSAT Journals
 
Physics Thermodynamics
Physics ThermodynamicsPhysics Thermodynamics
Physics ThermodynamicsHaroun Elmir
 
Second law of thermodynamics
Second law of thermodynamicsSecond law of thermodynamics
Second law of thermodynamicssachin chaurasia
 

What's hot (20)

Simulation of the effects of turbine exhaust recirculation
Simulation of the effects of turbine exhaust recirculationSimulation of the effects of turbine exhaust recirculation
Simulation of the effects of turbine exhaust recirculation
 
Lecture 3-4: Exergy, Heating and Cooling, Solar Thermal
Lecture 3-4: Exergy, Heating and Cooling, Solar ThermalLecture 3-4: Exergy, Heating and Cooling, Solar Thermal
Lecture 3-4: Exergy, Heating and Cooling, Solar Thermal
 
Energy and Exergy Analysis of a Country Sectors - Advanced Thermodynamics
Energy and Exergy Analysis of a Country Sectors - Advanced ThermodynamicsEnergy and Exergy Analysis of a Country Sectors - Advanced Thermodynamics
Energy and Exergy Analysis of a Country Sectors - Advanced Thermodynamics
 
available energy ,irreversibility,exchargy
available energy ,irreversibility,exchargyavailable energy ,irreversibility,exchargy
available energy ,irreversibility,exchargy
 
2007 PROJECT DOCUMENT ON EXERGY
2007  PROJECT DOCUMENT ON EXERGY 2007  PROJECT DOCUMENT ON EXERGY
2007 PROJECT DOCUMENT ON EXERGY
 
Energy, Heat and Work
Energy, Heat and WorkEnergy, Heat and Work
Energy, Heat and Work
 
Exergy notes
Exergy notesExergy notes
Exergy notes
 
Overview of thermodynamics
Overview of thermodynamicsOverview of thermodynamics
Overview of thermodynamics
 
First law of thermodynamics
First law of thermodynamicsFirst law of thermodynamics
First law of thermodynamics
 
Depc A Abusoglu
Depc A AbusogluDepc A Abusoglu
Depc A Abusoglu
 
The first law of thermodynamics
The first law of thermodynamicsThe first law of thermodynamics
The first law of thermodynamics
 
2nd law of thermodynamics, entropy
2nd law of thermodynamics, entropy2nd law of thermodynamics, entropy
2nd law of thermodynamics, entropy
 
THE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial Engineerig
THE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial EngineerigTHE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial Engineerig
THE SECOND LAW OF THERMODYNAMICS For Mechanical and Industrial Engineerig
 
Laws of thermodynamics
Laws of thermodynamicsLaws of thermodynamics
Laws of thermodynamics
 
Ch04
Ch04Ch04
Ch04
 
Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...
Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...
Basic mechanical engineering(BMET-101/102) unit 2 (part-2) thermodynamics law...
 
Applications of thermodynamics
Applications of thermodynamicsApplications of thermodynamics
Applications of thermodynamics
 
Impact of solar radiation and temperature levels on the variation of the seri...
Impact of solar radiation and temperature levels on the variation of the seri...Impact of solar radiation and temperature levels on the variation of the seri...
Impact of solar radiation and temperature levels on the variation of the seri...
 
Physics Thermodynamics
Physics ThermodynamicsPhysics Thermodynamics
Physics Thermodynamics
 
Second law of thermodynamics
Second law of thermodynamicsSecond law of thermodynamics
Second law of thermodynamics
 

Similar to Energy and exergy analysis of a 250 mw coal fired thermal power plant at different loads

Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...IJERA Editor
 
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...IJERA Editor
 
Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...
Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...
Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...theijes
 
Performance analysis of partially covered photovoltaic thermal (pvt) water co...
Performance analysis of partially covered photovoltaic thermal (pvt) water co...Performance analysis of partially covered photovoltaic thermal (pvt) water co...
Performance analysis of partially covered photovoltaic thermal (pvt) water co...eSAT Journals
 
IRJET-Detailed Energy Audit in a Captive Cogeneration Plant
IRJET-Detailed Energy Audit in a Captive Cogeneration PlantIRJET-Detailed Energy Audit in a Captive Cogeneration Plant
IRJET-Detailed Energy Audit in a Captive Cogeneration PlantIRJET Journal
 
