Ventilation fan constitutes one of the critical components of traction motor. As the weight of the component is to be kept minimum, it is made up of aluminium alloy casting. But it has to withstand high centrifugal acceleration and shock loads. Any failure of the fan shall lead to consequential damages to the motor resulting in long outages and huge expenditure. This paper presents an integrated approach with an improved quality plan to meet the operational criteria of the fan.
2. An Integrated Approach for The Improvement of Dynamic Characteristics of Ventilation Fan
of A Traction Motor
http://www.iaeme.com/ijmet/index.asp 111 editor@iaeme.com
Cite this Article: Bishnu Pada Pal, K. Ramakrishna and G. Jayaraman. An
Integrated Approach for The Improvement of Dynamic Characteristics of
Ventilation Fan of A Traction Motor, International Journal of Mechanical
Engineering and Technology, 7(1), 2016, pp. 110-118.
http://www.iaeme.com/currentissue.asp?JType=IJMET&VType=7&IType=1
1. INTRODUCTION
The ventilation fan impellers of the motor were observed to be giving limited
performance and resulting in premature failures. Fig1. Shows a sample failed
ventilation fan. Detailed investigation was carried out on some failed and new
samples of the same lot, which resulted in the following observations and
recommendations.
Scanning Electron Microscope (SEM) studies on the impeller with failure in the blade
portion shows shrinkage porosity with dendrite lobes. This behaviour can be caused
by an excessively high pouring temperature or by failure to provide proper risers.
Figure 1 Failed sample of the ventilator
In the case of umbrella type impeller failure, SEM studies reveal cleavage facets
indicating brittle failure and also presence of cavities. This could have been due to
entrapped air being carried into the mould.
Radiography requirement is class 5 for thickness greater than 10mm and class 4 for
thickness less than 10mm and full radiography analysis indicated class 8 in some
portions. It is recommended to maintain radiography of Class 3 or better
During mechanical testing some samples failed without ductility. Though the material
specification is GAl7SiMg which stands for sand casting, to further improve the
performance the casting process is revised to low pressure die casting.
Microstructures are not as per T6 heat treatment and traces of cavities are seen.
Fatigue strength evaluation on test bars is found to be necessary
Dimensional accuracy is found to be further improved by measuring dimension using
CMM.
2. FE ANALYSIS OF VENTILATION FAN
As failures of fan impellers in operation were observed in the umbrella mode, where
the back plate gets cracked, its minimum thickness was increased by 50% in the
prototype development
Finite Element Analyses was carried out on the Fan impeller using ANSYS tools
to obtain natural frequencies and stress distribution with over speed runs and
appropriate shock loads. Fig.2 shows the 3D model of the ventilator. Fig.3 shows the
vonMises stress plot of the ventilator and fig.4 shows Campbell diagram generated
from the FE modal analysis for first 10 modes.
3. Bishnu Pada Pal, K.Ramakrishna and G.Jayaraman
http://www.iaeme.com/ijmet/index.asp 112 editor@iaeme.com
It is seen from the FEA results that stresses and deformations are within limits
even at over-speed runs with appropriate shock loads and the umbrella mode occurs at
a very high modal frequency, which does not impose high stresses/deformations.
Hence, the failures are not due to these reasons and so they must be due to
inadequacies in the casting process and/or heat treatment.
Figure 2 3D model of the ventilator Figure 3 vonMises stress plot
Figure 4 Campbell diagram
3. CFD ANALYSIS OF FAN IMPELLER
CFD analysis was carried out to study the aerodynamics of the fan and to find out any
possibilities that flow induced stresses may be the cause of failures.
It can be concluded from the results obtained that the flow within and around the
impeller is in order. Neither pressure variations nor the velocities observed can be
termed potential sources for the kind of damage shown in impeller. Fig.5 and fig.6
shows the total pressure variation over ventilator and static Pressure variation over the
ventilator, respectively.
4. An Integrated Approach for The Improvement of Dynamic Characteristics of Ventilation Fan
of A Traction Motor
http://www.iaeme.com/ijmet/index.asp 113 editor@iaeme.com
Figure 5 Total pressure variation over ventilator
Figure 6 Static Pressure variation over the ventilator
4. REVISED QUALITY PLAN
Subsequent to the analysis dealt in the previous sections, a revised quality plan is
made that is discussed in the following sections
4.1. Component Geometry and Dimensions: Strictly as per drawing.
Quality Plan: Supplier has to arrange measurement of dimensions of each impeller
using computer-aided co-ordinate measurement machine (CMM) to ensure quality
and provide the results. The supplier has to also provide with each impeller a
certificate of compliance with the desired dimensions or indicate any deviations in the
dimensions. These measurements are to be made in the presence of representatives.
