Seismic Analysis and Design of a Multi-Storey Building Located
in Haql City, KSA
M. Ismaeil1*
, Kh. Elhadi2
, Y. Alashker2
, I.E. Yousef3
1. Assistant Professor, Department of Civil Engineering, King Khalid University, KSA. On leave from Sudan
University for Science and Technology, Khartoum, Sudan
2. Assistant Professor, Department of Civil Engineering, King Khalid University, KSA. On leave from Structural
Engineering Department, Zagazig University, Zagazige, Egypt
3. Lecturer, Department of Civil Engineering, King Khalid University, KSA
Corresponding author: maibrahim@kku.edu.sa
https://doi.org/10.22115/SCCE.2017.49083
ARTICLE INFO ABSTRACT
Article history:
Received: 29 July 2017
Revised: 02 August 2017
Accepted: 02 August 2017
Recently the design of RC building to mitigate seismic loads
has received great attention. Since Saudi Arabia has low to
moderate seismicity, most of the buildings were designed
only for gravity load. The objective of this paper is to
analysis design RC building located in the most active
seismic zone region in Saudi Arabia to mitigate seismic
loads. A multi-story reinforced concrete building, in Haql
city, was seismically analyzed and designed using the
Equivalent Lateral Force Procedure with the aid of SAP200
software. The chosen buildings which were Ordinary
Moment Resisting Frame (OMR), was analyzed and
designed by using SBC 301 (2007) Saudi Building Code [1],
SAP2000 (structural analysis software) [2] and ISACOL
"Information Systems Application on Reinforced Concrete
Columns" [3]. The results showed that the current design of
RC buildings located in the most active seismic zone region
in Saudi Arabia, Haql city was found unsafe, inadequate and
unsatisfied to mitigate seismic loads.
Keywords:
SAP2000;
SBC 301 (2007);
Active seismic zone region;
Saudi Arabia;
Equivalent static method;
Seismic loads.
36 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
1. Introduction
Haql is a town in the northwest of Saudi Arabia near the head of the Gulf of Aqaba, adjacent to
Aqaba across the Jordanian border. The coasts of Egypt, Israel, and Jordan, can be seen from
Haql. Haql city is located in the most active seismic zone region of the Kingdom of Saudi Arabia
where there is a complicated geological structure and tectonics. This paper is an attempt to study
the effect of seismic loads on RC residential buildings located in the most active seismic zone
region of the Kingdom of Saudi Arabia. Saudi Arabia is not free from earthquakes. It has
experienced many earthquakes during the recent history, and the previous studies in this field
demonstrated this argument. Most of the existing buildings in Saudi Arabia do not meet the
current design standards due to design shortage or construction shortcomings.
The last major event was the 1995 Haql earthquake in the Gulf of Aqaba (magnitude 7.3) which
caused significant damage on both sides of the Gulf and was felt hundreds of kilometers away.
As far as Saudi Arabia is concerned, the most active area is along the Gulf of Aqaba (Dead Sea
transform fault). On 19 May 2009, 19 earthquakes of M4.0 or greater took place in the volcanic
area of Harrat Lunayyir to the north of Yanbu, including an M5.4 event that caused minor
damage to structures [4]. The 1995 Gulf of Aqaba earthquake (also known as Nuweiba
earthquake) occurred on November 22 at 06:15 local time (04:15 UTC) and registered 7.3 on the
moment magnitude scale. The epicenter was located in the central segment of the Gulf of Aqaba.
The earthquake occurred along the Dead Sea Transform (DST) fault system, an active tectonic
plate boundary with seismicity that is characterized by long-running quiescent periods with
occasional large and damaging earthquakes, along with intermittent earthquake swarms. It was
the strongest tectonic event in the area for many decades and caused injuries, damage, and deaths
throughout the Levant and is also thought to have remotely triggered a series of small to
moderate earthquakes 500 kilometers (310 miles) to the north of the epicenter. In the aftermath
of the quake, several field investigations set out to determine the extent of any surface faulting,
and the distribution of aftershocks was analyzed. Areas affected: Egypt, Israel, Jordan and Saudi
Arabia as shown in Figure 1[4]. Recent studies, historical evidence, geological and geophysical
observations indicate that parts of the Kingdom fall within seismic risk regions. In western Saudi
Arabia, a design peak ground acceleration (PGA) ranging from 0.03g to 0.26g for an economic
life of 50 years was suggested. Seismic zonation was established with zone numbers 0, 1, 2A,
and 2B [5]. Saudi Arabia is not free from earthquakes. It has experienced many earthquakes
during the recent history, and the previous studies in this field demonstrated this argument. Most
of the existing buildings in Saudi Arabia do not meet the current design standards due to design
shortage or construction shortcomings. Therefore, buildings should be designed regarding their
capacity for resisting the expected seismic effects. The seismic hazard analysis for the Kingdom
was performed [6,7]. Seismograph stations of the Saudi National Seismic Network as shown in
Figure 2 [8], was developed for the Kingdom based on the peak ground acceleration, PGA,
values calculated for 50 years service lifetime with 10% probability of being exceeded.
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 37
Fig. 1. 1995 Gulf of Aqaba earthquake [4].
Fig. 2. Seismograph stations of the Saudi National Seismic Network [8].
2. Description and Model of the Building
A six-story residential building with plan and elevations as shown in Figures 3 to 6 is considered
for the study. The building is composed of moment resisting RC frame with solid slab, 140mm
thickness, situated in the most active seismic zone region of the Kingdom of Saudi Arabia. The
structure members are made of in-situ reinforced concrete. The overall plan of the building is
square with dimensions 14.5x15m as shown in Figure 3. The height of the building is 16 m, and
story height for each floor is 3.2 m. Columns and beams sizes are shown in Table 1. The building
is approximately symmetric in both directions. The plan and some frames of the studied building
as shown in Figures 3 to 5. Beams and columns have been modeled as frame elements while the
in-plane rigidity of the slab is simulated using rigid diaphragm action. The columns are assumed
to be fixed at the base. The building is analyzed.
As per seismic provisions provided by SBC 301-2007.
38 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
Table 1
The cross-section of beams and columns.
Building Beams Level Columns Reinforcement
mm mm
6 Stories 600*250 1st floor -2nd floor 600*250 12 Φ 16
(10 Φ 16) 3nd floor-4rd floor 500*250 10 Φ 16
5th floor 5th floor 450*250 10 Φ 16
Fig. 3. Architectural plan of the studied building.
Fig. 4. YZ elevation @ X=5.5 m of the studied building.
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 39
Fig. 5. XZ elevation @ Y=9.5 m of the studied building.
Fig. 6. XY Plan of studied building.
3. Current Design
It is a common practice in The Kingdom of Saudi Arabia to design buildings without any
consideration of seismic loads. Therefore, the one typical case study has been studied first under
the effect of gravity loads and without consideration of seismic loads in order to check the
current design. Dead and live loads are following the equations and tables given in the SBC-301-
2007(Saudi Arabia) and second under the effect of seismic loads.
4. Modeling and Analysis of RC Residential Buildings due to Earthquake
Loads (Equivalent Static Method as per SBC-303-2007)
Most buildings and structures in the kingdom of Saudi Arabia have not yet been designed and
constructed in compliance with earthquake provisions or given any consideration for earthquake
