Effective: November 2010 	 Supplement 1100-20
Liquid Level Transmitter
TeleSensor™
■	 External mounting	at tank
■ Electronic (4–20 mA)		
or pneumatic output
■ Unaffected by foam		
or vapor	
■ Safe for explosion		
hazard zones
Tank Flange Mounting
The basic configuration is designed for mounting to any
typical outlet near the bottom of the tank. It features a
pipe flange connection (2", 3", or 4" class 150 ANSI).
Since the TeleSensor sensing diaphragm responds to
the pressure due to the head of liquid in the tank,
KING-GAGE ®
the mounting location determines the starting level
measurement point. Owing to the direct contact, all wetted
materials should be selected based on compatibility with
the tank’s contents. Standard diaphragms are titanium.
Flange connectors are available in various materials as well.
The rugged design of the TeleSensor tank unit is remarkably
easy to maintain.
Rugged and Reliable
Measurement
These unique pneumatic sensors detect level
by sensing hydrostatic pressure created by liquid
depth. Acting on the force balance principle, a
sensitive diaphragm is exposed to the liquid contents
of the tank. Compressed air within the sensor creates
a pneumatic pressure that balances the force of the
liquid acting against the diaphragm. This compensating
pneumatic pressure is directly proportional to the depth
of liquid in the tank.
The pneumatic force balance technique is virtually
free from long term drift, hysteresis and temperature
sensitivity unlike strain measurements (including load
cells) since mechanical deflection of the diaphragm is
not directly measured. The compensating pneumatic
balance pressure which effectively isolates the sensor is
converted to a proportional 4–20 mAdc signal or can be
directly output to a suitable gauge. In actuality, the sensor
is measuring the mass (weight) of fluid matter that can
be correlated to units of standardized volume.
Force balance diaphragm has no inherent hysteresis or
bias induced by temperature (unlike strain measurement
devices) and mounts completely external to the tank.
Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com
Page 2
TeleSensor—Liquid Level Sensor	 Supplement 1100-20
Tank Gauging Applications
Acting on the force balance principle, a pneumatic sensor
generates air pressure equivalent to the hydrostatic force
created by liquid depth. This pneumatic pressure is directed
intotheD/Ptransmitter. Pressureisconvertedtoanelectronic
4–20 mAdc output proportional to liquid depth. Twisted
pair cabling is used to form the signal loop through which
the remote indicator receives the transmitter output. The
KING-GAGEindicatorsshowninthesesystemviewscorrelate
the transmitter output to total volume or weight of tank
contents. This is determined by using a pressure versus
capacitylistingcorrespondingtotheactualtankdimensions.
The diaphragm unit is generally paired with the 868 D/P
Sensor Control with integral transmitter. This converts the
pneumatic isolation pressure to a proportional 4–20 mAdc
signal suitable for process control or remote level indication.
The standard TeleSensor + 868 D/P package combines
accuracy, rugged durability, reduced maintenance, and
long term stability for liquid level tank gauging.
Transmitter Signal Loop
As is typical of two wire transmitters, electrical power to
the signal loop is supplied through twisted pair cable.
Excitation voltage (+V) is provided by the receiving device
or from a separate Vdc power supply installed in the loop.
The actual voltage necessary for operation of the system
will depend upon the overall load resistance of the loop.
