Calculating System Flow Requirements 
To select a pump, we need to know the flow rate (the amount of fluid to be pumped) and the system resistance or “head.” In the U.S., flow rates are given in gallons per minute, or GPM. The GPM is a function of the heat loss (or gain) of the building space served by the pump or the process load that is to be met by the pumped systems. It is ALSO a function of the design temperature change of the fluid as it travels through the hydronic system. The temperature change is commonly called the “Delta T,” or ΔT, where the triangle is the Greek symbol for the word “Delta.” 
Heat Load 
Determining the heat load of a building, a zone, or a process is beyond the scope of this paper. Once a time-consuming manual procedure, computer software now simplifies building load calculations considerably. You can download trial versions of some software from the Internet. 
Loads are expressed in British Thermal Units Per Hour, or BTUH. Other units of measure are: 
1. MBH = 1,000 BTUH 
2. Tons = 12,000 BTUH (used for cooling applications) 
3. Cooling tower tons = 15,000 BTUH* 
*This term is used only when the tower serves an electric chiller or other refrigeration system. In this application, the cooling tower must handle a building load of 12,000 BTUH per ton plus the compressor heat of about 3,000 BTUH/ton.1 
Design ΔT (Design Temperature Drop) This is conservative in light of today’s chiller efficiencies, which often consume less than 3,000 BTUH/ton. 
The system designer determines what ΔT he/she will use in the design. “Normal” T’s for comfort systems are:
2 
Heating Systems Cooling Systems Cooling Towers 
20, 30, or 40 °F 8, 10 or 12 °F 10 Degrees 
Note that these figures are only typical and are common in the HVAC industry. For specific HVAC applications and many process applications, the chosen delta T might be outside these ranges. 
Assuming that the chosen fluid will be water, once the ΔT is chosen, the GPM of the pump can be determined by the following formula: 
Formula 1: GPM = BTUH / 500 X ΔT 
Note that as the chosen ΔT goes up, the GPM goes down. This results in smaller pumps and smaller piping. However, larger ΔT’s tend to result in larger terminal equipment in the form of more rows of coil, more fan horse power, longer lengths of fin tube, etc. 
Note that the “500” factor in Formula 1 applies only to water. This is derived from the formula BTUH = #/HR X BTU/# X ΔT X S.H. where ΔT is given deg-F and S.H. is “Specific Heat” in BTU/#-Deg F. Note that #/HR of water = GPM X 8.33 #/GAL X 60 MIN/HR = GPM X 500; The S.H. for water = 1.0 at normal HVAC temperatures. Combining these equations and doing the appropriate algebraic substitutions yields Formula 1. 
For hydronic systems, we often use glycol mixtures to guard against freezing piping and coils that may be exposed to outside air.2 
For other fluids, the more general formula applies: These mixtures have different densities (#/GAL) and different specific heats (S.H) than water. So for various glycol mixtures, use the factors from Table 1 instead of 500. 
Formula 2: GPM = BTUH /(500 X S.G. X S.H. X ΔT) where S.G. is the fluid’s specific gravity. 
1 Single stage steam absorption chillers require about 3.6 GPM/Ton and have a heat rejection of around 30,000 BTUH/ton. Two stage absorption chillers require about 3.6-4.0 GPM/ton and have a heat rejection of around 22,000 BTUH/ton. 
2 Freeze and burst temperatures for various concentrations of ethylene and propylene glycol are listed in Appendix I at the end of this chapter.
3 
TABLE 1 
Load Factors for Propylene Glycol 
Volume % 
Temp. deg. –F 
10% 
20% 
30% 
40% 
50% 
20 
N/A 
481.7 
469.1 
453.3 
433.5 
40 
491.0 
482.8 
471.0 
455.6 
436.7 
60 
491.5 
484.0 
473.1 
458.1 
439.7 
80 
491.6 
485.1 
474.4 
460.3 
442.4 
100 
492.0 
485.6 
475.4 
462.2 
445.2 
120 
491.6 
486.0 
476.5 
463.7 
447.1 
140 
490.8 
485.5 
476.8 
464.4 
448.8 
160 
489.7 
485.1 
476.7 
465.2 
450.0 
180 
487.7 
484.4 
476.8 
465.7 
451.4 
200 
486.0 
483.3 
476.0 
465.7 
451.8 
Load Factors for Ethylene Glycol 
Volume % 
Temp. deg. -F 
10% 
20% 
30% 
40% 
50% 
20 
N/A 
464.4 
447.4 
428.7 
407.4 
40 
479.5 
466.3 
450.4 
432.2 
411.4 
60 
480.7 
468.4 
453.0 
435.4 
415.7 
80 
481.5 
469.7 
454.8 
438.2 
419.2 
100 
482.1 
470.8 
456.8 
440.8 
422.9 
120 
481.8 
466.4 
458.6 
443.1 
425.8 
140 
481.7 
471.8 
460.1 
445.2 
428.7 
160 
481.3 
472.5 
460.6 
447.3 
431.1 
180 
480.1 
472.2 
461.4 
448.7 
433.6 
200 
479.0 
471.6 
461.9 
449.7 
435.2 
Once the flow rate in GPM is determined, the next step in selecting the pump is to determine the head requirement. A discussion on this topic can be found as a separate topic within the “Technical Data” section of this website.
4 
Appendix 1---Freeze and Burst Temperatures for Glycol Solutions 
Note: Dowfrost products are propylene glycol based. 
Note: Dowtherm products are ethylene glycol based.
5 
Note: “Dowfrost” and “Dowtherm” are registered trademarks of the Dow Chemical Company. The information above is from Dow’s 1996 Engineering and Operating guides for their Downtherm and Dowfrost products and is included here for illustration.