effect.
40 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
The horizontal seismic loads are defined according to Saudi Buildings Code (SBC-303-2007).
The lateral force effect on the structure can be translated to equivalent lateral force at the base of
the structure which can be distributed to different stories. According to Saudi Buildings Code
(SBC-303-2007), the total seismic base shear force V is determined as follows:
V = Cs*W )1(
Where: Cs is the seismic coefficient, W is the total weight and V is the base shear. The seismic
design coefficient (Cs) shall be determined by the following equation:
Cs = SDS / (R / I) )2(
Where SDS = Design spectral response acceleration in the short period range
R = Response modification factor
I = Occupancy importance factor determined
The value of the seismic response coefficient, (Cs), need not be greater than the following
equation:
Cs = SD1 / [T. (R / I)] )3(
However, shall not be taken less than:
T = 0.1N )4(
Where N = Number of stories
Cs = 0.044SDS I )5(
Where, SDS = Design spectral response acceleration at a period of 1 sec
T = Fundamental period of the structure (sec)
Design earthquake spectral response acceleration at short periods, SDS, and at the 1-sec period,
SD1, shall be as follows.
SMS= Fa*SS )6(
SM1= Fv*S1 )7(
SDS= 2/3*SMS )8(
SD1= 2/3*SM1 )9(
Where:
SS: the maximum spectral response acceleration at short periods
S1: the maximum spectral response acceleration at a period of 1 sec
Fa: acceleration-based site coefficient
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 41
Fv: velocity-based site coefficient
SMS: the maximum spectral response acceleration at short periods adjusted for site class
SM1: the maximum spectral response acceleration at a period of 1 sec adjusted for site class
SDS: the design spectral response acceleration at short periods
SD1: the design spectral response acceleration at a period of 1 sec
5. Vertical Distribution of Base Force
The buildings are subjected to a lateral load distributed across the height of the buildings
based on the following formula specified by Saudi Buildings Code (SBC-303-2007):
Where Fx is the applied lateral force at level ‘x’, W is the story weight, h is the story height, and
V is the design base shear, and N is the number of stories. The summation in the denominator is
carried through all story levels. This results in an inverted triangular distribution when k is set
equal to unity. A uniform lateral load distribution consisting of forces that are proportional to the
story masses at each story level.
k = an exponent related to the structure period as follows:
For structures having a period of 0.5 sec or less, k = 1
For structures having a period of 2.5 sec or more, k= 2
6. LOAD COMBINATIONS AS PER SBC-303-2007
As per SBC-301 section 2.3, following load combinations should be considered for the design of
structures, components, and foundations.
1.4 (D + F)
1.2 (D + F + T) + 1.6 (L + H) + 0.5 (Lr or R)
1.2 D + 1.6 (Lr) + (f1L)
1.2D + f1L + 0.5 (Lr)
1.2D + 1.0 E + f1L
0.9D ± 1.0E
Where:
E = ρQE + 0.2SDSD
1.0 ≤ ρ ≤ 1.5
f1 = 1.0 for areas occupied as places of public assembly, for live loads more than 5.0 kN/m2,
and for parking garage live load.
42 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
f1 = 0.5 for other live loads.
SDS = the design spectral response acceleration in the short period range as determined from
Section.
QE = the effect of horizontal seismic (earthquake-induced) forces.
Table 6.1 shows the design parameters taken from both codes for analysis of buildings.
7. Seismic Map for the Kingdom of Saudi Arabia
The Saudi Buildings Code (SBC-303-2007) provides seismic maps for the Kingdom of Saudi
Buildings, as shown in Figures 7 and 8.
Fig. 7. Maximum Considered Earthquake Ground Motion for the Kingdom of 1 SEC Spectral Response
Acceleration (S1 in %g) (5 Percent of Critical Damping), Site Class B. (Region 1) [1].
Fig. 8. Maximum Considered Earthquake Ground Motion for the Kingdom of 0.2 SEC Spectral Response
Acceleration (Ss in %g) (5 Percent of Critical Damping), Site Class B. (Region 1) [1].
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 43
8. Mapped acceleration parameters
The design parameters that are used in the equivalent static method are illustrated as follows: The
parameters Ss and S1 shall be determined from the 0.2 and 1-second spectral response
accelerations shown on country maps
Where S1 is less than or equal to 0.04 and Ss is less than or equal 0.15, the structure is permitted
to be assigned to seismic design category A So,
S1= the mapped spectral accelerations for a 1- second period
Ss= the mapped spectral accelerations for a short period.
 On lack of a map of spectral accelerations of S1 and SS, the following can be assumed:
S1= 1.25 Z, Ss= 2.5 Z (amendment no. 3 to SI 413 (2009)) or from maps as shown in
Figures 7 and 8.
9. The Results and Discussions
Figures 9 and 10 show the label of columns and beams of the selected frames.
Fig. 9. The label of beams and columns in direction XZ@Y=9.5 m.
44 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
Fig. 10. The label of beams and columns in direction YZ@X= 5.5 m.
9.1. Results of analysis of considered buildings due to gravity loads
This part presents the results of analysis and design of considered RC buildings due to gravity
loads. We selected one frame in each direction X and Y as shown in figures 9 and 10 for columns
and beams.
1. Beams
Table 2 shows the Straining action of some beams in the selected frames at direction YZ @ X =
5.5
Table 2
The Straining action of some beams in the selected frames at direction YZ @ X = 5.5.
Direction Y-Z @ X=5.5
Load Case Ultimate (1.4DL+1.6LL)
Beam No. SHEAR MOMENT 3-3 (KN.m)
KN END START
B-03 -9.81 0.24 -6,81
B-09 21.7 -29.54 -1.62
B-11 -11.91 4.5 -10.15
B-17 21.42 -29.11 -1.61
B-19 -13.16 7.37 -12.3
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 45
2. Columns
Tables 3 shows the Straining action of some columns in the selected frames at direction YZ @ X
= 5.5
Table 3
The Straining action of some columns in the selected frames at direction YZ @ X = 5.5.
Direction Y-Z @ X=5.5
Load Case Ultimate (1.4DL+1.6LL)
Column No. AXIAL SHEAR MOMENT 3-3 (KN.m)
KN END START
C-01 -907.8 -0.61 -0.62 -2.57
C-03 -1307.75 -10.94 21.51 -13.51
C-09 -586.33 0.56 -1.46 -0.33
C-11 -855.93 -15.98 26.44 -24.68
C-17 -285.18 0.63 -1.17 0.84
C-19 -421.77 -11.1 18.29 -17.22
9.2. Results of analysis of considered buildings due to seismic loads
This part presents the results of analysis and design of considered RC buildings due to seismic
loads. Using the Saudi Buildings Code (SBC-301-2007) provisions, the following parameters
have been calculated to be used as input data for seismic analysis of the selected model with
notice that the Haql City falls in region 6. The calculated results of these parameters are as
follows:
Table 4
The seismic parameter for Haql City according to SBC301.
SDS 0.14 CS = 0.0714
SD1 0.04 CS (max.) = 0.0678
I 1.00 CS(min.) = 0.0057
R 2.00
W= 812.0 KN V= 55.1 TON
Take CS= 0.678
Table 5
Calculation of Base Shear and lateral load distribution with height.
Story W (ton) h (m) w*h cv Fx (TON)
Sixth Floor 16.66 21 350 0.015 0.9
Fifth Floor 142.67 18 2568 0.114 6.3
Fourth Floor 268.69 15 4030 0.179 9.8
Third Floor 394.70 12 4736 0.210 11.6
Second Floor 520.72 9 4686 0.208 11.4
First Floor 646.73 6 3880 0.172 9.5
Ground Floor 772.75 3 2318 0.103 5.7
SUM(W*H) 22570 SUM FX 55.1
46 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
1. Beams
Tables 6 shows the Straining action of some beams in the selected frames at direction YZ @ X =
5.5 m due to load case Group-Y
Table 6
The Straining action of some beams in the selected frames at direction YZ @ X = 5.5 m due to load case
Group-Y.
Direction Y-Z @ X=5.5 m
Load case: GroupY