In most applications, the KING-GAGE Digital Indicator or
LevelBAR indicator provide 24 Vdc excitation to power the
transmitter signal loop.
RL
4 to 20 mA
+VA
Vcom
+
–
-+
METER
TP2TP1
–+
1234
Internal connections
at D/P Sensor Control
V P
E
®
®
KIN
G-G
AG
E
KING
ENGINEE
RING
CORPOR
ATION
7
8
9
4
5
6
1
2
3
0
.
Menu
Selec
t
Edit
Enter
Reset
9982TANK1 GAL1.019
LevelB
A
R
®
®
K
IN
G
-G
A
G
E
Liqu
id
Lev
el
Gau
ging
Syst
em
KING
ENG
INEE
RING
COR
P.,
ANN
ARBO
R,
MICH
IGAN
U.S.A
.
™
2
10
20
30
40
50
60
70
80
90
100
200
200
0
100
0
200
0
300
0
400
0
500
0
600
0
700
0
800
0
900
0
100
00
EACHMARK=100GALS.1.00SP.GR.
EACHMARK=1PERCENTFULL1.00SP.GR.
TAN
K
1
Pow
er
LVB
-3
868 D/P Sensor
Control
Compressed
Air Supply
KING-GAGE
LevelBAR
Indicator
KING-GAGE
LP2 Indicator
4-20 mA signal
via twisted
pair cable
TeleSensor ■ 4–20 mA Output Version
TeleSensor
868 D/P
Sensor Control
TeleSensor + 868 D/P Sensor Control =
4–20 mA Output
Pneumatic force balance diaphragm sensor with regulator/
transmitter provides two wire 4–20 mAdc output. This
system is compatible with a wide range of indicators and
receivers (including PLCs).
3-Tube Cable
TeleSensor System Package with 868 D/P Sensor Control (4–20 mA Output)
Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com
TeleSensor—Liquid Level Sensor								 Supplement 1100-20
Page 3
Pneumatic Operation
TeleSensor diaphragm unit is paired with a Sensor Control
regulator to provide the continuous 1 CFH (cubic foot
per hour) air flow to the underside of the diaphragm to
attain pneumatic balance pressure. Constant back pressure
regulation maintains linear 1:1 response throughout the
entire operating range to ensure pneumatic pressure is directly
equivalent to the hydrostatic head of liquid in the tank.
Application Notes
Mounting flange and diaphragm are wetted surfaces
requiring compatibility with process media. Location of the
Sensor Control regulator should generally be no greater
than 50 feet (15 m) from the TeleSensor unit. The sensor
includes 15 feet (4.5 m) of bundled 3-tube cable for the
pneumatic interconnections with the Sensor Control.
Distances greater than 50 feet may increase response time
of sensor to changes in liquid level in the tank.
Explosion Hazard Use (Zone One or Division One)
The TeleSensor requires no electrical energy for operation when
using the 860 Sensor Control. It is possible to configure the tank
level system without zener barriers or intrinsic safety provisions.
The pneumatic signal may be routed to beyond the hazard zone
(1000 feet or more) to an indicator or transmitter.
Explosion
Hazard Area
860 Sensor
Control
Pneumatic
Signal
D/P
Transmitter
4-20 mA
Signal
KING-GAGE
LP2 Indicator
TeleSensor
®
®
KIN
G-G
AG
E
KING
ENGINEE
RING
CORPOR
ATION
7
8
9
4
5
6
1
2
3
0
.
Menu
Selec
t
Edit
Enter
Reset
9982TANK1 GAL1.019
G
V P
®
®
KIN
G-G
AG
E
KING
ENGINEE
RING
CORPOR
ATION
7
8
9
4
5
6
1
2
3
0
.
Menu
Selec
t
Edit
Enter
Reset
9982TANK1 GAL1.019
LevelB
A
R
®
®
K
IN
G
-G
A
G
E
Liqu
id
Lev
el
Gau
ging
Syst
em
KING
ENG
INEE
RING
COR
P.,
ANN
ARBO
R,
MICH
IGAN
U.S.A
.
™
2
10
20
30
40
50
60
70
80
90
100
200
200
0
100
0
200
0
300
0
400
0
500
0
600
0
700
0
800
0
900
0
100
00
EACHMARK=100GALS.1.00SP.GR.
EACHMARK=1PERCENTFULL1.00SP.GR.
TAN
K
1
Pow
er
LVB
-3
860 Sensor
Control
Compressed
Air Supply
Pneumatic Signal
via 1/4" tubing
D/P
Module
KING-GAGE
LP2 Indicator
KING-GAGE
LevelBAR
Indicator
4-20 mA
Signal
TeleSensor ■ Pneumatic Output Version
TeleSensor
860 Sensor
Control
TeleSensor + 860 Sensor Control =
Pneumatic Output
This package comprises a complete level sensing system
with specialized regulator assembly and force balance
