SlideShare a Scribd company logo
1 of 7
Download to read offline
Induction Motor Speed Torque Characteristics.
When applying VARIABLE Frequency Drives(VFD), the speed-torque
characteristics of an induction motor started at full voltage and operated on
utility power should first be reviewed.
Figure 1 shows the speed-torque curve for a 30HP, 1800 RPM induction motor in an
application such as a conveyor where the load-torque requirement is constant from 0 RPM
to approximately 1800 RPM.
When this motor is
started across-the-line, the
motor develops approximately
201% of full-load torque for
starting and then accelerates along
the speed-torque curve through the
pull-up torque point, and finally operates
near the full-load torque point,
depending upon the actual load torque
requirements.
If the load-torque requirement exceeds
the maximum torque capability of the
induction motor, the motor will not have
enough torque to accelerate the load
and will stall. For instance, if the load
line required more torque than the
motor could produce at the pull-up
torque point (for example, 160% load
torque versus 140% pull-up torque), the
motor would not increase in speed past
the pull-up torque speed and would not
be able to accelerate the load. This
would cause the motor to overheat,
and/or overload devices to trip. It is,
therefore, important to insure that the
motor has adequate accelerating torque to
reach full speed.
Normally, the motor accelerates the load and operates at the point of intersection of the load line and the motor
speed-torque curve. The motor then always operates between the breakdown torque point and the synchronous
speed point, which corresponds to the 1800 RPM location on the horizontal axis. If additional load torque is
required, the motor slows down or slips and develops more torque by moving up toward the breakdown torque
point. Conversely, if less torque is required, the motor will speed up slightly toward the 1800 RPM point. Again, if
the breakdown torque requirements are exceeded, the motor will stall.
Yaskawa Electric America, Inc
AR.MOTOR.01 10/1/06 -Page 1 of 7
700
600
500
400
300
200
100
0 200 600 1000 1400 1800
RPM
%FULL-LOADTORQUE
%FULL-LOADAMPS
STARTING
TORQUE
PULL-UP
TORQUE
AMPS
BREAKDOWN
TORQUE
FULL-LOAD
TORQUE
Figure 1. Speed Torque Current Curves
Yaskawa Electric America, Inc
AR.MOTOR.01 10/1/06 Page 2 of 7
Induction Motor
Speed Torque Characteristics
Typically, when a NEMA Design B induction motor is started across-the-line, an inrush current of 600 to 800% FLA occurs,
corresponding to the starting torque point. As the load is accelerated to the full-load torque point, the current decreases to
100% full-load current at 100% full-load torque. High currents, however, are drawn during acceleration time.
The amount of time that the motor takes to accelerate the load will depend on the average accelerating torque, which is the
difference between the motor speed-torque curve and the load speed-torque curve, and is the torque available to accelerate
the load inertia.
Figure 2 is an enlarged detail of the region between the breakdown torque point and the synchronous speed point, which is
where the motor would operate. This is of particular
interest because the current for the various torque
requirements can easily be seen. This would directly
affect the size of the adjustable frequency drive
required to produce a given torque, because the drive is
current rated.
At 100% full-load torque, 100% full-load nameplate
current is required. At 150% torque, 150% full-load
nameplate current is required. Beyond the 150% full-
load torque point, however, the torque-per-amp ratio is
no longer proportional. For this case, 313% breakdown
torque would require 450% current.
The number of poles is a function of how the motor is
wound. For example, for 60 Hertz power, a two pole
motor would operate at 3600 RPM, a four pole motor
at 1800 RPM, and a six pole motor at 1200 RPM.
Magnetic
Poles RPM
2 3600
4 1800
6 1200
8 900
10 720
400
300
200
100
0 1680 1720 1760 1800
RPM
%FULL-LOADTORQUE
%FULL-LOADAMPS
TORQUE
AMPS
Figure 2. Torque Current Curves
The actual or running speed of an induction motor is
