2.2. Basic Equations for Heat Exchanger Design
2.2.1. The Basic Design Equation and Overall Heat Transfer Coefficient
The basic heat exchanger equations applicable to shell and tube exchangers were developed in Chapter
1. Here, we will cite only those that are immediately useful for design in shell and tube heat exchangers
with sensible heat transfer on the shell-side. Specifically, in this case, we will limit ourselves to the case
when the overall heat transfer coefficient is constant and the other assumptions of the mean temperature
difference concept apply. Then the basic design equation becomes:
QT  U *
A*
F (LMTD) (2.1)
*
where QT is the total heat load to be transferred, U is the overall heat transfer coefficient referred to the
area A*, A* is any convenient heat transfer area, LMTD is the logarithmic mean temperature difference for
the purely countercurrent flow configuration, and F is the configuration correction factor for multiple tube -
side and/or shell-side passes. Charts of F for the common shell and tube exchanger configuration are
discussed later.
U* is most commonly referred to Ao the total outside tube heat transfer area, including fins, in which case
it is written as Uo and is related to the individual film coefficients, wall resistance, etc. by
Uo 
1
1
x A A 1 A (2.2)
 Rfo  Rfin w o
 Rfi
o
o
ho kw Am Ai hi Ai
where ho and hi are the outside and inside film heat transfer coefficients, respectively, Rfo and Rfi are
the outside and inside fouling resistances, xw , and kw are the wall thickness (in the finned section) and
wall thermal conductivity, and R fin is the resistance to heat transfer due to the presence of the fin. Since
all of the low-and medium-finned tubes manufactured by Wolverine are integral (i.e., tube and fins are all
one piece of metal), there is no need to include a contact resistance term.
Suitable correlations for ho and hi will be developed later in this section. The fouling resistances are
ordinarily specified by the customer based upon experience with the streams in question, but typical
values may be found in Chapter 1, Table 1.2.
The mean wall heat transfer area Am is given with sufficient precision as
A 
L
d
m
2
i  dr 

(2.3)
61
m2
3
f
If it is preferred to use an overall heat transfer coefficient based upon the inside heat transfer area
following relationship holds:
Uo Ao  Ui Ai
Ai the
(2.4)
It is of the greatest importance to always identify the reference area when quoting the value of a film or
overall heat transfer coefficient.
2.2.2. Fin Efficiency and Fin Resistance
The general concept of fin efficiency and fin resistance was developed in Chapter 1. Accordingly, we will
only reiterate the major equations and concepts here.
The value of R fin for use in Eq (2.2) is given by
 1  
 1 
Rfin 
A
h
Rfo  (2.5)
 root
  o 

Afin


where  is the fin efficiency and is given by:
1
 
1 do /dr
(2.6)
where
m  H (2.7)
Also,
A d L


s 
d
L N s
(2.8)
root  s  Y 
and
A  2

d 2  d 2 LN (2.9)
fin
4 o r f
Typical fin efficiencies for S/T Trufin are above 0.90 for virtually all applications, often approaching 1.00
for those applications in which low-finned Trufin is most valuable.
2
 1
  R k Y

ho
fo w

r r
62
These are shown in Chapter I as a function of
1
fo for the various metals out of which S/T Trufin is
o
manufactured. Use of these figures (1.51 and 1.52) shortcuts the need to carry out the calculation of
Eqns. (2.5 to 2.9) for most design cases.
2.2.3. Mean Temperature Difference, F Factors
We will use the Mean Temperature Difference (MTD) formulation for design of heat exchangers in this
Manual. The MTD is related to the Logarithmic Mean Temperature Difference (LMTD) by the equation
MTD=F(LMTD) (2.10)
where the LMTD is always defined as for the countercurrent flow arrangement shown in Fig. 2.4:
LMTD
T1 t2  T2 t1 
 T1  t2 



(2.11)
ln
T  t

 2 1 

In the rare occasion that the heat exchanger is a purely
cocurrent (parallel) flow arrangement, F = I and the
LMTD is given by
LMTD 
T1 t1  T2 t2 
 T  t 

(2.12)
ln 1 1 
 T2  t2 
where T1and t1 are the shellside and tubeside inlet temperatures, respectively, and T2
corresponding outlet temperatures.
and t2 are the
The value of F depends upon the exact arrangement of the streams within the exchangers, the number of
ex changers in series, and two parameters defined in terms of the terminal temperatures of the two
streams:
R 
T1  T2

