Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 1
RCC Column
What is Column?
Column may be defined as a vertical structural member that carry loads chiefly in compression. It can carry moment
as well, about one or both axes of the cross section. Bending action may produce tensile forces over a part of the
cross-section. Even in such case columns are referred as compression members because compression force
dominates its behavior. Its ratio of height to least lateral dimension is 
t
L
3.
Types of Column:
A) Based on reinforcement column can be divided into the following was:
1) Column reinforced with longitudinal bar and lateral ties.
2) Column reinforced with longitudinal bar and continuous spirals.
3) Composite compression members reinforced longitudinal with structural steel shapes,pipe or tubing.
B) Based on length:
1. Short column: Short columns those whose ratio of effective length to the minimum thickness is less then 12
(i.e. 12 ). Material strength is the main factor for its failure.
2. Long Column: Short columns those whose ratio of effective length to the minimum thickness is greater
then 12 ( 12). Material strength and buckling are the main factors for its failure.
C) Depending on position at a building or loading pattern:
1) Axially loaded column
2) Uni-axial column
3) Bi-axial column.
Preliminary size of column:
The initial stage in column design involves estimating the required of the column. There is no simple rule to do this
as the axial load capacity of a given cross-section varies depending on the moment acting on the section.The
approximate relation between axial load and gross area for tied column is,
)(45.0 ',
gyc
U
trialg
ff
P
A


The approximate relation between axial load and gross area for tied column is,
)(55.0 ',
gyc
U
trialg
ff
P
A


Depending on span length an initial approximation for gross area of column can also be made. For columns
supporting heavily loaded floors minimum overall dimensions of one-fifteenth the average span of the panel is
considered satisfactory.Roof columns may be somewhat lighter; one-eighteenth the average span is specified by
some codes as a minimum diameter.
Function of Tie/ spiral/ Transverse reinforcement:
1. To hold longitudinal bars in position in forms while the concrete is being placed. For this purpose both of
them are wired togetherto form a cage of reinforcement.
2. To prevent the highly stressed slenderlongitudinal bars from buckling outward bursting the thin concrete
cover.
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 2
Fig: Tied column Fig: Spiral column
Serial No. Contents Tied Spiral
a) Least Dimension Minm 10 in, in EQ regions 12 in. Minm 12 in
b) Least area -- ---------
c) Steel ratio, min,g 1% 1%
d) Steel ratio, max,g 8% 8%
e) Minm No. of longitudinal bar 4 6
f) Minm longitudinal bar size #5 bar #5 bar
g) Minm No. of tie bar #3 (for bundle bars or longitudinal
bar size>#10 use #4 bar as tie)
#3
h) Minm Clear cover 1.5 in 1.5 in
Note: Generally max,g is preferable between 1%- 4% to avoid steel congestion.
Guideline for Tie/ spiral reinforcement:
1) All bars of tied columns shall be enclosed by lateral ties, at least No. 3 in size for longitudinal bars up to No. 10,
and at least No. 4 in size for Nos. 11, 14, and 18 and bundled longitudinal bars.
2) The spacing of the ties shall not exceed 16 diameters of longitudinal bars (16D), 48 diameters of tie bars
(48d), nor the least dimension (tmin) of the column.
3) No bar shall be farther than 6 in. clear on either side from such a laterally supported bar.
4) The ties shall be so arranged that every corner and alternate longitudinal bar shall have lateral support pro -
vided by the corner of a tie having an included angle of not more than 135°.
5) Spirals shall be continuous bar of not less than #3. The c lear spacing between turns of the spiral must not
exceed 3 inch (but not less than 1 inch).
Design of axially loaded column:
WSD:
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 3
For concentrically loaded spirally reinforced column Code provides the following formula for maximum allowable
load:
)25.0( '
gscg ffAP 
For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable load:
)25.0(85.0 '
gscg ffAP 
Ag = Gross concrete area,
g
s
g
A
A
 .
USD:
Let us consider an axially loaded column where the load is taken by both concrete and steel. Therefore,
sycc AfAfP  '
. But full strength of
'
cf is not used rather 0.85
'
cf . So we can say:
sycc AfAfP  '
85.0 . Rearranging the equation we get,
g
g
s
ysgc A
A
A
fAAfP  )(85.0 '
})1(85.0{ '
gygcg ffAP  
For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable
load:
})1(85.0{ '
gygcg ffAP  
85.0 and 75.0 for spiral column
80.0 and 70.0 for tied column
Recommendation for tie:
Fig: Minimum details for frames in regions of moderate risk
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 4
Problem 1:
Design a tied column for load 500 kip both in WSD and USD.
Suggestedsolution:
WSD
Considering, 02.0g
)25.0(85.0 '
gscg ffAP 
)02.0604.0325.0(85.0500  gA
2
24.478 inAg  [ "87.2124.4782
 hh ]
Therefore select a square section 22''22''.
As = gg A = 0.022222 = 9.68 in2. So provide 10 No. # 9 bar as main bar.
Tie reinforcement:
1) 16D= 16 18
8
9
 '' 2) 48d= 18
8
3
48  '' 3) tmin= 22'', So provide #3 @18''c/c as tie reinforcement.
USD
})1(85.0{ '
gygcg ffAP  
As 80.0 and 70.0 for tied column. Considering, 01.0g
)01.060)01.01(385.0(70.08.0500  gA
2
76.285 inAg  [ "7.1676.2852
 hh ]
Select a square section 18''18''.
As = gg A = 0.011818 = 3.2420.28 in2
So provide 6 No. # 6 bar as main bar.
Tie reinforcement:
1) 16D= 16 12
8
6
 '' 2) 48d= 18
8
3
48  '' 3) tmin= 18'', So provide #3 @12''c/c as tie reinforcement.
Note: This problem is done assuming an arbitrary g value. If anyone does this problem assuming an arbitrary gA
then this way is also ok but remember that the g value must have to be greater than 0.01.
Problem 2:
A plan showing the beams and columns of a 10 storied market building is shown in Fig: 1(a). Here brick walls are
used only for partition. Design the Column A for Ground floor and 4th floor in both WSD and USD having the
following information:
a) Slab thickness = 6.5'',
b) Beam cross-section = 18''12''
c) Live load on the floor = 100 psf
d) Live load in the roof = 60 psf.
e) Brick wall thickness = 5''.
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 5
f) Story clear height = 10'
g)
'
cf =3 ksi, and yf = 60 ksi
SuggestedSolution:
WSD
Item No Item Calculation Load
1. Slab self load calculation =




 10)
12
5.6
2
1720
2
2225
(15.0
353.3 kip
2. Beam weight =





 10)
1212
2218
2
17202225
(15.0
173.25
3. Wall weight =


 10)10
12
5
2
17202225
(12.0
210 kip
4. Floor Live load =
0.1 



9)
2
1720
2
2225
(
391.3 kip
5. Roof Live load =
0.06 



1)
2
1720
2
2225
(
26.1 kip
1153.95 kip
Trial gross area of column,
)(45.0 ',
gyc
trialg
ff
P
A

 , considering, 03.0g
2
, 24.534
)03.0603(45.0
95.1153
inA trialg 

 [ "11.2324.5342
 hh ]
Select a square section = 24''24''.
Self load of column = 0.15' 60100
12
24
12
24
 kip
Total load = 1153.95 + 60 = 1214 kip
For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable load:
)25.0(85.0 '
gscg ffAP 
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 6
)03.0604.0325.0(85.012.1032  gA
2
03.826 inAg  [ "74.2803.8262
 hh ]
Select a square section = 30''30''.
Self load of column = 0.15'  100
12
30
12
30
93.8 kip
Total load = 981.7+93.8=1075.45 kip
)25.0(85.0 '
gscg ffAP 
)03.0604.0325.0(85.045.1075  gA
2
7.860 inAg  [ "34.297.8602
 hh ]
Therefore the selected square section 30''30'' is ok!!!!
As = gg A = 0.033030 = 27 in2, So provide 28 No. # 9 bar as main bar.
Note: Sometimes extra bar has to be used to make the section symmetric.
Tie reinforcement:
1) 16D= 16 18
8
9
 '' 2) 48d= 18
8
3
48  '' 3) tmin= 30'', So provide #3 @18''c/c as tie reinforcement.
USD
Item No Item Calculation Load
6. Slab self load calculation =