diaphragm unit. Pneumatic package has no electrical
components and simply requires compressed air supply
for operation.
3-Tube Cable
TeleSensor System Package with 860 Sensor Control (Pneumatic Output)
Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com
KING-GAGE®
TeleSensor							 Liquid Level Transmitter
Specifications
Sensitivity
Better than .001 psi (± .02" water /.508 mm water)
Repeatability
Better than ± .002 psi (± .05" water / 1.27 mm water)
Primary Accuracy
± .007 psi (± 0.2" water /.508 mm water)
Temperature Range
30°F to 300°F (0°C to 149°C)
Pressure Range
Sensor is a 1:1 pneumatic force balance diaphragm
capable of repeating hydrostatic pressure as an equiva-
lent pneumatic output. Functional pressure limit is 130
psi (or 3598 inches @ 1.00 specific gravity) determined
by supply pressure (35–150 psi) less 20 psi.
Maximum Depth Measurement
1937 in. water (49.0 m water)
Wetted Materials
Viton O-ring, titanium diaphragm, commercially pure.
Optional diaphragm materials: silicone rubber
Mounting flange options: 316L stainless, PVC,
brewery special flange
Air Consumption
Total air consumption of sensor package (including
sensor control) is less than 10 CFH or 0.16 scfm.
D/P Sensor Control Combined Accuracy *
0–5 psid transmitter/control ± 0.34% FS
0–10 psid transmitter/control ± 0.27% FS
0–15 psid transmitter/control ± 0.24% FS
0–30 psid transmitter/control ± 0.22% FS
0–50 psid transmitter/control ± 0.21% FS
Voltage Supply Requirements
14–40 Vdc (unregulated) to power signal loop using
868 D/P Sensor Control.
Compressed Air Supply Requirements
35–150 psig (2.4–10.3 bar); clean, dry air (or inert
gas)
*Combined accuracy refers to the primary accuracy of the sensor in
combination with the secondary accuracy of the D/P transmitter.
® KING-GAGE and the KE emblem are registered trademarks 	
and TeleSensor is a trademark of King Engineering Corp.
© 2010 King Engineering Corporation. All rights reserved.
KING-GAGE
2,3 or 4 in.
150-lb ANSI Flange
*
* 4 in. Flange has 8 bolt circle,
2 and 3 in. Flange have 4 bolt circle.
KING-GAGE
4-in.
102 mm
bolt circle
3-5/8 in.
92 mm
TeleSensor w/ Special
3-in. Brewery Flange (304 SS)
Compressed Air Supply
Operation of the TeleSensor requires a compressed air/gas
source providing supply pressure of 35–150 psig (2.4–10.3
bar). Pneumatic components require instrumentation-grade
compressed air that is clean, dry, and oil-free to ensure trouble
free performance.
8019 Ohio River Blvd. Newell, WV 26050 U.S.A.
Phone: 304-387-1200 • 800-242-8871
Fax: 304-387-4417
marshbellofram.com • king-gage.com
Marsh Bellofram Group of Companies
Span Adjustment Range
Transmitter turndown ratio is 3:1 for the 0–15, 0–30, 0–50
psid nominal ranges.
Nominal	 Minimum	 Range of Adjustment
0–5 psid	 0–3 psid	 0–83 in. thru 0–138 in. water / 		
0–2.1 m thru 0–3.5 m water
0–10 psid	 0–3 psid	 0–83 in. thru 0–277 in. water / 		
0–2.1 m thru 0–7.0 m water
0–15 psid	 0–3 psid	 0–83 in. thru 0–415 in. water / 		
0–2.1 m thru 0–10.5 m water
0–30 psid	 0–10 psid	 0–277 in. thru 0–830 in. water / 		
0–7.0 m thru 0–21.0 m water
0–50 psid	 0–15 psid	 0–415 in. thru 0–1384 in. water / 		
0–10.5 m thru 0–35.1 m water
IMPORTANT! Accuracy, linearity, and non-repeatability values are
based on nominal range.
Operating Limit (Maximum Pressure)
Pressure above 300% nominal range (overrange) will result
in damage to the transmitter (200% may cause a shift in
calibration).Burstpressureis200psiandwillcausecatastrophic
and physical failure of the pressure element.
LtKe1100-20__3-13-2012 cw
Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com