Investigating The Performance of A Steam Power Plant
Investigating The Performance of A Steam Power PlantInvestigating The Performance of A Steam Power Plant
Investigating The Performance of A Steam Power PlantIJMERJOURNAL
 
Analysis and optimization of mechanical utility system
Analysis and optimization of mechanical utility systemAnalysis and optimization of mechanical utility system
Analysis and optimization of mechanical utility systemeSAT Journals
 
Energy audit in Industry.pptx
Energy audit in Industry.pptxEnergy audit in Industry.pptx
Energy audit in Industry.pptxAyush51240
 
Stirling engine performance prediction using schmidt
Stirling engine performance prediction using schmidtStirling engine performance prediction using schmidt
Stirling engine performance prediction using schmidteSAT Publishing House
 
COMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMES
COMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMESCOMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMES
COMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMESijmech
 
Exergy analysis and igcc plant technology to improve the efficiency and to re...
Exergy analysis and igcc plant technology to improve the efficiency and to re...Exergy analysis and igcc plant technology to improve the efficiency and to re...
Exergy analysis and igcc plant technology to improve the efficiency and to re...eSAT Publishing House
 
An approach to evaluate the heat exchanger retrofit for installed industrial ...
An approach to evaluate the heat exchanger retrofit for installed industrial ...An approach to evaluate the heat exchanger retrofit for installed industrial ...
An approach to evaluate the heat exchanger retrofit for installed industrial ...eSAT Journals
 
Novel technique for maximizing the thermal efficiency of a hybrid pv
Novel technique for maximizing the thermal efficiency of a hybrid pvNovel technique for maximizing the thermal efficiency of a hybrid pv
Novel technique for maximizing the thermal efficiency of a hybrid pveSAT Journals
 
Stirling engine performance prediction using schmidt analysis by considering ...
Stirling engine performance prediction using schmidt analysis by considering ...Stirling engine performance prediction using schmidt analysis by considering ...
Stirling engine performance prediction using schmidt analysis by considering ...eSAT Journals
 
Comparison of Differential Evolution and Particle Swarm Optimization for Opti...
Comparison of Differential Evolution and Particle Swarm Optimization for Opti...Comparison of Differential Evolution and Particle Swarm Optimization for Opti...
Comparison of Differential Evolution and Particle Swarm Optimization for Opti...IOSRJEEE
 
Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...
Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...
Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...IJMER
 
Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...
Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...
Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...IJPEDS-IAES
 
IRJET- Thermoelectrical Generator for Waste heat Recovery- Review
IRJET-  	  Thermoelectrical Generator for Waste heat Recovery- ReviewIRJET-  	  Thermoelectrical Generator for Waste heat Recovery- Review
IRJET- Thermoelectrical Generator for Waste heat Recovery- ReviewIRJET Journal
 
comparative analysis of solar photovoltaic thermal (pvt) water and solar
comparative analysis of solar photovoltaic thermal (pvt) water and solarcomparative analysis of solar photovoltaic thermal (pvt) water and solar
comparative analysis of solar photovoltaic thermal (pvt) water and solarIJCMESJOURNAL
 

Similar to Energy and exergy analysis of a 250 mw coal fired thermal power plant at different loads (20)

Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
 
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
Application of Exergy and Taguchi Methodology for a Power Plant under Varying...
 
Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...
Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...
Enhancing the Performance of 75mw Steam Power Plant with Second Law Efficienc...
 
Performance analysis of partially covered photovoltaic thermal (pvt) water co...
Performance analysis of partially covered photovoltaic thermal (pvt) water co...Performance analysis of partially covered photovoltaic thermal (pvt) water co...
Performance analysis of partially covered photovoltaic thermal (pvt) water co...
 
IRJET-Detailed Energy Audit in a Captive Cogeneration Plant
IRJET-Detailed Energy Audit in a Captive Cogeneration PlantIRJET-Detailed Energy Audit in a Captive Cogeneration Plant
IRJET-Detailed Energy Audit in a Captive Cogeneration Plant
 
Investigating The Performance of A Steam Power Plant
Investigating The Performance of A Steam Power PlantInvestigating The Performance of A Steam Power Plant
Investigating The Performance of A Steam Power Plant
 
Analysis and optimization of mechanical utility system
Analysis and optimization of mechanical utility systemAnalysis and optimization of mechanical utility system
Analysis and optimization of mechanical utility system
 
Energy audit in Industry.pptx
Energy audit in Industry.pptxEnergy audit in Industry.pptx
Energy audit in Industry.pptx
 
