SUBSTATION
HIGH VOLTAGE COMPONENTS
POWER PLANT
SWITCHING STATION
(SWITCHYARD)
SUBSTATION
• SUBSTATION - A station in the power transmission system at
which electric power is transformed to a conveniently used
form. The station may consist of transformers, switches,
circuit breakers and other auxilliary equipment. Its main
function is to receive energy transmitted at high voltage from
the generating station, by either step-up or step-down the
voltage to a value appropriate for local use and provide
facilities for switching. Substations have some additional
functions. Its provide points where safety devices may be
installed to disconnect circuits or equipment in the event of
trouble.
Some substation, such as power plant switchyard are
simply switching stations where different connections can be
made between various transmission lines.
Typical Components of a Power Plant
Substation (Switchyard)
•A - Busbar
•B - Disconnector
•C - Circuit Breaker
•D - Current Transformer
•E - Voltage Transformer
•F - Earthing Switch
•G - Surge Arrestor
• CONNECT
• CONNECT & DIS-CONNECT
• CONNECT, DIS-CONNECT & DETECT
• DETECT & TRANSFORM
• DETECT & TRANSFORM
• PROTECT & SAFETY
• PROTECT
A. BUSBAR
• BUSBAR (or bus, for short) – is a term we use for a main bar or
conductor carrying an electric current to which many
connection may be made.
Buses are merely convenient means of connecting
switches and other equipment into various arrangements. The
usual arrangement of connections in most substations permit
working on almost any piece of equipment without
interruption to incoming or outgoing feeders. In the
switchyard or substation, buses are open to the air. Aluminum
or copper conductors supported on porcelain insulators, carry
the electric energy from point to point.
Busbars
(long heavy
tube type)
B. DISCONNECTS
• DISCONNECT – is an easily removed piece of the actual
conductor of a circuit. The purpose of disconnects is to isolate
equipment. Disconnects are not used to interrupt circuits;
they are no-load devices. A typical use of disconnects is to
isolate a circuit breaker by installing one disconnect on either
side of the circuit breaker (in series with the breaker).
Operation of disconnects is one of the most important and
responsible jobs of a power plant operator. One error in
isolation of equipment, or the accidental grounding of line
equipment, can be a fatal mistake.
A
B
Disconnect Switch
( moving contact rod (A) &
contacts with flexible
fingers (B) )
C. CIRCUIT BREAKER
• CIRCUIT BREAKER – is used to interrupt circuits while current
is flowing through them. The making and breaking of contacts
in a Oil type circuit breaker are done under oil, this oil serves
to quench the arc when the circuit is opened. The operation
of the breaker is very rapid when opening. As with the
transformer, the high voltage connections are made through
bushings. Circuit breakers of this type are usually arranged for
remote electrical control from a suitably located switchboard.
Some recently developed circuit breakers have no oil, but
put out the arc by a blast of compressed air; these are called
air circuit breakers. Another type encloses the contacts in a
vacuum or a gas (sulfur hexafluoride, SF6) which tends to self
maintain the arc.
Circuit Breakers
( Connected in a typical 3-
phase circuit )
Operating
Mechanism
Panel
Position
Indicator
D. CURRENT TRANSFORMER
• CURRENT TRANSFORMER – Current transformer are used
with ammeters, watt meters, power-factor meters, watt-hour
meters,compensators, protective and regulating relays and
the trip coil of circuit breakers. One current transformer can
be used to operate several instruments, provided that the
combined burden does not exceed that for which the
transformer is designed and compensated. The current
transformer is connected directly in series with the line.
E. VOLTAGE TRANSFORMER
• VOLTAGE TRANSFORMER – also know as potential
transformer, are used with volt-meters, wattmeters, watt-
hour meters, power-factor meters, frequency meters,
synchroscopes and synchronizing apparatus, protective and
regulating relays and the no-voltage and over-voltage trip
coils of automatic circuit breakers. One transformer can be
used for a number of instruments at the same time if the total
current taken by the instrument does not exceed that for