More Related Content

What's hot

What's hot (20)

Jordan valve mark 80 self operated temperature regulator
Jordan valve mark 80 self operated temperature regulatorJordan valve mark 80 self operated temperature regulator
Jordan valve mark 80 self operated temperature regulator
 
Ins and Outs of I/P Transducers
Ins and Outs of I/P TransducersIns and Outs of I/P Transducers
Ins and Outs of I/P Transducers
 
Flow, Pressure & Vapor Instrumentation
Flow, Pressure & Vapor InstrumentationFlow, Pressure & Vapor Instrumentation
Flow, Pressure & Vapor Instrumentation
 
Digital Vortex Flowmeters From Yokogawa
Digital Vortex Flowmeters From YokogawaDigital Vortex Flowmeters From Yokogawa
Digital Vortex Flowmeters From Yokogawa
 
Liquid Level Measurement Using the Bubbler Method
Liquid Level Measurement Using the Bubbler MethodLiquid Level Measurement Using the Bubbler Method
Liquid Level Measurement Using the Bubbler Method
 
Combustion Airflow Measurement Station
Combustion Airflow Measurement StationCombustion Airflow Measurement Station
Combustion Airflow Measurement Station
 
Turbine flow meters for gas service from Hoffer
Turbine flow meters for gas service from HofferTurbine flow meters for gas service from Hoffer
Turbine flow meters for gas service from Hoffer
 
Turbine Flowmeters for Liquids
Turbine Flowmeters for LiquidsTurbine Flowmeters for Liquids
Turbine Flowmeters for Liquids
 
Improved closed loop cooling arrangement
Improved closed loop cooling arrangementImproved closed loop cooling arrangement
Improved closed loop cooling arrangement
 
Technical description etc converter 2014 (en) light
Technical description etc converter 2014 (en) lightTechnical description etc converter 2014 (en) light
Technical description etc converter 2014 (en) light
 
Yokogawa Differential Pressure Transmitter
Yokogawa Differential Pressure TransmitterYokogawa Differential Pressure Transmitter
Yokogawa Differential Pressure Transmitter
 
Technical description vg 2014 (en) light
Technical description vg 2014 (en) lightTechnical description vg 2014 (en) light
Technical description vg 2014 (en) light
 
VRF system presentation !
VRF system presentation !VRF system presentation !
VRF system presentation !
 
Adicomp OIL & GAS
Adicomp OIL & GASAdicomp OIL & GAS
Adicomp OIL & GAS
 
Dekon vrf system brief introduction
Dekon vrf system brief introductionDekon vrf system brief introduction
Dekon vrf system brief introduction
 
Adicomp REFERENCE LIST
Adicomp REFERENCE LISTAdicomp REFERENCE LIST
Adicomp REFERENCE LIST
 
Hs29 6 20-ton_ehb_hs29_072to240_0706
Hs29 6 20-ton_ehb_hs29_072to240_0706Hs29 6 20-ton_ehb_hs29_072to240_0706
Hs29 6 20-ton_ehb_hs29_072to240_0706
 
Powerstream Turbo chiller
Powerstream Turbo chillerPowerstream Turbo chiller
Powerstream Turbo chiller
 
Beebe steam turbines cm apr2016 r1
Beebe steam turbines cm apr2016 r1Beebe steam turbines cm apr2016 r1
Beebe steam turbines cm apr2016 r1
 
Current To Pneumatic Converter for Process Control
Current To Pneumatic Converter for Process ControlCurrent To Pneumatic Converter for Process Control
Current To Pneumatic Converter for Process Control
 

Similar to Hydrostatic Pressure Liquid Level Transmitter

Similar to Hydrostatic Pressure Liquid Level Transmitter (20)

Down Pipe Liquid Level Sensor
Down Pipe Liquid Level SensorDown Pipe Liquid Level Sensor
Down Pipe Liquid Level Sensor
 
Flowphant t dtt31, dtt35 endress+hauser datasheet-flow switch
Flowphant t dtt31, dtt35 endress+hauser datasheet-flow switchFlowphant t dtt31, dtt35 endress+hauser datasheet-flow switch
Flowphant t dtt31, dtt35 endress+hauser datasheet-flow switch
 
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
 
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
2600T Series Pressure Transmitter Model 261GS Gauge Model 261AS Absolute stan...
 
Siemens Duct sensor
Siemens Duct sensorSiemens Duct sensor
Siemens Duct sensor
 
Bender rc48 c
Bender rc48 cBender rc48 c
Bender rc48 c
 
transmitter
transmittertransmitter
transmitter
 
Bhel vis powerplant
Bhel vis powerplantBhel vis powerplant
Bhel vis powerplant
 
Target flowmeter catalog.zero100tf
Target flowmeter catalog.zero100tfTarget flowmeter catalog.zero100tf
Target flowmeter catalog.zero100tf
 
Target flowmeter catalog Z100TF
Target flowmeter catalog Z100TFTarget flowmeter catalog Z100TF
Target flowmeter catalog Z100TF
 
