IJRET : International Journal of Research in Engineering and Technology is an international peer reviewed, online journal published by eSAT Publishing House for the enhancement of research in various disciplines of Engineering and Technology. The aim and scope of the journal is to provide an academic medium and an important reference for the advancement and dissemination of research results that support high-level learning, teaching and research in the fields of Engineering and Technology. We bring together Scientists, Academician, Field Engineers, Scholars and Students of related fields of Engineering and Technology
Design evaluation and optimization of steering yoke of an automobile
Similar to Effect of approching temperature on the performance and size of li br water vapour absorption refrigeration in the absence of solution heat exchanger
Similar to Effect of approching temperature on the performance and size of li br water vapour absorption refrigeration in the absence of solution heat exchanger (20)
Effect of approching temperature on the performance and size of li br water vapour absorption refrigeration in the absence of solution heat exchanger
1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 704
EFFECT OF APPROCHING TEMPERATURE ON THE PERFORMANCE AND SIZE OF LiBr-WATER VAPOUR ABSORPTION REFRIGERATION IN THE ABSENCE OF SOLUTION HEAT EXCHANGER Sunil.B.S1, Manu S2, C.V.Mahesh3, T.K.Chandrashekar4 1 M.Tech, 4th sem Mechanical Engineering, SSIT, Tumkur. 2Assistant Professor, Department of Mechanical Engineering, SSIT, Tumkur 3Professor, Department of Mechanical Engineering, SSIT, Tumkur 4Professor, Department of Mechanical Engineering, MIT, Moodabidri Abstract In this study, a detailed thermodynamic analysis of the water/lithium bromide absorption refrigeration cycle is performed. The influences of approaching temperatures, conductance and coefficients of performance are investigated. Plots of coefficients of performance and conductance are shown against approaching temperatures of the system. It is concluded that the performance and conductance decreases with increase in approaching temperature of all the components. Keywords: Refrigeration, Absorption, Water/Lithium bromide.
----------------------------------------------------------------------***------------------------------------------------------------------------ 1. INTRODUCTION During the recent years research has attempted to develop new technologies that can reduces energy consumption and cost without decreasing the level of comforts. By this reason absorption refrigeration technologies has greater advantages compared to conventional refrigeration systems because the system utilises waste heat and it is friendly with environment. Among different combination of refrigerant and absorbent, Lithium Bromide –Water (LiBr-H2O) showed the promising solution for effective ultisation of waste heat and zero determental effect on the atmospher since it uses water has refrigerant and Lithium-Bromide solution as absorbent
Number of research has been carried out to enhance the performance of the system and reduce the size of the system. A.Kececiler et al. [1] conducted experiments in laboratory on LiBr H2O system which uses low temperature geothermal energy as a powering source. The result showed that, low-heat geothermal sources cannot be used efficiently in electricity generation and effective for the storing range at 4-10ºC. Da- Wen Sun [2] performed simulation on LiBr H2O absorption refrigeration systems. The simulation provides the detailed thermodynamic design data and optimum design map and also for new absorbent/refrigeration pairs. O. Kaynakli et al. [3] investigated the effect of operating temperature on the performance of single effect LiBr H2O absorption refrigeration cycle. The result showed that as the generator and evaporator temperature increases there is a drastic increase of COP (Coefficient of Performance) but decreases with rise of condenser and absorber temperatures. M. Izquierdo et al. [4] performed trials to investigate the performance of a commercial 4.5 kW air cooled, single effect LiBr H2O absorption chillier which is used for residential. The result showed as the cooling power tends to decreases with increase of outdoor dry bulb temperature and for the temperature ranges of 35 to 41.3ºC but the chilled water outlet temperature of evaporator peaks to 15ºC. Mostafavi and Agnew [5] investigated the effect of ambient temperature on the surface area of the component of an air-cooled absorption machine. The objective of the study to investigate the effect of approaching temperature on the performance of single stage water cooled LiBr–water absorption machine. The theoretical simulation is performed using MAT lab Software for the capacity of 0.5kW. 1.1 Approaching Temperature The approaching temperature refers to the maximum heat transfer for hot body to the cold body. If the approaching temperature is less then greater is the heat transfer. This approaching temperature play key role on the performance of the system because the system is cooled by the water and refrigeration effect is aborbed by the chilled water. There are mainly four approaching temperatures comes in the system and they are as follows:-Approaching absorber temperature (DTa). It is the temperature difference between T12 and T15, Approaching evaporator temperature (DTe), It is the temperature difference between T16and T1, Approaching generator temperature (DTg), It is the temperature difference between T10 and T7.Approaching Condenser temperature (DTc), It is the temperature difference between T14 and T13.