4.2. Material
Aluminium Alloy G-Al Si 7 Mg Wa (DIN 1725) or equivalent as per Product
Standard
Quality Plan: Supplier has to certify the quality of the material. Virgin material (not
re-melted from scrap) to be procured from reputed suppliers to ensure quality.
4.3. Material Specifications
As per Product Standard with modified elongation of 7 – 9% on Test Bar and
minimum 5% on casting.
5. Bishnu Pada Pal, K.Ramakrishna and G.Jayaraman
http://www.iaeme.com/ijmet/index.asp 114 editor@iaeme.com
Quality Plan: Test bars are to be made along with each lot of impeller castings.
Supplier has to arrange for tests on Test bars and at least one impeller casting in a lot
to ensure that elongations as specified above are obtained and provide the results. The
supplier has to also provide with each lot of impellers a certificate of compliance or
deviation. Spare Test bars are to be supplied to carry out tests independently.
4.4. Material Testing
As per specification Product Standard
Quality Plan: Test bars are to be made along with each lot of impeller castings.
Supplier has to arrange for tests on Test bars and at least one impeller casting in a lot
to ensure that other material properties and quality as specified in Product Standard
No. TM 07375 are met. All the results are to be provided and also provide with each
lot of impellers a certificate of compliance or deviation. Spare Test bars are to be
supplied to carry out tests independently.
4.5. Casting Process
Preferably Gravity/Low Pressure Die Casting.
Quality Plan: Supplier has to give details of casting process being followed.
4.6 Melting process
Preferably Induction melting
Quality Plan: Supplier has to give details of the melting process being followed.
4.7. Heat Treatment
T6 condition
Quality Plan: Supplier has to certify that heat treatment is carried out as per T6
condition.
4.8. Microstructure
Globular micro-structure
Quality Plan: Supplier has to arrange for micro-structure tests on each lot and
provide the results along with certification about achievement of Globular micro-
structure.
4.9. Casting tolerance
As per IS 4897 CL-1.
Quality Plan: Suppler has to certify that casting tolerances are as per IS 4897 CL-1.
4.10. Radiography
Class 3 or better (100 % radiography to be done on all castings as per Product
Standard at positions marked ‘A’ in the drawing and DP Testing as per Corporate
R&D Standard AA0850131 & AA0850132 for remaining portion).
Quality Plan: Supplier has to arrange to carry out cent per cent radiography and DP
testing as specified above and provide the test results along with certification about
actual micro-structure obtained.
6. An Integrated Approach for The Improvement of Dynamic Characteristics of Ventilation Fan
of A Traction Motor
http://www.iaeme.com/ijmet/index.asp 115 editor@iaeme.com
4.11. Balancing
Dynamic balancing to be done on each impeller by addition of suitable weights at slot
X shown in drawing at a minimum speed of 500 RPM.
Quality Plan: Supplier has to arrange to get dynamic balancing done at a minimum
speed of 500 RPM on each impeller and provide compliance certificate
4.12. Stress relieving
Fan impellers to be stress relieved as per stress relieving cycle given in the drawing
Quality Plan: Supplier has to arrange to get stress relieving done on each impeller
and provide compliance certificate
5. MANUFACTURE OF PROTOTYPES
The Die & prototype ventilation fans manufactured with utmost quality control
following the above revised quality plan and specifications have resulted in improved
fan impellers, which may be expected to perform much better in service. Fig.7a and
fig.7b shows two views of the Die made by the vendor for casting the ventilation fan
impeller. Fig.8 shows the prototype ventilation fan.
Figure 7a Figure 7b
Figure 7a and 7b Two views of the Die for casting of ventilation fan
Figure 8 One prototype ventilation fan
6. TEST RIG FOR VENTILATION FAN
In addition to regular spinning & vibratory loads in operation, traction machine
ventilation fan is subjected to shock loads when the train passes over track joints. A
7. Bishnu Pada Pal, K.Ramakrishna and G.Jayaraman
http://www.iaeme.com/ijmet/index.asp 116 editor@iaeme.com
Test Rig has been established to test prototype ventilators subjected to simulated
operational loads. In this test rig, shock loads are simulated (in addition to regular
loads) through a cam-operated spring-loaded hammer. The fan impeller along with
shaft & bearings is mounted on a base plate and connected to the drive motor (which
is not mounted on the said base plate) through a flexible coupling. This base plate is
subjected to intermittent shock loads through a shock-frame which gets intermittent
hits from the cam-operated spring-loaded hammer. Springs of different stiffness can
be used to get different shock load conditions. The cams are operated with a geared
motor, whose speed can be varied to change the frequency of the shock loads. The
base plate is mounted on a spring matrix to simulate vibratory loads coming on the
impeller in operation. The basic spinning of the impeller is done by the main motor,
whose speed can be varied using the VF drive controller. Thus, different load
conditions can be simulated to get a complete picture of the operational performance
of the fan impeller. Fig.9 show the solid model of the ventilation fan test rig and
fig.10 shows the photograph of the actual test rig established.
