Primex Plastics  
Executive Summary Review 
           Of 
   Corsicana, TX Plant 
           By 
     Quality Energy 
    January 12, 2009 
 
Measurement and Verification 
Primex Plastics is making a concentrated effort toward sustainability and profitability by reducing their carbon footprint 
and ongoing energy costs in all US plants. The Corsicana, TX plant was chosen as a pilot plant to test the claims made by 
Quality Energy that, the utilization of Elspec dynamic VAR compensation systems would reduce the power consumed, 
improve power factor, increase the total capacity of the existing electrical infrastructure and improve plant power 
quality. To verify these claims, prior to the installation of the Elspec systems, Quality Energy installed our Elspec G4k 
Class A electrical meter at the main switch gear of the Corsicana, TX facility. The G4k recorded energy usage and power 
quality data before and after the installation of the three Elspec systems located at the main switchgear and at extrusion 
lines 4 & 6.  The following graph details the data recorded by the G4k meter and illustrates energy parameters before 
and after commissioning the 3 Elspec systems November 7, 2008 as represented below: 




                                                                                                                                 

The data illustrates several positive results which verify the forecasted savings in our proposal.  Data from the above 
illustrates a significant increase in voltage and power factor coupled with an equally significant decrease in current, KVar 
and watts consumed.  This data and the financial impact are illustrated in the table on the following page. 
    ________________________________________________________
      Quality Energy • 6 Wilhelm Court • Fairfield, OH 45014 • 513.829.0002(P) • 513.829.3627 (F) • www.quality-energy.com
 

To summarize the previous chart: 


                                            BEFORE                   AFTER                           CHANGE % CHANGE $ SAVINGS/YR
VOLTAGE                                    489.2 volts            498.4 volts                               9.2      1.88%
CURRENT                                    669.7 amps             492.4 amps                            ‐177.3     ‐26.47%
REACTIVE POWER                             655.6 kvar             258.2 kvar                            ‐397.4     ‐60.62%
POWER FACTOR                              0.7358                 0.9462                                 0.2104      28.59%  $17,910.77
ENERGY                                   
                                        58,246 watts/hr         52,759 watts/hr                         ‐6,000     ‐10.30%  $37,080.46
DEMAND REDUCTION*                         877.75 kw              848.75 kw                                 ‐29      ‐3.30%   $2,053.20
*FROM UTILITY BILL                                                                                          METERED SAVINGS $57,044.43
DOWN TIME**                                                                                                                 $9,000.00
EQUIPMENT REPAIR**                                                                                                           $7,000.00
**FROM CUSTOMER SUPPLIED DATA                                                                          TOTAL ANNUAL SAVINGS $73,044.43
 

Conclusions: 
Total amp load & wattage for the entire plant was reduced by 26.5% and 10.3% respectively. Also, it is important to note 
the KW demand is reduced by 3.3%.  In many of your plant locations, this could be a larger portion of total savings based 
on local utility tariffs. 

The results in a KVAR reduction of over 60.62% will enable expansion of an additional line in the Corsican, TX operation 
without the need for expensive expansion in electrical infrastructure. 

The results in a KWH reduction of almost 10.3% will be directly reflected in the Constellation New Energy bill.  Based on 
the past 12 months bills (EXHIBIT 1 attached) show the electrical usage totaled 4,440,441 KWH annualized to 4,591,894.  
                                                                                      FORCASTED                   ACTUAL
This would result in savings for Primex of approximately                       Area        Monthly   Annual        Annual
                                                                             Improved      Savings  Savings        Savings
472,965KWH/yr @$.0784/KWH = $37,080/yr.                                                                           RESULTS
                                                                   Power Factor:    .73 to .95        $1,492.56       $17,910.77                 $17,910.77 @ .95 pf
                                                                          KWH:     Reduce 6%          $2,325.02       $27,900.18                 $37,080.00 @10% Reduction
The Power Factor improved from .7358 to .9462                        Down Time: Reduce 3 Hrs/Mo.*       $750.00        $9,000.00                  $9,000.00
                                                               Equipment Repair: Motors & PLC's*        $583.33        $7,000.00                  $7,000.00
resulting in an annual savings in future power factor                  Demand :                   Did not Forcast Did not Forcast                 $2,053.20 @3.3% Reduction
                                                                                      *Customer Supplied Data
penalties of $17, 910.77/yr.                                                                             $ SavingsTotal/yr:
                                                                                                                                 FORCASTED
                                                                                                                                 $61,810.96
                                                                                                                                               DELIVERED
                                                                                                                                                $73,043.97



Power Quality issues in the Primex electrical network                                    SAVINGS % BY CATEGORY FROCASTED & RESULTS