which the transformer is designed and compensated. The
ordinary voltage transformer is connected across the line, and
the magnetic flux in the core depends upon the primary
voltage
F. EARTHING SWITCH
• EARTHING SWITCH – also known as ground disconnect, which
used to connects the equipment to a grid of electrical
conductors buried in the earth on the station property. It is
intended to protect people working on the grounded
equipment. It does this by completing a circuit path, thereby
reducing the voltage difference between the equipment and
its surroundings. For safety reasons, it is important that
ground disconnects and all associated connections have good
contact and low resistance. It is also important that the
protective ground not be accidentally remove, that is why all
the earthing switches, disconnect switches and circuit
breakers are all interlocked to each other and proper/correct
sequencing must be followed.
G. SURGE ARRESTOR
• SURGE ARRESTOR – are devices used to provide the
necessary path to ground for such surges, yet prevent any
power current from following the surge. An ideal arrester
must therefore have the following properties:
1. Ability to remove the surge energy from the line in a min. time.
2. High resistive to flow of power current.
3. A valve action automatically allowing surge to pass and then
closing up so as not to permit power current to flow to
ground.
4. Always ready to perform.
5. Performance such that no system disturbances are introduced
by its operation.
6. Economically feasible
• OVERHEAD GROUND WIRE – by a ground wire is meant a
wire, generally of steel, supported from the top of
transmission-line towers and solidly grounded at each tower.
It is considered a preventive device, but it does not entirely
prevent the formation of travelling waves on a line.
Furthermore, those lines which are not equipped with ground
wires will be subjected to disturbances which produce surges
that must be allowed to escaped to ground, or the apparatus
connected to the line must be strong enough to reflect or
absorb these surges until they are entirely damped out.
PREVENTIVE MAINTENANCE
• BUSBARS & OVERHEAD GROUND WIRE
At least once a year
 Visual Inspection & Examination of all wiring connectors.
 Check Insulator , clean or apply HVIC if necessary.
 Check the physical condition of bus (cables or bars)
 For ground wire, check or test the grounding system.
• DISCONNECT & EARTHING SWITCHES
At least once a month
 Visual Inspection.
 Check heating resistor located at its control panel for proper functioning.
At least once a year
 Clean contacts of disconnectors as well as earthing switches and apply electrical
contact grease , if necessary.
 Check disconnectors and earthing switches, joints and bearings of the operating
linkages for deformed bearing points.
 Check flexible connections of earthing switches.
 Check all screwed joints for tight fit.
 Clean insulators if necessary, when an excessive amount of dirt has
accumulated.
 Carry-out the maintenance of operating mechanism.
• VOLTAGE TRANSFORMER
At least once a month
 Inspect the voltage divider to be sure that no oil leak or serious accumulation of
soot, dust or salt composite is present.
 Inspect the intermediate voltage transformer and check the minimum
permissible oil level.
At least once a year
 Check all screwed joints & contact for tight fit.
 Clean insulators if necessary, when an excessive amount of dirt has
accumulated.
CURRENT TRANSFORMER
At least once a month
 Visual Inspection to check oil level and defects or possible oil leaks.
At least once a year
 Check all screwed joints & contact for tight fit.
 Clean insulators if necessary, when an excessive amount of dirt has
accumulated.
 Check primary and secondary connectors and conduct necessary tightening.
Note: Never open a secondary winding of a CT while on service.
• SURGE ARRESTOR
At least once a year
 Visual Inspection & Examination of all wiring connectors.
 Check Insulator and metal circular ring, clean or apply HVIC if necessary.
 Check the physical condition of bus (cables or bars)
 For ground wire, check or test the grounding system.
Note: Arrestors should never be touched unless completely disconnected from all
live lines and equipment and effectively connected to ground at the line side of
the arrestor.

