A study on Electrical equipment used in working
modules and power distribution at AVCTPL
An Industrial Project Report
Submitted In Partial Fulfillment of
the requirements for the Award of the Degree of
BACHELOR OF TECHNOLOGY
IN
ELECTRICAL ENGINEERING
Submitted by
DEEPAK KUMAR DASH
Under the Esteemed Guidance of
Mr.D.Kiran Kumar
(Associate Manager, H.R., AVCTPL)
Mr.Siddhant Chatterjee
(Head of Engineering Department, AVCTPL)
DEPARTMENT OF ELECTRICAL ENGINEERING
GANDHI INSTITUTE OF ENGINEERING & TECHNOLOGY
GUNUPUR – 765 022, Dist.: Rayagada (Odisha), India
(Approved by AICTE, Govt. of Orissa and Affiliated to Biju Patnaik University of Technology)
2015-16
DECLARATION
I hereby declare that the Industrial project “A study of
electrical equipment used in working modules and power
distribution at AVCTPL” submitted for the B.Tech Degree is
done by me with the association of “Adani Vizag Coal
Terminal Port Pvt.ltd, Port Area, Visakhapatnam, Andhra
Pradesh 530035, India.”
Name & Signature of the Student:
SaswatMohapatra
Place: AVCTPL, Vizag
Date: 15-06-2015
ACKNOWLEDGEMENT
We would like to express our profound sense of gratitude to all for having helped us
in completing this dissertation. We would like to express our deep felt gratitude and sincere
thanks to our guide “Mr.B.Pradeep Kumar, H.O.D., electrical” for his skillful guidance,
timely suggestions and encouragement in completing this project.
We are highly obliged to our project coordinator Mr.Siddhant Chatterjee, Head of
the Engineering department, for having extended his affable guidance, constant supervision
and encouragement throughout the progress of this project, which helped us to complete it
within the stipulated time.
We would like to express our sincere thanks to Mr.D.Kiran Kumar, Associate
Manager, H.R., AVCTPL, for providing the necessary facilities for the successful
completion of this work.
Last but not least, we wish to thank our Instructor & Other Staffs, our parents and
all our friends for their constant moral support, cooperation and encouragement during this
period.
CONTENTS
ABSTRACT i
LIST OF FIGURES & TABLES ii
INTRODUCTION 1-2
CHAPTER 1: WORKING MODULES OF AVCTPL
1.1 Introduction 3
1.2 Intermediate transfer tower(ITT) 3
1.2.1 Definition 3
1.2.2 Types 4
1.2.2.0 ITT1 4
1.2.2.1 ITT2
1.2.2.2 ITT3 4
1.2.2.3 ITT4 4
1.2.2.4 ITT5 4
1.2.3 Use of automation 4
1.3 Intermediate Belt Conveyor 5
1.3.1 Definition 5
1.3.2 Types 5
1.3.2.0 IBC1 5
1.3.2.1 IBC2 5
1.3.2.2 IBC3 6
1.3.2.3 IBC3A 6
1.3.2.4 IBC4 6
1.3.3 Use of automation 6
1.4 Stacker and Reclaimer 7
1.4.1 Definition 7
1.4.2 Modes of operation 7
1.4.3 E-house and its function 7
1.4.4 Use of automation 9
1.5 SILO 9
1.5.1 Definition 9
1.5.2 Functional part of SILO 9
1.5.3 Technology of choice and automation 11
1.5.4 Wagon loading 13
1.6 Pump house 13
1.6.1 Need of pump house 13
1.6.2 Main component of pump house 13
CHAPTER 2: CONTROLROOM
2.1 Introduction 15
2.2 Layout view of AVCTPL 15
2.3 Layout view of DS System 16
CHAPTER 3: AVCTPL SUBSTATION GRID
3.1 Main objective of Distribution system 17
3.2 Functional parts of substation grid 17
3.3 A Brief lay out of distribution of AVCTPL 22
3.4 New glance of technology in distribution 23
3.5 Case study analysis on distribution system 24
3.6 UPS System 25
3.7 DG Supply 26
3.8 Reactive power compensation 26
3.9 some industrial measurements 27
CHAPTER 4: SAFETY
4.1 Definition 28
4.2 Need of Safety for AVCTPL 28
4.3 Safety equipment and procedure 29
REFERENCE 30
ABSTRACT
In today's world of power shortages, increasing demand and the energy efficiency
debate, how the electricity network is run right through from the power station to consumer
end is becoming ever more important. A substation is a part of an electrical generation,
transmission, and distribution system. Substations transform voltage from high to low, or the
reverse, or perform any of several other important functions. Between the generating station
and consumer, electric power may flow through several substations at different voltage levels.
A Distribution substation transfers power from the transmission system to the distribution
system of an area. It is uneconomical to directly connect electricity consumers to the main
transmission network, unless they use large amounts of power, so the distribution station
reduces voltage to a level suitable for local distribution.
The highest priority in a substation is to detect and isolate failures in the transmission
system as hastily as possible. Upholding power quality is one of the main functions of a
substation, and it affects operating conditions of the whole transmission and distribution
networks. Power quality information is of strategic importance for electricity companies and
essential for ensuring competitive operation.
In this era, every industry frantically needs both the performance and efficiency
simultaneously so as to maintain the performances and efficiencies of different electrical
machine is the new challenges for the engineers.