Range of shell fluid (2.13)
t 2 t1 Range of tube fluid
P 
t2  t1 
 Range of tube fluid (2.14)
T1  t1 Maximum temperature difference
The mathematical relationships between F, R, and P have been reported in a number of places, e.g.,
Refs. (1, 2), but the graphical representations are of the greatest interest to us in this Manual. These are
shown for the most important cases in Figs. 2.5 to 2.12, inclusive.
h
 R
63
Once the terminal temperatures of both streams of a heat exchanger are specified or otherwise
determined, R, P, and LMTD can be calculated, F found for the heat exchanger configuration, and finally
the MTD can be calculated. Values of F below 0.8 or 0.75 at the lowest should not be used for three
reasons:
1. The charts cannot be read accurately.
2. The low value of F means that substantial additional area must be supplied in the heat exchanger
to overcome the inefficient thermal profile.
3. Design in or near the steep portion of the curves indicates that the thermodynamically limiting
configuration is being approached, even if all the assumptions are perfectly satisfied. Violation of
even one of the assumptions (e.g., excessive bypassing) by even a little bit may result in an ex-
changer that is in fact thermodynamically incapable of meeting the specified temperatures.
If the value of F determined for the proposed configuration is too low, the use of additional shells in series
will result in an improvement, as shown by the successive F charts for given values of R and P.
Alternatively, it may be possible to redesign the exchangers to permit the use of fixed tube sheet units
and purely countercurrent flow (for which F is unity.)
64
65
66
67
68
69
70
71

More Related Content

Similar to 22 basic-equations-for-heat-exchanger-design (2)

JIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperJIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference Paper
Ahmed Sohail Izhar
 
Heatexchangers 120419133732-phpapp02 (1)
Heatexchangers 120419133732-phpapp02 (1)Heatexchangers 120419133732-phpapp02 (1)
Heatexchangers 120419133732-phpapp02 (1)
asim ahsan
 
Planar pcb design guide(ferroxcube) no pw
Planar pcb design guide(ferroxcube) no pwPlanar pcb design guide(ferroxcube) no pw
Planar pcb design guide(ferroxcube) no pw
Jaeseong Cho
 

Similar to 22 basic-equations-for-heat-exchanger-design (2) (20)

JIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference PaperJIMEC Thermal modeling and Simulation of HX Conference Paper
JIMEC Thermal modeling and Simulation of HX Conference Paper
 
Estimation of hottest spot temperature
Estimation of hottest spot temperatureEstimation of hottest spot temperature
Estimation of hottest spot temperature
 
Module 2.pptx
Module 2.pptxModule 2.pptx
Module 2.pptx
 
IRJET- Multi-Objective Optimization of Shell and Tube Heat Exchanger – A Case...
IRJET- Multi-Objective Optimization of Shell and Tube Heat Exchanger – A Case...IRJET- Multi-Objective Optimization of Shell and Tube Heat Exchanger – A Case...
IRJET- Multi-Objective Optimization of Shell and Tube Heat Exchanger – A Case...
 
Layer-Type Power Transformer Thermal Analysis Considering Effective Parameter...
Layer-Type Power Transformer Thermal Analysis Considering Effective Parameter...Layer-Type Power Transformer Thermal Analysis Considering Effective Parameter...
Layer-Type Power Transformer Thermal Analysis Considering Effective Parameter...
 
Heatexchangers 120419133732-phpapp02 (1)
Heatexchangers 120419133732-phpapp02 (1)Heatexchangers 120419133732-phpapp02 (1)
Heatexchangers 120419133732-phpapp02 (1)
 
Lect 9 Forced convection.pdf
Lect 9 Forced convection.pdfLect 9 Forced convection.pdf
Lect 9 Forced convection.pdf
 
Shell
ShellShell
Shell
 
Shelltube
ShelltubeShelltube
Shelltube
 
Ch 2 - Steady state 1-D, Heat conduction.pdf
Ch 2 - Steady state 1-D, Heat conduction.pdfCh 2 - Steady state 1-D, Heat conduction.pdf
Ch 2 - Steady state 1-D, Heat conduction.pdf
 
Heat exchanger 3-STHE manual calculation
Heat exchanger 3-STHE manual calculationHeat exchanger 3-STHE manual calculation
Heat exchanger 3-STHE manual calculation
 
Plate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger SizingPlate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger Sizing
 
Cep plate and_frame_hx
Cep plate and_frame_hxCep plate and_frame_hx
Cep plate and_frame_hx
 
Design plate heat exchangers
Design plate heat exchangersDesign plate heat exchangers
Design plate heat exchangers
 
Heat exchanger
Heat exchangerHeat exchanger
Heat exchanger
 
Applying The Wheatstone Bridge Circuit
Applying The Wheatstone Bridge CircuitApplying The Wheatstone Bridge Circuit
Applying The Wheatstone Bridge Circuit
 