influenced by the applied load and the resultant slip. The
torque the motor produces is also a function of slip; more
slip, more torque. A NEMA Design B motor generally
operates at 3% slip, or 50 RPM of slip.
Speed µ Frequency x 120 - Slip
Poles
At 3% slip, the motor will produce its rated torque. The
motor can slip further, with resultant increase in torque. This
would continue until the breakdown peak, at which time the
motor would stall. Other motor designs such as NEMA D
can slip as much as 13% at full load.
The horsepower and torque output of an induction motor
can be calculated by these formulas:
RPM x Torque
HP = 5250
HP x 5250
Torque = RPM
With all of the formulas now explained, they can be applied
to a motor in an actual situation, to see how changes in
voltage and frequency affect operation.
- - - - - U.S. OPERATION - - - - -
30 HP 460 VAC
1800 RPM 60 Hertz
89.4 lb-ft torque 69 Amps
In simple terms, the variables of operation are:
– Voltage controls power output or HP
– Frequency controls speed or RPM
– Current controls torque.
If the same motor is used in Europe, which has a different
power grid than in the U.S. (most of Europe operates at 380
VAC, 50 Hertz), the following conditions would be noted:
- - EUROPEAN OPERATION - -
25 HP 380 VAC
1500 RPM 50 Hertz
89.4 lb-ft torque 69 Amps
The fixed speed motor can be operated at another line
voltage because the ratio of voltage and frequency remained
the same. This can be referred to as the volts/Hertz ratio for
which the motor is wound.
460/60 = 7.7 V/Hz 380/50 = 7.7 V/Hz
If the motor is operated at 575 VAC at 60 Hertz, it would
overexcite or saturate, burning up.
At 230 VAC at 60 Hertz, it would be underexcited and stall
due to high induced currents. This formula explains this
phenomenon:
Magnetic Flux
Torque µ Density Within µ Volts/Hertz
Motor Air Gap
In order to vary the speed of an induction motor, the drive
would have an output characteristic as shown in Figure 3.
The voltage is varied directly with the frequency,
maintaining a constant V/Hz ratio. For instance, a 460 volt
Yaskawa drive would typically be adjusted (i.e.
programmed) to provide 460 volts output at 60 Hertz and
230 volts at 30 Hertz.
Yaskawa Electric America, Inc
AR.MOTOR.01 10/1/06 Page 3 of 7
Induction Motor
Speed Torque Characteristics
460
345
230
115
0
15 30 45 60
FREQUENCY (Hz)
OUTPUTVOLTAGE
Figure 3. Drive Output
The drive would typically start an induction motor by starting at low voltage and low frequency and increasing the voltage
and frequency to the desired operating point. This would contrast to the typical way of starting induction motors by
applying full voltage (460 volts at 60 Hertz) immediately to the motor.
By starting the motor with low voltage and low frequency, the inrush current associated with across-the-line starting is
completely eliminated. In addition, the motor operates between the breakdown torque point and synchronous speed point as
soon as it is started, as compared to starting across-the-line in which case the motor accelerates to a point between the
synchronous speed and breakdown torque point.
The curve in Figure 4 shows the actual speed-torque curves which result when a motor is operated from a constant volts-
per-Hertz voltage source supply. When low voltage and low frequency is applied to the motor, the maximum torque
available decreases at reduced speeds. This is a result of the resistive voltage drop of the stator windings.
The motor would always operate between the maximum torque or breakdown torque point and the synchronous speed point
which is represented by the intersection with the horizontal axis.
As the applied motor voltage and frequency is increased from 0 volts and 0 Hertz, the motor speed torque curve moves to
the right as shown in Figure 4.
The maximum starting torque for constant volts-per-Hertz operation may actually be much less than full-load torque. This
may provide adequate torque for starting some
loads such as a centrifugal load, but other loads
such as a constant torque load will require higher
starting torques. This is achieved by applying a
voltage boost, or additional voltage, at low
frequency.
Yaskawa Electric America, Inc
AR.MOTOR.01 10/1/06 Page 4 of 7