Beam No. SHEAR MOMENT 3-3 (KN.m)
KN END START
B-03 53.39 -93.73 90.13
B-09 22.07 -30.12 -1.65
B-11 49.02 -86.03 82.88
B-17 21.78 -29.68 -1.64
B-19 32.05 -52.51 49.84
Where:
Load Case Group-Y is load combination included seismic loads at Y direction.
Load Case Ultimate is load combination included dead and live loads only
2. Columns
Tables 7 shows the Straining action of some columns in the selected frames at direction YZ @ X
= 5.5 m
Table 7
The Straining action of some Columns in the selected frames at direction YZ @ X = 5.5 m due to load
case Group-Y.
Direction Y-Z @ X=5.5
Load Case: GroupY
Column No. AXIAL SHEAR MOMENT 3-3 (KN.m)
KN END START
C-01 -922.95 1.23 -2.68 -2.62
C-03 -1331.32 -11.18 21.93 -13.8
C-09 -596.12 1.74 -3.28 2.3
C-11 -871.43 -18.32 27.01 -25.21
C-17 -289.96 0.74 -1.33 1.04
C-19 -429.44 -11.33 18.68 -17.59
10. Design of structural elements against gravity loads
The reinforced concrete sections were designed according to the BSI 8110 [9] using the limit
state design method (Mosley and Bungey, 1997) [10].
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 47
10.1. Design of columns
(a) Calculation of internal forces in columns
The columns were designed to resist axial compression forces and bending moment due to
gravity load. The design forces in columns obtained from the computer analysis program
SAP2000 are shown in Table 8.
*Direction YZ@X=5.5
Table 8
Internal forces in columns due to gravity loads.
Column No. Output Case Shear Force (KN) Bending Moment (KN.m) Axial Force (KN)
C04 1.4DL+1.6LL 11.26 13.99 1372.02
C03 1.4DL+1.6LL 10.94 13.51 1307.75
C02 1.4DL+1.6LL 1.64 3.78 997.52
C01 1.4DL+1.6LL -0.61 2.57 907.80
(b) Design of columns before adding seismic loads
* Direction YX@X=5.5
The design of columns has been performed using a computer program called ISACOL [5].
Figures 11 and 13 show the main window of ISACOL program and sample of column design.
Fig. 11. ISACOL program results for C40 [3].
48 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
Table 9
Design of columns before adding seismic Loads.
Column No.
Original design Present design
Dimensions Reinforcement Dimensions Reinforcement
C04 250 X 500 12 Φ 16 250 X 500 10 Φ 16
C03 250 X 500 12 Φ 16 250 X 500 10 Φ 16
C02 250 X 500 12 Φ 16 250 X 500 10 Φ 16
C01 250 X 500 12 Φ 16 250 X 500 10 Φ 16
250*500 250*500
12 Φ 16 10 Φ 16
Fig. 12. Design of some columns before adding seismic Loads.
10.2. Design of beams
As for the beams, the internal forces due to gravity loads have been calculated first. Then the BSI
[9], has been used to check the existing design. It has been found that the existing design is
adequate.
11. Design of structural elements against gravity loads and earthquake loads
The reinforced concrete sections were designed according to the BSI 8110 [9] using the limit
state design method (Mosley and Bungey, 1997) [10].
11.1. Design of columns
(a) Calculation of internal forces in columns
The columns were designed to resist seismic and gravity load. The design forces in columns
obtained from the computer analysis program SAP2000 are shown in Table 10.
* Direction YZ@X=5.5 m
Table 10
Internal forces in columns due to seismic loads.
Column No. Output Case Shear Force (KN) Bending Moment (KN.m) Axial Force (KN)
C04 GROUPX 159.27 298.95 1397.14
C03 GROUPX 137.69 256.36 1331.32
C02 GROUPX 125.60 223.55 1041.80
C01 GROUPX 96.96 173.70 922.95
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 49
(b) Design of columns after adding seismic loads
The design of columns has been performed using a computer program called ISACOL [3].
Figures 12 and 14 show the design of some columns before and after adding seismic loads.
Fig. 13. ISACOL program results for C04 [3].
Table 11. Shows the design of columns after adding seismic loads.
Table 11
Design of columns after adding seismic loads-direction (y).
Column No. Original design Including seismic loads
Dimensions Reinforcement Dimensions Reinforcement
C04 250 X 500 10 Φ 16 250*1550 18 Φ 20
C03 250 X 500 10 Φ 16 250*1250 14 Φ 20
C02 250 X 500 10 Φ 16 250*1200 14 Φ 20
C01 250 X 500 10 Φ 16 250*850 12 Φ 20
250*1200 250*850
14 Φ 20 12 Φ 20
Fig.14. Design of some columns after adding seismic loads
50 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51
12. Conclusion
This paper provides a set of seismic analysis and design of RC buildings located in the most
active seismic zone region in Saudi Arabia. The building was analyzed and designed before and
after considering earthquake loads applied in two directions; XX and YY. From the results
obtained it can be seen that:
1. There are slight changes in the values of the bending moments and shear forces on the beams
before and after considering earthquake loads as shown in Tables 2 and 6. There is an increase in
some internal beams, such as B-3, B-11, and B-19.
2. The values of the bending moments and shear forces on the columns due to seismic loads are
nearly five times that due to gravity loads as shown in Tables 8 and 10.
3. The values of the axial forces on the columns due to seismic loads are approximately similar
to gravity loads as shown in Tables 8 and 10.
4. As an overall trend the results showed that the current design of RC buildings located in the
most active seismic zone region of the Kingdom of Saudi Arabia, Haql city were found unsafe,
inadequate and unsatisfied to mitigate seismic loads.
The present study represents the first attempt to investigate the seismic resistance of residual
buildings in Haql city in Saudi Arabia. Due to the lack of knowledge about the seismic activity in
this country some buildings are designed and constructed without any seismic load
consideration. Seismicity of Saudi Arabia may be considered as moderate. Hence, all buildings
should be checked against earthquake resistance. The present paper proposes a simple procedure
to check the seismic resistance of such buildings.
The obtained results emphasize the following conclusions:
1- Current design of some residual buildings in Saudi Arabia does not consider earthquake loads.
2- It has been found that the current design of residual buildings in the Haql city is unsafe for the
current seismicity of the Haql city.
Acknowledgments
The author would like to express his gratitude to King Khalid University, Saudi Arabia for
providing administrative and technical support.
References
[1] Saudi Building Code SBC-301-2007: Loads and Forces Requirements, Saudi Buildings Code
National Committee. 2007.
[2] Wilson EL. Three-dimensional static and dynamic analysis of structures. Computers and Structures
Inc., Berkeley, California, U.S.A: Computers and structures; 2002.
M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 51
[3] Shehata AY. Information Systems Application on Reinforced Concrete Columns. M. Sc. Thesis,
Faculty of Engineering, Department of Structural Engineering, Cairo University, Giza, Egypt,
1999.
[4] https://en.wikipedia.org/wiki/1995_Gulf_of_Aqaba_earthquake n.d.
[5] Attar MS. Evaluation of the Seismic Performance of A Typical School Building. Master Thesis,
College of Engineering, KAAU, 2003.
[6] Al-Haddad M, Siddiqi GS, Al-Zaid R, Arafah A, Necioglu A, Turkelli N. A Study Leading to a
Preliminary Seismic Design Criteria, for the Kingdom. Final Report, KACST Proj No AR-9-31,
Riyadh 1992.
[7] Al-Haddad M, Siddiqi GH, Al-Zaid R, Arafah A, Necioglu A, Turkelli N. A basis for evaluation of
seismic hazard and design criteria for Saudi Arabia. Earthq Spectra 1994;10:231–58.
[8] Hassaballa AE, Adam FM, Ismaeil MA. Seismic Analysis of a Ten-Storey Reinforced Concrete
Building in Jazan Area, KSA. Open J Civ Eng 2017;07:252–66. doi:10.4236/ojce.2017.72016.
[9] BS8110. Structural Use of Concrete,. British Standard Institution, London: 1997.
[10] Mosley WH, Bungey JH. Reinforced Concrete Design; BS 8110:Part 1, 2nd Ed. Macmillan ,
London: 1997.