 4.110)
12
5.6
2
1720
2
2225
(15.0
494.62 kip
7. Beam weight =


 4.110)10
12
5
2
17202225
(12.0
294 kip
8. Floor Live load =
0.1 



7.19)
2
1720
2
2225
(
665.21
9. Roof Live load =
0.06 



7.11)
2
1720
2
2225
(
44.37 kip
1498.2 kip
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 7
Trial gross area of column,
)(45.0 ',
gyc
trialg
ff
P
A

 , considering, 03.0g
2
, 96.1046
)03.0603(45.0
2.1498
inA trialg 

 [ "36.3296.10462
 hh ]
Select a square section = 33''33''.
Self load of column = 0.15'  4.1100
12
33
12
33
158.82 kip
Total load = 1498.2+158.82=1657.1 kip
For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable load:
})1(85.0{ '
gygcg ffAP  
80.0 and 70.0 for tied column
)03.060)03.01(385.0(70.08.01.1657  gA
2
43.692 inAg  [ "31.2643.6932
 hh ]
Select a square section = 27''27''.
Self load of column = 0.15'  4.1100
12
27
12
27
106.31 kip
Total load = 1498.2+106.31=1604.6 kip
})1(85.0{ '
gygcg ffAP  
as 80.0 and 70.0 for tied column
)03.060)03.01(385.0(70.08.06.1604  gA
2
5.670 inAg  [ "89.255.6702
 hh ]
Select a square section 26''26''.
As = gg A = 0.032626 = 20.28 in2. So provide 26 No. # 8 bar as main bar.
Note: Sometimes extra bar has to be used to make the section symmetric.
Tie reinforcement:
1) 16D= 16 16
8
8
 '' 2) 48d= "18
8
3
48  3) tmin= 26'', So provide #3 @16''c/c as tie reinforcement.
Short column: Its strength is governed by strength of materials (i.e. concrete and steel) nd geometry of
cross-section.
𝜌𝑠 can be selected by the equation, 𝜌𝑠 = 0.45(
𝐴 𝑔
𝐴 𝑐
− 1)
𝑓𝑐
′
𝑓𝑦
Problem :3 Design a column for 474 kip load.
Answer:
Assume the missing data, 𝒇 𝒄
′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 15x15 in2
.
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 8
})1(85.0{ '
gygcgn ffAPP  
80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column,
})1(85.0{ '
gygcg ffAP  
)60)1(485.0(151570.08.0474 gg  
01.00064.0  g , use 01.0min 
2
25.2151501.0 inbhA gs  
Problem :4 Design a column for 700 kip load.
Answer:
Assume the missing data, 𝒇 𝒄
′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 15x15 in2
.
})1(85.0{ '
gygcgn ffAPP  
80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column,
})1(85.0{ '
gygcg ffAP  
)60)1(485.0(151570.08.0700 gg  
00381.0 g
2
57.815150381.0 inbhA gs  
Problem :5 Design a column for 1200 kip load.
Answer:
Assume the missing data, 𝒇 𝒄
′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 15x15 in2
.
})1(85.0{ '
gygcgn ffAPP  
80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column,
})1(85.0{ '
gygcg ffAP  
)60)1(485.0(151570.08.01200 gg  
08.011.0  g
Change the material property/ section/ both and redesign
Assume the missing data, 𝒇 𝒄
′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 24x18 in2
.
})1(85.0{ '
gygcgn ffAPP  
80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column,
})1(85.0{ '
gygcg ffAP  
)60)1(485.0(182470.08.01200 gg  
01.00276.0  g
2
91.1118240276.0 inbhA gs  
Spacing of transverse reinforcement should be not less
then (NON-EQ zone)
𝑠 = (
16 diameter of Longitudinal steel (16D)
48 diameter of transverse steel (48d)
Least dimension of column (tmin)
)
Spacing of transverse reinforcement should be not less
then (EQ zone)
𝑠 = (
8 diameter of Longitudinal steel (8D)
24 diameter of transverse steel (24d)
1
2
of least dimension of column
)
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 9
and 2s
Problem :6 Design a square column at middle for a DL=1 kip/ft and LL= 0.7 kip/ft. Consider that the
building 10 storied. Also Consider, 𝒇 𝒄
′ = 3 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖,
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 10
Load at each over the column=(1 × 1.4 + 0.7 × 1.7) × (
25
2
+
25
2
+
18
2
+
18
2
) = 2.59 × 43 = 111.37 kip
So, 𝑃10 = 111.37 × 10 = 1113.7 kip
Considering, 𝜌𝑔 = 0.03,
𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐
′(1 − 𝜌𝑔) + 𝑓𝑦 𝜌𝑔)
=> 1113.7 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.03) + 60 × 0.03)
=> 𝐴 𝑔 = 465.4 𝑖𝑛2 = 21.57 × 21.57,take − 24" × 24"
𝐴 𝑠 = 0.03 × 24" × 24" = 17.28 𝑖𝑛2 = 30 #7
Provide this column at 1st
, 2nd, 3rd
and 4th
story.
So, 𝑃6 = 111.37 × 6 = 668.2 kip
Considering, 𝜌𝑔 = 0.02,
𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐
′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔)
=> 668.2 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.02) + 60 × 0.02)
=> 𝐴 𝑔 = 322.6 𝑖𝑛2 = 17.96 × 17.96, take − 20" × 20"
𝐴 𝑠 = 0.02 × 20" × 20" = 8 𝑖𝑛2 = 20 #6
Provide this column at 5th
, 6th
and 7th
story.
So, 𝑃3 = 111.37 × 3 = 334.11 kip
Considering, 𝜌𝑔 = 0.01,
𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐
′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔)
=> 334.11 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.01) + 60 × 0.01)
=> 𝐴 𝑔 = 190.95 𝑖𝑛2 = 13.82 × 13.82, take − 15" × 15"
𝐴 𝑠 = 0.01 × 15" × 15" = 2.25 𝑖𝑛2 = 8 #5
Provide this column at 8th
, 9th
and 10th
story.
Check the column considering column self weight.
So, 𝑃10 = 111.37 × 10 + 1.4 × {(0.15 ×
22
12
×
22
12
× 10) × 4 + (0.15 ×
18
12
×
18
12
× 10) × 3
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 11
+(0.15 ×
15
12
×
15
12
× 10) × 3} = 111.37 + 52.25 = 1166 kip
Considering, 𝜌𝑔 = 0.03,
𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐
′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔)
=> 1166 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.03) + 60 × 0.03)
=> 𝐴 𝑔 = 487.2 𝑖𝑛2 = 22.07 × 22.07 < 24×24(ok)
So, 𝑃6 = 111.37 × 6 = 668.2 kip
Considering, 𝜌𝑔 = 0.02,
𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐
′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔)
=> 668.2 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.02) + 60 × 0.02)
=> 𝐴 𝑔 = 322.6 𝑖𝑛2 = 17.96 × 17.96, take − 18" × 18"
𝐴 𝑠 = 0.02 × 18" × 18" = 6.48 𝑖𝑛2 = 16 #6
Provide this column at 5th
, 6th
and 7th
story.
So, 𝑃3 = 111.37 × 3 = 334.11 kip
Considering, 𝜌𝑔 = 0.01,
𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐
′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔)
=> 334.11 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.01) + 60 × 0.01)
=> 𝐴 𝑔 = 190.95 𝑖𝑛2 = 13.82 × 13.82, take − 15" × 15"
𝐴 𝑠 = 0.01 × 15" × 15" = 2.25 𝑖𝑛2 = 8 #5
Provide this column at 8th
, 9th
and 10th
story.
Interaction Diagram (ID):
For a column subjected to concentrated load or the loading condition where 10.
h
e  the following equations are
the dominating equations for design.
)25.0(85.0 '
gscg ffAP  (WSD) , })1(85.0{ '
gygcg ffAP   (USD)
But if 10.
h
e  then it is an easy practice to take the help of Interaction Diagram.
Interaction diagram is the graphical presentation of the different safe combinations
of load (P) and moment (M). The following equations are necessary this diagram.
sssscn fAfAabfP  '''
85.0
)
2
()'
2
()
22
(85.0 ''' h
dfAd
h
fA
ah
abfM sssscn 
These equations will be able to give us the Nominal strength curve only. To make
that usable an ACI design strength curve has to be made. Depending on column
geometry, tie/ spiral values of  and  are important for that. The shaded portion
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 12
is the final ID for a typical column. By the help of ID any type of column even shear walls can be designed.
Design of column subjected to Uni-axial moment:
Problem: 7
In a two storied structure an exterior column is to be designed for a service dead load of 142 kips, maximum live
load of 213 kips, dead load moment of 83 kip-ft, live load moment of 124 kip-ft. The minimum live load compatible
with the full the full live load moment is 106 kips, obtained when no live load is placed on the roof but a full live
load is placed on the 2nd floor. Consider column dimension b = 16 in, and h = 20 in.
'
cf =4 ksi, and yf = 60 ksi
(a) Find the column RF for the full live load condition.
(b) Check to ensure that the column is adequate for the condition of no live load on the roof.
Answer:
(a)
kipPu 5612137.11424.1 
ftkipMu  3271247.1834.1
Now, ksi
A
P
g
u
75.1
320
561
 and
ksi
hA
M
g
u
61.0
20320
12327