Induction Motor
Speed Torque Characteristics
300
200
100
0 50 100
% SPEED
%FULL-LOADTORQUE
Figure 4. Speed Torque Curves
In order to obtain more starting torque, as shown in Figure 5, a voltage boost is applied at low frequency to overcome the
resistive drop of the motor at low frequency. This drop also occurs at higher frequencies, but has much less effect since it
becomes a smaller percentage of the applied voltage. This voltage boost
is typically around 5% of the motor full-load nameplate voltage.
The voltage boost can be adjusted to produce various levels of starting torque. Figure 5 shows the torque that would be
provided without boost and the torque that would be provided with voltage boost set to 150% starting torque.
The voltage boost should be adjusted to provide the required torque and to overcome the resistive drop of the motor. If this
voltage boost is too high, saturation could occur and cause high motor currents and excessive motor heating.
Figure 6 shows resultant speed/torque curves with voltage boost.
Yaskawa Electric America, Inc
AR.MOTOR.01 10/1/06 Page 5 of 7
Induction Motor
Speed Torque Characteristics
10
20
30
40
50
10
50
3020
100
150
3
FREQUENCY (Hz)
%FULL-LOADTORQUE
%VOLTAGE
TORQUE(%FULLLOAD)
BOOST
VOLTS/HERTZ
WITH BOOST
TORQUE
WITH BOOST
CONSTANT
VOLTS/HERTZ
TORQUE
WITHOUT BOOST
Figure 5. Starting Torque Characteristics
RPM
HZ
0
0
600
20
1200
40
1800
60
0
200%
175%
150%
125%
100%
75%
50%
25%
Figure 6. Adjustable Frequency Speed/Torque
Figure 7 shows the resulting motor/drive speed-torque curve for the range of operation below 100% speed which would
correspond to the 60 Hertz operating point. As a reference, the speed-torque/current curve of an induction motor started
across-the-line is also shown.
The dark line corresponding to the 100% full-load torque/current point represents the maximum continuous torque available
from the combined motor and VFD. The dashed line at 150% indicates the short-time current/torque rating of the drive.
At any given speed, the motor would operate as previously discussed between the maximum torque point and the
synchronous speed point. The amount of torque available would depend on the amount of current which could be supplied
by the drive.
As previously discussed, the starting torque characteristics and the maximum torque available from the motor/drive
combination may be different from the torque available when operating the motor from utility power and starting with full
voltage.
Yaskawa Electric America, Inc
AR.MOTOR.01 10/1/06 -Page 6 of 7
Induction Motor
Speed Torque Characteristics
700
600
500
400
300
200
100
0 200 600 1000 1400 1800
RPM
%FULL-LOADTORQUE
%FULL-LOADAMPS
STARTING
TORQUE
PULL-UP
TORQUE
AMPS
BREAKDOWN
TORQUE
FULL-LOAD
TORQUE
SHORT-TERM
TORQUE
Figure 7. Speed Torque Current Curves
The previous discussion was related to operation of an induction motor at 60 Hertz and below. When using a motor/motor
combination, the motor is no longer limited to 60 Hertz operation, and can actually be operated above 60 Hertz. Figure 8
shows the speed torque and horsepower curves for a motor and Yaskawa drive both below and above 60 Hertz.
The region below 60 Hertz is typically referred to as the constant torque range of operation, and the area above 60 Hertz is
generally referred to as the constant horsepower range of operation. Up to 60 Hertz, the voltage is varied directly with the
frequency. Above 60 Hertz, however, the voltage is fixed and only the frequency is increased.
It should be evident that in the constant horsepower region there is a decrease in available torque. This phenomenon is
explained by the same formula mentioned earlier:
Magnetic Flux
Torque µ Density Within µ Volts/Hertz
Motor Air Gap
As frequency increases, the V/Hz ratio decreases and torque follows.
For further details on operation in the constant horsepower region, refer to the LOAD PROFILES AD4011.
Yaskawa Electric America, Inc
AR.MOTOR.01 10/1/06 Page 7 of 7
Induction Motor
Speed Torque Characteristics
CONSTANT
TORQUE
CONSTANT
HP
TORQUE
HORSEPOWER
% SPEED
%FULL-LOADHORSEPOWER
%FULL-LOADTORQUE
FREQUENCY (Hz)
50%
30
100%
60
150%
90
100
50
Figure 8. Adjustable Frequency Motor Speed Torque Curve