Figure 9 Solid model of Fan Test Rig
Figure 10 Photograph of fan test rig Assembly with Air Duct
7. LAB TESTING OF THE FANS
To evaluate the structural performance of the prototype impeller, it was strain gauged
at the critical location and the spin & vibration/shock test of one of the prototype DE
ventilator fans in the lab. To simulate the actual service conditions, the impeller was
rotated at over speed and intermittent shock loads as per IEC 61373 standard were
given at about 30 seconds intervals using the cam & Hammer arrangement to simulate
the track-joint jolts in actual operation. Fig.11 shows the strain gauging carried out on
the fan for lab testing.
8. An Integrated Approach for The Improvement of Dynamic Characteristics of Ventilation Fan
of A Traction Motor
http://www.iaeme.com/ijmet/index.asp 117 editor@iaeme.com
Figure 11Strain gauged prototype ventilator
Fig.12. shows the connection of strain gauges and slip ring with the ventilator
while rotation.
Figure 12.The ventilator while rotation.
Strain gauges are placed at the locations where the maximum stresses occur based
on Finite Element Analysis and also that is the location of the failure reported in the
site. Two strain gauges are placed in the radial direction and two are for hoop
direction. Each strain gauge is connected with the slip ring and to the data acquisition
system. All four strain gauges reading are monitored in the dynamic strain indicator
system and daq software is used to record the test data online. Fifth channel is
connected with an accelerometer to see the shock level in vertical direction.
Fig.13. shows the Instrumented set-up for data acquisition via Slip Rings
assembly using dynamic strain indicator
Figure 13 Instrumented set-up for data acquisition via Slip Rings assembly
9. Bishnu Pada Pal, K.Ramakrishna and G.Jayaraman
http://www.iaeme.com/ijmet/index.asp 118 editor@iaeme.com
7.1. Results summary
The maximum Hoop and radial strain levels during steady state operation is less than
300 micro strains
The maximum Hoop and radial strain levels during shock loading is less than 350
micro strain.
The steady state strain levels are found to be stable and well within the limits after
the completion of the testing, indicating that no plastic deformation is taking place.
Based on the above results of spin and shock testing, it is concluded that the
maximum strain levels are well below the yield strain limit of 2600 micro strain,
which corresponds to the yield stress limit of 190MPa for Aluminum and also no
plastic deformation in the ventilator is observed during/after the prolonged testing.
Further as against the IEC standard requirement of shock loads for 18 cycles, the
testing was done extensively for more than 1000 cycles. Thus it can be concluded
from the test results that the ventilator is fit for prolonged operation at rated speed and
designed shock loads.
8. CONCLUSIONS
Detailed investigation was carried out on some failed and new samples of the same lot.
FE and CFD analyses carried out on fan impeller not only give insight into the
loading and flow distribution in the present fan, but also will be helpful in new design.
Indigenous vendor developed can be expected to still improve the quality in view of
the experience gained from this work and give still better products in the future. The
Die & prototype fan impellers manufactured with utmost quality control in various
aspects including material, casting process, dimensional accuracy, mechanical
strength, heat treatment & microstructure have resulted in improved fan impellers,
which may be expected to perform much better in service. The results of the
aerodynamic performance and endurance tests carried out on the prototype impellers
for varying speed and vibratory/shock loads as experienced in actual operation have
given more confidence on the better performance of these fan impellers in actual
operation.
REFERENCES
[1] Detailed technical Report on the project ‘Development of Design methodology,
Analysis, Manufacture and Endurance testing of Ventilation Fans for Traction
machines’ by M. Mohan Prabhu and Bishnu Pada Pal.
[2] Strain Gauge manual.
[3] IEC 61373 standard.
[4] Ansys user manual.
[5] ASTM standard and for radiography.
[6] Sanjib Kalita. Uses of Mems Accelerometer in Seismology, International Journal
of Advanced Research in Engineering and Technology, 4(6), 2013, pp. 57-61.
[7] Dr. N.R. Bhasme and Mr. Pranit Durge. Comparative Study of Electrical Motors
for Ceiling Fan Application, International Journal of Electrical Engineering and
Technology, 6(5), 2015, pp. 08-13.