Stirling engine performance prediction using schmidt
Stirling engine performance prediction using schmidtStirling engine performance prediction using schmidt
Stirling engine performance prediction using schmidt
 
COMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMES
COMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMESCOMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMES
COMPARATIVE STUDY OF DIFFERENT COMBINED CYCLE POWER PLANT SCHEMES
 
Exergy analysis and igcc plant technology to improve the efficiency and to re...
Exergy analysis and igcc plant technology to improve the efficiency and to re...Exergy analysis and igcc plant technology to improve the efficiency and to re...
Exergy analysis and igcc plant technology to improve the efficiency and to re...
 
An approach to evaluate the heat exchanger retrofit for installed industrial ...
An approach to evaluate the heat exchanger retrofit for installed industrial ...An approach to evaluate the heat exchanger retrofit for installed industrial ...
An approach to evaluate the heat exchanger retrofit for installed industrial ...
 
Novel technique for maximizing the thermal efficiency of a hybrid pv
Novel technique for maximizing the thermal efficiency of a hybrid pvNovel technique for maximizing the thermal efficiency of a hybrid pv
Novel technique for maximizing the thermal efficiency of a hybrid pv
 
Stirling engine performance prediction using schmidt analysis by considering ...
Stirling engine performance prediction using schmidt analysis by considering ...Stirling engine performance prediction using schmidt analysis by considering ...
Stirling engine performance prediction using schmidt analysis by considering ...
 
Comparison of Differential Evolution and Particle Swarm Optimization for Opti...
Comparison of Differential Evolution and Particle Swarm Optimization for Opti...Comparison of Differential Evolution and Particle Swarm Optimization for Opti...
Comparison of Differential Evolution and Particle Swarm Optimization for Opti...
 
Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...
Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...
Energy Based Analysis of a Thermal Power Station for Energy Efficiency Improv...
 
Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...
Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...
Thermodynamic modeling and Exergy Analysis of Gas Turbine Cycle for Different...
 
IRJET- Thermoelectrical Generator for Waste heat Recovery- Review
IRJET-  	  Thermoelectrical Generator for Waste heat Recovery- ReviewIRJET-  	  Thermoelectrical Generator for Waste heat Recovery- Review
IRJET- Thermoelectrical Generator for Waste heat Recovery- Review
 
comparative analysis of solar photovoltaic thermal (pvt) water and solar
comparative analysis of solar photovoltaic thermal (pvt) water and solarcomparative analysis of solar photovoltaic thermal (pvt) water and solar
comparative analysis of solar photovoltaic thermal (pvt) water and solar
 
R&D of Photovoltaic Thermal (PVT) Systems: an Overview
R&D of Photovoltaic Thermal (PVT) Systems: an OverviewR&D of Photovoltaic Thermal (PVT) Systems: an Overview
R&D of Photovoltaic Thermal (PVT) Systems: an Overview
 

More from eSAT Journals

Mechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavementsMechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavementseSAT Journals
 
Material management in construction – a case study
Material management in construction – a case studyMaterial management in construction – a case study
Material management in construction – a case studyeSAT Journals
 
Managing drought short term strategies in semi arid regions a case study
Managing drought    short term strategies in semi arid regions  a case studyManaging drought    short term strategies in semi arid regions  a case study
Managing drought short term strategies in semi arid regions a case studyeSAT Journals
 
Life cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangaloreLife cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangaloreeSAT Journals
 
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialsLaboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialseSAT Journals
 
Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...eSAT Journals
 
Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...eSAT Journals
 
Influence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizerInfluence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizereSAT Journals
 
Geographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementGeographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementeSAT Journals
 
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...eSAT Journals
 
Factors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concreteFactors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concreteeSAT Journals
 
Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...eSAT Journals
 
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...eSAT Journals
 
Evaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabsEvaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabseSAT Journals
 
Evaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in indiaEvaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in indiaeSAT Journals
 
Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...eSAT Journals
 
Estimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodEstimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodeSAT Journals
 
Estimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniquesEstimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniqueseSAT Journals
 
Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...eSAT Journals
 
Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...eSAT Journals
 

More from eSAT Journals (20)

Mechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavementsMechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavements
 
Material management in construction – a case study
Material management in construction – a case studyMaterial management in construction – a case study
Material management in construction – a case study
 
Managing drought short term strategies in semi arid regions a case study
Managing drought    short term strategies in semi arid regions  a case studyManaging drought    short term strategies in semi arid regions  a case study
Managing drought short term strategies in semi arid regions a case study
 
Life cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangaloreLife cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangalore
 
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialsLaboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
 
Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...
 
Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...
 
Influence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizerInfluence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizer
 
Geographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementGeographical information system (gis) for water resources management
Geographical information system (gis) for water resources management
 
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
 
Factors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concreteFactors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concrete
 
Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...
 
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
 
Evaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabsEvaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabs
 
Evaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in indiaEvaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in india
 
Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...
 
Estimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodEstimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn method
 
Estimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniquesEstimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniques
 
Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...
 
Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...
 

Recently uploaded

Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 

Energy and exergy analysis of a 250 mw coal fired thermal power plant at different loads

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 54 ENERGY AND EXERGY ANALYSIS OF A 250MW COAL FIRED THERMAL POWER PLANT AT DIFFERENT LOADS Soupayan Mitra1 , Joydip Ghosh2 1 Associate Professor, Mechanical Engineering Department, Jalpaiguri Government Engineering College, Jalpaiguri- 735102, West Bengal,India 2 Post Graduate Scholar, Mechanical Engineering Department, Jalpaiguri Government Engineering College, Jalpaiguri-735102, West Bengal,India Abstract In this present investigation exergy and energy efficiencies of a coal fired 250 MW thermal power plant operating in eastern part of India are determined both for 100% and 90% load based on actual operating data. The efficiencies are evaluated for the overall plant as well as for different equipments like boiler, turbine, all feed water heaters and condenser. Similarly effectiveness of the feed water heaters is evaluated for both the loads. Exergy destruction % for each of the equipment are also given for clear understandingof the loss of available energy due to irreversibilities involved in the processes for each equipment and the whole plant. It is observed that a major irreversibility or, exergy destruction takes place at boiler though 1st law energy efficiency is quite high. This signifies that there might have further scope of improvement in this equipment. Similar analyses are carried out for other equipments. The results obtained in present analysis are compared with those of other investigators. Keywords: Energy, Exergy, Efficiency, Effectiveness, Exergy destruction, Power plant --------------------------------------------------------------------***------------------------------------------------------------------ 1. INTRODUCTION Exergy or, availability of a system signifies the part of the system energy that can be converted into maximum useful or desired work with respect to immediate surrounding condition, referred to as ‘dead state’. The term Exergy was used for the first time by Rant, Z. in 1956. According to 1st law of thermodynamics energy is conserved, but energy is conserved only quantitatively and not qualitatively. But exergy is a manifestation of quality of energy and unlike energy, exergy is not conserved and in fact, get destroyed due to irreversibility during a process. The energy efficiency or, 1st law efficiency merely implies the ratio of desired or, useful work output against total energy input for a system. But this does not consider the true capability of the system by considering the thermodynamic limitations for which the system is not responsible. Efficiency based on exergy for any system like whole thermal power plant or, say, a turbine reflect the true capability of the