More Related Content

What's hot

How does a servo motor work?
How does a servo motor work?How does a servo motor work?
How does a servo motor work?rashid baloch
 
Dynamics of Electrical Drives
Dynamics of Electrical DrivesDynamics of Electrical Drives
Dynamics of Electrical DrivesSwapnil Gadgune
 
Control of electric drive
Control of electric driveControl of electric drive
Control of electric driveVijay Krishna
 
Synchronous motor
Synchronous motorSynchronous motor
Synchronous motorkarthi1017
 
QuickSilver Controls QCI-WP003
QuickSilver Controls  QCI-WP003QuickSilver Controls  QCI-WP003
QuickSilver Controls QCI-WP003Electromate
 
Iaetsd energy management of induction motor
Iaetsd energy management of induction motorIaetsd energy management of induction motor
Iaetsd energy management of induction motorIaetsd Iaetsd
 
Electric Drive-Parts. Classification of Electric Drives, Four- Quadarant Control
Electric Drive-Parts. Classification of Electric Drives, Four- Quadarant ControlElectric Drive-Parts. Classification of Electric Drives, Four- Quadarant Control
Electric Drive-Parts. Classification of Electric Drives, Four- Quadarant ControlWaqas Afzal
 
Серводвигатели серии BSM Baldor
Серводвигатели серии BSM BaldorСерводвигатели серии BSM Baldor
Серводвигатели серии BSM BaldorArve
 
Efficient Motor Control Solutions: High Performance Servo Control (Design Con...
Efficient Motor Control Solutions: High Performance Servo Control (Design Con...Efficient Motor Control Solutions: High Performance Servo Control (Design Con...
Efficient Motor Control Solutions: High Performance Servo Control (Design Con...Analog Devices, Inc.
 
11305119, roll. no 5, akshay kumar
11305119, roll. no 5, akshay kumar11305119, roll. no 5, akshay kumar
11305119, roll. no 5, akshay kumarAkshay Kumar
 

What's hot (20)

Soft starters
Soft startersSoft starters
Soft starters
 
How does a servo motor work?
How does a servo motor work?How does a servo motor work?
How does a servo motor work?
 
At21
At21At21
At21
 
Dynamics of Electrical Drives
Dynamics of Electrical DrivesDynamics of Electrical Drives
Dynamics of Electrical Drives
 
Control of electric drive
Control of electric driveControl of electric drive
Control of electric drive
 
D43042025
D43042025D43042025
D43042025
 
Synchronous motor
Synchronous motorSynchronous motor
Synchronous motor
 
QuickSilver Controls QCI-WP003
QuickSilver Controls  QCI-WP003QuickSilver Controls  QCI-WP003
QuickSilver Controls QCI-WP003
 
Electric traction
Electric tractionElectric traction
Electric traction
 
Motors & starting
Motors & startingMotors & starting
Motors & starting
 
Motors
MotorsMotors
Motors
 
Final thesis
Final thesisFinal thesis
Final thesis
 
Dc servo motor
Dc servo motorDc servo motor
Dc servo motor
 
Abb technical guide no.05 revc
Abb technical guide no.05 revcAbb technical guide no.05 revc
Abb technical guide no.05 revc
 
Iaetsd energy management of induction motor
Iaetsd energy management of induction motorIaetsd energy management of induction motor
Iaetsd energy management of induction motor
 
Pbl 1
Pbl 1Pbl 1
Pbl 1
 
Electric Drive-Parts. Classification of Electric Drives, Four- Quadarant Control
Electric Drive-Parts. Classification of Electric Drives, Four- Quadarant ControlElectric Drive-Parts. Classification of Electric Drives, Four- Quadarant Control
Electric Drive-Parts. Classification of Electric Drives, Four- Quadarant Control
 
Серводвигатели серии BSM Baldor
Серводвигатели серии BSM BaldorСерводвигатели серии BSM Baldor
Серводвигатели серии BSM Baldor
 
Efficient Motor Control Solutions: High Performance Servo Control (Design Con...
Efficient Motor Control Solutions: High Performance Servo Control (Design Con...Efficient Motor Control Solutions: High Performance Servo Control (Design Con...
Efficient Motor Control Solutions: High Performance Servo Control (Design Con...
 