More Related Content

What's hot

Refrigeration and-air-conditioning-by-iit-kgp
Refrigeration and-air-conditioning-by-iit-kgpRefrigeration and-air-conditioning-by-iit-kgp
Refrigeration and-air-conditioning-by-iit-kgp
Olumide Daniel
 
Chiller repair, condenser & refrigerant loop test, pump alignment, videos...
Chiller repair, condenser & refrigerant loop test, pump alignment, videos...Chiller repair, condenser & refrigerant loop test, pump alignment, videos...
Chiller repair, condenser & refrigerant loop test, pump alignment, videos...
pkpravin89
 
Pump and cooling tower energy performance
Pump and cooling tower energy performancePump and cooling tower energy performance
Pump and cooling tower energy performance
maulik610
 

What's hot (20)

Roy hubbard
Roy hubbardRoy hubbard
Roy hubbard
 
Cooling Systems - Chiller Technologies
Cooling Systems - Chiller TechnologiesCooling Systems - Chiller Technologies
Cooling Systems - Chiller Technologies
 
A STUDY ON ROLE OF CONDENSER AND NATURAL DRAFT COOLING TOWER ON THE PERFORMAN...
A STUDY ON ROLE OF CONDENSER AND NATURAL DRAFT COOLING TOWER ON THE PERFORMAN...A STUDY ON ROLE OF CONDENSER AND NATURAL DRAFT COOLING TOWER ON THE PERFORMAN...
A STUDY ON ROLE OF CONDENSER AND NATURAL DRAFT COOLING TOWER ON THE PERFORMAN...
 
HVAC for Data Centers
HVAC for Data CentersHVAC for Data Centers
HVAC for Data Centers
 
Adm apn045-en 0912
Adm apn045-en 0912Adm apn045-en 0912
Adm apn045-en 0912
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 
Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled Airconditioning
 
Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234
 
S3 Lec 2 (Condenser) Note
S3 Lec 2 (Condenser) NoteS3 Lec 2 (Condenser) Note
S3 Lec 2 (Condenser) Note
 
Refrigeration and-air-conditioning-by-iit-kgp
Refrigeration and-air-conditioning-by-iit-kgpRefrigeration and-air-conditioning-by-iit-kgp
Refrigeration and-air-conditioning-by-iit-kgp
 
project
projectproject
project
 
Refrigeration Engineering Lecture notes
Refrigeration Engineering Lecture notesRefrigeration Engineering Lecture notes
Refrigeration Engineering Lecture notes
 
Refrigeration system
Refrigeration systemRefrigeration system
Refrigeration system
 
Project Report
Project ReportProject Report
Project Report
 
air cooled chiller
air cooled chillerair cooled chiller
air cooled chiller
 
ANALYSIS OF MULTIPLE EVAPORATOR REFRIGERATION SYSTEM
ANALYSIS OF MULTIPLE EVAPORATOR REFRIGERATION SYSTEMANALYSIS OF MULTIPLE EVAPORATOR REFRIGERATION SYSTEM
ANALYSIS OF MULTIPLE EVAPORATOR REFRIGERATION SYSTEM
 
Chiller repair, condenser & refrigerant loop test, pump alignment, videos...
Chiller repair, condenser & refrigerant loop test, pump alignment, videos...Chiller repair, condenser & refrigerant loop test, pump alignment, videos...
Chiller repair, condenser & refrigerant loop test, pump alignment, videos...
 