                                                                                 Monthly Savings                                          Monthly Savings
which produced resonance conditions resulted in the                               Projections for                                           Results for

numerous electrical problems. These power quality                         Equipment
                                                                                                                                   Equipment
                                                                                                                                    Repair:  Demand :        Power
                                                                           Repair:
                                                                                                                         Down                  3%            Factor:
                                                                                                                                      10%
issues have been reduced with the larger than normal                         11%                            Power
                                                                                                            Factor:
                                                                                                             29%
                                                                                                                         Time:
                                                                                                                          12%
                                                                                                                                                              24%

                                                                  Down Time:
reactors we installed on the Elspec systems on extrusion             15%




lines 4 and 6.                                                                                KWH:
                                                                                               45%
                                                                                                                                                             KWH:
                                                                                                                                                              51%




In our proposal to management for this pilot plant                                        Figure 3
dated August 8, 2008, we projected ongoing annual costs reductions of $61,810 and have delivered $73,043 or 171% of 
projected savings.  Additionally, the electrical network in the plant will realize a substantially improved power quality 
environment and the subsequent negative impacts on equipment repair and down time will be reduced.  


    ________________________________________________________
       Quality Energy • 6 Wilhelm Court • Fairfield, OH 45014 • 513.829.0002(P) • 513.829.3627 (F) • www.quality-energy.com
The Elspec systems also increased 
the voltage in the facility by 9.2 
volts over the existing level of 
489.2 volts to 498.4 volts.  After a 
few months of operation with all 
Elspecs operating we would like 
your permission to approach the 
utility provider with the 
recommendation of a “tap down” 
of 2.5% on the main transformer 
providing power to the plant.  If 
this is possible, additional savings 
of 4% or more in KWH 
consumption may be achievable. 

The graph of “Comparison of 
Investments” illustrates the long 
range financial benefit of this 
project compared to a 9% 
certificate of deposit, based on the results of the pilot plant in TX.  We look forward to evaluating the savings potential 
at other Primex Plastics locations. It is our sincere belief that similar energy savings opportunities exist throughout your 
company.   

 

Sincerely, 

 

Phil  Mullins 

Quality Energy 

Attachment




    ________________________________________________________
       Quality Energy • 6 Wilhelm Court • Fairfield, OH 45014 • 513.829.0002(P) • 513.829.3627 (F) • www.quality-energy.com
EXHIBIT 1 
                        RESULTS FROM METERED SAVINGS
Primex Plastics Corp - Corsicana, TX                                       BEFORE
           Billing Period                  KWH                 Days          KWH/Day        Billed Amt         Factor    Demand
          7/16/2008 8/13/2008                 371,271           28             13,260        $36,186.61            0.892     832
          6/16/2008 7/15/2008                 355,332           29             12,253        $34,893.94            0.848     828
          5/14/2008 6/15/2008                 390,114           32             12,191        $40,490.24            0.882     857
          4/15/2008 5/13/2008                 343,412           28             12,265        $36,367.23            0.906     878
          3/14/2008 4/14/2008                 373,793           31             12,058        $40,011.33            0.670     855
          2/14/2008 3/13/2008                 357,763           28             12,777        $38,456.86            0.691     875
          1/16/2008 2/13/2008                 361,768           28             12,920        $38,886.62            0.669     882
         12/13/2007 1/15/2008                 336,939           33             10,210        $36,519.57            0.686     873
         11/12/2007 12/12/2007                374,370           30             12,479        $39,479.90            0.972     857
         10/12/2007 11/11/2007                410,420           30             13,681        $43,050.05            0.716     864
          9/13/2007 10/11/2007                393,421           28             14,051        $41,586.89            0.712     866
          8/14/2007 9/12/2007                 371,838           29             12,822        $39,559.58            0.696     823
                          Total             4,440,441          354                             $465,489
                Monthly Average               370,037                            12,581         $38,791            0.778           858
     Adjusted to a 365 Day Year             4,591,894
    Monthly Average Annualized                382,658           365

                                                                 METERED RESULTS
                           Saved KWH/mo                         %KWH SAVINGS               $ Saved/mo       Pf Improved         New Pf
       AVERAGE SAVINGS/MO.     39,414                              10.30%                   $3,090.04           0.172            0.95


                                                               KWH                          Billed Amt      Pf
                            AVG Savings/mo                       39,414 kwh                    $3,090.04  $1,492.56
                           ANNUALIZED                           472,965 kwh/yr               $37,080.46  $17,910.77
                FORCASTED ANNUAL SAVINGS                            6.00%                  $ 27,900.18 $ 17,910.77
                 ACTUAL ANUALIZED SAVINGS                          10.30%                    $37,080     $17,911
            %ACTUAL TO FORCASTED SAVINGS                           171.67%                     133%       100%

                                        SUMMARY OF METERED SAVINGS
                                                         Actual Metered     Forcasted
                                       Power Factor        $17,910.77       $17,910.77
                                              KWH          $37,080.46       $ 27,900.18
                                         Down Time          $9,000.00        $9,000.00
                                   Equipment Repair         $7,000.00        $7,000.00
                                           Demand          $2,053.20           $0.00
                                            TOTAL          $73,044.44       $61,810.96

 

 

 