United Electric TX200 Pressure Transmitter
United Electric TX200 Pressure TransmitterUnited Electric TX200 Pressure Transmitter
United Electric TX200 Pressure Transmitter
 
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled PipesKrohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
 
Products
ProductsProducts
Products
 
i196_2.pdf
i196_2.pdfi196_2.pdf
i196_2.pdf
 
Brooks Ar-Mite Low Flow Armored Flowmeter
Brooks Ar-Mite Low Flow Armored FlowmeterBrooks Ar-Mite Low Flow Armored Flowmeter
Brooks Ar-Mite Low Flow Armored Flowmeter
 
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 NewOriginal High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
 
MPX5010.pdf
MPX5010.pdfMPX5010.pdf
MPX5010.pdf
 
Vapour pressure-model-1354 atac
Vapour pressure-model-1354 atacVapour pressure-model-1354 atac
Vapour pressure-model-1354 atac
 
Depth and level_sensor_pdcr1830
Depth and level_sensor_pdcr1830Depth and level_sensor_pdcr1830
Depth and level_sensor_pdcr1830
 
Siemens Terminal Box Controller (APOGEE Automation System )
Siemens Terminal Box Controller (APOGEE Automation System )Siemens Terminal Box Controller (APOGEE Automation System )
Siemens Terminal Box Controller (APOGEE Automation System )
 

More from Mountain States Engineering and Controls

More from Mountain States Engineering and Controls (20)

Design of Fluid Systems - Steam Utilization
Design of Fluid Systems - Steam UtilizationDesign of Fluid Systems - Steam Utilization
Design of Fluid Systems - Steam Utilization
 
Valves Used in Mining Operations
Valves Used in Mining OperationsValves Used in Mining Operations
Valves Used in Mining Operations
 
Regenerative Turbine Chemical Process Pumps
Regenerative Turbine Chemical Process PumpsRegenerative Turbine Chemical Process Pumps
Regenerative Turbine Chemical Process Pumps
 
Dual Snap Pressure, Temperature and Flow Switches
Dual Snap Pressure, Temperature and Flow SwitchesDual Snap Pressure, Temperature and Flow Switches
Dual Snap Pressure, Temperature and Flow Switches
 
Piston Isolation Valves For Steam and Condensate
Piston Isolation Valves For Steam and CondensatePiston Isolation Valves For Steam and Condensate
Piston Isolation Valves For Steam and Condensate
 
Trunnion Mount Ball Valves For Industrial Pipelines
Trunnion Mount Ball Valves For Industrial PipelinesTrunnion Mount Ball Valves For Industrial Pipelines
Trunnion Mount Ball Valves For Industrial Pipelines
 
Thermodynamic Steam Traps for Condensate Removal
Thermodynamic Steam Traps for Condensate RemovalThermodynamic Steam Traps for Condensate Removal
Thermodynamic Steam Traps for Condensate Removal
 
Steam Thermocompressor Technical Information
Steam Thermocompressor Technical InformationSteam Thermocompressor Technical Information
Steam Thermocompressor Technical Information
 
Pneumatic Actuators For Industrial Valves
Pneumatic Actuators For Industrial ValvesPneumatic Actuators For Industrial Valves
Pneumatic Actuators For Industrial Valves
 
Direct Operated Temperature Regulators
Direct Operated Temperature RegulatorsDirect Operated Temperature Regulators
Direct Operated Temperature Regulators
 
Pneumatic Rack and Pinion Valve Actuators
Pneumatic Rack and Pinion Valve ActuatorsPneumatic Rack and Pinion Valve Actuators
Pneumatic Rack and Pinion Valve Actuators
 
Three Piece Ball Valves Available With Metal Seats
Three Piece Ball Valves Available With Metal SeatsThree Piece Ball Valves Available With Metal Seats
Three Piece Ball Valves Available With Metal Seats
 
Industrial Linear Electric Actuators for Valves
Industrial Linear Electric Actuators for ValvesIndustrial Linear Electric Actuators for Valves
Industrial Linear Electric Actuators for Valves
 
Trunnion mounted ball valves for industrial applications
Trunnion mounted ball valves for industrial applicationsTrunnion mounted ball valves for industrial applications
Trunnion mounted ball valves for industrial applications
 
Floating Ball Valves for Industrial Application
Floating Ball Valves for Industrial ApplicationFloating Ball Valves for Industrial Application
Floating Ball Valves for Industrial Application
 