The main focus on this project is to scrutinizing the efficient performance of the
industry by maintaining the power factor at the acceptable limit and providing healthy
performance to the machine used in different modules. So it provides a good economic strength
to the industry. The other objective of this project is to analyzing the new technology involved
in each working module and the type of electrical equipment used in each module of AVCTPL
distribution substation. A careful case study of the project can give an ephemeral idea about
the distribution system and the new technology used over here with its future appliances.
i
LIST OF FIGURES
Figure
No.
Description page no.
Fig. 1 BLOCK DIAGRAM OF PLC CONTROL 12
Fig. 2 LAYOUT VIEW OF AVCTPL 15
Fig 3 LAYOUT VIEW OF DS SYSTEM 16
Fig: 4 AVCTPL PANEL 20
Fig. 5 LAYOUT OF DISTRIBUTION OF AVCTPL 22
Fig. 6 LAYOUT OF UPS SYSTEM 25
Fig. 7 DG AND MAIN SUPPLY CONNECTION 26
LIST OF TABLES
Table
No.
Description pageno.
Table 1.0 SPECIFICATION OF HT MOTOR 3
Table 1.1 SPECIFICATON OF DRY TANSFORMER[E-HOUSE] 8
Table 1.2 SPECIFICATION OF MOTOR 10
Table 1.3 SPECIFICATION OF MOTOR[PUMP HOUSE] 13
Table 1.4 PANEL POWER SUPPLY 21
Table 1.5 SPECIFICATION OF DRY TRANSFORMER[LIGHTING] 24
Table 1.6 SPECIFICATION OF APFC 27
ii
INTRODUCTION
The Adani Vizag Coal Terminal Private Ltd (AVCTPL), a subsidiary of APSEZ and
also a part of Adani group which is global integrated infrastructure player with interests in
resources, logistics, energy and agribusiness. It is an Indian multinational company founded by
the former chairman Mr.Goutam Adani. AVCTPL had entered into a concession agreement
with Visakhapatnam Port Trust to set up fully mechanized steam coal handling facility with a
capacity of 6.4 million tonnes a year in March 2011 with completion deadline of August 2014.
The facility is completed eight months ahead of schedule at a cost of Rs400 crore.AVCTPL,
being a part of Visakhapatnam Port is strategic for coal imports to feed the local industries and
power plants of the states of Andhra Pradesh, Odisha, Chhattisgarh and Maharashtra.
AVCTPL occupies a large area of back up yard about 25 Acres. AVCTPL is basically
import terminal type to handle the cargo (steam coal) and terminal capacity is 5.0 MMTPA. It
is having a Berth of size 280 meters and width of 6.1 meters. It contains maximum vessel size
of 80000 DWT. It has a Deck top level of 3.65 meter.
Constructional AVCTPL is divided into three different working sites in such a way
that failure of any one site can cause a huge amount of loss to the company. So AVCTPL has
its own control room from where it invigilates any site easily at any time. AVCTPL has its own
substation which is situated inside the operational building. The port site is present in the west
side to the operational building. Two Mobile Harbor Crane (MHC) are employed there,
which is operated by the operator master. These are mainly running for luffing purpose of cargo
which is present inside the vessel. It can be also visualized directly through the control room.
AVCTPL has its own storing site used for cargo (i.e. coal) storage purpose. These site mainly
contains other working modules namely 2 Stackers, a Pump House and ITT towers. The
intermediate transfer tower(ITT) mainly consists of HT Motors(High Tension Motor) and
Chutes and all the ITT towers are interconnected by the IBC(intermediate belt conveyor).The
Stackers are mainly running in two modes i.e. stacking mode and reclaiming mode depending
on the operation to be operated. Pump house at AVCTPL has a reservoir at which it store water
and by the help of pump, water is pumped up and supplied to the water sprinklers. Water
sprinklers are mainly used for dust separation purpose. In general it is used environment safety
1
by preventing the unnecessary air pollution due to blowing of coal dust. AVCTPL has a large
cargo storing tank called SILO which is used for storing the cargo in large amount and used
for wagon loading. There is an ITT Tower (i.e.ITT5) is present on the SILO. It also has so
many parts which can be discussed later.
AVCTPL has a substation which is equipped with all the advanced technology. The
substation of AVCTPL mainly consists of FEEDERS, UPS ROOM, LIGHTING
TRANSFORMER ROOM, INCOMERS, RELAY TRIPS and ALARMS. All the
transformers, machines, HT Motor and diesel generators (DG) controls are integrated at the
substation with all type of safety has been taking into account. RELAY TRIPS mainly gives
protection to the electrically operated modules and DGs are used to give supply instantly for
lighting purpose of the plant. DGs are running when there is a failure of main supply
encountered.
AVCTPL has a control room which is situated on the operational building. This
control room is designed in such a way that the total control of the plant can be further possible
from this Centre. Control room control equipment are fully based on automation and it is only
possible through the application SCADA and PLC. The control room has two big size monitors
which are connected with the close circuit cameras. So it may help to invigilate the problem
encountered with the working modules easily in short period time.
AVCTPL mainly focused on the safety of its labors as well as environments.so for
safety of its labor it provides safety helmets, safety jacket, gloves and safety boots to all the
labors those who are going to the working field and for environment safety it uses some
equipment like DSS (DRY DUST SEPARATION), WATER SPRINKLER etc.
2
CHAPTER 1: WORKING MODULES OF AVCTPL
1.1:INTRODUCTION
AVCTPL has number of working modules like ITT, IBC, STACKER & RECLAIMER,
SILO, PUMP HOUSE, SUBSTATION GRID etc. In this chapter we are predominantly
emphasizing on the ITT (Intermediate Transfer Tower) and describing its function which
designating the smooth operation of the plant.