More Related Content

What's hot

Design of rcc structures
Design of rcc structuresDesign of rcc structures
Design of rcc structuresR VIJAYAKUMAR
 
Design of pile cap
Design of  pile capDesign of  pile cap
Design of pile capPuspendu Ray
 
Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...
Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...
Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...Rahul Leslie
 
Soil pressure in etabs
Soil pressure in etabsSoil pressure in etabs
Soil pressure in etabsJacob shah
 
Eccentric Loading In Welded Connections
Eccentric Loading In Welded ConnectionsEccentric Loading In Welded Connections
Eccentric Loading In Welded ConnectionsAbhishek Kansara
 
Structure Reinforced Concrete
Structure Reinforced ConcreteStructure Reinforced Concrete
Structure Reinforced ConcreteNik M Farid
 
Design of RCC Column footing
Design of RCC Column footingDesign of RCC Column footing
Design of RCC Column footingArun Kurali
 
[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)
[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)
[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)Gabriel Ramirez Cortez
 
Lecture chapter 2
Lecture chapter 2Lecture chapter 2
Lecture chapter 2rgo-amo
 
Cold-Formed-Steel Design And Construction ( Steel Structure )
Cold-Formed-Steel Design And Construction ( Steel Structure )Cold-Formed-Steel Design And Construction ( Steel Structure )
Cold-Formed-Steel Design And Construction ( Steel Structure )Hossam Shafiq I
 
Concrete filled steel tubes
Concrete filled steel tubesConcrete filled steel tubes
Concrete filled steel tubesHarikrishna M.S
 
prestressing steel
 prestressing steel prestressing steel
prestressing steelAzraanvar1
 

What's hot (20)

Beam design
Beam designBeam design
Beam design
 
Reinforced concrete column
Reinforced concrete columnReinforced concrete column
Reinforced concrete column
 
Design of rcc structures
Design of rcc structuresDesign of rcc structures
Design of rcc structures
 
COMPRESSION MEMBERS
COMPRESSION MEMBERS COMPRESSION MEMBERS
COMPRESSION MEMBERS
 
ETABS Modelling
ETABS ModellingETABS Modelling
ETABS Modelling
 
Design of pile cap
Design of  pile capDesign of  pile cap
Design of pile cap
 
Shear wall and its design guidelines
Shear wall and its design guidelinesShear wall and its design guidelines
Shear wall and its design guidelines
 
Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...
Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...
Part-I: Seismic Analysis/Design of Multi-storied RC Buildings using STAAD.Pro...
 
Soil pressure in etabs
Soil pressure in etabsSoil pressure in etabs
Soil pressure in etabs
 
Eccentric Loading In Welded Connections
Eccentric Loading In Welded ConnectionsEccentric Loading In Welded Connections
Eccentric Loading In Welded Connections
 
Structure Reinforced Concrete
Structure Reinforced ConcreteStructure Reinforced Concrete
Structure Reinforced Concrete
 
Six storey residential building design
Six storey residential building designSix storey residential building design
Six storey residential building design
 
Design of RCC Column footing
Design of RCC Column footingDesign of RCC Column footing
Design of RCC Column footing
 
Design notes for seismic design of building accordance to Eurocode 8
Design notes for seismic design of building accordance to Eurocode 8 Design notes for seismic design of building accordance to Eurocode 8
Design notes for seismic design of building accordance to Eurocode 8
 
[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)
[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)
[Braja m. das]_principles_of_foundation_engineerin(book_fi.org)
 
Lecture chapter 2
Lecture chapter 2Lecture chapter 2
Lecture chapter 2
 
Cold-Formed-Steel Design And Construction ( Steel Structure )
Cold-Formed-Steel Design And Construction ( Steel Structure )Cold-Formed-Steel Design And Construction ( Steel Structure )
Cold-Formed-Steel Design And Construction ( Steel Structure )
 
Concrete filled steel tubes
Concrete filled steel tubesConcrete filled steel tubes
Concrete filled steel tubes
 
prestressing steel
 prestressing steel prestressing steel
prestressing steel
 
Bs8110 design notes
Bs8110 design notesBs8110 design notes
Bs8110 design notes
 

Similar to Seismic Analysis and Design of Multi-Storey Building in Saudi Arabia

IRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationC
IRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationCIRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationC
IRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationCIRJET Journal
 
Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...
Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...
Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...IRJET Journal
 
A Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC FramesA Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC FramesIRJET Journal
 
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...IRJET Journal
 
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...Mintu Choudhury
 
Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...
Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...
Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...ijtsrd
 
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...IRJET Journal
 
40. g+20
40. g+2040. g+20
40. g+20gssnie
 
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...IJERA Editor
 
Seismic Analysis of Multi Storied Irregular Building using Flat Slab and Gri...
Seismic Analysis of Multi Storied Irregular Building  using Flat Slab and Gri...Seismic Analysis of Multi Storied Irregular Building  using Flat Slab and Gri...
Seismic Analysis of Multi Storied Irregular Building using Flat Slab and Gri...IRJET Journal
 
Earthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover AnalysisEarthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover AnalysisIRJET Journal
 
Study on the Effect of Response Spectrum Analysis and Construction Sequence A...
Study on the Effect of Response Spectrum Analysis and Construction Sequence A...Study on the Effect of Response Spectrum Analysis and Construction Sequence A...
Study on the Effect of Response Spectrum Analysis and Construction Sequence A...ijtsrd
 
Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...IRJET Journal
 
A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...IRJET Journal
 
IRJET- Comparative Seismic Analysis of RC G+13 Multistorey Building Frame
IRJET-  	  Comparative Seismic Analysis of RC G+13 Multistorey Building FrameIRJET-  	  Comparative Seismic Analysis of RC G+13 Multistorey Building Frame
IRJET- Comparative Seismic Analysis of RC G+13 Multistorey Building FrameIRJET Journal
 

Similar to Seismic Analysis and Design of Multi-Storey Building in Saudi Arabia (20)

IRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationC
IRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationCIRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationC
IRJET-Earthquake Resistant Structure using Seismic Cloaked FoundationC
 
Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...
Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...
Analysis of Multistory Semi Rigid Steel Frame with Cross Bracings Subjected t...
 
A Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC FramesA Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC Frames
 
Evaluation of the Impact of Dynamic Analysis on Different Building Height
Evaluation of the Impact of Dynamic Analysis on Different Building Height Evaluation of the Impact of Dynamic Analysis on Different Building Height
Evaluation of the Impact of Dynamic Analysis on Different Building Height
 
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
IRJET- Comparative Study on CFST and Steel Diagrid Structural System for High...
 
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
MODAL AND RESPONSE SPECTRUM (IS 18932002) ANALYSIS 0F R.C FRAME BUILDING (IT ...
 
Tallbuildings_2013.pdf
Tallbuildings_2013.pdfTallbuildings_2013.pdf
Tallbuildings_2013.pdf
 
Lf3519191924
Lf3519191924Lf3519191924
Lf3519191924
 
Iw3315041514
Iw3315041514Iw3315041514
Iw3315041514
 
Ojer 2013081311033759
Ojer 2013081311033759Ojer 2013081311033759
Ojer 2013081311033759
 
Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...
Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...
Design and Analysis of a Multistory Reinforced Concrete Frame in Different Se...
 
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
 
40. g+20
40. g+2040. g+20
40. g+20
 
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
 
Seismic Analysis of Multi Storied Irregular Building using Flat Slab and Gri...
Seismic Analysis of Multi Storied Irregular Building  using Flat Slab and Gri...Seismic Analysis of Multi Storied Irregular Building  using Flat Slab and Gri...
Seismic Analysis of Multi Storied Irregular Building using Flat Slab and Gri...
 
Earthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover AnalysisEarthquake Analysis of RCC structure by using Pushover Analysis
Earthquake Analysis of RCC structure by using Pushover Analysis
 
Study on the Effect of Response Spectrum Analysis and Construction Sequence A...
Study on the Effect of Response Spectrum Analysis and Construction Sequence A...Study on the Effect of Response Spectrum Analysis and Construction Sequence A...
Study on the Effect of Response Spectrum Analysis and Construction Sequence A...
 
Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...Inelastic seismic performance of low-rise multi-story structure in hilly area...
Inelastic seismic performance of low-rise multi-story structure in hilly area...
 
A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...
 
IRJET- Comparative Seismic Analysis of RC G+13 Multistorey Building Frame
IRJET-  	  Comparative Seismic Analysis of RC G+13 Multistorey Building FrameIRJET-  	  Comparative Seismic Analysis of RC G+13 Multistorey Building Frame
IRJET- Comparative Seismic Analysis of RC G+13 Multistorey Building Frame
 

More from Journal of Soft Computing in Civil Engineering

More from Journal of Soft Computing in Civil Engineering (11)

Fuzzy Vibration Suppression of a Smart Elastic Plate Using Graphical Computin...
Fuzzy Vibration Suppression of a Smart Elastic Plate Using Graphical Computin...Fuzzy Vibration Suppression of a Smart Elastic Plate Using Graphical Computin...
Fuzzy Vibration Suppression of a Smart Elastic Plate Using Graphical Computin...
 
Predicting Budget from Transportation Research Grant Description: An Explorat...
Predicting Budget from Transportation Research Grant Description: An Explorat...Predicting Budget from Transportation Research Grant Description: An Explorat...
Predicting Budget from Transportation Research Grant Description: An Explorat...
 
Artificial Neural Networks for Construction Management: A Review
Artificial Neural Networks for Construction Management: A ReviewArtificial Neural Networks for Construction Management: A Review
Artificial Neural Networks for Construction Management: A Review
 
Development of Intelligent Systems to Predict Diamond Wire Saw Performance
Development of Intelligent Systems to Predict Diamond Wire Saw PerformanceDevelopment of Intelligent Systems to Predict Diamond Wire Saw Performance
Development of Intelligent Systems to Predict Diamond Wire Saw Performance
 
Optimisation of Recycled Thermoplastic Plate (Tile)
Optimisation of Recycled Thermoplastic Plate (Tile)Optimisation of Recycled Thermoplastic Plate (Tile)
Optimisation of Recycled Thermoplastic Plate (Tile)
 
Calculation of Torsion Capacity of the Reinforced Concrete Beams Using Artifi...
Calculation of Torsion Capacity of the Reinforced Concrete Beams Using Artifi...Calculation of Torsion Capacity of the Reinforced Concrete Beams Using Artifi...
Calculation of Torsion Capacity of the Reinforced Concrete Beams Using Artifi...
 
A Method for Constructing Non-Isosceles Triangular Fuzzy Numbers Using Freque...
A Method for Constructing Non-Isosceles Triangular Fuzzy Numbers Using Freque...A Method for Constructing Non-Isosceles Triangular Fuzzy Numbers Using Freque...
A Method for Constructing Non-Isosceles Triangular Fuzzy Numbers Using Freque...
 
Using of Backpropagation Neural Network in Estimation of Compressive Strength...
Using of Backpropagation Neural Network in Estimation of Compressive Strength...Using of Backpropagation Neural Network in Estimation of Compressive Strength...
Using of Backpropagation Neural Network in Estimation of Compressive Strength...
 
No-Deposition Sediment Transport in Sewers Using Gene Expression Programming
No-Deposition Sediment Transport in Sewers Using Gene Expression ProgrammingNo-Deposition Sediment Transport in Sewers Using Gene Expression Programming
No-Deposition Sediment Transport in Sewers Using Gene Expression Programming
 
Comparison Study of Soft Computing Approaches for Estimation of the Non-Ducti...
Comparison Study of Soft Computing Approaches for Estimation of the Non-Ducti...Comparison Study of Soft Computing Approaches for Estimation of the Non-Ducti...
Comparison Study of Soft Computing Approaches for Estimation of the Non-Ducti...
 
Advanced ANN Prediction of Moisture Damage in CNT Modified Asphalt Binder
Advanced ANN Prediction of Moisture Damage in CNT Modified Asphalt BinderAdvanced ANN Prediction of Moisture Damage in CNT Modified Asphalt Binder
Advanced ANN Prediction of Moisture Damage in CNT Modified Asphalt Binder
 

Recently uploaded

Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 

Recently uploaded (20)

Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 

Seismic Analysis and Design of Multi-Storey Building in Saudi Arabia

  • 1. Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 How to cite this article: Ismaeil M, Elhadi Kh, Alashker Y, Yousef IE. Seismic analysis and design of a multi-storey building located in Haql city, KSA. J Soft Comput Civ Eng 2017;1(2):35–51. https://doi.org/10.22115/scce.2017.49083. 2588-2872/ © 2017 The Authors. Published by Pouyan Press. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/). Contents lists available at SCCE Journal of Soft Computing in Civil Engineering Journal homepage: www.jsoftcivil.com Seismic Analysis and Design of a Multi-Storey Building Located in Haql City, KSA M. Ismaeil1* , Kh. Elhadi2 , Y. Alashker2 , I.E. Yousef3 1. Assistant Professor, Department of Civil Engineering, King Khalid University, KSA. On leave from Sudan University for Science and Technology, Khartoum, Sudan 2. Assistant Professor, Department of Civil Engineering, King Khalid University, KSA. On leave from Structural Engineering Department, Zagazig University, Zagazige, Egypt 3. Lecturer, Department of Civil Engineering, King Khalid University, KSA Corresponding author: maibrahim@kku.edu.sa https://doi.org/10.22115/SCCE.2017.49083 ARTICLE INFO ABSTRACT Article history: Received: 29 July 2017 Revised: 02 August 2017 Accepted: 02 August 2017 Recently the design of RC building to mitigate seismic loads has received great attention. Since Saudi Arabia has low to moderate seismicity, most of the buildings were designed only for gravity load. The objective of this paper is to analysis design RC building located in the most active seismic zone region in Saudi Arabia to mitigate seismic loads. A multi-story reinforced concrete building, in Haql city, was seismically analyzed and designed using the Equivalent Lateral Force Procedure with the aid of SAP200 software. The chosen buildings which were Ordinary Moment Resisting Frame (OMR), was analyzed and designed by using SBC 301 (2007) Saudi Building Code [1], SAP2000 (structural analysis software) [2] and ISACOL "Information Systems Application on Reinforced Concrete Columns" [3]. The results showed that the current design of RC buildings located in the most active seismic zone region in Saudi Arabia, Haql city was found unsafe, inadequate and unsatisfied to mitigate seismic loads. Keywords: SAP2000; SBC 301 (2007); Active seismic zone region; Saudi Arabia; Equivalent static method; Seismic loads.
  • 2. 36 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 1. Introduction Haql is a town in the northwest of Saudi Arabia near the head of the Gulf of Aqaba, adjacent to Aqaba across the Jordanian border. The coasts of Egypt, Israel, and Jordan, can be seen from Haql. Haql city is located in the most active seismic zone region of the Kingdom of Saudi Arabia where there is a complicated geological structure and tectonics. This paper is an attempt to study the effect of seismic loads on RC residential buildings located in the most active seismic zone region of the Kingdom of Saudi Arabia. Saudi Arabia is not free from earthquakes. It has experienced many earthquakes during the recent history, and the previous studies in this field demonstrated this argument. Most of the existing buildings in Saudi Arabia do not meet the current design standards due to design shortage or construction shortcomings. The last major event was the 1995 Haql earthquake in the Gulf of Aqaba (magnitude 7.3) which caused significant damage on both sides of the Gulf and was felt hundreds of kilometers away. As far as Saudi Arabia is concerned, the most active area is along the Gulf of Aqaba (Dead Sea transform fault). On 19 May 2009, 19 earthquakes of M4.0 or greater took place in the volcanic area of Harrat Lunayyir to the north of Yanbu, including an M5.4 event that caused minor damage to structures [4]. The 1995 Gulf of Aqaba earthquake (also known as Nuweiba earthquake) occurred on November 22 at 06:15 local time (04:15 UTC) and registered 7.3 on the moment magnitude scale. The epicenter was located in the central segment of the Gulf of Aqaba. The earthquake occurred along the Dead Sea Transform (DST) fault system, an active tectonic plate boundary with seismicity that is characterized by long-running quiescent periods with occasional large and damaging earthquakes, along with intermittent earthquake swarms. It was the strongest tectonic event in the area for many decades and caused injuries, damage, and deaths throughout the Levant and is also thought to have remotely triggered a series of small to moderate earthquakes 500 kilometers (310 miles) to the north of the epicenter. In the aftermath of the quake, several field investigations set out to determine the extent of any surface faulting, and the distribution of aftershocks was analyzed. Areas affected: Egypt, Israel, Jordan and Saudi Arabia as shown in Figure 1[4]. Recent studies, historical evidence, geological and geophysical observations indicate that parts of the Kingdom fall within seismic risk regions. In western Saudi Arabia, a design peak ground acceleration (PGA) ranging from 0.03g to 0.26g for an economic life of 50 years was suggested. Seismic zonation was established with zone numbers 0, 1, 2A, and 2B [5]. Saudi Arabia is not free from earthquakes. It has experienced many earthquakes during the recent history, and the previous studies in this field demonstrated this argument. Most of the existing buildings in Saudi Arabia do not meet the current design standards due to design shortage or construction shortcomings. Therefore, buildings should be designed regarding their capacity for resisting the expected seismic effects. The seismic hazard analysis for the Kingdom was performed [6,7]. Seismograph stations of the Saudi National Seismic Network as shown in Figure 2 [8], was developed for the Kingdom based on the peak ground acceleration, PGA, values calculated for 50 years service lifetime with 10% probability of being exceeded.
  • 3. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 37 Fig. 1. 1995 Gulf of Aqaba earthquake [4]. Fig. 2. Seismograph stations of the Saudi National Seismic Network [8]. 2. Description and Model of the Building A six-story residential building with plan and elevations as shown in Figures 3 to 6 is considered for the study. The building is composed of moment resisting RC frame with solid slab, 140mm thickness, situated in the most active seismic zone region of the Kingdom of Saudi Arabia. The structure members are made of in-situ reinforced concrete. The overall plan of the building is square with dimensions 14.5x15m as shown in Figure 3. The height of the building is 16 m, and story height for each floor is 3.2 m. Columns and beams sizes are shown in Table 1. The building is approximately symmetric in both directions. The plan and some frames of the studied building as shown in Figures 3 to 5. Beams and columns have been modeled as frame elements while the in-plane rigidity of the slab is simulated using rigid diaphragm action. The columns are assumed to be fixed at the base. The building is analyzed. As per seismic provisions provided by SBC 301-2007.
  • 4. 38 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 Table 1 The cross-section of beams and columns. Building Beams Level Columns Reinforcement mm mm 6 Stories 600*250 1st floor -2nd floor 600*250 12 Φ 16 (10 Φ 16) 3nd floor-4rd floor 500*250 10 Φ 16 5th floor 5th floor 450*250 10 Φ 16 Fig. 3. Architectural plan of the studied building. Fig. 4. YZ elevation @ X=5.5 m of the studied building.
  • 5. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 39 Fig. 5. XZ elevation @ Y=9.5 m of the studied building. Fig. 6. XY Plan of studied building. 3. Current Design It is a common practice in The Kingdom of Saudi Arabia to design buildings without any consideration of seismic loads. Therefore, the one typical case study has been studied first under the effect of gravity loads and without consideration of seismic loads in order to check the current design. Dead and live loads are following the equations and tables given in the SBC-301- 2007(Saudi Arabia) and second under the effect of seismic loads. 4. Modeling and Analysis of RC Residential Buildings due to Earthquake Loads (Equivalent Static Method as per SBC-303-2007) Most buildings and structures in the kingdom of Saudi Arabia have not yet been designed and constructed in compliance with earthquake provisions or given any consideration for earthquake effect.