COMSOL Paper
COMSOL PaperCOMSOL Paper
COMSOL Paper
 
Planar pcb design guide(ferroxcube) no pw
Planar pcb design guide(ferroxcube) no pwPlanar pcb design guide(ferroxcube) no pw
Planar pcb design guide(ferroxcube) no pw
 
Thermal conductivity
Thermal conductivityThermal conductivity
Thermal conductivity
 
MERKELS METHOD FOR DESIGNING INDUCED DRAFT COOLING TOWER
MERKELS METHOD FOR DESIGNING INDUCED DRAFT COOLING TOWERMERKELS METHOD FOR DESIGNING INDUCED DRAFT COOLING TOWER
MERKELS METHOD FOR DESIGNING INDUCED DRAFT COOLING TOWER
 

More from Maria Isabel

Food industry technical_professional epa
Food industry technical_professional epaFood industry technical_professional epa
Food industry technical_professional epa
Maria Isabel
 
Advances in-preservation-of-dairy-and-food-products-2001
Advances in-preservation-of-dairy-and-food-products-2001Advances in-preservation-of-dairy-and-food-products-2001
Advances in-preservation-of-dairy-and-food-products-2001
Maria Isabel
 

More from Maria Isabel (17)

evalves.pdf
evalves.pdfevalves.pdf
evalves.pdf
 
Fluid Mechanics.pdf
Fluid Mechanics.pdfFluid Mechanics.pdf
Fluid Mechanics.pdf
 
Food industry technical_professional epa
Food industry technical_professional epaFood industry technical_professional epa
Food industry technical_professional epa
 
Thermodynamic and food
Thermodynamic and foodThermodynamic and food
Thermodynamic and food
 
Exercise
ExerciseExercise
Exercise
 
Boiling curve
Boiling curveBoiling curve
Boiling curve
 
The pizza game
The pizza gameThe pizza game
The pizza game
 
Xie et al 2016 risk analysis
Xie et al 2016 risk analysisXie et al 2016 risk analysis
Xie et al 2016 risk analysis
 
Introduction to iso22000 101106 !!!!
Introduction to iso22000 101106 !!!!Introduction to iso22000 101106 !!!!
Introduction to iso22000 101106 !!!!
 
Brc unannounced audits bb
Brc unannounced audits bbBrc unannounced audits bb
Brc unannounced audits bb
 
Haccp based system dutch standard bb
Haccp based system dutch standard bbHaccp based system dutch standard bb
Haccp based system dutch standard bb
 
Introduction to qmp iso
Introduction to qmp isoIntroduction to qmp iso
Introduction to qmp iso
 
Haccp based system dutch standard
Haccp based system dutch standard Haccp based system dutch standard
Haccp based system dutch standard
 
Comparison between codex haccp and iso22000
Comparison between codex haccp and iso22000Comparison between codex haccp and iso22000
Comparison between codex haccp and iso22000
 
Advances in-preservation-of-dairy-and-food-products-2001
Advances in-preservation-of-dairy-and-food-products-2001Advances in-preservation-of-dairy-and-food-products-2001
Advances in-preservation-of-dairy-and-food-products-2001
 
Siemens room stat instructions
Siemens room stat instructionsSiemens room stat instructions
Siemens room stat instructions
 
Siemens room stat instructions
Siemens room stat instructionsSiemens room stat instructions
Siemens room stat instructions
 

Recently uploaded

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 

Recently uploaded (20)

University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 

22 basic-equations-for-heat-exchanger-design (2)