1.2:INTERMEDIATETRANSFER TOWER (ITT)
1.2.1:DEFINITION
Intermediate transfer tower is one of the foremost functional unit of AVCTPL. It can be
demarcated as the tower which has a conveyor system which is again connected by a HT Motor
for running the conveyor belt in a particular direction depending on the mode of operation.
Further ITT TOWER also contains some mechanical systems like Pulley, scooping system,
Drop down system, PCS (Pull cord system), Hooter etc. and some electrical systems like BSS
(Belt side system) and metal detector (MD) and a HT Motor (3-ph induction motor). These are
the main system which can be found in each and every ITT Towers of AVCTPL.
SPECFICATION OF HT MOTOR:
[TABLE-1.0]
TYPE KW RPM EFFICIENCY VOLTAGE CURRENT DUTY POWER
FACTOR
3-PH 720 1492 94.5 6.6kv 77.0Amp S1 0.87
IMS (Inline magnetic Separator) is electromagnetic type which is used for the separation of
the ferrous metal. Apart from these equipment AVCTPL uses some PLC and SCADA
integrated circuit for automation control at the ITT Towers. There is a CBS (Chute Block
Switch) named switch present at all ITT Towers for the detection of any problem encountered
in the chute where the cargo is stored.
3
1.2.2:TYPES
In AVCTPL the ITT TOWER is broadly divided into 5 different Towers based upon their
position and working principle. These are namely as ITT1, ITT2, ITT3, ITT4 and ITT5.The
last tower i.e. ITT5 is present on the SILO.
1.2.2.0: ITT1
ITT1 is situated at the port side which provides the connecting medium between IBC1 and
IBC2. Its main function is to collect the cargo from hopper through IBC1 and sends it to ITT2.
1.2.2.1: ITT2
ITT2 is having a trichute which has a distinctive of bidirectional flow of cargo with the help of
a diverting gate. It mainly decides the flow direction of cargo to ITT3 or IIT4.So ITT2 is present
between ITT3 and ITT4.There is an electromechanical actuator is present in this tower.
1.2.2.2: ITT3
ITT3 provides the connecting medium between IBC3 and IBC2.It is not having any diverting
gate. It is unidirectional to ITT4.There is no additional electrical equipment is used over here.
1.2.2.3: ITT4
ITT4 receives cargo from ITT2 and ITT3 by means of a gate. The reclaiming process the major
factor of ITT4 which cannot be ignored. The cargo is carried out by the reclaiming process is
directly connected to the ITT5 present on the SILO.
1.2.2.4: ITT5
ITT5 is the last Tower of the AVCTPL ITT TOWERs which is present on the SILO. So
Here the cargo are store in the SILO and finally used for Wagon loading.
1.2.3:USE OF AUTOMATION
The use of automation increases safety, efficiency and performance of ITT. The use of PLC
and SCADA gives a very good performance on automatic control of the motor as well as in the
semiauto mode of operation. The program of plc is done by means of all the control condition
of electrical motor before starting. So before writing the program an engineer should focus on
4
all the braking and short circuit condition etc. All these mechanisms done so as to provide error
free environment and this leads to good performance of ITT.
Here we are using SIEMENS PLC device which are integrated with SCADA enable device
present at the control room of AVCTPL which is again connected to the other modules where
the control is required
AVCTPL also provides its WORKERS and ENGINEERS a pulse maker walky-talky for
direct contacts of workers with their respective engineers at the control room if any problem
encounter at any time.
1.3:INTERMEDIATE BELT CONVEYOR (IBC)
1.3.1: DEFINATION
IBC is the important constituent from all the working modules of AVCTPL through which
cargo is transferred. So IBC is having the high tensile strength because it is carrying the cargo
for the long distance.
In AVCTPL working area 1.5km length conveyor belt is present. As the belt is carrying cargo
so many protecting switch is present like BSS (Belt Side Switch), ZSS (Zero Speed switch),
BRS (Belt Rip Switch) etc. The function of all these parts are described in the use of
Automation part. Beside these protecting switch some other systems are connected with IBC
such as MD(METAL DETECTOR) is used to separate the ferrous metal from cargo which is
toned on the conveyor belt and a DROP DOWN SYSTEM is also used to prevent the initial
displacement of the cargo loaded belt which is caused due to sudden power supply to IBC.
One end of IBC is always connected to the motor and the other end is connected with the pulley.
1.3.2: TYPES
1.3.2.0: IBC1
IBC1 is related with the belt in which cargo is transferred from MHC (Mobile Harbor Crain)
to ITT1.
1.3.2.1: IBC2
The function of IBC2 is to transfer the cargo from ITT1 to ITT2 and from ITT2 to ITT3.Here
MD is present and it is used for the detection of the nonferrous metal.
5
1.3.2.2: IBC3
IBC3 is related to transfer of cargo from ITT3 to ITT4 and here two mode of operation is
present i.e. stacking mode and reclaiming mode in the respective operation.
1.3.2.3: IBC3A
IBC3A deals with the transfer of cargo from ITT2 to ITT4.Here also both stacking mode and
reclaiming mode is present.
1.3.2.4: IBC4
The main goal of IBC4 is to transfer the cargo from ITT4 to ITT5.MD is present over here.
1.3.3: USE OF AUTOMATION
The use of automation makes more efficient while IBC performing its operation. So in IBC,
many protecting switch is present like
BSS: It is an electrical device which internally connected with a sensor.It is used to prevent the
Cargo carrying belt to be one sided. So here a switch is present which is connected to
Belt support in order to sense the exact position of the belt. If belt is encountered any
problem with the position then the sensor activated and the related IBC panel is stop
working for the solution.