concerned system i.e., their actual working capability against their maximum possible capability due to irreversibility present in the system process. Thus unlike, energy efficiency, exergy efficiency gives more insight into the problem and help design, analyse and performance improvement of the energy conversion systems more effectively by identifying the locations and associated irreversibilities. A relationship between energy and exergy is pictorially shown in Fig-1.Of late, many researchers are using exergy methodology for analysing different types of energy conversion systems [1– 6] and in fact, some good books are now available in this arena [8 – 10]. In the present investigation, for a 250 MW thermal power plant energy, exergy efficiency and effectiveness of different equipments as well as for the whole plant are determined based on plant operating data at 100% and 90% load. The results for the loads are compared, analysed and discussed. The present results obtained are compared with those of other investigators. It is believed that present investigation will help understanding the possible improvement locations for a power plant as well as will indicate the priority areas of action for better performance and operation of the plant.
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 55 Fig-1: Relationship between Energy and Exergy 2. A BRIEF NOTE ABOUT THE POWER PLANT SELECTED FOR PRESENT ANALYSIS For the present analysis operating data of a 250 MW thermal power plant located in India are collected. The plant was commissioned about six years back and running smoothly. The plant is based on cornered fired firing technology. The prevailing ambient temperature varies from 0 to 450 C, normal being about 300 C. At the time of collecting data temperature was 300 C. It’s a condensing steam plant and like other steam power plant it runs on Rankine cycle. Water from river is chemically treated and demineralised at D.M (Demineralised) plant. Water enters into boiler through economiser and ultimately converted into superheated steam. The superheated steam passes through HP, IP, LP turbines and turbine shafts are coupled with generator to produce electric power. Exhaust two-phase steam from LP turbine then enters into condenser and get condensed by circulating cooling water. The condensate then passes through low pressure (LP) heaters and deaerator. After deaerator by feed pump pressure of the water is raised considering the pressure required for boiler and then water passes through high pressure (HP) feed water heaters and enters into boiler through economiser and the cycle repeats. The LP, HP and deaerator are continuously supplied with bled or, extracted steam from CRH ( Cold ReHeat ) line, IP and LP turbines at selective points. The details of the plant layout including extraction of steams, heater drips etc. are shown in Fig-2. The plant normally runs on E-grade coal. The ultimate analysis of operating coal is given by C = 34.20%, H = 5.00%, N = 1.80%, O = 10.70%, M (moisture) = 8.00%, S= 0.30 %. Ash = 40.00% . Coal GCV is 3700 KCal/kg i.e.15490 KJ/kg. 3. REFERENCE OR DEAD STATE In any exergy analysis proper selection of reference or Dead state is of extreme importance. The exergy value of any system, flow or equipment depends on the reference or Dead state. In our exergy analysis the dead state pressure(po)and temperature(To)are considered as 1 bar and 303 K i.e., 300 C respectively.In fact, this corresponds to plant operating ambient condition. Dead state enthalpy ( ho) and entropy ( so) are given by 125.83 KJ/kg and 0.437 KJ/kg-K respectively.
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 56 4. FLOW LAYOUT DIAGRAM OF THE POWER PLANT Total flow layout of the power plant is shown in Fig.-2 Fig-2: Plant flow layout diagram 5. METHODOLOGY OF ANALYSIS : In this present investigation following methodology and equations are used to determine energy, exergy efficiencies, and effectiveness of different equipments like boiler, turbine, heaters, and condenser of the plant. We note that all the flow processes through different equipments of the thermal power plant individually and also through the whole power plant are steady and hence no energy or exergy is stored within any system or equipment.  Mass balance equation : 𝑚𝑖𝑛 = 𝑚 𝑜𝑢𝑡 1  Energy balance equation : 𝐸𝑖𝑛 𝑖𝑛 + 𝑄 = 𝐸𝑜𝑢𝑡 𝑜𝑢𝑡 + 𝑊 (2)  General Exergy balance equation : 𝑚𝑖𝑛 𝑥𝑖𝑛 𝑖𝑛 + 𝑋 𝑄 + 𝑋 𝐶𝐻 = 𝑚 𝑜𝑢𝑡 𝑥 𝑜𝑢𝑡 𝑜𝑢𝑡 + 𝑊 + 𝑋 𝑑𝑒𝑠 3  Energy efficiency equation or, 1st Law efficiency : η1 = Useful i.e.desired energy output Total energy input (4) But, for condenser, η1= Actual temperature rise of the cold fluid Maximum possible temperature rise of the cold fluid For example, overall power plant, η1 = Total Power output Total Energy supplied by fuel