  • 1. 60 2.2. Basic Equations for Heat Exchanger Design 2.2.1. The Basic Design Equation and Overall Heat Transfer Coefficient The basic heat exchanger equations applicable to shell and tube exchangers were developed in Chapter 1. Here, we will cite only those that are immediately useful for design in shell and tube heat exchangers with sensible heat transfer on the shell-side. Specifically, in this case, we will limit ourselves to the case when the overall heat transfer coefficient is constant and the other assumptions of the mean temperature difference concept apply. Then the basic design equation becomes: QT  U * A* F (LMTD) (2.1) * where QT is the total heat load to be transferred, U is the overall heat transfer coefficient referred to the area A*, A* is any convenient heat transfer area, LMTD is the logarithmic mean temperature difference for the purely countercurrent flow configuration, and F is the configuration correction factor for multiple tube - side and/or shell-side passes. Charts of F for the common shell and tube exchanger configuration are discussed later. U* is most commonly referred to Ao the total outside tube heat transfer area, including fins, in which case it is written as Uo and is related to the individual film coefficients, wall resistance, etc. by Uo  1 1 x A A 1 A (2.2)  Rfo  Rfin w o  Rfi o o ho kw Am Ai hi Ai where ho and hi are the outside and inside film heat transfer coefficients, respectively, Rfo and Rfi are the outside and inside fouling resistances, xw , and kw are the wall thickness (in the finned section) and wall thermal conductivity, and R fin is the resistance to heat transfer due to the presence of the fin. Since all of the low-and medium-finned tubes manufactured by Wolverine are integral (i.e., tube and fins are all one piece of metal), there is no need to include a contact resistance term. Suitable correlations for ho and hi will be developed later in this section. The fouling resistances are ordinarily specified by the customer based upon experience with the streams in question, but typical values may be found in Chapter 1, Table 1.2. The mean wall heat transfer area Am is given with sufficient precision as A  L d m 2 i  dr   (2.3)
  • 2. 61 m2 3 f If it is preferred to use an overall heat transfer coefficient based upon the inside heat transfer area following relationship holds: Uo Ao  Ui Ai Ai the (2.4) It is of the greatest importance to always identify the reference area when quoting the value of a film or overall heat transfer coefficient. 2.2.2. Fin Efficiency and Fin Resistance The general concept of fin efficiency and fin resistance was developed in Chapter 1. Accordingly, we will only reiterate the major equations and concepts here. The value of R fin for use in Eq (2.2) is given by  1    1  Rfin  A h Rfo  (2.5)  root   o   Afin   where  is the fin efficiency and is given by: 1   1 do /dr (2.6) where m  H (2.7) Also, A d L   s  d L N s (2.8) root  s  Y  and A  2  d 2  d 2 LN (2.9) fin 4 o r f Typical fin efficiencies for S/T Trufin are above 0.90 for virtually all applications, often approaching 1.00 for those applications in which low-finned Trufin is most valuable. 2  1   R k Y  ho fo w  r r
  • 3. 62 These are shown in Chapter I as a function of 1 fo for the various metals out of which S/T Trufin is o manufactured. Use of these figures (1.51 and 1.52) shortcuts the need to carry out the calculation of Eqns. (2.5 to 2.9) for most design cases. 2.2.3. Mean Temperature Difference, F Factors We will use the Mean Temperature Difference (MTD) formulation for design of heat exchangers in this Manual. The MTD is related to the Logarithmic Mean Temperature Difference (LMTD) by the equation MTD=F(LMTD) (2.10) where the LMTD is always defined as for the countercurrent flow arrangement shown in Fig. 2.4: LMTD T1 t2  T2 t1   T1  t2     (2.11) ln T  t   2 1   In the rare occasion that the heat exchanger is a purely cocurrent (parallel) flow arrangement, F = I and the LMTD is given by LMTD  T1 t1  T2 t2   T  t   (2.12) ln 1 1   T2  t2  where T1and t1 are the shellside and tubeside inlet temperatures, respectively, and T2 corresponding outlet temperatures. and t2 are the The value of F depends upon the exact arrangement of the streams within the exchangers, the number of ex changers in series, and two parameters defined in terms of the terminal temperatures of the two streams: R  T1  T2  Range of shell fluid (2.13) t 2 t1 Range of tube fluid P  t2  t1   Range of tube fluid (2.14) T1  t1 Maximum temperature difference The mathematical relationships between F, R, and P have been reported in a number of places, e.g., Refs. (1, 2), but the graphical representations are of the greatest interest to us in this Manual. These are shown for the most important cases in Figs. 2.5 to 2.12, inclusive. h  R
  • 4. 63 Once the terminal temperatures of both streams of a heat exchanger are specified or otherwise determined, R, P, and LMTD can be calculated, F found for the heat exchanger configuration, and finally the MTD can be calculated. Values of F below 0.8 or 0.75 at the lowest should not be used for three reasons: 1. The charts cannot be read accurately. 2. The low value of F means that substantial additional area must be supplied in the heat exchanger to overcome the inefficient thermal profile. 3. Design in or near the steep portion of the curves indicates that the thermodynamically limiting configuration is being approached, even if all the assumptions are perfectly satisfied. Violation of even one of the assumptions (e.g., excessive bypassing) by even a little bit may result in an ex- changer that is in fact thermodynamically incapable of meeting the specified temperatures. If the value of F determined for the proposed configuration is too low, the use of additional shells in series will result in an improvement, as shown by the successive F charts for given values of R and P. Alternatively, it may be possible to redesign the exchangers to permit the use of fixed tube sheet units and purely countercurrent flow (for which F is unity.)
  • 5. 64
  • 6. 65
  • 7. 66
  • 8. 67
  • 9. 68
  • 10. 69
  • 11. 70
  • 12. 71