 . With a cover 2.5 in
75.0
20
520



Having these main information from the graph
039.0g
Therefore,
2
48.122016039.0 inbhA gs  
Select 10 No.10 bars.
(b)
kipPu 3791067.11424.1 
ftkipMu  327 (as before)
Now, ksi
A
P
g
u
18.1
320
379
 and ksi
hA
M
g
u
61.0
20320
12327



 . With a cover 2.5 in 75.0
20
520



Having these main information from the graph 032.0g
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 13
Therefore,
2
24.102016032.0 inbhA gs  
< the result of case (a). So no modification is required.
Problem: 8
A column carries a factored load 518 kip and factored
moment 530 kip-ft. Design the column.
Answer:
As no other information are given so let us assume
03.0g , h = 24 inch and a concrete cover 3 inch
75.0
24
624


 .
Now, eccentricity, inch
P
M
e
u
u
3.12
518
12530


 ,
51.0
24
3.12

h
e
. Using g and e from graph
ksi
A
P
g
u
35.1
2
52.11241603.0 inbhA gs  
Select 8 No.11 bars.
What will happen if interaction diagram is not given?????????
Design of column subjected to Bi-axial moment:
Problem: 9
The column shown below has to carry a factored load 275 kips. The is acting with eccentricities "3ye and
"6xe . The material strength
'
cf = 4 ksi, and yf = 60 ksi. Check the adequacy of the trial section.
Answer:
Let us follow the Reciprocal load method.
Considering bending about the Y-axis Considering bending about the Y-axis
;
75.0
20
520



3.0
20
6

h
e
033.0
2012
8



g
s
A
A
;
58.0
12
512


 (say = 0.6)
25.0
12
6

h
e
033.0
2012
8



g
s
A
A
inchb
P
bhA u
g
1698.15
2435.1
518
35.1




Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 14
From Graph A.7
kipPksi
A
P
yOu
g
yOu
40875.1 ,
,
 

kipPksi
A
P
o
g
o
87665.3  

From Graph A.7
kipPksi
A
P
xOu
g
xOu
43282.1 ,
,
 

kipPksi
A
P
o
g
o
87665.3  

Known,
OyOnxOnn PPPP 
1111
,,

876
1
408
1
432
11

nP
92.275 un PP kip> the design load (275 kip). Therefore the selection of column section is ok!!
Design for long/slender column:
Problem: 10
A 22X14 inch2 (trial section)column carries an axial load Pd = 125 Md = 105 k-ft, Pl=112 kip, and Ml =96 kip-ft
due to live load. The column is part of a frame that is braced against side-sway ant bent in single curvature about its
major axis. The unsupported column length is lu = 19 ft. The moments at both ends of the column are equal. Design
the column. The material strength
'
cf = 4 ksi, and yf = 60 ksi.
Answer:
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 15
kipPu 4.3651127.11254.1 
ftkipMu  2.310967.11054.1
Now, ksi
A
P
g
u
2.1
1422
4.365


 and ksi
hA
M
g
u
55.0
221422
122.310



 . Considering 75.0 from graph
026.0g
Now let us check whether it is slender or not……



 )5.34
223.0
12191
(
r
klu
)2211234(1234
2
1

M
M
Therefore it is a slender column.
478.0
4.365
1254.1
7.14.1
4.1





LD
D
d
2
12119435
478.01
1242236054.0
1
4.0
inkip
IE
EI
d
gc







kip
kl
EI
P
u
c 3313
)( 2
2


)(4.014.06.0
4.0
6.0
2
1
ok
M
M
Cm 
Moment magnifier 17.1
331375.0
4.365
1
1
75.0
1






c
u
m
nx
P
P
C

Design ftkipMM unsc  3632.31017.1
Again,
Now, ksi
A
P
g
u
2.1
1422
4.365


 and ksi
hA
M
g
u
65.0
221422
12363



 .
From the same graph 036.0g
2
1.111422036.0 inbhA gs   Provide 12 No. 9 bars
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 16
Construction of interaction diagram:
Basic equations Manipulation:
s
s
y
E
f

yu
u
b dc




ca 85.0 (At balanced condition bcc  )
ysus f
c
cd
Ef 

 
ysus f
c
dc
Ef 


''

sssscn fAfAabfP  '''
85.0
)
2
()'
2
()
22
(85.0 ''' h
dfAd
h
fA
ah
abfM sssscn 
s
s
u
u
b
E
f
dc




ysus f
c
cd
Ef 

 
ysus f
c
dc
Ef 


''

sssscn fAfAcbf.P  '''2
850
)
2
()'
2
()
2
85.0
(85.0 '''2 h
dfAd
h
fA
ch
bfM sssscn 


Problem: 11
a. Construct an interaction diagram of the column section shown at right.
b. Construct an ACI design strength diagram for the same section.
c. Is the column is good choice for a load 540 kips applied at an eccentricity e = 4.44''?
Answer:
At first let us simplify the process:
ssn
ssn
sssscnn
ffccM
ff
c
cM
h
dfAd
h
fA
ch
cbfePM
5.225.22)425.08(8.57
)
2
16
13(25.22)3
2
16
(25.22)
2
85.016
(16585.0
)
2
()'
2
()
2
85.0
(85.0
'
'2
'''2







ssn
ssn
sssscn
ffcP
ffcP
fAfAcbf.P
5.45.480.57
25.2225.2216585.0
850
'
'2
'''2



Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 17
Table for Interaction diagram:
Condition
c
sf '
s
f ssn ffcP 5.45.480.57 '
 ssn ffccM 5.225.22)425.08(8.57 '