ZSS: The function of ZSS is to protect the belt, if the belt is cut in the middle or longitudinally.
As the motor is connected through IBC externally, during the cutting of belt in the
middle, motor will not stop but pulley will be stopped. A pulse formation mechanism is
connected to the pulley. If the pulley is stopped working then pulse formation will also
stopped. So we can easily determine by looking the pulse formation.
BRS: If the belt is cut vertically then neither motor nor pulley will stop.So in this condition we
are having a sensor i.e. transmitter and receiver and it is connected below the belt
Conveyor. Transmitter transmits the IR waves and receiver receives. If the belt is cut in
the middle then cargo will be wasted at the middle and disturbs the IR wave. After that
the sensor will activate and will stop the working of the HT Motor.
6
All the protecting switches are programed before the starting of motor accordingly. Apart from
these automation there is a manual switch present across the sides of the conveyor known as
PCS. This switch is connected through a rope so that any worker can pull the rope from any
position so as to stop the running conveyor and find the problem related to the belt then the
motor is disconnected from the gearbox.
1.4: STACKER AND RECLAIMER
1.4.1: DEFINATION
AVCTPL is having two Stacker and Reclaimer i.e. one is on the running mode and the other
one is on the standby mode (namely STACKER1 and STACKER2) .The function of the stacker
is to stack or creating the heap of cargo. The function of Reclaimer is to take the cargo from
the heap to the SILO. It is shortly designed as SCR (Stacker cum Reclaimer).SCR is having so
many functional units like E-house, conveyor and bucket etc.
1.4.2: MODES OF OPERATION
SCR is having two modes of operation like (i) STACKING
(ii) RECLAIMING
In stacking mode, cargo is collected from ITT2 and ITT3 and it is used for creating the heap of
12meter. There is two stack pile is present in AVCTPL campus where heap of cargo is made.
In reclaiming mode, the cargo is collected from the heap and allow for transferring the cargo
to the ITT4, then ITT5 and finally SILO respectively through the conveyor belt.
1.4.3: E-HOUSE AND ITS FUNCTION
The function of E-house is to provide the power supply to the working module present on the
SCR. As two SCRs are present so two E-house are available for SR1 and SR2.
SCR takes 6.6KV from the substation grid and step down to 0.433 KV/433V by means of DRY
TRANSFORMER.
7
SPECIFICATION OF DRY TRANSFORMER [E-HOUSE]:
The E-house acts as a small substation and used to provide the supply to different working
modules. It consists of PLC panel, AOP, MLDB (Main line Distribution Board).
[TABLE 1.1]
TYPE 3
FREQUENCY 50 HZ
AMB. Temperature 45 C
IMPEDANCERISE 5.14%
CORE ANDWINDING 3420
INSULATION CLASS F
NO LOAD VOLTAGE
HV 6.6 KV
LV O.433 KV
CURRENT
HV 109.35 AMP
LV 1666.72 AMP
CONNECTION TYPE -
8
1.4.4: USE OF AUTOMATION
The PLC used over here is basically SIEMENS. All the control logic deals with the sensors
and performed by means of RELAY which makes the system to be understand easily by every
Engineers.
1.5: SILO
1.5.1: DEFINATION
It is the most important constituent among all the working module of AVCTPL. The function
of SILO can be defined as to collect the cargo from ITT5 and stored at a large amount
approximately 3600 tonnes per hour and released it during wagon loading.
1.5.2: FUNCTIONAL PART OF SILO
The functional part of SILO is the tank where the cargo is stored and the control mechanism
related to the wagon loading.
SILO has so many working modules like POWER STACK, ACCUMULATOR and
CONTROL ROOM for wagon loading etc. In SILO, so many systems are present like,
HYDRAULIC SYSTEM, AIR BLASTING SYSTEM, DFDS(Dry Fog Separation
System).SILO is operated at operating pressure of 18000 psi(1psi=0.06895 Bar=0.06895*10^5
Pascal).
DFDS is the mixture of water and dust used to settled down the dry dust. This function is
similar to DSS.
In SILO, POWER STACK is present which consists of (i) MOTOR
(ii) PUMP
(iii) ACCUMULATOR
Motor and Pump are mechanically coupled. The motor having following specification which
is on the next page.
9
SPECIFICATION OF MOTOR:
[TABLE 1.2]
TYPE 3-PH IM
% EFFICIENCY 93.5%
AMB.TEMPERATURE 50 C
FRAME 250m
DUTY S1
IP 55
FREQUENCY 50hz
VOLT 415v
KW 55
AMP 97
RPM 1482
POWER FACTOR 0.86
Pump is having a big inlet diameter and a small outlet diameter and one end of the pump (outlet)
is connected by means of a FILTER to filter out any raw particle. The inlet of the pump is
hydraulic oil filter is having filtered unit of 10 microns. It is having 300hours maintenance
period.
In the power stack we are having the cooling systemby means of recirculation pump and Heat
exchanger by means of fan. Cooling pressure can be measured by cooling system pressure,
stand by pressure and pump pressure. Here the circulation type is 1-phase.
Air Blasting System is present to blast the compressed the compressed nitrogen cylinder if the
cargo remains in the heavy solid form in case of gate removal. So by doing this we are breaking
the heavy solid cargo to small pieces. At the top of the tank 4 Gates and 8 Cylinders and at
the bottom of the tank 2 Gates and 4 cylinders are present. The blasting of the cylinders is
done by means of the solenoid coils and it is operated by 24vDC supply.