Technical Information for PC4000 Pipeline Connector
Technical Information for PC4000 Pipeline ConnectorTechnical Information for PC4000 Pipeline Connector
Technical Information for PC4000 Pipeline Connector
 
Valve usage and replacement when converting power generation from coal to gas
Valve usage and replacement when converting power generation from coal to gasValve usage and replacement when converting power generation from coal to gas
Valve usage and replacement when converting power generation from coal to gas
 
Steam to Water Heat Exchangers for Hot Water on Demand
Steam to Water Heat Exchangers for Hot Water on DemandSteam to Water Heat Exchangers for Hot Water on Demand
Steam to Water Heat Exchangers for Hot Water on Demand
 
High Pressure Float Type Steam Trap
High Pressure Float Type Steam TrapHigh Pressure Float Type Steam Trap
High Pressure Float Type Steam Trap
 
Regenerative turbine pump application, design, and features
Regenerative turbine pump application, design, and featuresRegenerative turbine pump application, design, and features
Regenerative turbine pump application, design, and features
 

Recently uploaded

1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
AldoGarca30
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 

Recently uploaded (20)

1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth Reinforcement
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
fitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .pptfitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .ppt
 
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Signal Processing and Linear System Analysis
Signal Processing and Linear System AnalysisSignal Processing and Linear System Analysis
Signal Processing and Linear System Analysis
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdf
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 

