INERGEN is a mixture of nitrogen, argon and carbon dioxide, and has been specially developed to provide fire protection for sensitive electrical and electronic instruments and equipment.
How does INERGEN work?
INERGEN extinguishes fire by reducing the oxygen level in a room to below 15% (the point at which most combustibles will no longer burn). Simultaneously the patented carbon dioxide in INERGEN protects anyone that may be trapped in the fire area from the effects of the lowered oxygen levels.
Gas suppression systems are extensively used in electronic data protection and electrical system switch environments. Systems comprise electrical detection linked to a bank of cylinders where the gas is stored ready for discharge into the fire area.
2. Overview
• Cylinder assy. with CI 12-9 valve
• PRU 300/200 and discharge hose
• Manifold & high pressure fittings
• Fixing components
• Distribution valves
• PRU 200/60
• Nozzles
• Actuation accessories
• Other accessories
Mail: info@gielle.it - Website: www.gielle.it
3. System Setup "Orifice"
Single Hazard
150/200 bar system
300 bar
150 / 200 bar
<200 bar
300 bar system
Mail: info@gielle.it - Website: www.gielle.it
4. System Setup "Orifice"
Multiple Hazards
150/200 bar system
Pressure reducing unit
(orifice)
300 bar
150 / 200 bar
300 bar system <200 bar
Mail: info@gielle.it - Website: www.gielle.it
5. System Setup "Constant Flow"
DRV Flow Regulator
200 or 300 bar system
200 / 300 bar
max. 60 bar
200 or 300 bar system
Seperate Presentation
Mail: info@gielle.it - Website: www.gielle.it
6. Pilot Cylinder Assembly
• Container sizes: 8/27/80 litre
• Filling: 200 bar Inergen
• Approval: TPED (pi-marked)
• Assembly consists of
– container c/w transport cap
– CI 12-6 valve assembly
– container label Inergen
200 bar
Mail: info@gielle.it - Website: www.gielle.it
7. Container Valve CI 12-6
Functional description: pilot cylinder (200 bar)
inlet agent container
Mail: info@gielle.it - Website: www.gielle.it
8. Agent Container Assembly
• Container size: 80 litre
• Filling: 23.6 m³ (33.5 kg)
Inergen @ 300 bar
• Approval: TPED (pi-marked)
• Assembly consists of
– container c/w transport cap
– CI 12-9 valve assembly Inergen
– container label 300 bar
Container = grey
Mail: info@gielle.it - Website: www.gielle.it
9. Container Valve CI 12-8
• Type: CI 12-8
• Nominal Ø: 12 mm
• Max. operating pressure: 360 bar
• Release (membrane)
– electric
– pneumatic p e CI 12-9
– manual Valve rep laced by ty
• Bursting disc
– @ 65°C 420 bar +30 / -10 bar
– @ 20°C 450 bar maximum
Mail: info@gielle.it - Website: www.gielle.it
10. Container Valve CI 12-8
Functional description: agent container
pressure from pilot cylinder
type CI 12-9
Valve re placed by
inlet agent container
Mail: info@gielle.it - Website: www.gielle.it
11. Pressure Reducing Unit
• PRU 300/200
• Type: DRE-V/S for valve CI 12-8
• Pressure reduction from 300 bar to
200 bar direct at the valve outlet
Orifice plate
Diameters 3-9 mm
(in steps of 0.5 mm)
Mail: info@gielle.it - Website: www.gielle.it
12. Container Valve CI 12-9
• Type: CI 12-9
• Nominal Ø: 12 mm
• valve outlet is female thread
• Max. operating pressure: 360 bar
• Release (no membrane)
– pneumatic (pilot cylinder)
• Bursting disc
– @ 65°C 420 bar +30 / -10 bar
– @ 20°C 450 bar maximum
Mail: info@gielle.it - Website: www.gielle.it
13. Pressure Reducing Unit
• PRU 300/200
• Type: DRE-V/S II for valve CI 12-9
• Pressure reduction from 300 bar to
200 bar direct at the valve outlet
Orifice plate
Diameters 3-9 mm
(in steps of 0.5 mm)
Mail: info@gielle.it - Website: www.gielle.it
16. Discharge Hose
• DN 12 / 300 bar
• Minimum bend radius: 150 mm
• Both ends with swivel nut and pre-installed o-rings
• Installation in any orientation.