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 57  Exergy efficiency equation or, 2nd Law efficiency : η2= Exergy recovered Total exergy input or,supplied or, may be given by, = Actual thermal efficiency Maximum possible reversible thermal efficiency (5)  Effectiveness ( for heaters) : ϵ= Actual temperature rise of the cold fluid Maximum possible temperature rise of the cold fluid (6)  Total exergy flow rate into a control volume or, an equipment is given by : 𝑋𝑖𝑛 = 𝑚𝑖𝑛 𝑥𝑖𝑛 (7) Similarly, exergy outlet flow rate can be determined.  Specific exergyis given by : x= ( h – ho) – To ( s – so ) (8) 6. ENERGY AND EXERGY FLOW RATES THROUGHOUT THE POWER PLANT In Table-1, at 100% load operating pressure, temperature and flow of the working fluid are given in each node of the plant corresponding to Fig-2. Based on this in the same Table-1, at 100% load corresponding specific enthalpy, specific entropy, total energy flow rate and total exergy flow rate are given. For 90% load corresponding operating parameters are not tabulated here, but all relevant calculations are carried out and results are shown. Table-1: Operational Data For 100% Load at Each Node Shown in Fig.-2 Node [Pr, bar] [Temp,0 C] [Flow, TPH] [h, kJ/kg] [s, kJ/kg-K] [𝐸, MW ] [𝑋, MW ] 1 147.00 549.00 785.00 3450.940 6.532 752.497 322.357 2 40.50 549.00 715.00 3557.460 7.226 706.551 273.003 3 41.53 360.00 785.00 3114.730 6.602 679.184 244.420 4 41.53 360.00 715.00 3114.730 6.602 618.620 222.624 5 41.53 360.00 70.00 3114.730 6.602 60.564 21.795 6 20.00 437.00 68.00 3329.510 7.247 62.891 21.538 7 10.00 348.00 647.00 3153.920 7.296 566.830 170.703 8 10.00 348.00 627.20 3153.920 7.296 549.483 165.479 9 10.00 348.00 19.80 3153.920 7.296 17.347 5.224 10 1.82 216.00 30.00 2903.710 7.620 24.198 5.012 11 1.64 120.00 38.00 2709.810 7.226 28.604 5.562 12 0.10 45.800 559.20 2414.000 7.575 374.975 19.472 13 0.10 45.800 559.20 199.660 0.649 31.014 1.490 14 0.10 45.80 635.20 199.660 0.649 35.229 1.693 15 12.00 51.000 635.20 214.540 0.716 37.854 0.736 16 10.00 76.00 635.20 318.940 1.027 56.275 2.530 17 8.00 98.00 635.20 411.200 1.284 72.554 5.069 18 6.00 158.80 795.00 670.500 1.931 148.069 20.314 19 20.00 167.00 795.00 706.790 2.011 156.083 22.975 20 190.00 171.00 795.00 733.740 2.029 162.034 27.722 21 189.00 207.00 795.00 890.810 2.369 196.721 39.658 22 185.00 242.00 795.00 1049.070 2.688 231.670 53.262
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 58 23 175.00 253.00 795.00 1100.440 2.789 243.014 57.848 24 8.00 170.40 138.00 721.020 2.046 27.639 4.127 25 26.00 215.00 70.000 920.760 2.471 17.904 3.473 26 10.00 210.00 2.000 2852.200 6.746 1.585 0.453 27 0.80 93.40 38.000 391.640 1.232 4.134 0.263 28 1.00 99.60 30.000 417.440 1.302 3.479 0.246 29 6.00 30.00 33000.00 126.29 0.437 1157.650 4.216 30 5.00 38.90 33000.00 163.380 0.558 1497.650 8.131 7. SOME SAMPLE CALCULATIONS Some sample calculations are carried out hereunder to illustrate the use of the above equations. (1) Energy efficiency (η1) of overall plant at 100 % load : Total gross power output from the power plant at 100% load = 250 MW. Energy supplied by coal to the plant at 100% load = Coal GCV ( 15490kJ/kg) × Coal firing rate (158 TPH i.e.43.88 kg/s ) = 679.7012 MW. η1= ( 250/679.7012 ) × 100 % = 36.78 % Similarly,at 90% load with coal firing rate 151 TPH, η1 = (225 MW /651.90 MW)× 100% = 34.51 % (2)Efficiency (η1) of Condenser at 100% load η1= Actual temperature rise of the cooling water saturated steam inlet temp .to condenser − Cooling water inlet temp = [( 38.90 – 30 ) /(45.8 – 30 ) ] × 100% = 56.32 % (3) Exergy efficiency (η2)of L.P. Heater (LPH) No.