  • 6. 40 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 The horizontal seismic loads are defined according to Saudi Buildings Code (SBC-303-2007). The lateral force effect on the structure can be translated to equivalent lateral force at the base of the structure which can be distributed to different stories. According to Saudi Buildings Code (SBC-303-2007), the total seismic base shear force V is determined as follows: V = Cs*W )1( Where: Cs is the seismic coefficient, W is the total weight and V is the base shear. The seismic design coefficient (Cs) shall be determined by the following equation: Cs = SDS / (R / I) )2( Where SDS = Design spectral response acceleration in the short period range R = Response modification factor I = Occupancy importance factor determined The value of the seismic response coefficient, (Cs), need not be greater than the following equation: Cs = SD1 / [T. (R / I)] )3( However, shall not be taken less than: T = 0.1N )4( Where N = Number of stories Cs = 0.044SDS I )5( Where, SDS = Design spectral response acceleration at a period of 1 sec T = Fundamental period of the structure (sec) Design earthquake spectral response acceleration at short periods, SDS, and at the 1-sec period, SD1, shall be as follows. SMS= Fa*SS )6( SM1= Fv*S1 )7( SDS= 2/3*SMS )8( SD1= 2/3*SM1 )9( Where: SS: the maximum spectral response acceleration at short periods S1: the maximum spectral response acceleration at a period of 1 sec Fa: acceleration-based site coefficient
  • 7. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 41 Fv: velocity-based site coefficient SMS: the maximum spectral response acceleration at short periods adjusted for site class SM1: the maximum spectral response acceleration at a period of 1 sec adjusted for site class SDS: the design spectral response acceleration at short periods SD1: the design spectral response acceleration at a period of 1 sec 5. Vertical Distribution of Base Force The buildings are subjected to a lateral load distributed across the height of the buildings based on the following formula specified by Saudi Buildings Code (SBC-303-2007): Where Fx is the applied lateral force at level ‘x’, W is the story weight, h is the story height, and V is the design base shear, and N is the number of stories. The summation in the denominator is carried through all story levels. This results in an inverted triangular distribution when k is set equal to unity. A uniform lateral load distribution consisting of forces that are proportional to the story masses at each story level. k = an exponent related to the structure period as follows: For structures having a period of 0.5 sec or less, k = 1 For structures having a period of 2.5 sec or more, k= 2 6. LOAD COMBINATIONS AS PER SBC-303-2007 As per SBC-301 section 2.3, following load combinations should be considered for the design of structures, components, and foundations. 1.4 (D + F) 1.2 (D + F + T) + 1.6 (L + H) + 0.5 (Lr or R) 1.2 D + 1.6 (Lr) + (f1L) 1.2D + f1L + 0.5 (Lr) 1.2D + 1.0 E + f1L 0.9D ± 1.0E Where: E = ρQE + 0.2SDSD 1.0 ≤ ρ ≤ 1.5 f1 = 1.0 for areas occupied as places of public assembly, for live loads more than 5.0 kN/m2, and for parking garage live load.
  • 8. 42 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 f1 = 0.5 for other live loads. SDS = the design spectral response acceleration in the short period range as determined from Section. QE = the effect of horizontal seismic (earthquake-induced) forces. Table 6.1 shows the design parameters taken from both codes for analysis of buildings. 7. Seismic Map for the Kingdom of Saudi Arabia The Saudi Buildings Code (SBC-303-2007) provides seismic maps for the Kingdom of Saudi Buildings, as shown in Figures 7 and 8. Fig. 7. Maximum Considered Earthquake Ground Motion for the Kingdom of 1 SEC Spectral Response Acceleration (S1 in %g) (5 Percent of Critical Damping), Site Class B. (Region 1) [1]. Fig. 8. Maximum Considered Earthquake Ground Motion for the Kingdom of 0.2 SEC Spectral Response Acceleration (Ss in %g) (5 Percent of Critical Damping), Site Class B. (Region 1) [1].
  • 9. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 43 8. Mapped acceleration parameters The design parameters that are used in the equivalent static method are illustrated as follows: The parameters Ss and S1 shall be determined from the 0.2 and 1-second spectral response accelerations shown on country maps Where S1 is less than or equal to 0.04 and Ss is less than or equal 0.15, the structure is permitted to be assigned to seismic design category A So, S1= the mapped spectral accelerations for a 1- second period Ss= the mapped spectral accelerations for a short period.  On lack of a map of spectral accelerations of S1 and SS, the following can be assumed: S1= 1.25 Z, Ss= 2.5 Z (amendment no. 3 to SI 413 (2009)) or from maps as shown in Figures 7 and 8. 9. The Results and Discussions Figures 9 and 10 show the label of columns and beams of the selected frames. Fig. 9. The label of beams and columns in direction XZ@Y=9.5 m.
  • 10. 44 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 Fig. 10. The label of beams and columns in direction YZ@X= 5.5 m. 9.1. Results of analysis of considered buildings due to gravity loads This part presents the results of analysis and design of considered RC buildings due to gravity loads. We selected one frame in each direction X and Y as shown in figures 9 and 10 for columns and beams. 1. Beams Table 2 shows the Straining action of some beams in the selected frames at direction YZ @ X = 5.5 Table 2 The Straining action of some beams in the selected frames at direction YZ @ X = 5.5. Direction Y-Z @ X=5.5 Load Case Ultimate (1.4DL+1.6LL) Beam No. SHEAR MOMENT 3-3 (KN.m) KN END START B-03 -9.81 0.24 -6,81 B-09 21.7 -29.54 -1.62 B-11 -11.91 4.5 -10.15 B-17 21.42 -29.11 -1.61 B-19 -13.16 7.37 -12.3
  • 11. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 45 2. Columns Tables 3 shows the Straining action of some columns in the selected frames at direction YZ @ X = 5.5 Table 3 The Straining action of some columns in the selected frames at direction YZ @ X = 5.5. Direction Y-Z @ X=5.5 Load Case Ultimate (1.4DL+1.6LL) Column No. AXIAL SHEAR MOMENT 3-3 (KN.m) KN END START C-01 -907.8 -0.61 -0.62 -2.57 C-03 -1307.75 -10.94 21.51 -13.51 C-09 -586.33 0.56 -1.46 -0.33 C-11 -855.93 -15.98 26.44 -24.68 C-17 -285.18 0.63 -1.17 0.84 C-19 -421.77 -11.1 18.29 -17.22 9.2. Results of analysis of considered buildings due to seismic loads This part presents the results of analysis and design of considered RC buildings due to seismic loads. Using the Saudi Buildings Code (SBC-301-2007) provisions, the following parameters have been calculated to be used as input data for seismic analysis of the selected model with notice that the Haql City falls in region 6. The calculated results of these parameters are as follows: Table 4 The seismic parameter for Haql City according to SBC301. SDS 0.14 CS = 0.0714 SD1 0.04 CS (max.) = 0.0678 I 1.00 CS(min.) = 0.0057 R 2.00 W= 812.0 KN V= 55.1 TON Take CS= 0.678 Table 5 Calculation of Base Shear and lateral load distribution with height. Story W (ton) h (m) w*h cv Fx (TON) Sixth Floor 16.66 21 350 0.015 0.9 Fifth Floor 142.67 18 2568 0.114 6.3 Fourth Floor 268.69 15 4030 0.179 9.8 Third Floor 394.70 12 4736 0.210 11.6 Second Floor 520.72 9 4686 0.208 11.4 First Floor 646.73 6 3880 0.172 9.5 Ground Floor 772.75 3 2318 0.103 5.7 SUM(W*H) 22570 SUM FX 55.1