Mail: info@gielle.it - Website: www.gielle.it
17. Release Head AK III
• Puncture pin to open
release membrane
Puncture pin
Mail: info@gielle.it - Website: www.gielle.it
18. Solenoid Actuator
• Standard actuator SF-2 Indicator
• 24 V DC / 15 W
• IP 65
• Swivel nut fits onto release
head III
• The power lead fitted with
a DIN plug for connection
to the solenoid is supplied
with the solenoid actuator.
Mail: info@gielle.it - Website: www.gielle.it
19. Solenoid Actuator
• Explosion proof type
• EEx me II T4
• 24 V DC / 9 W
• IP 65
• Swivel nut fits onto release
head III
• The power lead fitted with
a DIN plug for connection
to the solenoid is supplied
with the solenoid actuator.
Mail: info@gielle.it - Website: www.gielle.it
20. Solenoid Actuator
Solenoid actuator
Solenoid actuator
Release head
AK III
Release head AK III Container valve
CI 12-6 (12-8)
Mail: info@gielle.it - Website: www.gielle.it
21. Step Motor Actuator
• Step motor delay device SM V-1
• TWF impulse technology
• 24 V DC / 15 W
• IP 54
• At present this technology is
only suitable for use with the
“Fast 2000” control panel range.
Mail: info@gielle.it - Website: www.gielle.it
22. Actuator Resetting Tool
• Used to reset both the
standard (SF-2) and the
explosion proof solenoid
actuator
• The tool is supplied with
the actuator.
Mail: info@gielle.it - Website: www.gielle.it
23. Local Manual Actuator
• Used to manually
operate the pilot cylinder
• fitted on top of the
release head III
Manual actuator
Release head III
Mail: info@gielle.it - Website: www.gielle.it
24. Pneumatic Actuator PAK
• Used in the twin release assembly
• installed between the release
head AK III and the electric
actuating device
Mail: info@gielle.it - Website: www.gielle.it
25. Twin Release
• Combination of electric
and pneumatic release
for the pilot cylinder
valve
• normal: both valves
activated electrically PAK
• fault on one electric
AK III
actuator: both pilot
cylinders still opend
Mail: info@gielle.it - Website: www.gielle.it
30. Container Fixing
Retention bar
• anchored to the wall
• 2 containers / 560 mm
• 3 containers / 840 mm
Mail: info@gielle.it - Website: www.gielle.it
31. Container Fixing
Free standing post
• used when there is
no wall to fix the
retention bar
• one post at each
end of the retention
bar(s) retention bar
Mail: info@gielle.it - Website: www.gielle.it
32. Manifold Fixing
Manifold bracket
• bolted to the
retention bar
• basis for the
manifold, which
is clamped using
U-bolts
• short for single long
row
• long for double
row
Mail: info@gielle.it - Website: www.gielle.it
33. Manifolds
• 200 bar component supplied by TSP only
• pressure tested to 320 bar
• nominal diameter = 50 mm
• opposite handed threads G2 - ISO 228
(right hand / left hand)
• easily connected on site using standard high pressure
fittings
• plugs and check valves are factory fitted to the inlet ports
as specified in the order
Mail: info@gielle.it - Website: www.gielle.it
36. High Pressure Fittings
All fittings used in the high pressure 200 bar part of
the system are supplied by TSP only.