Chilled water systems
Chilled water systemsChilled water systems
Chilled water systems
 
Pump and cooling tower energy performance
Pump and cooling tower energy performancePump and cooling tower energy performance
Pump and cooling tower energy performance
 
B.tech i eme u 4 r & ac
B.tech i eme u 4 r & acB.tech i eme u 4 r & ac
B.tech i eme u 4 r & ac
 

Similar to Cih taco3-calc flow---web-bill

Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosure
erdinc klima
 
2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl
michaeljmack
 
Boiler doc 02 principles & heat transfer
Boiler doc 02   principles & heat transferBoiler doc 02   principles & heat transfer
Boiler doc 02 principles & heat transfer
Mars Tsani
 
2015_Doble Paper
2015_Doble Paper2015_Doble Paper
2015_Doble Paper
Kevin Riley
 

Similar to Cih taco3-calc flow---web-bill (20)

Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosure
 
2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl
 
Plate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger SizingPlate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger Sizing
 
Cep plate and_frame_hx
Cep plate and_frame_hxCep plate and_frame_hx
Cep plate and_frame_hx
 
Design plate heat exchangers
Design plate heat exchangersDesign plate heat exchangers
Design plate heat exchangers
 
Boiler doc 02 principles & heat transfer
Boiler doc 02   principles & heat transferBoiler doc 02   principles & heat transfer
Boiler doc 02 principles & heat transfer
 
study material on shell and tube heat exchagers.pdf
study material on shell and tube heat exchagers.pdfstudy material on shell and tube heat exchagers.pdf
study material on shell and tube heat exchagers.pdf
 
M371content
M371contentM371content
M371content
 
Comparison of two different cooling methods for extrusion
Comparison of two different cooling methods for extrusionComparison of two different cooling methods for extrusion
Comparison of two different cooling methods for extrusion
 
Aph operation and emergency handling
Aph operation and emergency handlingAph operation and emergency handling
Aph operation and emergency handling
 
Chapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.pptChapter_11.ppt RAC REFRIGERATOR.ppt
Chapter_11.ppt RAC REFRIGERATOR.ppt
 
2015_Doble Paper
2015_Doble Paper2015_Doble Paper
2015_Doble Paper
 
Improve plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlImprove plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater control
 
4.4.heat exchanger
4.4.heat exchanger4.4.heat exchanger
4.4.heat exchanger
 
Harga pasang water heater 082122541663
Harga pasang water heater 082122541663Harga pasang water heater 082122541663
Harga pasang water heater 082122541663
 
Cooling system by Bhanupratap Niranjan IIT kanpur
Cooling system by Bhanupratap Niranjan IIT kanpurCooling system by Bhanupratap Niranjan IIT kanpur
Cooling system by Bhanupratap Niranjan IIT kanpur
 
hvac and refrigeration system
hvac and refrigeration systemhvac and refrigeration system
hvac and refrigeration system
 
Waste Heat Recovery Publication
Waste Heat Recovery PublicationWaste Heat Recovery Publication
Waste Heat Recovery Publication
 
Refrigeration system 2
Refrigeration system 2Refrigeration system 2
Refrigeration system 2
 
Waste Heat Recovery
Waste Heat RecoveryWaste Heat Recovery
Waste Heat Recovery
 

Recently uploaded

Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
HyderabadDolls
 
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
gajnagarg
 
In Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in Riyadh
In Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in RiyadhIn Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in Riyadh
In Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in Riyadh
ahmedjiabur940
 
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
nirzagarg
 
Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...
Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...
Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...
nirzagarg
 
Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...
Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...
Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...
HyderabadDolls
 
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
CristineGraceAcuyan
 
9352852248 Call Girls Naroda Escort Service Available 24×7 In Naroda
9352852248 Call Girls  Naroda Escort Service Available 24×7 In Naroda9352852248 Call Girls  Naroda Escort Service Available 24×7 In Naroda
9352852248 Call Girls Naroda Escort Service Available 24×7 In Naroda
gargpaaro
 
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
gajnagarg
 

Recently uploaded (20)

Bhubaneswar🌹Vip Call Girls Chandrashekharpur ❤Heer 9777949614 💟 Full Trusted ...
Bhubaneswar🌹Vip Call Girls Chandrashekharpur ❤Heer 9777949614 💟 Full Trusted ...Bhubaneswar🌹Vip Call Girls Chandrashekharpur ❤Heer 9777949614 💟 Full Trusted ...
Bhubaneswar🌹Vip Call Girls Chandrashekharpur ❤Heer 9777949614 💟 Full Trusted ...
 
Gamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad IbrahimGamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad Ibrahim
 
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
 
TRose UXPA Experience Design Concord .pptx
TRose UXPA Experience Design Concord .pptxTRose UXPA Experience Design Concord .pptx
TRose UXPA Experience Design Concord .pptx
 
Raebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for Friendship
Raebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for FriendshipRaebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for Friendship
Raebareli Girl Whatsapp Number 📞 8617370543 | Girls Number for Friendship
 
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Meerut [ 7014168258 ] Call Me For Genuine Models We...
 
In Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in Riyadh
In Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in RiyadhIn Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in Riyadh
In Saudi Arabia Jeddah (+918761049707)) Buy Abortion Pills For Sale in Riyadh
 
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
Top profile Call Girls In Sonipat [ 7014168258 ] Call Me For Genuine Models W...
 
Radhanpur / Independent Call Girls Ahmedabad Phone No 8005736733 Elite Escort...
Radhanpur / Independent Call Girls Ahmedabad Phone No 8005736733 Elite Escort...Radhanpur / Independent Call Girls Ahmedabad Phone No 8005736733 Elite Escort...
Radhanpur / Independent Call Girls Ahmedabad Phone No 8005736733 Elite Escort...
 
Just Call Vip call girls Kasganj Escorts ☎️8617370543 Two shot with one girl ...
Just Call Vip call girls Kasganj Escorts ☎️8617370543 Two shot with one girl ...Just Call Vip call girls Kasganj Escorts ☎️8617370543 Two shot with one girl ...
Just Call Vip call girls Kasganj Escorts ☎️8617370543 Two shot with one girl ...
 
Aminabad * High Profile Escorts Service in Lucknow Phone No 9548273370 Elite ...
Aminabad * High Profile Escorts Service in Lucknow Phone No 9548273370 Elite ...Aminabad * High Profile Escorts Service in Lucknow Phone No 9548273370 Elite ...
Aminabad * High Profile Escorts Service in Lucknow Phone No 9548273370 Elite ...
 
Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...
Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...
Top profile Call Girls In Moradabad [ 7014168258 ] Call Me For Genuine Models...
 
Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...
Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...
Salkhia @ Cheap Call Girls In Kolkata | Book 8005736733 Extreme Naughty Call ...
 
Mohanlalganj ! Call Girls in Lucknow - 450+ Call Girl Cash Payment 9548273370...
Mohanlalganj ! Call Girls in Lucknow - 450+ Call Girl Cash Payment 9548273370...Mohanlalganj ! Call Girls in Lucknow - 450+ Call Girl Cash Payment 9548273370...
Mohanlalganj ! Call Girls in Lucknow - 450+ Call Girl Cash Payment 9548273370...
 
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best ServiceHigh Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
High Profile Escorts Nerul WhatsApp +91-9930687706, Best Service
 
Only Cash On Delivery Call Girls Service In Mysore Enjoy 24/7 Escort Service
Only Cash On Delivery Call Girls Service In Mysore Enjoy 24/7 Escort ServiceOnly Cash On Delivery Call Girls Service In Mysore Enjoy 24/7 Escort Service
Only Cash On Delivery Call Girls Service In Mysore Enjoy 24/7 Escort Service
 
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
 
9352852248 Call Girls Naroda Escort Service Available 24×7 In Naroda
9352852248 Call Girls  Naroda Escort Service Available 24×7 In Naroda9352852248 Call Girls  Naroda Escort Service Available 24×7 In Naroda
9352852248 Call Girls Naroda Escort Service Available 24×7 In Naroda
 
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
Top profile Call Girls In Mysore [ 7014168258 ] Call Me For Genuine Models We...
 
Just Call Vip call girls Fatehpur Escorts ☎️8617370543 Two shot with one girl...
Just Call Vip call girls Fatehpur Escorts ☎️8617370543 Two shot with one girl...Just Call Vip call girls Fatehpur Escorts ☎️8617370543 Two shot with one girl...
Just Call Vip call girls Fatehpur Escorts ☎️8617370543 Two shot with one girl...
 