B 7.69'' 53.06 413.52 4647.03
T 6.69 47.99 332.64 4423.8
T 5.69 41.13 243.97 4111.16
T 4.69 31.35 142.16 3683.7
T 3.69 16.27 16.5 3087.85
C 9 38.67 616.19 4391.91
C 11 15.82 834.61 3819.99
C 13 0.00 1021.4 3209.72
C 15 -11.60 1189.2 2497.88
Note: The more the pointscan be plotted the better the shape of ID will be.
Interaction diagram and ACI design strength diagram
If the column is subjected to a load 540 kips applied at an eccentricity e = 4.44'' then the corresponding moment is
inchkip 23764.4540 . Form the figure it is seen that the point lies in the ACI recommended safe zone.
There it can be said that the column is a good choice for a load 540 kips applied at an eccentricity e = 4.44''
Column Interaction Diagram0; 1628
2497.88; 1189.2
3209.72; 1021.4
3819.99; 834.61
4391.91; 616.19
4674.03; 413.52
4423.8; 332.64
4111.16; 243.97
3683.7; 142.16
3087.85; 16.5
0; 1139.6
2246.804; 832.44
2673.993; 584.227
3074.337; 431.333
3271.821; 289.464
3096.66; 232.848
2877.812; 170.779
2578.59; 99.512
2161.495; 11.55
2376; 540
1748.516; 832.44
0; 911.68
0
200
400
600
800
1000
1200
1400
1600
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Moment (Kip-inch)
Load(Kip)
Lecture note of Dr.H.M.A.Mahzuz on RCC Column
Page- 18
Few questions:
Why  is lower for column?
What is the significance of distributed and un-symmetric reinforcement on column?
Lecture Summery for column:
1) Introduction.
2) Several considerations in design of column.
3) Short column:
i) Concentrically loaded column.
ii) Eccentrically loaded column:
a) Uni-axial
b) Bi-axial
4) Long column.
5) Construction of Strength Interaction Diagram.
The End

More Related Content

What's hot

What's hot (20)

Portal and cantilever method
Portal and cantilever methodPortal and cantilever method
Portal and cantilever method
 
Reinforced column design
Reinforced column design Reinforced column design
Reinforced column design
 
Design of industrial roof truss
Design of industrial roof truss Design of industrial roof truss
Design of industrial roof truss
 
Deep beams
Deep beams Deep beams
Deep beams
 
Design of pile cap
Design of  pile capDesign of  pile cap
Design of pile cap
 
Column Interaction Diagram construction
Column Interaction Diagram constructionColumn Interaction Diagram construction
Column Interaction Diagram construction
 
Design of short columns using helical reinforcement
Design of short columns using helical reinforcementDesign of short columns using helical reinforcement
Design of short columns using helical reinforcement
 
Design of steel beams
Design of steel beamsDesign of steel beams
Design of steel beams
 
Ductile detailing
Ductile detailingDuctile detailing
Ductile detailing
 
Design of columns axial load as per IS 456-2000
Design of columns  axial load as per IS 456-2000Design of columns  axial load as per IS 456-2000
Design of columns axial load as per IS 456-2000
 
Two way slab
Two way slabTwo way slab
Two way slab
 
Design of slabs 1
Design of slabs 1Design of slabs 1
Design of slabs 1
 
Design of columns as per IS 456-2000
Design of columns as per IS 456-2000Design of columns as per IS 456-2000
Design of columns as per IS 456-2000
 
Axially loaded columns
Axially loaded columnsAxially loaded columns
Axially loaded columns
 
Slabs -Design steps
Slabs -Design steps Slabs -Design steps
Slabs -Design steps
 
Structural engineering i
Structural engineering iStructural engineering i
Structural engineering i
 
0 ne way slab
0 ne way slab0 ne way slab
0 ne way slab
 
Design of singly reinforced.
Design of singly reinforced.Design of singly reinforced.
Design of singly reinforced.
 
T beam TYPES
T beam TYPEST beam TYPES
T beam TYPES
 
Classification of cross section
Classification of cross sectionClassification of cross section
Classification of cross section
 

Similar to Column math

Lecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptx
Lecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptxLecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptx
Lecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptxAbelMulugeta8
 
Div_Syd_detailing_of_reinforcement_in_concrete_structures.pdf
Div_Syd_detailing_of_reinforcement_in_concrete_structures.pdfDiv_Syd_detailing_of_reinforcement_in_concrete_structures.pdf
Div_Syd_detailing_of_reinforcement_in_concrete_structures.pdfLandelSmith1
 
Esd ppt 150180106093,111,160183106008 GECDAHOD
Esd ppt 150180106093,111,160183106008 GECDAHODEsd ppt 150180106093,111,160183106008 GECDAHOD
Esd ppt 150180106093,111,160183106008 GECDAHODyasir Khan
 
Compression member
Compression memberCompression member
Compression memberVikas Mehta
 
Chapter 6 column
Chapter 6   columnChapter 6   column
Chapter 6 columnSimon Foo
 
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGDESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGLiyaWilson4
 
Lec5-Torsion of thin walled beams
Lec5-Torsion of thin walled beamsLec5-Torsion of thin walled beams
Lec5-Torsion of thin walled beamsMahdi Damghani
 
10346 07 08 examination paper
10346 07 08 examination paper10346 07 08 examination paper
10346 07 08 examination paperEddy Ching
 
MACHINE DESIGN QUESTION BANK ...
MACHINE DESIGN QUESTION BANK                                                 ...MACHINE DESIGN QUESTION BANK                                                 ...
MACHINE DESIGN QUESTION BANK ...musadoto
 
77201946
7720194677201946
77201946IJRAT
 
77201946
7720194677201946
77201946IJRAT
 
Column uniaxial axial loaded column design
Column  uniaxial axial loaded column designColumn  uniaxial axial loaded column design
Column uniaxial axial loaded column designUmarSaba1
 
rectangular and section analysis in bending and shear
rectangular and section analysis in bending and shearrectangular and section analysis in bending and shear
rectangular and section analysis in bending and shearqueripan
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Sd i-module2- rajesh sir
Sd i-module2- rajesh sirSd i-module2- rajesh sir
Sd i-module2- rajesh sirSHAMJITH KM
 

Similar to Column math (20)

Lecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptx
Lecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptxLecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptx
Lecture-7-Detailing-PHG-A1-Rev-10-2-Nov-16-Print.pptx
 
Div_Syd_detailing_of_reinforcement_in_concrete_structures.pdf
Div_Syd_detailing_of_reinforcement_in_concrete_structures.pdfDiv_Syd_detailing_of_reinforcement_in_concrete_structures.pdf
Div_Syd_detailing_of_reinforcement_in_concrete_structures.pdf
 
Esd ppt 150180106093,111,160183106008 GECDAHOD
Esd ppt 150180106093,111,160183106008 GECDAHODEsd ppt 150180106093,111,160183106008 GECDAHOD
Esd ppt 150180106093,111,160183106008 GECDAHOD
 
Compression member
Compression memberCompression member
Compression member
 
Chapter 6 column
Chapter 6   columnChapter 6   column
Chapter 6 column
 
Rectangular tank
Rectangular tankRectangular tank
Rectangular tank
 
unit-3.ppt
unit-3.pptunit-3.ppt
unit-3.ppt
 
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGDESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
 
Lec5-Torsion of thin walled beams
Lec5-Torsion of thin walled beamsLec5-Torsion of thin walled beams
Lec5-Torsion of thin walled beams
 
X10703 (me8593)
X10703 (me8593)X10703 (me8593)
X10703 (me8593)
 
10346 07 08 examination paper
10346 07 08 examination paper10346 07 08 examination paper
10346 07 08 examination paper
 
MACHINE DESIGN QUESTION BANK ...
MACHINE DESIGN QUESTION BANK                                                 ...MACHINE DESIGN QUESTION BANK                                                 ...
MACHINE DESIGN QUESTION BANK ...
 