11305119, roll. no 5, akshay kumar
11305119, roll. no 5, akshay kumar11305119, roll. no 5, akshay kumar
11305119, roll. no 5, akshay kumar
 

Similar to Ar.motor.01

4.5 assessment of motors n
4.5 assessment of  motors n4.5 assessment of  motors n
4.5 assessment of motors npriya3757
 
Especificaciones de motores siemens
Especificaciones de motores siemensEspecificaciones de motores siemens
Especificaciones de motores siemensfedericoblanco
 
EMA410S_Synchronous Motors Part 2.pptx
EMA410S_Synchronous Motors Part 2.pptxEMA410S_Synchronous Motors Part 2.pptx
EMA410S_Synchronous Motors Part 2.pptxAcktofelRebbyRubby
 
DC Motors Explanation 1.pdf
DC Motors Explanation 1.pdfDC Motors Explanation 1.pdf
DC Motors Explanation 1.pdfIsiMiyake
 
DC Motor Fundamentals.pptx
DC Motor Fundamentals.pptxDC Motor Fundamentals.pptx
DC Motor Fundamentals.pptxvijayprabhuj
 
Induction Synchronous Motor
Induction Synchronous MotorInduction Synchronous Motor
Induction Synchronous MotorShahzad Khalil
 
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...Waqas Afzal
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Excessive vibration issues in two pole electric motors
Excessive vibration issues in two pole electric motorsExcessive vibration issues in two pole electric motors
Excessive vibration issues in two pole electric motorsAdam Bron
 
Introduction to vfd
Introduction to vfdIntroduction to vfd
Introduction to vfdrrsurani
 
Numerical examples
Numerical examplesNumerical examples
Numerical examplesFelipe Gomes
 
Starting of 3-Phase Induction Motors
Starting of 3-Phase Induction MotorsStarting of 3-Phase Induction Motors
Starting of 3-Phase Induction Motorsmorin moli
 

Similar to Ar.motor.01 (20)

electric motor
electric motorelectric motor
electric motor
 
4.5 assessment of motors n
4.5 assessment of  motors n4.5 assessment of  motors n
4.5 assessment of motors n
 
Especificaciones de motores siemens
Especificaciones de motores siemensEspecificaciones de motores siemens
Especificaciones de motores siemens
 
EMA410S_Synchronous Motors Part 2.pptx
EMA410S_Synchronous Motors Part 2.pptxEMA410S_Synchronous Motors Part 2.pptx
EMA410S_Synchronous Motors Part 2.pptx
 
DC Motors Explanation 1.pdf
DC Motors Explanation 1.pdfDC Motors Explanation 1.pdf
DC Motors Explanation 1.pdf
 
Gymr motor starting_solutions
Gymr motor starting_solutionsGymr motor starting_solutions
Gymr motor starting_solutions
 
DC Motor Fundamentals.pptx
DC Motor Fundamentals.pptxDC Motor Fundamentals.pptx
DC Motor Fundamentals.pptx
 
Induction Synchronous Motor
Induction Synchronous MotorInduction Synchronous Motor
Induction Synchronous Motor
 
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
synchronous motor, Starting Torque, Types, Equivalent Circuit, Torque-speed c...
 