Mail: info@gielle.it - Website: www.gielle.it
37. High Pressure Fittings
• nominal diameter: 50 mm / 80 mm
• right hand and/or left hand threads G2 - ISO 228
• left hand threads are identified by a groove around the
diameter of the fitting
• fittings are supplied with O-rings for easy connection
on site
• pressure tested to 360 bar
Mail: info@gielle.it - Website: www.gielle.it
44. Actuation Line 200 bar
P
1
P P
1 2
Mail: info@gielle.it - Website: www.gielle.it
45. Actuation Line 200 bar
Connection
5 9
hose DN 10 11
6 Lock Off unit
Adjustable tee
9
RA10xM16
Actuation
11
hose DN8
6
Agent container
5
Pilot cylinder
Mail: info@gielle.it - Website: www.gielle.it
46. Actuation Line 200 bar
Lock Off unit
Required by DIN EN 12094-6 and CEA 4032
Mail: info@gielle.it - Website: www.gielle.it
47. Actuation Line 200 bar
9 Adjustable tee RA10xM16
11 Actuation hose DN8
30 T-coupling for SGV-2
31 Pressure relief valve ELV-1
32 Automatic vent valve SGV-1
now SGV-2
Mail: info@gielle.it - Website: www.gielle.it
48. Actuation Line 200 bar
Manual pressure relief valve SGV-2
• required for each actuation line
• used to manually relieve the
residual pilot pressure in the
actuation line after a discharge
• used to automatically vent minor
flow of pilot gas that might occur
due to leakage in the pilot system
Mail: info@gielle.it - Website: www.gielle.it
49. Actuation Line 200 bar
Manual pressure relief valve SGV-2
• T-coupling
P
1
Mail: info@gielle.it - Website: www.gielle.it
50. Actuation Line 200 bar
Pilot hose DN8
Mail: info@gielle.it - Website: www.gielle.it
51. Actuation Line 200 bar
Test and relief unit
1 From pilot cylinder "Main"
2 From pilot cylinder "Reserve"
3 To actuation line
4 Connection for test cylinder
4
3
1 2
Mail: info@gielle.it - Website: www.gielle.it
52. Pressure Reducing Unit
200 bar to 60 bar
PRU 200/60
PRU 200/60
PRU 300/200
Mail: info@gielle.it - Website: www.gielle.it
53. Pressure Reducing Unit
DRE-2S (PRU 200/60)
VdS Approved
for single container only
Orifice
Diameters 1.0 – 5.0 mm
(in steps of 0.5 mm)
Manual page 71 M18x1.5 (200bar)
M24x1.5 (300bar)
Mail: info@gielle.it - Website: www.gielle.it
54. Pressure Reducing Unit
DRE-2N (PRU 200/60)
Orifice plate with
VdS approved 2 O-rings
for multiple container
systems (single hazard)
two sizes availabe
DN 50 – G2" ISO 228
200 bar 60 bar
DN 80 – G3" ISO 228
Orifice sizes
3.0 – 12.0 mm (0.5 mm steps)
DN 50
13.0 – 35.0 mm (1.0 mm steps)
DN 80 20.0 – 56.0 mm (2.0 mm steps)
Mail: info@gielle.it - Website: www.gielle.it
56. Pressure Reducing Unit
DRE-3 (PRU 200/60)
NOT VdS approved
for multiple container
systems
one sizes DN 50 200 bar 60 bar
2" NPT or R2"
Orifice sizes
3.0 – 12.0 mm (0.5 mm steps)
DN 50
13.0 – 35.0 mm (1.0 mm steps)
Mail: info@gielle.it - Website: www.gielle.it
57. Distribution Valve System
EPSL controlled
Control Panel Fire Alarm
VdS approved
1 set per hazard
pressure
reducer SMV
Pilot
P
cylinder Confirmation closed
Distribution
valve
valve
open
P
EPSL
300 bar 200 bar 60 bar 10 bar Agent
container
Mail: info@gielle.it - Website: www.gielle.it
58. Distribution Valve System
EPSL controlled
Control Panel
VdS approved
P
P
P
P
EPSL
300 bar 200 bar 60 bar 10 bar Agent
container
Mail: info@gielle.it - Website: www.gielle.it
60. Distribution Valve Assy.
HD-BV / 3 assembly PRU 200/60
VdS approved
closed and unpressurised
when in standby mode
pilot pressure to open =
10 bar
closed manually
3 sizes availabe
Orifice sizes
3.0 – 12.0 mm (0.5 mm steps)
DN 25 13.0 – 18.0 mm (1.0 mm steps) 200 bar 60 bar
3.0 – 12.0 mm (0.5 mm steps)
DN 50 13.0 – 35.0 mm (1.0 mm steps)
DN 80 20.0 – 56.0 mm (2.0 mm steps)
Mail: info@gielle.it - Website: www.gielle.it
63. Distribution Valve Assy.
Non VdS assembly
closed and
unpressurised
when in standby
mode
pilot pressure to
open = 7 bar
minimum
closed manually
50 mm NPT as
standard, other
Pressure reducing unit
sizes on request seperate behind the valve.
Mail: info@gielle.it - Website: www.gielle.it
64. Distribution Valve Assy.
5
R
Non VdS assembly R
3b
1 Distribution valve manifold NPT
2 HP union joint 4
3a set of 2 distribution pipes NPT
3b G2"R - 2"NPT and G2"L - 2"NPT
3a
4 Distribution valve L
L
5 Pressure reducing unit 2
R
R R
R
1
Mail: info@gielle.it - Website: www.gielle.it
65. Distribution Pipes
The pipes and fittings downstream the pressure reducer.