The operation of the Gate opening and closing is done by means of hydraulic system during
wagon loading.
10
Why Hydraulic system is preferable then the Electrical system during opening and
closing of gate during wagon loading?
We can’t use electrical system during the opening and closing of Gate during wagon loading
because electrical systems are used on those systems where are needing sudden changes in the
operation but here we need a smooth operation. Another reason is this operation is done by
means of pressure, as hydraulic system is responsible for creating the pressure but electrical
system is not able to create any pressure.
.Apart from the step down transformer is also there for stepping down to low voltage and
rectifier arrangement is also there for conversion from ac to dc (24dc).
1.5.3: CHOICE OF NEW TECHNOLOGY AND USE OF AUTOMATION
SILO is having some new technology like use of sensor and automation in its working unit. In
the pump inlet we are having FILTER CLOG SENSOR to sense the filtered particle. We are
having proximity sensor like contact type and non-contact type. In contact type manually we
have to do and in non-contact type, below 5mm sensor will sense. Three types of proximity
sensor are available i.e. (i) fully close
(ii) Mid way
(iii) Fully open
If we consider a new technology, in power stack breather is present to remove the vapor from
the hydraulic oil.
3 modes of operation are dealing with the SILO i.e. auto, semiauto, manual mode. For
automatic mode of operation, we are having the PLC OF MARIT which is connected
through every sensor unit and performed operation by Relay
[P.T.O]
11
00
00
0
BLOCK DIAGRAM OF PLC CONTROL :( MERIT)
[FIGURE- 1]
Here the term secondary is referred as the stand by, RB refers to the relay Board. MCB refers
as Miniature circuit Breaker. RS 232 is used for communication of data but here technically
it is called as command CPU is involved for execution of all the command.
So many command is given by control room of SILO i.e. Gate command open/close, Motor
command, solenoid command for blasting etc.
PRIMARY
CPU
CPU
SECONDARY
CPU
PRIMARY
I/O
SECONDARY
I/O
RB1 RB2 RB3 RB4
RB5 RB6 RB7
MCB1 MCB2 MCB3 MCB4 MCB5 MCB6 MCB7 MCB8
MCB16MCB15MCB14MCB13MCB12MCB11MCB10MCB9
POWER
SOCKET
MCB17 RS232
RS 232
LAN
CONVERTER
24 DC
12
00
00
0
1.5.4:WAGON LOADING
It is the final touch of the entire processing system of AVCTPL. Here the wagon is present on
the track and the open/close command is given from the control room. According to the
command, cargo is put into the respective wagon and wagon loading takes place.
There are two sensors relates with the wagon loading i.e. BOXN and BOXNHS. BOXN sensor
is present at the height of 1 meter from the ground level. BOXNHS SENSOR is present at the
height of 1.2 meter from the ground level which gives the position of wagon.
1.6:PUMP HOUSE
1.6.1:NEED OF PUMP HOUSE
Pump house is the very important working module not only for AVCTPL but also for
environmental point of view. As AVCTPL is basically a coal port industry so there is
occurrence of dust during stacking, reclaiming and wagon loading etc. But the thing is that we
can’t compromise for the environmental safety. So any how we have to settle down the dust
by using DSS and water sprinkler etc.
VPT has made a conditional attachment with AVCTPL that heap should not exceed more then
12meter. The strong wind flow also makes the dust in heavy amount. So the need of pump
house becomes more essential for AVCTPL.
1.6.2:MAIN COMPONENTOF PUMP HOUSE
The main component of pump house is water sprinkler and pump. The pump used over here is
basically (i) CENTRIFUGAL PUMP and (ii) INLINE PUMP. Water is collected from the large
reservoir by means of pump and is supplied to sprinkler.
The motor in which pump is mechanically coupled is normally 3-ph Induction motor.
SPECIFICATION OF MOTOR [PUMP HOUSE]
[TABLE-1.3]
TYPE 3-Ph
FRAME 160 meter
VOLTAGE 415V
CURRENT 21.0 AMP
FEQUENCY 50 Hz
EFFICIENCY 88.4%
CONNECTION TYPE
RPM 1450
INSULATION TYPE F
13
00
00
0
Pump is having capacity 360HP, pressure 0.5kg/m^2 and speed1170rpm
Here also we are having auto, semiauto and manual mode operation. So we can control the
operation of the sprinkler directly from the control room or we can do manually that depends
on the choice of the operation. The details layout of the DS SYSTEM is explained in
CHAPTER 2.
14
00
00
0
CHAPTER 2: CONTROL ROOM
2.1:INTRODUCTION
AVCTPL is having a control room in which all the command for every operation, certain
instruction and automatic mode of operation is possible. The thing is that here we are having a
complete visualization of each and every working site. Here every time engineer scrutinizing
the operation of entire working module and giving the required instruction and command.
The presence of control room giving very efficient operation of AVCTPL. More over here we
can see the wagon loading activity.
2.2:LAYOUT VIEW OF AVCTPL
In control room we can see the entire layout of the AVCTPL. So each and every site of working
module can be seen with respect to its function in the control room.
[FIGURE-2]
As we have discussed the entire working modules which are present on the layout in the
previous chapter. Here we only focus on the short notation of the variables like,
1. Z- ZSS 2. B- BSS 3.P- PCS 4. MD- METAL DETECTOR
15
2.3:LAYOUT VIEW OF DS SYSTEM
As we have discussed the presence of DS system is very much essential for the environmental
safety point of view. Here we careful focus on the layout.