Slide 1.pptx
Slide 1.pptxSlide 1.pptx
Slide 1.pptx
 
Eee 551
Eee 551Eee 551
Eee 551
 
Eece 259 dc motor
Eece 259 dc motorEece 259 dc motor
Eece 259 dc motor
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Motor starter
Motor starterMotor starter
Motor starter
 
123456
123456123456
123456
 
Excessive vibration issues in two pole electric motors
Excessive vibration issues in two pole electric motorsExcessive vibration issues in two pole electric motors
Excessive vibration issues in two pole electric motors
 
Drives training
Drives trainingDrives training
Drives training
 
Introduction to vfd
Introduction to vfdIntroduction to vfd
Introduction to vfd
 
Numerical examples
Numerical examplesNumerical examples
Numerical examples
 
Starting of 3-Phase Induction Motors
Starting of 3-Phase Induction MotorsStarting of 3-Phase Induction Motors
Starting of 3-Phase Induction Motors
 

Ar.motor.01

  • 1. Induction Motor Speed Torque Characteristics. When applying VARIABLE Frequency Drives(VFD), the speed-torque characteristics of an induction motor started at full voltage and operated on utility power should first be reviewed. Figure 1 shows the speed-torque curve for a 30HP, 1800 RPM induction motor in an application such as a conveyor where the load-torque requirement is constant from 0 RPM to approximately 1800 RPM. When this motor is started across-the-line, the motor develops approximately 201% of full-load torque for starting and then accelerates along the speed-torque curve through the pull-up torque point, and finally operates near the full-load torque point, depending upon the actual load torque requirements. If the load-torque requirement exceeds the maximum torque capability of the induction motor, the motor will not have enough torque to accelerate the load and will stall. For instance, if the load line required more torque than the motor could produce at the pull-up torque point (for example, 160% load torque versus 140% pull-up torque), the motor would not increase in speed past the pull-up torque speed and would not be able to accelerate the load. This would cause the motor to overheat, and/or overload devices to trip. It is, therefore, important to insure that the motor has adequate accelerating torque to reach full speed. Normally, the motor accelerates the load and operates at the point of intersection of the load line and the motor speed-torque curve. The motor then always operates between the breakdown torque point and the synchronous speed point, which corresponds to the 1800 RPM location on the horizontal axis. If additional load torque is required, the motor slows down or slips and develops more torque by moving up toward the breakdown torque point. Conversely, if less torque is required, the motor will speed up slightly toward the 1800 RPM point. Again, if the breakdown torque requirements are exceeded, the motor will stall. Yaskawa Electric America, Inc AR.MOTOR.01 10/1/06 -Page 1 of 7 700 600 500 400 300 200 100 0 200 600 1000 1400 1800 RPM %FULL-LOADTORQUE %FULL-LOADAMPS STARTING TORQUE PULL-UP TORQUE AMPS BREAKDOWN TORQUE FULL-LOAD TORQUE Figure 1. Speed Torque Current Curves
  • 2. Yaskawa Electric America, Inc AR.MOTOR.01 10/1/06 Page 2 of 7 Induction Motor Speed Torque Characteristics Typically, when a NEMA Design B induction motor is started across-the-line, an inrush current of 600 to 800% FLA occurs, corresponding to the starting torque point. As the load is accelerated to the full-load torque point, the current decreases to 100% full-load current at 100% full-load torque. High currents, however, are drawn during acceleration time. The amount of time that the motor takes to accelerate the load will depend on the average accelerating torque, which is the difference between the motor speed-torque curve and the load speed-torque curve, and is the torque available to accelerate the load inertia. Figure 2 is an enlarged detail of the region between the breakdown torque point and the synchronous speed point, which is where the motor would operate. This is of particular interest because the current for the various torque requirements can easily be seen. This would directly affect the size of the adjustable frequency drive required to produce a given torque, because the drive is current rated. At 100% full-load torque, 100% full-load nameplate current is required. At 150% torque, 150% full-load nameplate current is required. Beyond the 150% full- load torque point, however, the torque-per-amp ratio is no longer proportional. For this case, 313% breakdown torque would require 450% current. The number of poles is a function of how the motor is wound. For example, for 60 Hertz power, a two pole motor would operate at 3600 RPM, a four pole motor at 1800 RPM, and a six pole motor at 1200 RPM. Magnetic Poles RPM 2 3600 4 1800 6 1200 8 900 10 720 400 300 200 100 0 1680 1720 1760 1800 RPM %FULL-LOADTORQUE %FULL-LOADAMPS TORQUE AMPS Figure 2. Torque Current Curves