FM-200®
Sapphire™
CO2
TWF / VdS Software
Inergen® TSP / Ansul Software Software ??? ??? *
Constant Flow
Pipe pressure (bar)
20 40 80 100 120
25 60
The installer has to ensure, that the correct pressure rating for pipes and
fittings acc. to the flow calculation result is guaranteed.
* The final peak pressure in the pipe will result from the hydraulic flow calculation.
Mail: info@gielle.it - Website: www.gielle.it
66. Nozzles
IRD nozzle: Not VdS approved
Material: Brass (standard)
Sizes: ½" NPT or BSPT
1" NPT or BSPT
1 ½" NPT or BSPT
Pattern: 180°
360 orifice
Coverage: 95 m² at max. 3.7 m height
70 m² at max. 5.0 m height
Max. throw: 360°: 5.5 m at Hmax 3.7 m / 4.7 m at Hmax 5.0 m
180°: 7.7 m at Hmax 3.7 m / 6.7 m at Hmax 5.0 m
Mail: info@gielle.it - Website: www.gielle.it
67. Nozzles
GRD nozzle: VdS approved
Material: Brass (standard)
Sizes: R ½" DIN 29999
R 1" DIN 2999
Pattern: 360
Coverage: 30 m² at max.
5.0 m height
orifice
Mail: info@gielle.it - Website: www.gielle.it
68. Nozzles
GOD nozzle: VdS approved
Material: Brass (standard)
Sizes: R ½" DIN 29999
R 1" DIN 2999
Pattern: -
Coverage: 20 m² for floor
voids
orifice
A R ½" R ½" R ½" R ½" R 1"
C 82 mm 97 mm 128 mm 292 mm 296 mm
G 50 mm 70 mm 110 mm 110 mm 110 mm
Mail: info@gielle.it - Website: www.gielle.it
70. Discharge Pressure Switch
Latching type reset button
• max. working
pressure 350 bar
• min. 3 bar for
operation
• mounted in the
distribution pipe work
or actuation line
• SPDT bracket
• switches under
pressure and latches
¼" NPT femal
• manual reset ½" NPT male
necessary
Mail: info@gielle.it - Website: www.gielle.it
71. Discharge Pressure Switch
Non-latching type
• max. working pressure
120 bar
• mounted in the
distribution pipe work
• SPDT
• resets automatically at
the lower switch point
(4 bar)
• IP 65 (housing)
IP 54 (cable gland)
Mail: info@gielle.it - Website: www.gielle.it
72. Curtain Trip Assembly
• max. working pressure
60 bar
• mounted in the
distribution pipe work
• installation in horizontal cable
connected
plane to curtain
pressure
connection
3/8" NPT
manual release
Mail: info@gielle.it - Website: www.gielle.it
73. Grates
Steel grates, to prevent containers to be standing
in dirt/moisture and/or to level the ground
840 mm
560 mm
Mail: info@gielle.it - Website: www.gielle.it
75. Caution Plates
Door caution plate
- No lock-off -
Used when it is
permitted to leave the
system in automatic
mode even while the
area is occupied
oxygen level > 10%
(LOAEL)
One plate to be fixed
to all entrance doors
Mail: info@gielle.it - Website: www.gielle.it
76. Caution Plates
Door caution plate
- Lock-off -
Used when it is
necessary to place the
system on manual
control before entering
the hazard
oxygen level < 10%
(LOAEL)
One plate to be fixed
to all entrance doors
Mail: info@gielle.it - Website: www.gielle.it
77. Caution Plates
Manual release
One plate to be fixed
adjacent to all
positions from where
the system can be
released manually.
Mail: info@gielle.it - Website: www.gielle.it
79. Company
Profile
46 years of expertise and
experience in fire
protection
Mail: info@gielle.it - Website: www.gielle.it
Editor's Notes
August 7, 2012
August 7, 2012 Training fee is to cover the trainer expenses (flight, hotel, taxi, ..) and the training materials and varies depending on the location and number of attendees – a thumb value is 2500 € for a 2 days course on site
August 7, 2012 Training fee is to cover the trainer expenses (flight, hotel, taxi, ..) and the training materials and varies depending on the location and number of attendees – a thumb value is 2500 € for a 2 days course on site