Hydrostatic Pressure Liquid Level Transmitter

  • 1. Effective: November 2010 Supplement 1100-20 Liquid Level Transmitter TeleSensor™ ■ External mounting at tank ■ Electronic (4–20 mA) or pneumatic output ■ Unaffected by foam or vapor ■ Safe for explosion hazard zones Tank Flange Mounting The basic configuration is designed for mounting to any typical outlet near the bottom of the tank. It features a pipe flange connection (2", 3", or 4" class 150 ANSI). Since the TeleSensor sensing diaphragm responds to the pressure due to the head of liquid in the tank, KING-GAGE ® the mounting location determines the starting level measurement point. Owing to the direct contact, all wetted materials should be selected based on compatibility with the tank’s contents. Standard diaphragms are titanium. Flange connectors are available in various materials as well. The rugged design of the TeleSensor tank unit is remarkably easy to maintain. Rugged and Reliable Measurement These unique pneumatic sensors detect level by sensing hydrostatic pressure created by liquid depth. Acting on the force balance principle, a sensitive diaphragm is exposed to the liquid contents of the tank. Compressed air within the sensor creates a pneumatic pressure that balances the force of the liquid acting against the diaphragm. This compensating pneumatic pressure is directly proportional to the depth of liquid in the tank. The pneumatic force balance technique is virtually free from long term drift, hysteresis and temperature sensitivity unlike strain measurements (including load cells) since mechanical deflection of the diaphragm is not directly measured. The compensating pneumatic balance pressure which effectively isolates the sensor is converted to a proportional 4–20 mAdc signal or can be directly output to a suitable gauge. In actuality, the sensor is measuring the mass (weight) of fluid matter that can be correlated to units of standardized volume. Force balance diaphragm has no inherent hysteresis or bias induced by temperature (unlike strain measurement devices) and mounts completely external to the tank. Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com
  • 2. Page 2 TeleSensor—Liquid Level Sensor Supplement 1100-20 Tank Gauging Applications Acting on the force balance principle, a pneumatic sensor generates air pressure equivalent to the hydrostatic force created by liquid depth. This pneumatic pressure is directed intotheD/Ptransmitter. Pressureisconvertedtoanelectronic 4–20 mAdc output proportional to liquid depth. Twisted pair cabling is used to form the signal loop through which the remote indicator receives the transmitter output. The KING-GAGEindicatorsshowninthesesystemviewscorrelate the transmitter output to total volume or weight of tank contents. This is determined by using a pressure versus capacitylistingcorrespondingtotheactualtankdimensions. The diaphragm unit is generally paired with the 868 D/P Sensor Control with integral transmitter. This converts the pneumatic isolation pressure to a proportional 4–20 mAdc signal suitable for process control or remote level indication. The standard TeleSensor + 868 D/P package combines accuracy, rugged durability, reduced maintenance, and long term stability for liquid level tank gauging. Transmitter Signal Loop As is typical of two wire transmitters, electrical power to the signal loop is supplied through twisted pair cable. Excitation voltage (+V) is provided by the receiving device or from a separate Vdc power supply installed in the loop. The actual voltage necessary for operation of the system will depend upon the overall load resistance of the loop. In most applications, the KING-GAGE Digital Indicator or LevelBAR indicator provide 24 Vdc excitation to power the transmitter signal loop. RL 4 to 20 mA +VA Vcom + – -+ METER TP2TP1 –+ 1234 Internal connections at D/P Sensor Control V P E ® ® KIN G-G AG E KING ENGINEE RING CORPOR ATION 7 8 9 4 5 6 1 2 3 0 . Menu Selec t Edit Enter Reset 9982TANK1 GAL1.019 LevelB A R ® ® K IN G -G A G E Liqu id Lev el Gau ging Syst em KING ENG INEE RING COR P., ANN ARBO R, MICH IGAN U.S.A . ™ 2 10 20 30 40 50 60 70 80 90 100 200 200 0 100 0 200 0 300 0 400 0 500 0 600 0 700 0 800 0 900 0 100 00 EACHMARK=100GALS.1.00SP.GR. EACHMARK=1PERCENTFULL1.00SP.GR. TAN K 1 Pow er LVB -3 868 D/P Sensor Control Compressed Air Supply KING-GAGE LevelBAR Indicator KING-GAGE LP2 Indicator 4-20 mA signal via twisted pair cable TeleSensor ■ 4–20 mA Output Version TeleSensor 868 D/P Sensor Control TeleSensor + 868 D/P Sensor Control = 4–20 mA Output Pneumatic force balance diaphragm sensor with regulator/ transmitter provides two wire 4–20 mAdc output. This system is compatible with a wide range of indicators and receivers (including PLCs). 3-Tube Cable TeleSensor System Package with 868 D/P Sensor Control (4–20 mA Output) Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com