  • 12. 46 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 1. Beams Tables 6 shows the Straining action of some beams in the selected frames at direction YZ @ X = 5.5 m due to load case Group-Y Table 6 The Straining action of some beams in the selected frames at direction YZ @ X = 5.5 m due to load case Group-Y. Direction Y-Z @ X=5.5 m Load case: GroupY Beam No. SHEAR MOMENT 3-3 (KN.m) KN END START B-03 53.39 -93.73 90.13 B-09 22.07 -30.12 -1.65 B-11 49.02 -86.03 82.88 B-17 21.78 -29.68 -1.64 B-19 32.05 -52.51 49.84 Where: Load Case Group-Y is load combination included seismic loads at Y direction. Load Case Ultimate is load combination included dead and live loads only 2. Columns Tables 7 shows the Straining action of some columns in the selected frames at direction YZ @ X = 5.5 m Table 7 The Straining action of some Columns in the selected frames at direction YZ @ X = 5.5 m due to load case Group-Y. Direction Y-Z @ X=5.5 Load Case: GroupY Column No. AXIAL SHEAR MOMENT 3-3 (KN.m) KN END START C-01 -922.95 1.23 -2.68 -2.62 C-03 -1331.32 -11.18 21.93 -13.8 C-09 -596.12 1.74 -3.28 2.3 C-11 -871.43 -18.32 27.01 -25.21 C-17 -289.96 0.74 -1.33 1.04 C-19 -429.44 -11.33 18.68 -17.59 10. Design of structural elements against gravity loads The reinforced concrete sections were designed according to the BSI 8110 [9] using the limit state design method (Mosley and Bungey, 1997) [10].
  • 13. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 47 10.1. Design of columns (a) Calculation of internal forces in columns The columns were designed to resist axial compression forces and bending moment due to gravity load. The design forces in columns obtained from the computer analysis program SAP2000 are shown in Table 8. *Direction YZ@X=5.5 Table 8 Internal forces in columns due to gravity loads. Column No. Output Case Shear Force (KN) Bending Moment (KN.m) Axial Force (KN) C04 1.4DL+1.6LL 11.26 13.99 1372.02 C03 1.4DL+1.6LL 10.94 13.51 1307.75 C02 1.4DL+1.6LL 1.64 3.78 997.52 C01 1.4DL+1.6LL -0.61 2.57 907.80 (b) Design of columns before adding seismic loads * Direction YX@X=5.5 The design of columns has been performed using a computer program called ISACOL [5]. Figures 11 and 13 show the main window of ISACOL program and sample of column design. Fig. 11. ISACOL program results for C40 [3].
  • 14. 48 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 Table 9 Design of columns before adding seismic Loads. Column No. Original design Present design Dimensions Reinforcement Dimensions Reinforcement C04 250 X 500 12 Φ 16 250 X 500 10 Φ 16 C03 250 X 500 12 Φ 16 250 X 500 10 Φ 16 C02 250 X 500 12 Φ 16 250 X 500 10 Φ 16 C01 250 X 500 12 Φ 16 250 X 500 10 Φ 16 250*500 250*500 12 Φ 16 10 Φ 16 Fig. 12. Design of some columns before adding seismic Loads. 10.2. Design of beams As for the beams, the internal forces due to gravity loads have been calculated first. Then the BSI [9], has been used to check the existing design. It has been found that the existing design is adequate. 11. Design of structural elements against gravity loads and earthquake loads The reinforced concrete sections were designed according to the BSI 8110 [9] using the limit state design method (Mosley and Bungey, 1997) [10]. 11.1. Design of columns (a) Calculation of internal forces in columns The columns were designed to resist seismic and gravity load. The design forces in columns obtained from the computer analysis program SAP2000 are shown in Table 10. * Direction YZ@X=5.5 m Table 10 Internal forces in columns due to seismic loads. Column No. Output Case Shear Force (KN) Bending Moment (KN.m) Axial Force (KN) C04 GROUPX 159.27 298.95 1397.14 C03 GROUPX 137.69 256.36 1331.32 C02 GROUPX 125.60 223.55 1041.80 C01 GROUPX 96.96 173.70 922.95
  • 15. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 49 (b) Design of columns after adding seismic loads The design of columns has been performed using a computer program called ISACOL [3]. Figures 12 and 14 show the design of some columns before and after adding seismic loads. Fig. 13. ISACOL program results for C04 [3]. Table 11. Shows the design of columns after adding seismic loads. Table 11 Design of columns after adding seismic loads-direction (y). Column No. Original design Including seismic loads Dimensions Reinforcement Dimensions Reinforcement C04 250 X 500 10 Φ 16 250*1550 18 Φ 20 C03 250 X 500 10 Φ 16 250*1250 14 Φ 20 C02 250 X 500 10 Φ 16 250*1200 14 Φ 20 C01 250 X 500 10 Φ 16 250*850 12 Φ 20 250*1200 250*850 14 Φ 20 12 Φ 20 Fig.14. Design of some columns after adding seismic loads
  • 16. 50 M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 12. Conclusion This paper provides a set of seismic analysis and design of RC buildings located in the most active seismic zone region in Saudi Arabia. The building was analyzed and designed before and after considering earthquake loads applied in two directions; XX and YY. From the results obtained it can be seen that: 1. There are slight changes in the values of the bending moments and shear forces on the beams before and after considering earthquake loads as shown in Tables 2 and 6. There is an increase in some internal beams, such as B-3, B-11, and B-19. 2. The values of the bending moments and shear forces on the columns due to seismic loads are nearly five times that due to gravity loads as shown in Tables 8 and 10. 3. The values of the axial forces on the columns due to seismic loads are approximately similar to gravity loads as shown in Tables 8 and 10. 4. As an overall trend the results showed that the current design of RC buildings located in the most active seismic zone region of the Kingdom of Saudi Arabia, Haql city were found unsafe, inadequate and unsatisfied to mitigate seismic loads. The present study represents the first attempt to investigate the seismic resistance of residual buildings in Haql city in Saudi Arabia. Due to the lack of knowledge about the seismic activity in this country some buildings are designed and constructed without any seismic load consideration. Seismicity of Saudi Arabia may be considered as moderate. Hence, all buildings should be checked against earthquake resistance. The present paper proposes a simple procedure to check the seismic resistance of such buildings. The obtained results emphasize the following conclusions: 1- Current design of some residual buildings in Saudi Arabia does not consider earthquake loads. 2- It has been found that the current design of residual buildings in the Haql city is unsafe for the current seismicity of the Haql city. Acknowledgments The author would like to express his gratitude to King Khalid University, Saudi Arabia for providing administrative and technical support. References [1] Saudi Building Code SBC-301-2007: Loads and Forces Requirements, Saudi Buildings Code National Committee. 2007. [2] Wilson EL. Three-dimensional static and dynamic analysis of structures. Computers and Structures Inc., Berkeley, California, U.S.A: Computers and structures; 2002.
  • 17. M. Ismaeil et al./ Journal of Soft Computing in Civil Engineering 1-2 (2017) 35-51 51 [3] Shehata AY. Information Systems Application on Reinforced Concrete Columns. M. Sc. Thesis, Faculty of Engineering, Department of Structural Engineering, Cairo University, Giza, Egypt, 1999. [4] https://en.wikipedia.org/wiki/1995_Gulf_of_Aqaba_earthquake n.d. [5] Attar MS. Evaluation of the Seismic Performance of A Typical School Building. Master Thesis, College of Engineering, KAAU, 2003. [6] Al-Haddad M, Siddiqi GS, Al-Zaid R, Arafah A, Necioglu A, Turkelli N. A Study Leading to a Preliminary Seismic Design Criteria, for the Kingdom. Final Report, KACST Proj No AR-9-31, Riyadh 1992. [7] Al-Haddad M, Siddiqi GH, Al-Zaid R, Arafah A, Necioglu A, Turkelli N. A basis for evaluation of seismic hazard and design criteria for Saudi Arabia. Earthq Spectra 1994;10:231–58. [8] Hassaballa AE, Adam FM, Ismaeil MA. Seismic Analysis of a Ten-Storey Reinforced Concrete Building in Jazan Area, KSA. Open J Civ Eng 2017;07:252–66. doi:10.4236/ojce.2017.72016. [9] BS8110. Structural Use of Concrete,. British Standard Institution, London: 1997. [10] Mosley WH, Bungey JH. Reinforced Concrete Design; BS 8110:Part 1, 2nd Ed. Macmillan , London: 1997.