-2 at 100% load Total Exergysuppliedto the heater = 𝑋16 + 𝑋10 = 2.53 + 5.012 = 7.542 MW Total Exergyrecovered from the heater = 𝑋17 + 𝑋27= 5.069 + 0.246 = 5.315 MW Therefore, η2 = ( 5.315/ 7.542 ) × 100% = 70.47 % (4) Exergy efficiency (η2) of Boiler at 100% load : Exergy supply by coal= Coal GCV(15490 kJ/kg ) × Coal firing rate (158 TPH i.e., 43.8888 kg/s) × 1.06= 720.4832 MW where 1.06 is the Exergy Grade Function( f )for coal [ 7 , 8 ]. Exergy flow into boiler = 𝑋23 + 𝑋4 + Coal exergy= 1000.95 MW Exergy flow out from the boiler = 𝑋1 + 𝑋2= 595.36 MW. η2= (595.36 /1000.95) × 100% = 59.47 % (5) Effectiveness (ϵ) of HPH No.-1 at 100% load : Actual temperature rise of cold fluid = ( 207 – 171 ) 0 C = 36 0 C Maximum possible temperature rise = ( hotfluid inlet temperature, 437 0 C)– ( 1710 C ) = 266 0 C Effectiveness (ϵ)= 36 0 C/266 0 C = 0.135 8. RESULTS AND DISCUSSION All relevant calculations are done based on above stated methodology for both 100% and 90% load at different equipment level as well as considering the whole power plant. The results obtained are given in both tabular and graphical forms for ease of comparison and understanding. In Table-2,η1 and η2for 90% and 100% load are given side by side. Table-2: Energy and Exergy efficiencies for 100% and 90% load Equipment 100% Load 90% Load η1 ( % ) η2 ( % ) η1 ( % ) η2 ( % ) Boiler 94.52 59.47 94.38 58.05 Turbine 91.96 84.99 87.05 79.55 Condenser 56.32 40.61 69.04 43.93 Overall Plant 36.78 32.15 34.51 30.34
  • 6. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 59 Table-3: Exergy efficiency and effectiveness for 100% and 90% load Equipment 100% Load 90% Load η2 ( % ) ϵ η2 ( % ) ϵ LPH-1 44.35 0.36 43.82 0.33 LPH-2 70.47 0.15 71.56 0.14 HPH-1 83.03 0.13 81.42 0.12 HPH-2 92.32 0.22 93.78 0.25 Fig.-3: Energy Efficiency(η1 , % ) Fig.-4: Exergy Efficiency (η2, % ) 0 10 20 30 40 50 60 70 80 90 100 Boiler Turbine Condenser Overall Plant Energy Efficiency ( % ) 90% Load 100% Load 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 LPH-1 LPH-2 HPH-1 HPH-2 Boiler Turbine Condenser Overall Plant Exergy Efficiency ( % ) 90% Load 100% Load
  • 7. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 60 Fig.-5: Effectiveness of Heaters (ϵ) Fig.-6: Exergy destruction ( % ) for equipment & overall plant at 100% load We searched literatures to compare our results to those obtained by other investigators. But not much data are available for energy and exergy efficiency and for effectiveness of individual component and for the overall power plant of 250 MW capacity under more or less similar conditions to ours. In some cases only some scattered data are available. Based on the available data, we have compared our results which are given in Table-4 and Table- 5. Table – 4: Comparison of Energy efficiency ( η1 in % )and effectiveness (ϵ )at 100% load Sl No. Parameter Present Investigation Ref [3] 1. Boiler η1 94.52 85.23 2. Condenser η1 56.32 53.33 3. Overall Plantη1 36.78 36.74 4. LPH-1 ϵ 0.36 0.46 5. LPH-2 ϵ 0.15 0.14 6. HPH-1 ϵ 0.13 0.13 7. HPH-2 ϵ 0.22 0.29 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 LPH-1 LPH-2 HPH-1 HPH-2 90% Load 100% Load
  • 8. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 61 Table-5: Comparison of Exergy efficiency (η2 in % ) at 100% load Sl No. Parameter Present Investigation Ref [4 ] Ref[5] Ref [6] 1. Boiler η2 59.47 46.24 53.00 48.55 2. Turbine η2 84.99 87.78 92.25 92.71 3. Overall Plant η2 32.15 NA 36.80 44.07 4. LPH-1 η2 44.35 89.71 NA NA 5. LPH-2 η2 70.47 96.46 NA NA 6. HPH-1 η2 83.03 97.64 NA NA 7. HPH-2 η2 92.32 93.52 NA NA From the above results and comparison, it is clear that our obtained results compare reasonably well with other available results of similar category power plant. Of course, the energy and exergy efficiency and effectiveness of heaters in a plant depend on many other factors apart from size of the plant. For example, ultimate composition of coal, coal GCV, coal burning mechanism and associated irresversibilities in the combustion process and irreversibility for large temperature gradient heat transfer from flue gas to water & steam, individual equipment irreversibility, prevailing ambient condition are some of the factors to name which effect the performance of the plant and the plant equipments. Finally, our results along with other available results can generate a data pool and by analysing this type of data pool more insights about the performance of the power plant and its equipments can be obtained. This definitely will boil down to more effective design and operation of the power plant and thereby will save our precious energy resources and help reduce pollution effects. 