More Related Content

Similar to Electrical_substation_general_equipments.ppt

Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1anuphowlader1
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgearAdnan Sayed
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)Ameh Messiah Edache
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at JassureShuvam Pathania
 
switchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptxswitchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptxDrNiveditaSingh3
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSatish Pydimarla
 
TOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptxTOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptxMartMantilla1
 
400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf Ishan Khandelwal
 
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)Rahul Prajapati
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNadir Baloch
 
Design of substation
Design of substationDesign of substation
Design of substationSayanSarkar55
 
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharPpt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharYatendra Parashar
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard finalHAIDER ALI
 
DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLyohannes feleke
 
Electric power substation
Electric power substationElectric power substation
Electric power substationqwerty25ty
 
33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE 33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE Lalit Kumar
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBRVijay Raskar
 

Similar to Electrical_substation_general_equipments.ppt (20)

Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
 
Introduction to switchgear
Introduction to switchgearIntroduction to switchgear
Introduction to switchgear
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
Relays
  Relays  Relays
Relays
 
switchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptxswitchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptx
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
 
TOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptxTOPIC 2.1- Relays.pptx
TOPIC 2.1- Relays.pptx
 
400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf
 
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
Presentation on 132/33KV BSPTCL(Bodhgaya Substation)
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Design of substation
Design of substationDesign of substation
Design of substation
 
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra ParasharPpt on 400 kv gss raiser Bikaner- Yatendra Parashar
Ppt on 400 kv gss raiser Bikaner- Yatendra Parashar
 
ET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptxET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptx
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard final
 
rough.pptx
rough.pptxrough.pptx
rough.pptx
 
DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROL
 
Electric power substation
Electric power substationElectric power substation
Electric power substation
 
33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE 33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBR
 

Recently uploaded

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 

Recently uploaded (20)