77201946
7720194677201946
77201946
 
77201946
7720194677201946
77201946
 
Column uniaxial axial loaded column design
Column  uniaxial axial loaded column designColumn  uniaxial axial loaded column design
Column uniaxial axial loaded column design
 
Shear lug verification example
Shear lug verification exampleShear lug verification example
Shear lug verification example
 
6th Semester Mechanical Engineering (June/July-2015) Question Papers
6th Semester Mechanical Engineering  (June/July-2015) Question Papers6th Semester Mechanical Engineering  (June/July-2015) Question Papers
6th Semester Mechanical Engineering (June/July-2015) Question Papers
 
rectangular and section analysis in bending and shear
rectangular and section analysis in bending and shearrectangular and section analysis in bending and shear
rectangular and section analysis in bending and shear
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Sd i-module2- rajesh sir
Sd i-module2- rajesh sirSd i-module2- rajesh sir
Sd i-module2- rajesh sir
 

More from Dr. H.M.A. Mahzuz

Lecture 4, constituents of concrete-coarse aggregate
Lecture 4, constituents of concrete-coarse aggregateLecture 4, constituents of concrete-coarse aggregate
Lecture 4, constituents of concrete-coarse aggregateDr. H.M.A. Mahzuz
 
Lecture 3, constituents of concrete-fine aggregate
Lecture 3, constituents of concrete-fine aggregateLecture 3, constituents of concrete-fine aggregate
Lecture 3, constituents of concrete-fine aggregateDr. H.M.A. Mahzuz
 
Lecture 2, constituents of concrete-cement
Lecture 2, constituents of concrete-cementLecture 2, constituents of concrete-cement
Lecture 2, constituents of concrete-cementDr. H.M.A. Mahzuz
 
Lecture 5 rcc building design considering earthquake and wind load
Lecture 5 rcc building design considering earthquake and wind loadLecture 5 rcc building design considering earthquake and wind load
Lecture 5 rcc building design considering earthquake and wind loadDr. H.M.A. Mahzuz
 
Lecture 6 steel building design considering earthquake and wind load
Lecture 6 steel building design considering earthquake and wind loadLecture 6 steel building design considering earthquake and wind load
Lecture 6 steel building design considering earthquake and wind loadDr. H.M.A. Mahzuz
 
Lecture 4 beam design and load combination
Lecture 4 beam design and load combinationLecture 4 beam design and load combination
Lecture 4 beam design and load combinationDr. H.M.A. Mahzuz
 
Lecture 3 section identify and 3 d frame
Lecture 3 section identify and 3 d frameLecture 3 section identify and 3 d frame
Lecture 3 section identify and 3 d frameDr. H.M.A. Mahzuz
 
Lecture 1 what is rcc column and its importance
Lecture 1 what is rcc column and its importanceLecture 1 what is rcc column and its importance
Lecture 1 what is rcc column and its importanceDr. H.M.A. Mahzuz
 

More from Dr. H.M.A. Mahzuz (20)

Lecture 7 steel
Lecture 7 steelLecture 7 steel
Lecture 7 steel
 
Lecture 5, concrete-hmm
Lecture 5, concrete-hmmLecture 5, concrete-hmm
Lecture 5, concrete-hmm
 
Lecture 4, constituents of concrete-coarse aggregate
Lecture 4, constituents of concrete-coarse aggregateLecture 4, constituents of concrete-coarse aggregate
Lecture 4, constituents of concrete-coarse aggregate
 
Lecture 3, constituents of concrete-fine aggregate
Lecture 3, constituents of concrete-fine aggregateLecture 3, constituents of concrete-fine aggregate
Lecture 3, constituents of concrete-fine aggregate
 
Lecture 11, paint
Lecture 11, paintLecture 11, paint
Lecture 11, paint
 
Lecture 2, constituents of concrete-cement
Lecture 2, constituents of concrete-cementLecture 2, constituents of concrete-cement
Lecture 2, constituents of concrete-cement
 
Some fun facts
Some fun factsSome fun facts
Some fun facts
 
Lecture 5 rcc building design considering earthquake and wind load
Lecture 5 rcc building design considering earthquake and wind loadLecture 5 rcc building design considering earthquake and wind load
Lecture 5 rcc building design considering earthquake and wind load
 
Lecture 7 shear wall
Lecture 7 shear wallLecture 7 shear wall
Lecture 7 shear wall
 
Lecture 6 steel building design considering earthquake and wind load
Lecture 6 steel building design considering earthquake and wind loadLecture 6 steel building design considering earthquake and wind load
Lecture 6 steel building design considering earthquake and wind load
 
Lecture 4 beam design and load combination
Lecture 4 beam design and load combinationLecture 4 beam design and load combination
Lecture 4 beam design and load combination
 
Lecture 3 section identify and 3 d frame
Lecture 3 section identify and 3 d frameLecture 3 section identify and 3 d frame
Lecture 3 section identify and 3 d frame
 
Lecture 2 grid system
Lecture 2 grid systemLecture 2 grid system
Lecture 2 grid system
 
Lecture 1 outline -latest
Lecture 1 outline -latestLecture 1 outline -latest
Lecture 1 outline -latest
 
Lecture 1 what is rcc column and its importance
Lecture 1 what is rcc column and its importanceLecture 1 what is rcc column and its importance
Lecture 1 what is rcc column and its importance
 
Tannery hmm
Tannery hmmTannery hmm
Tannery hmm
 
River bank erosion hmm
River bank erosion hmmRiver bank erosion hmm
River bank erosion hmm
 
Public health in disaster
Public health in disasterPublic health in disaster
Public health in disaster
 
Lecture 2 flood
Lecture 2 floodLecture 2 flood
Lecture 2 flood
 
Lecture 1 flood
Lecture 1 floodLecture 1 flood
Lecture 1 flood
 

Recently uploaded

Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startQuintin Balsdon
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Intro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfIntro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfrs7054576148
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 

Recently uploaded (20)

Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Intro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfIntro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdf
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 