Cih taco3-calc flow---web-bill

  • 1. 1 Calculating System Flow Requirements To select a pump, we need to know the flow rate (the amount of fluid to be pumped) and the system resistance or “head.” In the U.S., flow rates are given in gallons per minute, or GPM. The GPM is a function of the heat loss (or gain) of the building space served by the pump or the process load that is to be met by the pumped systems. It is ALSO a function of the design temperature change of the fluid as it travels through the hydronic system. The temperature change is commonly called the “Delta T,” or ΔT, where the triangle is the Greek symbol for the word “Delta.” Heat Load Determining the heat load of a building, a zone, or a process is beyond the scope of this paper. Once a time-consuming manual procedure, computer software now simplifies building load calculations considerably. You can download trial versions of some software from the Internet. Loads are expressed in British Thermal Units Per Hour, or BTUH. Other units of measure are: 1. MBH = 1,000 BTUH 2. Tons = 12,000 BTUH (used for cooling applications) 3. Cooling tower tons = 15,000 BTUH* *This term is used only when the tower serves an electric chiller or other refrigeration system. In this application, the cooling tower must handle a building load of 12,000 BTUH per ton plus the compressor heat of about 3,000 BTUH/ton.1 Design ΔT (Design Temperature Drop) This is conservative in light of today’s chiller efficiencies, which often consume less than 3,000 BTUH/ton. The system designer determines what ΔT he/she will use in the design. “Normal” T’s for comfort systems are:
  • 2. 2 Heating Systems Cooling Systems Cooling Towers 20, 30, or 40 °F 8, 10 or 12 °F 10 Degrees Note that these figures are only typical and are common in the HVAC industry. For specific HVAC applications and many process applications, the chosen delta T might be outside these ranges. Assuming that the chosen fluid will be water, once the ΔT is chosen, the GPM of the pump can be determined by the following formula: Formula 1: GPM = BTUH / 500 X ΔT Note that as the chosen ΔT goes up, the GPM goes down. This results in smaller pumps and smaller piping. However, larger ΔT’s tend to result in larger terminal equipment in the form of more rows of coil, more fan horse power, longer lengths of fin tube, etc. Note that the “500” factor in Formula 1 applies only to water. This is derived from the formula BTUH = #/HR X BTU/# X ΔT X S.H. where ΔT is given deg-F and S.H. is “Specific Heat” in BTU/#-Deg F. Note that #/HR of water = GPM X 8.33 #/GAL X 60 MIN/HR = GPM X 500; The S.H. for water = 1.0 at normal HVAC temperatures. Combining these equations and doing the appropriate algebraic substitutions yields Formula 1. For hydronic systems, we often use glycol mixtures to guard against freezing piping and coils that may be exposed to outside air.2 For other fluids, the more general formula applies: These mixtures have different densities (#/GAL) and different specific heats (S.H) than water. So for various glycol mixtures, use the factors from Table 1 instead of 500. Formula 2: GPM = BTUH /(500 X S.G. X S.H. X ΔT) where S.G. is the fluid’s specific gravity. 1 Single stage steam absorption chillers require about 3.6 GPM/Ton and have a heat rejection of around 30,000 BTUH/ton. Two stage absorption chillers require about 3.6-4.0 GPM/ton and have a heat rejection of around 22,000 BTUH/ton. 2 Freeze and burst temperatures for various concentrations of ethylene and propylene glycol are listed in Appendix I at the end of this chapter.
  • 3. 3 TABLE 1 Load Factors for Propylene Glycol Volume % Temp. deg. –F 10% 20% 30% 40% 50% 20 N/A 481.7 469.1 453.3 433.5 40 491.0 482.8 471.0 455.6 436.7 60 491.5 484.0 473.1 458.1 439.7 80 491.6 485.1 474.4 460.3 442.4 100 492.0 485.6 475.4 462.2 445.2 120 491.6 486.0 476.5 463.7 447.1 140 490.8 485.5 476.8 464.4 448.8 160 489.7 485.1 476.7 465.2 450.0 180 487.7 484.4 476.8 465.7 451.4 200 486.0 483.3 476.0 465.7 451.8 Load Factors for Ethylene Glycol Volume % Temp. deg. -F 10% 20% 30% 40% 50% 20 N/A 464.4 447.4 428.7 407.4 40 479.5 466.3 450.4 432.2 411.4 60 480.7 468.4 453.0 435.4 415.7 80 481.5 469.7 454.8 438.2 419.2 100 482.1 470.8 456.8 440.8 422.9 120 481.8 466.4 458.6 443.1 425.8 140 481.7 471.8 460.1 445.2 428.7 160 481.3 472.5 460.6 447.3 431.1 180 480.1 472.2 461.4 448.7 433.6 200 479.0 471.6 461.9 449.7 435.2 Once the flow rate in GPM is determined, the next step in selecting the pump is to determine the head requirement. A discussion on this topic can be found as a separate topic within the “Technical Data” section of this website.
  • 4. 4 Appendix 1---Freeze and Burst Temperatures for Glycol Solutions Note: Dowfrost products are propylene glycol based. Note: Dowtherm products are ethylene glycol based.
  • 5. 5 Note: “Dowfrost” and “Dowtherm” are registered trademarks of the Dow Chemical Company. The information above is from Dow’s 1996 Engineering and Operating guides for their Downtherm and Dowfrost products and is included here for illustration.