  • 3. The actual or running speed of an induction motor is influenced by the applied load and the resultant slip. The torque the motor produces is also a function of slip; more slip, more torque. A NEMA Design B motor generally operates at 3% slip, or 50 RPM of slip. Speed µ Frequency x 120 - Slip Poles At 3% slip, the motor will produce its rated torque. The motor can slip further, with resultant increase in torque. This would continue until the breakdown peak, at which time the motor would stall. Other motor designs such as NEMA D can slip as much as 13% at full load. The horsepower and torque output of an induction motor can be calculated by these formulas: RPM x Torque HP = 5250 HP x 5250 Torque = RPM With all of the formulas now explained, they can be applied to a motor in an actual situation, to see how changes in voltage and frequency affect operation. - - - - - U.S. OPERATION - - - - - 30 HP 460 VAC 1800 RPM 60 Hertz 89.4 lb-ft torque 69 Amps In simple terms, the variables of operation are: – Voltage controls power output or HP – Frequency controls speed or RPM – Current controls torque. If the same motor is used in Europe, which has a different power grid than in the U.S. (most of Europe operates at 380 VAC, 50 Hertz), the following conditions would be noted: - - EUROPEAN OPERATION - - 25 HP 380 VAC 1500 RPM 50 Hertz 89.4 lb-ft torque 69 Amps The fixed speed motor can be operated at another line voltage because the ratio of voltage and frequency remained the same. This can be referred to as the volts/Hertz ratio for which the motor is wound. 460/60 = 7.7 V/Hz 380/50 = 7.7 V/Hz If the motor is operated at 575 VAC at 60 Hertz, it would overexcite or saturate, burning up. At 230 VAC at 60 Hertz, it would be underexcited and stall due to high induced currents. This formula explains this phenomenon: Magnetic Flux Torque µ Density Within µ Volts/Hertz Motor Air Gap In order to vary the speed of an induction motor, the drive would have an output characteristic as shown in Figure 3. The voltage is varied directly with the frequency, maintaining a constant V/Hz ratio. For instance, a 460 volt Yaskawa drive would typically be adjusted (i.e. programmed) to provide 460 volts output at 60 Hertz and 230 volts at 30 Hertz. Yaskawa Electric America, Inc AR.MOTOR.01 10/1/06 Page 3 of 7 Induction Motor Speed Torque Characteristics 460 345 230 115 0 15 30 45 60 FREQUENCY (Hz) OUTPUTVOLTAGE Figure 3. Drive Output
  • 4. The drive would typically start an induction motor by starting at low voltage and low frequency and increasing the voltage and frequency to the desired operating point. This would contrast to the typical way of starting induction motors by applying full voltage (460 volts at 60 Hertz) immediately to the motor. By starting the motor with low voltage and low frequency, the inrush current associated with across-the-line starting is completely eliminated. In addition, the motor operates between the breakdown torque point and synchronous speed point as soon as it is started, as compared to starting across-the-line in which case the motor accelerates to a point between the synchronous speed and breakdown torque point. The curve in Figure 4 shows the actual speed-torque curves which result when a motor is operated from a constant volts- per-Hertz voltage source supply. When low voltage and low frequency is applied to the motor, the maximum torque available decreases at reduced speeds. This is a result of the resistive voltage drop of the stator windings. The motor would always operate between the maximum torque or breakdown torque point and the synchronous speed point which is represented by the intersection with the horizontal axis. As the applied motor voltage and frequency is increased from 0 volts and 0 Hertz, the motor speed torque curve moves to the right as shown in Figure 4. The maximum starting torque for constant volts-per-Hertz operation may actually be much less than full-load torque. This may provide adequate torque for starting some loads such as a centrifugal load, but other loads such as a constant torque load will require higher starting torques. This is achieved by applying a voltage boost, or additional voltage, at low frequency. Yaskawa Electric America, Inc AR.MOTOR.01 10/1/06 Page 4 of 7 Induction Motor Speed Torque Characteristics 300 200 100 0 50 100 % SPEED %FULL-LOADTORQUE Figure 4. Speed Torque Curves