Column math

  • 1. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 1 RCC Column What is Column? Column may be defined as a vertical structural member that carry loads chiefly in compression. It can carry moment as well, about one or both axes of the cross section. Bending action may produce tensile forces over a part of the cross-section. Even in such case columns are referred as compression members because compression force dominates its behavior. Its ratio of height to least lateral dimension is  t L 3. Types of Column: A) Based on reinforcement column can be divided into the following was: 1) Column reinforced with longitudinal bar and lateral ties. 2) Column reinforced with longitudinal bar and continuous spirals. 3) Composite compression members reinforced longitudinal with structural steel shapes,pipe or tubing. B) Based on length: 1. Short column: Short columns those whose ratio of effective length to the minimum thickness is less then 12 (i.e. 12 ). Material strength is the main factor for its failure. 2. Long Column: Short columns those whose ratio of effective length to the minimum thickness is greater then 12 ( 12). Material strength and buckling are the main factors for its failure. C) Depending on position at a building or loading pattern: 1) Axially loaded column 2) Uni-axial column 3) Bi-axial column. Preliminary size of column: The initial stage in column design involves estimating the required of the column. There is no simple rule to do this as the axial load capacity of a given cross-section varies depending on the moment acting on the section.The approximate relation between axial load and gross area for tied column is, )(45.0 ', gyc U trialg ff P A   The approximate relation between axial load and gross area for tied column is, )(55.0 ', gyc U trialg ff P A   Depending on span length an initial approximation for gross area of column can also be made. For columns supporting heavily loaded floors minimum overall dimensions of one-fifteenth the average span of the panel is considered satisfactory.Roof columns may be somewhat lighter; one-eighteenth the average span is specified by some codes as a minimum diameter. Function of Tie/ spiral/ Transverse reinforcement: 1. To hold longitudinal bars in position in forms while the concrete is being placed. For this purpose both of them are wired togetherto form a cage of reinforcement. 2. To prevent the highly stressed slenderlongitudinal bars from buckling outward bursting the thin concrete cover.
  • 2. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 2 Fig: Tied column Fig: Spiral column Serial No. Contents Tied Spiral a) Least Dimension Minm 10 in, in EQ regions 12 in. Minm 12 in b) Least area -- --------- c) Steel ratio, min,g 1% 1% d) Steel ratio, max,g 8% 8% e) Minm No. of longitudinal bar 4 6 f) Minm longitudinal bar size #5 bar #5 bar g) Minm No. of tie bar #3 (for bundle bars or longitudinal bar size>#10 use #4 bar as tie) #3 h) Minm Clear cover 1.5 in 1.5 in Note: Generally max,g is preferable between 1%- 4% to avoid steel congestion. Guideline for Tie/ spiral reinforcement: 1) All bars of tied columns shall be enclosed by lateral ties, at least No. 3 in size for longitudinal bars up to No. 10, and at least No. 4 in size for Nos. 11, 14, and 18 and bundled longitudinal bars. 2) The spacing of the ties shall not exceed 16 diameters of longitudinal bars (16D), 48 diameters of tie bars (48d), nor the least dimension (tmin) of the column. 3) No bar shall be farther than 6 in. clear on either side from such a laterally supported bar. 4) The ties shall be so arranged that every corner and alternate longitudinal bar shall have lateral support pro - vided by the corner of a tie having an included angle of not more than 135°. 5) Spirals shall be continuous bar of not less than #3. The c lear spacing between turns of the spiral must not exceed 3 inch (but not less than 1 inch). Design of axially loaded column: WSD:
  • 3. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 3 For concentrically loaded spirally reinforced column Code provides the following formula for maximum allowable load: )25.0( ' gscg ffAP  For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable load: )25.0(85.0 ' gscg ffAP  Ag = Gross concrete area, g s g A A  . USD: Let us consider an axially loaded column where the load is taken by both concrete and steel. Therefore, sycc AfAfP  ' . But full strength of ' cf is not used rather 0.85 ' cf . So we can say: sycc AfAfP  ' 85.0 . Rearranging the equation we get, g g s ysgc A A A fAAfP  )(85.0 ' })1(85.0{ ' gygcg ffAP   For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable load: })1(85.0{ ' gygcg ffAP   85.0 and 75.0 for spiral column 80.0 and 70.0 for tied column Recommendation for tie: Fig: Minimum details for frames in regions of moderate risk
  • 4. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 4 Problem 1: Design a tied column for load 500 kip both in WSD and USD. Suggestedsolution: WSD Considering, 02.0g )25.0(85.0 ' gscg ffAP  )02.0604.0325.0(85.0500  gA 2 24.478 inAg  [ "87.2124.4782  hh ] Therefore select a square section 22''22''. As = gg A = 0.022222 = 9.68 in2. So provide 10 No. # 9 bar as main bar. Tie reinforcement: 1) 16D= 16 18 8 9  '' 2) 48d= 18 8 3 48  '' 3) tmin= 22'', So provide #3 @18''c/c as tie reinforcement. USD })1(85.0{ ' gygcg ffAP   As 80.0 and 70.0 for tied column. Considering, 01.0g )01.060)01.01(385.0(70.08.0500  gA 2 76.285 inAg  [ "7.1676.2852  hh ] Select a square section 18''18''. As = gg A = 0.011818 = 3.2420.28 in2 So provide 6 No. # 6 bar as main bar. Tie reinforcement: 1) 16D= 16 12 8 6  '' 2) 48d= 18 8 3 48  '' 3) tmin= 18'', So provide #3 @12''c/c as tie reinforcement. Note: This problem is done assuming an arbitrary g value. If anyone does this problem assuming an arbitrary gA then this way is also ok but remember that the g value must have to be greater than 0.01. Problem 2: A plan showing the beams and columns of a 10 storied market building is shown in Fig: 1(a). Here brick walls are used only for partition. Design the Column A for Ground floor and 4th floor in both WSD and USD having the following information: a) Slab thickness = 6.5'', b) Beam cross-section = 18''12'' c) Live load on the floor = 100 psf d) Live load in the roof = 60 psf. e) Brick wall thickness = 5''.
  • 5. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 5 f) Story clear height = 10' g) ' cf =3 ksi, and yf = 60 ksi SuggestedSolution: WSD Item No Item Calculation Load 1. Slab self load calculation =      10) 12 5.6 2 1720 2 2225 (15.0 353.3 kip 2. Beam weight =       10) 1212 2218 2 17202225 (15.0 173.25 3. Wall weight =    10)10 12 5 2 17202225 (12.0 210 kip 4. Floor Live load = 0.1     9) 2 1720 2 2225 ( 391.3 kip 5. Roof Live load = 0.06     1) 2 1720 2 2225 ( 26.1 kip 1153.95 kip Trial gross area of column, )(45.0 ', gyc trialg ff P A   , considering, 03.0g 2 , 24.534 )03.0603(45.0 95.1153 inA trialg    [ "11.2324.5342  hh ] Select a square section = 24''24''. Self load of column = 0.15' 60100 12 24 12 24  kip Total load = 1153.95 + 60 = 1214 kip For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable load: )25.0(85.0 ' gscg ffAP 