[ FIGURE-3]
In this layout we are having total 55 water sprinkler which are operated by means of side wise
like, in STOCK PILE 1 first sprinkler no.1 and sprinkler no.2 will turn on then 2 and 22
respectively. All the sprinklers are operated on the same sequence.
16
00
00
CHAPTER 3: AVCTPL SUBSTATION GRID
3.1:MAIN OBJECTIVE OF THE DISTRIBUTION SYSTEM
The main planning approach for electrical distribution system to optimize the number of
feeders and their roots. It is very much essential for the electrical substation is to maximize the
network reliability and minimize the total installation and operational cost.
So from generation of electricity to utilization distribution system plays an intermediary
operation. So without distribution system the consumers can’t get the electricity from the
generation station.
Here also AVCTPL is having own substation grid and with a distribution system to each
working modules which readily depends on the electricity.
3.2:FUNCTIONALPART OF SUBSTATION GRID
The main functional unit of SUBSTATION GRID are (i) Transformer
(ii) CT & PT
(iii) ACB & VCB
(iv) Feeder and distribution panel
(v) Reactive power compensation
(vi) UPS
(vii) DG Supply
1. TRANSFORMER
We can say that transformer is the main constituent of the entire sub-station because
step up and step down of the voltage can be done by means of transformer. AVCTPL substation
Grid receives the 33KV supply from the APEPDCL. This high voltage is stepping down to 6.6
KV and this 6.6 KV is again stepping down to 433 KV. We are using both 6.6 KV for the
working of all HT MOTOR and 433KV for the DISTRIBUTION and LIGHTING purpose.
17
00
00
0
There are total 4 step down transformer and 1 one to one transformer is there. Out of 4
transformer two transformers are used for 33KV/ 6.6KV and two transformer are used for
6.6KV/433V. The thing is that one is always running and other one is always on the stand by
position.
Apart from that a single one to one transformer is there used for the lightening purpose, so
sudden change in the fluctuation of the voltage can be filtered out. This transformer is dry type
transformer.
There are two methods are used for transformer tap changing i.e. 1. On load tap changer
2. Off load tap changer
During the on load tap changer method the transformer is connected through the load and
charged condition and during the off load tap changer method, we have to off the transformer
first and change the tap. The changing of tap is required because we can’t get the constant input
voltage for the transformer so there is a problem of getting the desired output.
33KV/6.6KV transformer is called as on load tap changer and 6.6KV/0.433KV transformer
is called as off load tap changer.
2. CT & PT
CT- current Transformer
PT- Potential Transformer
CT is used for current measurement and PT is used for potential measurement.
There are two types of PT used namely LINE PT and BUS PT.
3. ACB & VCB
ACB- Air Circuit Breaker
VCB- Vaccum Circuit Breaker
18
00
00
0
3. FEEDERAND DISTRIBUTION PANEL
We are having two FEEDERS like FEEER1 and FEEDER2 and its main function is to feed the
power from VCB (Vaccum Circuit Breaker) to TRANSFORMER for step down of
high.voltage. There are two INCOMER are present like INCOMER1 and INCOMER2 which
are used for giving the power to all HT MOTOR. Two INCOMERS are connected by means
of BUSCOUPLER. BUS PT is used over here to give the information about the INCOMER
that which one is running and finally 6.6KV is coming from the INCOMER is stepping down
to 0.433KV and used for the distribution
[P.T.O]
19
00
00
0
AVCTPL is having a panel like
[FIGURE-4]
PANEL TYPE 1 (MAIN)
PANEL TYPE 2(DISTRIBUTION)
MVAPFC1 SPARE PH CSS1 SPARE SR1 SPARE MHC1 SPARE
IBC1 IBC2 IBC3 SPARE DIST TRAFO1 SPARE BUS APT INCOMER1
BUS COUPLER BUS PT WITH INCOMER2 DISTTRAFO2 SPARE IBC3A IBC4-M1 IBC4-M-2
BUS RISER
SPARE MHC2 SPARE SR2 SPARE SILO CSS2 MV APFC SPARE2
PANEL TYPE 3
MLDB- MAIN LINE DISTRIBUTION BOARD PH- PUMP HOUSE
PCC- POWER CONTROL CIRCUIT MCC- MOTOR CONTROL CIRCUIT
1 2 3 4 5 6 7 8
161514131211109
2423222120191817
28272625 29 30 31 32
BETTERY
CHARGER1
INCOMER3
10KW
IN
MLDB DG INCOMER
BUS
COUPLER2
MCC2 PCC
INCOMER
2
BUS
COUPLER1
PCC
INCOMER2
1
FEEDER1
2
INCOMER
3
FEEDER2
20
00
00
AMFC- AUTO MAIN FAILURE CONTROLLER:
[AMFC provide consistent power supply to the load in the absence of main supply.]
The function of AMFC is to maintain the constant power supply to the load in the absence of
the main supply. It is having DG set of protection.
This panel supplies the power that can be shown below:
[TABLE-1.4]
PANEL NO. NAME OF THE PANEL POWER
3 PH CSS1 500 KVA
5 SR1 1250 KVA
7 MHC1 1350 KW
9 IBC-1 220 KW
10 IBC-2 450 KW
11 IBC-3 720 KW
12 DIST TRAFO 1.5 MVA
22 IBC 3A 720 KW
23 IBC-4-M-A 450 KW
28 SR2 1250 MVA
31 MV APFC2 1400 KVAR
The function of APFC (Automatic power factor control) is to control the power factor that can
be discussed in the reactive power compensation part.