2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 705
1.2 Circulation Ratio
The circulation ratio (CR) can be defined as the ratio of the
mass flow rate of the solution coming from the generator to
the absorber to the mass flow rate of the working fluid.
CR =
m s
mH 2o
2. VAPOUR ABSORPTION REFRIGERATION
(VAR) SYSTEM
.
Fig-1: Schematic diagram of LiBr-H2O vapour absorption
refrigeration cycle
The refrigerant is vaporized in the evaporator after taking heat
from the water. It is then sent to the absorber where the
refrigerant vapours get condensed. During the process, latent
heat liberated during condensation of refrigerant vapours is
taken by the cooling water in absorber. The weak solution
coming from absorber and rich in refrigerant concentration is
pressurized through pump upto generator pressure where it is
heated to give off refrigerant vapour, forming strong
concentration refrigerant solution. This strong concentration
refrigerant solution then returns to absorber and mixes with
refrigerant vapours coming from evaporator, forming a strong
concentration refrigerant solution which is then re-circulated
in the circuit. The refrigerant vapours are condensed in the
condenser liberating heat of condensation. Throttle valve and
expansion valve are used to reduce the pressure of poor
concentration refrigerant solution and refrigerant coming out
from condenser to absorber and evaporator pressure
respectively. The heat is supplied to the generator by hot
water. The heat rejected in the condenser is passed to the
circulating cold water.
3. RESULTS AND DISCUSSION
3.1 Effect of Approaching Condenser Temperature
Fig-2(a) and (b) shows the variation of condenser approaching
temperature on the performance of the system and the
conductance. The simulation was performed by varying
condenser approaching temperatures for
DTa=DTg=DTe=5°C. The Fig 2(a), (b) shows an approaching
temperature of condenser increases there is a decrease in the
performance and conductance of the condenser. This is due to
decrease in the heat transfer rate to the cooling water resulting
in decrease in the condensate rate this reduces the performance
of the system. Decreasing in the conductance of the condenser
is due increase in the condenser temperature.
0 1 2 3 4 5
0.46
0.48
0.50
0.52
0.54
0.56
0.58
0.60
0.62
0.64
0.66
Performance
Approach Condenser Temperature (DTc) (
O
C)
COP
Fig-2(a): Condenser approaching temperature
Vs. Variation of performance
0 1 2 3 4 5
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
Conductance (W K
-1
)
Approach Condenser Temperature (DTc) (
O
C)
UAa
UAc
UAe
UAg
Fig- 2(b): Condenser approaching
temperature Vs. Conductance
3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 706
3.2 Effect of Approaching Evaporator Temperature
Fig-3(a) and (b) shows the variation of evaporator
approaching temperature on the performance of the system
and the conductance. The simulation was performed by
varying evaporator approaching temperatures for
DTa=DTg=DTc=5°C.The Fig-3(a) and (b) shows an
approaching temperature of evaporator increases there is a
decrease in the performance and conductance of the
evaporator. This is due to decrease in the heat transfer rate to
the water resulting in decrease in the evaporation rate of
refrigerant resulted in reduction in the performance of the
system. Decreasing in the conductance of the evaporator is
due increase in the evaporator temperature.
3.3 Effect of Approaching Generator Temperature
Fig-4(a) and (b) shows the variation of generator approaching
temperature on the performance of the system and the
conductance. The simulation was performed by varying
generator approaching temperatures for DTa=DTe=DTc=5°C.