  • 6. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 6 )03.0604.0325.0(85.012.1032  gA 2 03.826 inAg  [ "74.2803.8262  hh ] Select a square section = 30''30''. Self load of column = 0.15'  100 12 30 12 30 93.8 kip Total load = 981.7+93.8=1075.45 kip )25.0(85.0 ' gscg ffAP  )03.0604.0325.0(85.045.1075  gA 2 7.860 inAg  [ "34.297.8602  hh ] Therefore the selected square section 30''30'' is ok!!!! As = gg A = 0.033030 = 27 in2, So provide 28 No. # 9 bar as main bar. Note: Sometimes extra bar has to be used to make the section symmetric. Tie reinforcement: 1) 16D= 16 18 8 9  '' 2) 48d= 18 8 3 48  '' 3) tmin= 30'', So provide #3 @18''c/c as tie reinforcement. USD Item No Item Calculation Load 6. Slab self load calculation =      4.110) 12 5.6 2 1720 2 2225 (15.0 494.62 kip 7. Beam weight =    4.110)10 12 5 2 17202225 (12.0 294 kip 8. Floor Live load = 0.1     7.19) 2 1720 2 2225 ( 665.21 9. Roof Live load = 0.06     7.11) 2 1720 2 2225 ( 44.37 kip 1498.2 kip
  • 7. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 7 Trial gross area of column, )(45.0 ', gyc trialg ff P A   , considering, 03.0g 2 , 96.1046 )03.0603(45.0 2.1498 inA trialg    [ "36.3296.10462  hh ] Select a square section = 33''33''. Self load of column = 0.15'  4.1100 12 33 12 33 158.82 kip Total load = 1498.2+158.82=1657.1 kip For concentrically loaded tied reinforced column Code provides the following formula for maximum allowable load: })1(85.0{ ' gygcg ffAP   80.0 and 70.0 for tied column )03.060)03.01(385.0(70.08.01.1657  gA 2 43.692 inAg  [ "31.2643.6932  hh ] Select a square section = 27''27''. Self load of column = 0.15'  4.1100 12 27 12 27 106.31 kip Total load = 1498.2+106.31=1604.6 kip })1(85.0{ ' gygcg ffAP   as 80.0 and 70.0 for tied column )03.060)03.01(385.0(70.08.06.1604  gA 2 5.670 inAg  [ "89.255.6702  hh ] Select a square section 26''26''. As = gg A = 0.032626 = 20.28 in2. So provide 26 No. # 8 bar as main bar. Note: Sometimes extra bar has to be used to make the section symmetric. Tie reinforcement: 1) 16D= 16 16 8 8  '' 2) 48d= "18 8 3 48  3) tmin= 26'', So provide #3 @16''c/c as tie reinforcement. Short column: Its strength is governed by strength of materials (i.e. concrete and steel) nd geometry of cross-section. 𝜌𝑠 can be selected by the equation, 𝜌𝑠 = 0.45( 𝐴 𝑔 𝐴 𝑐 − 1) 𝑓𝑐 ′ 𝑓𝑦 Problem :3 Design a column for 474 kip load. Answer: Assume the missing data, 𝒇 𝒄 ′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 15x15 in2 .
  • 8. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 8 })1(85.0{ ' gygcgn ffAPP   80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column, })1(85.0{ ' gygcg ffAP   )60)1(485.0(151570.08.0474 gg   01.00064.0  g , use 01.0min  2 25.2151501.0 inbhA gs   Problem :4 Design a column for 700 kip load. Answer: Assume the missing data, 𝒇 𝒄 ′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 15x15 in2 . })1(85.0{ ' gygcgn ffAPP   80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column, })1(85.0{ ' gygcg ffAP   )60)1(485.0(151570.08.0700 gg   00381.0 g 2 57.815150381.0 inbhA gs   Problem :5 Design a column for 1200 kip load. Answer: Assume the missing data, 𝒇 𝒄 ′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 15x15 in2 . })1(85.0{ ' gygcgn ffAPP   80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column, })1(85.0{ ' gygcg ffAP   )60)1(485.0(151570.08.01200 gg   08.011.0  g Change the material property/ section/ both and redesign Assume the missing data, 𝒇 𝒄 ′ = 4 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖, 𝐴 𝑔= 24x18 in2 . })1(85.0{ ' gygcgn ffAPP   80.0 and 70.0 for tied column, 85.0 and 75.0 for spiral column, })1(85.0{ ' gygcg ffAP   )60)1(485.0(182470.08.01200 gg   01.00276.0  g 2 91.1118240276.0 inbhA gs   Spacing of transverse reinforcement should be not less then (NON-EQ zone) 𝑠 = ( 16 diameter of Longitudinal steel (16D) 48 diameter of transverse steel (48d) Least dimension of column (tmin) ) Spacing of transverse reinforcement should be not less then (EQ zone) 𝑠 = ( 8 diameter of Longitudinal steel (8D) 24 diameter of transverse steel (24d) 1 2 of least dimension of column )
  • 9. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 9 and 2s Problem :6 Design a square column at middle for a DL=1 kip/ft and LL= 0.7 kip/ft. Consider that the building 10 storied. Also Consider, 𝒇 𝒄 ′ = 3 𝑘𝑠𝑖, 𝒇 𝒚 = 60 𝑘𝑠𝑖,
  • 10. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 10 Load at each over the column=(1 × 1.4 + 0.7 × 1.7) × ( 25 2 + 25 2 + 18 2 + 18 2 ) = 2.59 × 43 = 111.37 kip So, 𝑃10 = 111.37 × 10 = 1113.7 kip Considering, 𝜌𝑔 = 0.03, 𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐 ′(1 − 𝜌𝑔) + 𝑓𝑦 𝜌𝑔) => 1113.7 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.03) + 60 × 0.03) => 𝐴 𝑔 = 465.4 𝑖𝑛2 = 21.57 × 21.57,take − 24" × 24" 𝐴 𝑠 = 0.03 × 24" × 24" = 17.28 𝑖𝑛2 = 30 #7 Provide this column at 1st , 2nd, 3rd and 4th story. So, 𝑃6 = 111.37 × 6 = 668.2 kip Considering, 𝜌𝑔 = 0.02, 𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐 ′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔) => 668.2 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.02) + 60 × 0.02) => 𝐴 𝑔 = 322.6 𝑖𝑛2 = 17.96 × 17.96, take − 20" × 20" 𝐴 𝑠 = 0.02 × 20" × 20" = 8 𝑖𝑛2 = 20 #6 Provide this column at 5th , 6th and 7th story. So, 𝑃3 = 111.37 × 3 = 334.11 kip Considering, 𝜌𝑔 = 0.01, 𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐 ′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔) => 334.11 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.01) + 60 × 0.01) => 𝐴 𝑔 = 190.95 𝑖𝑛2 = 13.82 × 13.82, take − 15" × 15" 𝐴 𝑠 = 0.01 × 15" × 15" = 2.25 𝑖𝑛2 = 8 #5 Provide this column at 8th , 9th and 10th story. Check the column considering column self weight. So, 𝑃10 = 111.37 × 10 + 1.4 × {(0.15 × 22 12 × 22 12 × 10) × 4 + (0.15 × 18 12 × 18 12 × 10) × 3
  • 11. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 11 +(0.15 × 15 12 × 15 12 × 10) × 3} = 111.37 + 52.25 = 1166 kip Considering, 𝜌𝑔 = 0.03, 𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐 ′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔) => 1166 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.03) + 60 × 0.03) => 𝐴 𝑔 = 487.2 𝑖𝑛2 = 22.07 × 22.07 < 24×24(ok) So, 𝑃6 = 111.37 × 6 = 668.2 kip Considering, 𝜌𝑔 = 0.02, 𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐 ′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔) => 668.2 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.02) + 60 × 0.02) => 𝐴 𝑔 = 322.6 𝑖𝑛2 = 17.96 × 17.96, take − 18" × 18" 𝐴 𝑠 = 0.02 × 18" × 18" = 6.48 𝑖𝑛2 = 16 #6 Provide this column at 5th , 6th and 7th story. So, 𝑃3 = 111.37 × 3 = 334.11 kip Considering, 𝜌𝑔 = 0.01, 𝑃 = 𝜑𝑃𝑛 = 𝛼𝜑𝐴 𝑔(0.85𝑓𝑐 ′(1 − 𝜌𝑔 ) + 𝑓𝑦 𝜌𝑔) => 334.11 = 0.8 × 0.7𝐴 𝑔(0.85 × 3 × (1 − 0.01) + 60 × 0.01) => 𝐴 𝑔 = 190.95 𝑖𝑛2 = 13.82 × 13.82, take − 15" × 15" 𝐴 𝑠 = 0.01 × 15" × 15" = 2.25 𝑖𝑛2 = 8 #5 Provide this column at 8th , 9th and 10th story. Interaction Diagram (ID): For a column subjected to concentrated load or the loading condition where 10. h e  the following equations are the dominating equations for design. )25.0(85.0 ' gscg ffAP  (WSD) , })1(85.0{ ' gygcg ffAP   (USD) But if 10. h e  then it is an easy practice to take the help of Interaction Diagram. Interaction diagram is the graphical presentation of the different safe combinations of load (P) and moment (M). The following equations are necessary this diagram. sssscn fAfAabfP  ''' 85.0 ) 2 ()' 2 () 22 (85.0 ''' h dfAd h fA ah abfM sssscn  These equations will be able to give us the Nominal strength curve only. To make that usable an ACI design strength curve has to be made. Depending on column geometry, tie/ spiral values of  and  are important for that. The shaded portion