MCC panel supplies the power to all HT MOTOR present at the ITT. This panel is having
THRUSTER BRAKE for all the IBC and all the induction related to the ITT can be seen like,
oil circulation trip, radiator pump trip, radiator pump on, radiator pump off, actuator
on and actuator off etc.
21
00
00
0
3.3:A BRIEF LAY OUT OF DISTRIBUTION OF AVCTPL
[FIGURE-5]
LA- lightening arrest NGR- Natural Ground Register
ACB- Air Circuit Breaker VCB-Vaccum Circuit Breaker
22
00
00
0
3.4:THE NEW GLANCE OF TECHNOLOGY
AVCTPL substation grid is having various new technology like TRAFO FAULT RELAY,
MASTER TRIP RELAY, ANNOUCIATOR, MULTIFUNCTIONAL METER, O/C &
E/F RELAY and PROTECTIVE RELAY etc.
TRAFO FAULT RELAY:
The use of TRAFO FAULT RELAY is to protect the transformer from overcurrent. It is of
IDMT (Inverse Definite Time Relay Type).
MASTER TRIP RELAY:
MASTER TRIP RELAY is the main trip relay to which all the protection relays like distance
relays, overcurrent relays, earth fault relays and differential relays are connected in parallel.
That means master trip relays are providing the type of fault caused in the electrical drives to
the user in the display board continuously unless until it is respond by someone.
ANNOUCIATOR:
An ANNOUCIATOR panel is a centralized warning panel where a group of light used to
display the message related to the central industrial purpose. It is very costly to install and it is
dedicated to the wiring to the alarm initiating device to the process plant.
O/C & E/F RELAY:
This relay is used in the transformer winding in terms of CT and PT. Suppose three phase is
there having rated current 100A in each phase. If the current flow in one phase is above the
100A then this will go to OVER CURRENT RELAY (O/C) but if the current flow in any one
phase is below the rated current i.e. 10-20 AMP then this will go for EARTH FAULT RELAY
(E/F).
Apart from these there is a presence of MULTIFUNCTIONAL METER in which we can
able to see all the current rating like voltage, current, frequency, power factor, kw, KVAR,
KVA and %THD(TOTAL HARMONIC DISTRIBUTION) etc.
LA (lightening Arrester) is present to protect the cable from high flash over voltage. The
rated lightening impulse withstand voltage of each feeder is 170 KV.
23
00
00
0
SPECIFICATION OF DRY TRANSFORMER (LIGHTING)
In the entire substation the automatic modes of operation is also available by means of PLC
and SCADA. We are having the PLC of SIEMENS in all the panel. But practically semi auto
mode is used over here.
3.5:CASE STUDY ON THE DISTRIBUTION SYSTEM:
We have studied all the working unit of substation and we have seen each and every working
performance of each unit. But my point view if there is a presence of SF-6 Circuit Breaker
[TABLE-1.5]
TYPE
3
FREQUENCY 50 HZ
AMB. Temperature 45 C
VECTORGROUP Dy11
CORE ANDWINDING 3420
INSULATION CLASS F
NO LOAD VOLTAGE
PRIMARY 0.415KV
SECONDARY
0.415KV
CURRENT
PRIM 486.92 AMP
SEC 486.92 AMP
POWER 350 KVA
24
00
00
0
instead of ACB and VCB then then the performance may be improved. Otherwise each
working module present over here is having very good eye-catching performance.
3.6:UPS SYSTEM
The meaning of UPS is uninterrupted power supply. The meaning itself defines its
functionalities that the power supply should be continuous. UPS system consists of
RECTIFIER, INVERTER, SMPS (Switch Mode Power Supply) and BATTERY. Here ac
supply is converted to dc by means of rectifier and stored in battery and in the absence of main
supply that stored dc is again converted to ac by means of inverter.
LAYOUT OF UPS SYSTEM:
[FIGURE-6]:
MANUAL BYPASS
BYPASS ISOLATOR
AC SUPPLY
O/P
SWITCH MODE INVERTER POWER
POWER SUPPLY(SMPS) STSW
BATTERY ISOLATOR
BATTERY CHARGER
BATTERY CHARGER is used to store the DC supply which is converted from AC in terms
of RECTIFIER.
RECTIFIER INVERTER
25
00
00
0
3.7:DG SUPPLY
The function of DG supply is for back up purpose. The DG means DIESEL GENERATOR
which is connected by the BUS COUPLER in between two incomer. The performance of
AMFC is related to the DG SUPPLY. If the main supply is not present then the DG supply is
provided only for the lighting purpose.
The DG is connected to the main supply as shown below.
LOAD
DG SUPPLY KG KM T/F
AMF UNIT
[FIGURE-7]
3.8:REACTIVE POWER COMPENSATION
As all the load used over here is normally inductive load so the lagging power is more .So we
have compensate those lagging power. As Substation draws the heavy amount of power from
the APEPDCL grid so any how substation is to maintain the constant power factor otherwise
current consumption increases. In order to balance both the operation substation is provided
with CAPACITOR BANK in which reactive power is compensated and a constant power
factor is maintained. In substation we are having the CAPACITOR BANK of rating 1800.55
KVAR.
Actually the entire performance of the capacitor bank is known as APFC (Automatic Power
factor Control).
26
00
00
0
The technical function of APFC is to maintain the constant power factor at a suitable limit.
The capacitor bank is connected across the 3-Ph bus line by means of relay.