  • 3. TeleSensor—Liquid Level Sensor Supplement 1100-20 Page 3 Pneumatic Operation TeleSensor diaphragm unit is paired with a Sensor Control regulator to provide the continuous 1 CFH (cubic foot per hour) air flow to the underside of the diaphragm to attain pneumatic balance pressure. Constant back pressure regulation maintains linear 1:1 response throughout the entire operating range to ensure pneumatic pressure is directly equivalent to the hydrostatic head of liquid in the tank. Application Notes Mounting flange and diaphragm are wetted surfaces requiring compatibility with process media. Location of the Sensor Control regulator should generally be no greater than 50 feet (15 m) from the TeleSensor unit. The sensor includes 15 feet (4.5 m) of bundled 3-tube cable for the pneumatic interconnections with the Sensor Control. Distances greater than 50 feet may increase response time of sensor to changes in liquid level in the tank. Explosion Hazard Use (Zone One or Division One) The TeleSensor requires no electrical energy for operation when using the 860 Sensor Control. It is possible to configure the tank level system without zener barriers or intrinsic safety provisions. The pneumatic signal may be routed to beyond the hazard zone (1000 feet or more) to an indicator or transmitter. Explosion Hazard Area 860 Sensor Control Pneumatic Signal D/P Transmitter 4-20 mA Signal KING-GAGE LP2 Indicator TeleSensor ® ® KIN G-G AG E KING ENGINEE RING CORPOR ATION 7 8 9 4 5 6 1 2 3 0 . Menu Selec t Edit Enter Reset 9982TANK1 GAL1.019 G V P ® ® KIN G-G AG E KING ENGINEE RING CORPOR ATION 7 8 9 4 5 6 1 2 3 0 . Menu Selec t Edit Enter Reset 9982TANK1 GAL1.019 LevelB A R ® ® K IN G -G A G E Liqu id Lev el Gau ging Syst em KING ENG INEE RING COR P., ANN ARBO R, MICH IGAN U.S.A . ™ 2 10 20 30 40 50 60 70 80 90 100 200 200 0 100 0 200 0 300 0 400 0 500 0 600 0 700 0 800 0 900 0 100 00 EACHMARK=100GALS.1.00SP.GR. EACHMARK=1PERCENTFULL1.00SP.GR. TAN K 1 Pow er LVB -3 860 Sensor Control Compressed Air Supply Pneumatic Signal via 1/4" tubing D/P Module KING-GAGE LP2 Indicator KING-GAGE LevelBAR Indicator 4-20 mA Signal TeleSensor ■ Pneumatic Output Version TeleSensor 860 Sensor Control TeleSensor + 860 Sensor Control = Pneumatic Output This package comprises a complete level sensing system with specialized regulator assembly and force balance diaphragm unit. Pneumatic package has no electrical components and simply requires compressed air supply for operation. 3-Tube Cable TeleSensor System Package with 860 Sensor Control (Pneumatic Output) Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com
  • 4. KING-GAGE® TeleSensor Liquid Level Transmitter Specifications Sensitivity Better than .001 psi (± .02" water /.508 mm water) Repeatability Better than ± .002 psi (± .05" water / 1.27 mm water) Primary Accuracy ± .007 psi (± 0.2" water /.508 mm water) Temperature Range 30°F to 300°F (0°C to 149°C) Pressure Range Sensor is a 1:1 pneumatic force balance diaphragm capable of repeating hydrostatic pressure as an equiva- lent pneumatic output. Functional pressure limit is 130 psi (or 3598 inches @ 1.00 specific gravity) determined by supply pressure (35–150 psi) less 20 psi. Maximum Depth Measurement 1937 in. water (49.0 m water) Wetted Materials Viton O-ring, titanium diaphragm, commercially pure. Optional diaphragm materials: silicone rubber Mounting flange options: 316L stainless, PVC, brewery special flange Air Consumption Total air consumption of sensor package (including sensor control) is less than 10 CFH or 0.16 scfm. D/P Sensor Control Combined Accuracy * 0–5 psid transmitter/control ± 0.34% FS 0–10 psid transmitter/control ± 0.27% FS 0–15 psid transmitter/control ± 0.24% FS 0–30 psid transmitter/control ± 0.22% FS 0–50 psid transmitter/control ± 0.21% FS Voltage Supply Requirements 14–40 Vdc (unregulated) to power signal loop using 868 D/P Sensor Control. Compressed Air Supply Requirements 35–150 psig (2.4–10.3 bar); clean, dry air (or inert gas) *Combined accuracy refers to the primary accuracy of the sensor in combination with the secondary accuracy of the D/P transmitter. ® KING-GAGE and the KE emblem are registered trademarks and TeleSensor is a trademark of King Engineering Corp. © 2010 King Engineering Corporation. All rights reserved. KING-GAGE 2,3 or 4 in. 150-lb ANSI Flange * * 4 in. Flange has 8 bolt circle, 2 and 3 in. Flange have 4 bolt circle. KING-GAGE 4-in. 102 mm bolt circle 3-5/8 in. 92 mm TeleSensor w/ Special 3-in. Brewery Flange (304 SS) Compressed Air Supply Operation of the TeleSensor requires a compressed air/gas source providing supply pressure of 35–150 psig (2.4–10.3 bar). Pneumatic components require instrumentation-grade compressed air that is clean, dry, and oil-free to ensure trouble free performance. 8019 Ohio River Blvd. Newell, WV 26050 U.S.A. Phone: 304-387-1200 • 800-242-8871 Fax: 304-387-4417 marshbellofram.com • king-gage.com Marsh Bellofram Group of Companies Span Adjustment Range Transmitter turndown ratio is 3:1 for the 0–15, 0–30, 0–50 psid nominal ranges. Nominal Minimum Range of Adjustment 0–5 psid 0–3 psid 0–83 in. thru 0–138 in. water /  0–2.1 m thru 0–3.5 m water 0–10 psid 0–3 psid 0–83 in. thru 0–277 in. water /  0–2.1 m thru 0–7.0 m water 0–15 psid 0–3 psid 0–83 in. thru 0–415 in. water /  0–2.1 m thru 0–10.5 m water 0–30 psid 0–10 psid 0–277 in. thru 0–830 in. water /  0–7.0 m thru 0–21.0 m water 0–50 psid 0–15 psid 0–415 in. thru 0–1384 in. water /  0–10.5 m thru 0–35.1 m water IMPORTANT! Accuracy, linearity, and non-repeatability values are based on nominal range. Operating Limit (Maximum Pressure) Pressure above 300% nominal range (overrange) will result in damage to the transmitter (200% may cause a shift in calibration).Burstpressureis200psiandwillcausecatastrophic and physical failure of the pressure element. LtKe1100-20__3-13-2012 cw Mountain States Engineering and Controls | Lakewood, CO USA | 303.232.4100 | www.mnteng.com