The Fig 4(a) and (b) shows an approaching temperature of
generator increases there is a decrease in the performance and
conductance of the generator. This is due to decrease in the
heat transfer rate to the cooling water resulting in decrease in
the generation rate of refrigerant this reduces the performance
of the system. There is a drastic decreasing in the conductance
of the generator is due increase in the generator temperature.
3.4 Effect of Approaching Absorber Temperature
Fig-4(a) and (b) shows the variation of absorber approaching
temperature on the performance of the system and the
conductance. The simulation was performed by varying
absorber approaching temperatures for DTe=DTg=DTc=5°C.
The Fig 4(a) and (b) shows an approaching temperature of
absorber increases there is a decrease in the performance and
conductance of the absorber. This is due to decrease in the
heat transfer rate to the cooling water resulting in decrease in
the circulation rate this reduces the performance of the system.
Fig-4(a): Generator approaching temperature Vs.
Variation of performance
0 1 2 3 4 5
0.778
0.780
0.782
0.784
0.786
Perforrmance
Approach Generator Temperature (DTg) (
O
C)
COP
0 1 2 3 4 5
0.65
0.70
0.75
0.80
0.85
Perforrmance
Approach Evaporator Temperature (DTe) (
O
C)
COP
Fig-3(a): Evaporator approaching temperature
Vs. Variation of performance
0 1 2 3 4 5
0.2
0.4
0.6
0.8
1.0
1.2
Conductance (W K
-1
)
Approach Evaporator Temperature (DTe) (
O
C)
UAa
UAc
UAe
UAg
Fig- 3(b): Evaporator approaching temperature
Vs. Conductance
Fig- 4(b): Generator approaching temperature
Vs. Conductance
0 1 2 3 4 5
0
1
2
3
4
5
6
Conductance (W K
-1
)
Approach Generator Temperature (DTg) (
O
C)
UAa
UAc
UAe
UAg
4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
__________________________________________________________________________________________
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 707
There is a low decreasing in the conductance of the absorber is
due increase in the absorber temperature.
4. CONCLUSIONS
The theoretical simulation was performed on single effect
water cooled vapour absorption refrigeration. The simulation
is carried on MAT Lab software by varying approaching
temperature. The paper concludes that as approaching
temperature increases in condenser, evaporator, absorber,
generator there is a decrease in the performance and
conductance.
REFERENCES
[1] Kececiler, A., H.I. Acar, and A. Dogan,
Thermodynamic analysis of the absorption refrigeration
system with geothermal energy: an experimental study.
Energy Conversion and Management, 41(1): p. 37-48,
2000.
[2] Sun, D.-W., Thermodynamic design data and optimum
design maps for absorption refrigeration systems.
Applied Thermal Engineering, 17(3): p. 211-221, 1997.
[3] Kaynakli, O. and M. Kilic, Theoretical study on the
effect of operating conditions on performance of
absorption refrigeration system. Energy Conversion
and Management, 48(2): p. 599-607, 2007.
[4] Izquierdo, M., et al., Air conditioning using an air-cooled
single effect lithium bromide absorption chiller:
Results of a trial conducted in Madrid in August 2005.
Applied Thermal Engineering, 28(8-9): p. 1074-1081,
2008.
[5] T Mostafavi, M. and B. Agnew, The impact of
ambient temperature on lithium-bromide/water
absorption machine performance. Applied Thermal
Engineering, 16(6): p. 515-522, 1996.
0 1 2 3 4 5
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
Conductance (W K
-1
)
Approach Absorber Temperature (DTa) (
O
C)
UAa
UAc
UAe
UAg
Fig- 5 (b): Absorber approaching temperature Vs.
Conductance
0 1 2 3 4 5
0.775
0.780
0.785
0.790
0.795
0.800
0.805
0.810
0.815
Performance
Approach Absorber Temperature (DTa) (
O
C)
COP
Fig-5(a): Absorber approaching temperature Vs.
Variation of performance
(DTg=DTe=DTc=5°C)