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 

Electrical_substation_general_equipments.ppt

  • 1. SUBSTATION HIGH VOLTAGE COMPONENTS POWER PLANT SWITCHING STATION (SWITCHYARD)
  • 2. SUBSTATION • SUBSTATION - A station in the power transmission system at which electric power is transformed to a conveniently used form. The station may consist of transformers, switches, circuit breakers and other auxilliary equipment. Its main function is to receive energy transmitted at high voltage from the generating station, by either step-up or step-down the voltage to a value appropriate for local use and provide facilities for switching. Substations have some additional functions. Its provide points where safety devices may be installed to disconnect circuits or equipment in the event of trouble. Some substation, such as power plant switchyard are simply switching stations where different connections can be made between various transmission lines.
  • 3. Typical Components of a Power Plant Substation (Switchyard) •A - Busbar •B - Disconnector •C - Circuit Breaker •D - Current Transformer •E - Voltage Transformer •F - Earthing Switch •G - Surge Arrestor • CONNECT • CONNECT & DIS-CONNECT • CONNECT, DIS-CONNECT & DETECT • DETECT & TRANSFORM • DETECT & TRANSFORM • PROTECT & SAFETY • PROTECT
  • 4. A. BUSBAR • BUSBAR (or bus, for short) – is a term we use for a main bar or conductor carrying an electric current to which many connection may be made. Buses are merely convenient means of connecting switches and other equipment into various arrangements. The usual arrangement of connections in most substations permit working on almost any piece of equipment without interruption to incoming or outgoing feeders. In the switchyard or substation, buses are open to the air. Aluminum or copper conductors supported on porcelain insulators, carry the electric energy from point to point.
  • 6. B. DISCONNECTS • DISCONNECT – is an easily removed piece of the actual conductor of a circuit. The purpose of disconnects is to isolate equipment. Disconnects are not used to interrupt circuits; they are no-load devices. A typical use of disconnects is to isolate a circuit breaker by installing one disconnect on either side of the circuit breaker (in series with the breaker). Operation of disconnects is one of the most important and responsible jobs of a power plant operator. One error in isolation of equipment, or the accidental grounding of line equipment, can be a fatal mistake.
  • 7. A B Disconnect Switch ( moving contact rod (A) & contacts with flexible fingers (B) )
  • 8. C. CIRCUIT BREAKER • CIRCUIT BREAKER – is used to interrupt circuits while current is flowing through them. The making and breaking of contacts in a Oil type circuit breaker are done under oil, this oil serves to quench the arc when the circuit is opened. The operation of the breaker is very rapid when opening. As with the transformer, the high voltage connections are made through bushings. Circuit breakers of this type are usually arranged for remote electrical control from a suitably located switchboard. Some recently developed circuit breakers have no oil, but put out the arc by a blast of compressed air; these are called air circuit breakers. Another type encloses the contacts in a vacuum or a gas (sulfur hexafluoride, SF6) which tends to self maintain the arc.
  • 9. Circuit Breakers ( Connected in a typical 3- phase circuit ) Operating Mechanism Panel Position Indicator
  • 10. D. CURRENT TRANSFORMER • CURRENT TRANSFORMER – Current transformer are used with ammeters, watt meters, power-factor meters, watt-hour meters,compensators, protective and regulating relays and the trip coil of circuit breakers. One current transformer can be used to operate several instruments, provided that the combined burden does not exceed that for which the transformer is designed and compensated. The current transformer is connected directly in series with the line.
  • 11.
  • 12. E. VOLTAGE TRANSFORMER • VOLTAGE TRANSFORMER – also know as potential transformer, are used with volt-meters, wattmeters, watt- hour meters, power-factor meters, frequency meters, synchroscopes and synchronizing apparatus, protective and regulating relays and the no-voltage and over-voltage trip coils of automatic circuit breakers. One transformer can be used for a number of instruments at the same time if the total current taken by the instrument does not exceed that for which the transformer is designed and compensated. The ordinary voltage transformer is connected across the line, and the magnetic flux in the core depends upon the primary voltage
  • 13.
  • 14. F. EARTHING SWITCH • EARTHING SWITCH – also known as ground disconnect, which used to connects the equipment to a grid of electrical conductors buried in the earth on the station property. It is intended to protect people working on the grounded equipment. It does this by completing a circuit path, thereby reducing the voltage difference between the equipment and its surroundings. For safety reasons, it is important that ground disconnects and all associated connections have good contact and low resistance. It is also important that the protective ground not be accidentally remove, that is why all the earthing switches, disconnect switches and circuit breakers are all interlocked to each other and proper/correct sequencing must be followed.
  • 15. G. SURGE ARRESTOR • SURGE ARRESTOR – are devices used to provide the necessary path to ground for such surges, yet prevent any power current from following the surge. An ideal arrester must therefore have the following properties: 1. Ability to remove the surge energy from the line in a min. time. 2. High resistive to flow of power current. 3. A valve action automatically allowing surge to pass and then closing up so as not to permit power current to flow to ground. 4. Always ready to perform. 5. Performance such that no system disturbances are introduced by its operation. 6. Economically feasible
  • 16.
  • 17. • OVERHEAD GROUND WIRE – by a ground wire is meant a wire, generally of steel, supported from the top of transmission-line towers and solidly grounded at each tower. It is considered a preventive device, but it does not entirely prevent the formation of travelling waves on a line. Furthermore, those lines which are not equipped with ground wires will be subjected to disturbances which produce surges that must be allowed to escaped to ground, or the apparatus connected to the line must be strong enough to reflect or absorb these surges until they are entirely damped out.
  • 18.
  • 19. PREVENTIVE MAINTENANCE • BUSBARS & OVERHEAD GROUND WIRE At least once a year  Visual Inspection & Examination of all wiring connectors.  Check Insulator , clean or apply HVIC if necessary.  Check the physical condition of bus (cables or bars)  For ground wire, check or test the grounding system. • DISCONNECT & EARTHING SWITCHES At least once a month  Visual Inspection.  Check heating resistor located at its control panel for proper functioning. At least once a year  Clean contacts of disconnectors as well as earthing switches and apply electrical contact grease , if necessary.
  • 20.  Check disconnectors and earthing switches, joints and bearings of the operating linkages for deformed bearing points.  Check flexible connections of earthing switches.  Check all screwed joints for tight fit.  Clean insulators if necessary, when an excessive amount of dirt has accumulated.  Carry-out the maintenance of operating mechanism. • VOLTAGE TRANSFORMER At least once a month  Inspect the voltage divider to be sure that no oil leak or serious accumulation of soot, dust or salt composite is present.  Inspect the intermediate voltage transformer and check the minimum permissible oil level. At least once a year  Check all screwed joints & contact for tight fit.  Clean insulators if necessary, when an excessive amount of dirt has accumulated.
  • 21. CURRENT TRANSFORMER At least once a month  Visual Inspection to check oil level and defects or possible oil leaks. At least once a year  Check all screwed joints & contact for tight fit.  Clean insulators if necessary, when an excessive amount of dirt has accumulated.  Check primary and secondary connectors and conduct necessary tightening. Note: Never open a secondary winding of a CT while on service. • SURGE ARRESTOR At least once a year  Visual Inspection & Examination of all wiring connectors.  Check Insulator and metal circular ring, clean or apply HVIC if necessary.  Check the physical condition of bus (cables or bars)
  • 22.  For ground wire, check or test the grounding system. Note: Arrestors should never be touched unless completely disconnected from all live lines and equipment and effectively connected to ground at the line side of the arrestor.