  • 12. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 12 is the final ID for a typical column. By the help of ID any type of column even shear walls can be designed. Design of column subjected to Uni-axial moment: Problem: 7 In a two storied structure an exterior column is to be designed for a service dead load of 142 kips, maximum live load of 213 kips, dead load moment of 83 kip-ft, live load moment of 124 kip-ft. The minimum live load compatible with the full the full live load moment is 106 kips, obtained when no live load is placed on the roof but a full live load is placed on the 2nd floor. Consider column dimension b = 16 in, and h = 20 in. ' cf =4 ksi, and yf = 60 ksi (a) Find the column RF for the full live load condition. (b) Check to ensure that the column is adequate for the condition of no live load on the roof. Answer: (a) kipPu 5612137.11424.1  ftkipMu  3271247.1834.1 Now, ksi A P g u 75.1 320 561  and ksi hA M g u 61.0 20320 12327     . With a cover 2.5 in 75.0 20 520    Having these main information from the graph 039.0g Therefore, 2 48.122016039.0 inbhA gs   Select 10 No.10 bars. (b) kipPu 3791067.11424.1  ftkipMu  327 (as before) Now, ksi A P g u 18.1 320 379  and ksi hA M g u 61.0 20320 12327     . With a cover 2.5 in 75.0 20 520    Having these main information from the graph 032.0g
  • 13. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 13 Therefore, 2 24.102016032.0 inbhA gs   < the result of case (a). So no modification is required. Problem: 8 A column carries a factored load 518 kip and factored moment 530 kip-ft. Design the column. Answer: As no other information are given so let us assume 03.0g , h = 24 inch and a concrete cover 3 inch 75.0 24 624    . Now, eccentricity, inch P M e u u 3.12 518 12530    , 51.0 24 3.12  h e . Using g and e from graph ksi A P g u 35.1 2 52.11241603.0 inbhA gs   Select 8 No.11 bars. What will happen if interaction diagram is not given????????? Design of column subjected to Bi-axial moment: Problem: 9 The column shown below has to carry a factored load 275 kips. The is acting with eccentricities "3ye and "6xe . The material strength ' cf = 4 ksi, and yf = 60 ksi. Check the adequacy of the trial section. Answer: Let us follow the Reciprocal load method. Considering bending about the Y-axis Considering bending about the Y-axis ; 75.0 20 520    3.0 20 6  h e 033.0 2012 8    g s A A ; 58.0 12 512    (say = 0.6) 25.0 12 6  h e 033.0 2012 8    g s A A inchb P bhA u g 1698.15 2435.1 518 35.1    
  • 14. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 14 From Graph A.7 kipPksi A P yOu g yOu 40875.1 , ,    kipPksi A P o g o 87665.3    From Graph A.7 kipPksi A P xOu g xOu 43282.1 , ,    kipPksi A P o g o 87665.3    Known, OyOnxOnn PPPP  1111 ,,  876 1 408 1 432 11  nP 92.275 un PP kip> the design load (275 kip). Therefore the selection of column section is ok!! Design for long/slender column: Problem: 10 A 22X14 inch2 (trial section)column carries an axial load Pd = 125 Md = 105 k-ft, Pl=112 kip, and Ml =96 kip-ft due to live load. The column is part of a frame that is braced against side-sway ant bent in single curvature about its major axis. The unsupported column length is lu = 19 ft. The moments at both ends of the column are equal. Design the column. The material strength ' cf = 4 ksi, and yf = 60 ksi. Answer:
  • 15. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 15 kipPu 4.3651127.11254.1  ftkipMu  2.310967.11054.1 Now, ksi A P g u 2.1 1422 4.365    and ksi hA M g u 55.0 221422 122.310     . Considering 75.0 from graph 026.0g Now let us check whether it is slender or not……     )5.34 223.0 12191 ( r klu )2211234(1234 2 1  M M Therefore it is a slender column. 478.0 4.365 1254.1 7.14.1 4.1      LD D d 2 12119435 478.01 1242236054.0 1 4.0 inkip IE EI d gc        kip kl EI P u c 3313 )( 2 2   )(4.014.06.0 4.0 6.0 2 1 ok M M Cm  Moment magnifier 17.1 331375.0 4.365 1 1 75.0 1       c u m nx P P C  Design ftkipMM unsc  3632.31017.1 Again, Now, ksi A P g u 2.1 1422 4.365    and ksi hA M g u 65.0 221422 12363     . From the same graph 036.0g 2 1.111422036.0 inbhA gs   Provide 12 No. 9 bars
  • 16. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 16 Construction of interaction diagram: Basic equations Manipulation: s s y E f  yu u b dc     ca 85.0 (At balanced condition bcc  ) ysus f c cd Ef     ysus f c dc Ef    ''  sssscn fAfAabfP  ''' 85.0 ) 2 ()' 2 () 22 (85.0 ''' h dfAd h fA ah abfM sssscn  s s u u b E f dc     ysus f c cd Ef     ysus f c dc Ef    ''  sssscn fAfAcbf.P  '''2 850 ) 2 ()' 2 () 2 85.0 (85.0 '''2 h dfAd h fA ch bfM sssscn    Problem: 11 a. Construct an interaction diagram of the column section shown at right. b. Construct an ACI design strength diagram for the same section. c. Is the column is good choice for a load 540 kips applied at an eccentricity e = 4.44''? Answer: At first let us simplify the process: ssn ssn sssscnn ffccM ff c cM h dfAd h fA ch cbfePM 5.225.22)425.08(8.57 ) 2 16 13(25.22)3 2 16 (25.22) 2 85.016 (16585.0 ) 2 ()' 2 () 2 85.0 (85.0 ' '2 '''2        ssn ssn sssscn ffcP ffcP fAfAcbf.P 5.45.480.57 25.2225.2216585.0 850 ' '2 '''2   
  • 17. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 17 Table for Interaction diagram: Condition c sf ' s f ssn ffcP 5.45.480.57 '  ssn ffccM 5.225.22)425.08(8.57 '  B 7.69'' 53.06 413.52 4647.03 T 6.69 47.99 332.64 4423.8 T 5.69 41.13 243.97 4111.16 T 4.69 31.35 142.16 3683.7 T 3.69 16.27 16.5 3087.85 C 9 38.67 616.19 4391.91 C 11 15.82 834.61 3819.99 C 13 0.00 1021.4 3209.72 C 15 -11.60 1189.2 2497.88 Note: The more the pointscan be plotted the better the shape of ID will be. Interaction diagram and ACI design strength diagram If the column is subjected to a load 540 kips applied at an eccentricity e = 4.44'' then the corresponding moment is inchkip 23764.4540 . Form the figure it is seen that the point lies in the ACI recommended safe zone. There it can be said that the column is a good choice for a load 540 kips applied at an eccentricity e = 4.44'' Column Interaction Diagram0; 1628 2497.88; 1189.2 3209.72; 1021.4 3819.99; 834.61 4391.91; 616.19 4674.03; 413.52 4423.8; 332.64 4111.16; 243.97 3683.7; 142.16 3087.85; 16.5 0; 1139.6 2246.804; 832.44 2673.993; 584.227 3074.337; 431.333 3271.821; 289.464 3096.66; 232.848 2877.812; 170.779 2578.59; 99.512 2161.495; 11.55 2376; 540 1748.516; 832.44 0; 911.68 0 200 400 600 800 1000 1200 1400 1600 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 Moment (Kip-inch) Load(Kip)
  • 18. Lecture note of Dr.H.M.A.Mahzuz on RCC Column Page- 18 Few questions: Why  is lower for column? What is the significance of distributed and un-symmetric reinforcement on column? Lecture Summery for column: 1) Introduction. 2) Several considerations in design of column. 3) Short column: i) Concentrically loaded column. ii) Eccentrically loaded column: a) Uni-axial b) Bi-axial 4) Long column. 5) Construction of Strength Interaction Diagram. The End