  • 5. In order to obtain more starting torque, as shown in Figure 5, a voltage boost is applied at low frequency to overcome the resistive drop of the motor at low frequency. This drop also occurs at higher frequencies, but has much less effect since it becomes a smaller percentage of the applied voltage. This voltage boost is typically around 5% of the motor full-load nameplate voltage. The voltage boost can be adjusted to produce various levels of starting torque. Figure 5 shows the torque that would be provided without boost and the torque that would be provided with voltage boost set to 150% starting torque. The voltage boost should be adjusted to provide the required torque and to overcome the resistive drop of the motor. If this voltage boost is too high, saturation could occur and cause high motor currents and excessive motor heating. Figure 6 shows resultant speed/torque curves with voltage boost. Yaskawa Electric America, Inc AR.MOTOR.01 10/1/06 Page 5 of 7 Induction Motor Speed Torque Characteristics 10 20 30 40 50 10 50 3020 100 150 3 FREQUENCY (Hz) %FULL-LOADTORQUE %VOLTAGE TORQUE(%FULLLOAD) BOOST VOLTS/HERTZ WITH BOOST TORQUE WITH BOOST CONSTANT VOLTS/HERTZ TORQUE WITHOUT BOOST Figure 5. Starting Torque Characteristics RPM HZ 0 0 600 20 1200 40 1800 60 0 200% 175% 150% 125% 100% 75% 50% 25% Figure 6. Adjustable Frequency Speed/Torque
  • 6. Figure 7 shows the resulting motor/drive speed-torque curve for the range of operation below 100% speed which would correspond to the 60 Hertz operating point. As a reference, the speed-torque/current curve of an induction motor started across-the-line is also shown. The dark line corresponding to the 100% full-load torque/current point represents the maximum continuous torque available from the combined motor and VFD. The dashed line at 150% indicates the short-time current/torque rating of the drive. At any given speed, the motor would operate as previously discussed between the maximum torque point and the synchronous speed point. The amount of torque available would depend on the amount of current which could be supplied by the drive. As previously discussed, the starting torque characteristics and the maximum torque available from the motor/drive combination may be different from the torque available when operating the motor from utility power and starting with full voltage. Yaskawa Electric America, Inc AR.MOTOR.01 10/1/06 -Page 6 of 7 Induction Motor Speed Torque Characteristics 700 600 500 400 300 200 100 0 200 600 1000 1400 1800 RPM %FULL-LOADTORQUE %FULL-LOADAMPS STARTING TORQUE PULL-UP TORQUE AMPS BREAKDOWN TORQUE FULL-LOAD TORQUE SHORT-TERM TORQUE Figure 7. Speed Torque Current Curves
  • 7. The previous discussion was related to operation of an induction motor at 60 Hertz and below. When using a motor/motor combination, the motor is no longer limited to 60 Hertz operation, and can actually be operated above 60 Hertz. Figure 8 shows the speed torque and horsepower curves for a motor and Yaskawa drive both below and above 60 Hertz. The region below 60 Hertz is typically referred to as the constant torque range of operation, and the area above 60 Hertz is generally referred to as the constant horsepower range of operation. Up to 60 Hertz, the voltage is varied directly with the frequency. Above 60 Hertz, however, the voltage is fixed and only the frequency is increased. It should be evident that in the constant horsepower region there is a decrease in available torque. This phenomenon is explained by the same formula mentioned earlier: Magnetic Flux Torque µ Density Within µ Volts/Hertz Motor Air Gap As frequency increases, the V/Hz ratio decreases and torque follows. For further details on operation in the constant horsepower region, refer to the LOAD PROFILES AD4011. Yaskawa Electric America, Inc AR.MOTOR.01 10/1/06 Page 7 of 7 Induction Motor Speed Torque Characteristics CONSTANT TORQUE CONSTANT HP TORQUE HORSEPOWER % SPEED %FULL-LOADHORSEPOWER %FULL-LOADTORQUE FREQUENCY (Hz) 50% 30 100% 60 150% 90 100 50 Figure 8. Adjustable Frequency Motor Speed Torque Curve