9. CONCLUSION In this present study energy, exergy efficiencies and effectiveness of different relevant equipments as well as for the overall plant are carried out both at 100 % and 90% load for a 250 MW coal fired power plant based on plant operating data. The energy and exergy flow rates at each of the nodal points of the whole plant are calculated and tabulated. All relevant equations for performance calculations are illustrated by carrying out some sample calculations for each of the different situation. From the analysis it is found that major energy loss in the plant occurs at the condenser due to phase conversion of working fluid. Similarly major exergy loss occurs at the boiler and the condenser. Our results are compared reasonably well with other available investigators results for similar type of power plants; of course there are certain deviations. It is expected that all these data will form a pool of plant performance data which may ultimately results in better understanding of the plantand thereby possibly help improvement in plant design and operation. NOMENCLATURE E : Energy [MW ] h : Specific enthalpy [kJ/kg] m : Mass [Ton] s : Specific entropy [kJ/kg-K] X : Total exergy [MW] x : Specific Exergy [kW] ECO : Economizer GCV : Gross Calorific Value [kJ/kg] HPH : High Pressure Heater HPT : High Pressure Turbine IPT : Intermediate Pressure Turbine LPH : Low Pressure Heater LPT : Low Pressure Turbine NA : Not available Q : Heat input [MW] TPH : Ton per hour W : Work output [MW] ϵ : Effectiveness [unit less ] η1 : Energy efficiency or, 1st law efficiency [ % ] η2 : Exergyefficiency or, 2nd law efficiency [% ] Subscripts des : destruction in : at inlet condition out : at outlet condition 0 : reference or, dead state .(dot) : ‘dot’ over any parameter implies corresponding flow rate REFERENCES [1] Dincer and H. Al-Muslim ; ‘Thermodynamics analysis of reheat cycle steam power plant’, Int. J. Energy Research, vol :25(8), 2001 [2] S. C. Kaushik, V. S. Reddy and S. K. Tyagi ; ‘Energy and exergy analyses of thermal power plants : A review’, J. of Renewable and Sustainable Energy Reviews (RESR), Elsevier, vol :15, 2011 [3] M. Bajwa and P. Gulati ; ‘Comparing the thermal power plant performance at various output loads by energy auditing ( a statistical analysing tool )’, Int. J. Mechanical Engg & Tech. (IJMET), vol :2, issue :2, May-July2011 [4] K. Maghsoudi, A. Mehrpanahi and M. Tabaraki ; ‘Energy and exergy analysis of 250 MW steam power plant’, Switzerland Research Park Journal, vol :102, no. :11, Nov2013. [5] M. Ameri, P. Ahmadi and A. Hamidi ; ‘Energy, exergy and exergoeconomic analysis of a steam
  • 9. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 04 Issue: 07 | July-2015, Available @ http://www.ijret.org 62 power plant : a case study’, Int. Journal of Exergy Research, vol :33, 2009 [6] H. Zhao and Y. Chai ; ‘Exergy analysis of a power cycle system with 300 MW capacity’, Proc. Int. Conf. on ‘Advances in energy engineering’, Beijing, Chain, June 2010, IEEE [7] G. Reistad ; ‘Available energy conversion & utilization in the United States’. Journal of Energy Power,Vol :9, 1975 [8] Dincer & M. A. Rosen ; ‘Exergy Energy, Environment and sustainable development’, Elsevier publication, 2007 [9] T. J. Kotas ; ‘The Exergy method of thermal plant analysis’, Butterwards Pub., 1995 [10] J. Szargut, D.R. Morris and F.R Steward ; ‘Exergy Analysis of thermal, chemical and metallurgical process’, Hemisphere, NewYork, 1988. BIOGRAPHIES Dr. Soupayan Mitra, (B.E) From North Bengal University, (M.M.E) From Jadavpur University, [Ph.D(Engg.)] From Jadavpur University. Associate Professor, Department of Mechanical Engineering Jalpaiguri Government Engineering College Jalpaiguri -735102, West Bengal, India Joydip Ghosh, (B.Tech) from West Bengal University of Technology (M.Tech) from Jalpaiguri Government Engineering College. Post Graduate Scholar, Department of Mechanical Engineering, Jalpaiguri Government Engineering College Jalpaiguri -735102, West Bengal, India