SPECIFICATION OF APFC (AUTOMATIC POWER FACTOR CONTROL):
NET O/P KVAR 1800.55 KVAR.7.72 KV
RATED KVAR 1400 KVAR,6.6 KV
STEP CONFIGURATION 2*250KVAR + 2*450 KVAR
RATED CURRENT 122.47AMP
NO OF PHASE 3-Ph
RATED FREQUENCY 50 Hz
TEMP RISE 15 C
CONNECTION EXTERNAL
[TABLE-1.6]
3.9:SOME INDUSTRIAL MEASUREMENT
In AVCTPL we are having so many industrial measurement like MULTIMETRE,
MEGGER, CT & PT and TONG TESTER (CLAMP METER) etc.
In MULTIMETER we can measure the voltage, current, resistance etc. But now a days we
are using the TONG TESTER (CLAMP METER) in which we can measure the voltage
(ac/dc), resistance.
MEGGER is used for testing the HT motor before running means whether the motor is free
from short circuit or not and by using this we can measure the high resistance. If the MEGGER
reading is ‘0’ then the motor is unhealthy and if the motor reading is ‘infinite’ then motor
is healthy.
27
00
00
0
CHAPTER 4: SAFETY
4.1:DEFINITION
SAFETY is the state of being “SAFE”, the condition of being protected against physical,
social, financial, consequences of failure, damage, error, accidents, harm or any other events
which could be considered undesirable. Safety can also be defined to be the control of
recognized hazards to achieve an acceptable level of risk. This can take the form of being
protected from the event or being protected from the event or from exposure to something that
causes health or economical losses. It can include protection of people or of possessions.
SAFETY is the foremost thing which is engrossed formerly by any hazardous industries like
coal industry.
4.2: NEED OF SAFETYFOR AVCTPL
In view of the above discussion AVCTPL is therefore need of the hour. There are some direct
costs/effects of an accident but there are certain indirect costs involved in it also e.g. machine
down time, damage of machine, ideal time of nearby equipment and horror created among
workers, loss of time etc. in aid cost compensation, legal implications and allied costs etc. So
safety measures would not only eliminates/avoid above cost but would mean performing their
moral responsibility towards workmen/ operators also.
More over AVCTPL is a coal industry so more focus on safety is required towards the health
of the workers and towards the environment for the smooth running of the industry. An unsafe
condition may be present in various forms i.e. in the faulty or defective electrical fittings, use
of defective tools, blowing of coal dust on the air etc. so to prevent the occurrence of oath of
accidents, unsafe acts have to be avoided or checked properly for the safety purpose at
AVCTPL.
28
00
00
0
4.3:SAFETY EQUIPMENTSAND PROCEDURE
SAFETY INSTRUCTION
AVCTPL provides so many safety instruction like:
1. Use Helmet, Safety reflection jacket and Gloves while entering to the any working site.
2. Don’t touch any machineries without having the proper knowledge and don’t go alone to
any working site.
3. Read the instruction of any machine carefully while enter and touch the machine and can
take the reading.
4. See the Guard ring and don’t cross the guard ring during running condition. (If the guard
ring is not visible by you then tell your instructor to make you confirm about guard ring)
5. Don’t move under the conveyor belt during running.
6. Leave the working site if you hear any alarm sound.
7. Don’t go to heap site during the strong wind flow.
8. Carefully read the instruction guide given below the working module in order to run that
working module.
SAFETY equipment provided by the AVCTPL are HELMET, SAFETY REFLECTION
JACKET and GLOVES.
For the Environmental Safety concern AVCTPL provides water sprinkler, DSS and DFDS
in the dust producing site. Horticulture is also done in its campus to produce a pollution free
environment.
29
00
00
0
REFERENCE
1. ELECTRIC MOTOR HAND BOOK, by James L. Kirtley, Jr., H.Wayane Beaty,
Nirmal K Ghai, Steven B Leeb, Richard H.Lyon.
2. INDUSTRIAL POWER ENGINEERING AND APPLICATION, by K C Agarwaal.
3. ELECTRICAL GENERATION AND DISTRIBUTION SYSTEMS AND POWER
QUALITY, by Rey G.R.
4. POWER SYSTEM-ANALYSIS AND DESIGN, by B.R. Gupta.
30
00
00
Electrical equipment study of AVCTPL coal terminal port

More Related Content

What's hot

Analysis and control of four quadrant operation of three phase brushless dc (...
Analysis and control of four quadrant operation of three phase brushless dc (...Analysis and control of four quadrant operation of three phase brushless dc (...
Analysis and control of four quadrant operation of three phase brushless dc (...eSAT Publishing House
 
speed control of three phase induction motor using IOT
speed control of three phase induction motor using IOTspeed control of three phase induction motor using IOT
speed control of three phase induction motor using IOTswaroop009
 
SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...
SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...
SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...Editor IJMTER
 
IRJET - Renewable Energy based Robotic Grass Cutter using IoT
IRJET - Renewable Energy based Robotic Grass Cutter using IoTIRJET - Renewable Energy based Robotic Grass Cutter using IoT
IRJET - Renewable Energy based Robotic Grass Cutter using IoTIRJET Journal
 
Stepper Motor Drive For Position Control in Robotic Applications
Stepper Motor Drive For Position Control in Robotic ApplicationsStepper Motor Drive For Position Control in Robotic Applications
Stepper Motor Drive For Position Control in Robotic Applicationsijiert bestjournal
 
Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover IJSRED
 
Theory and Analysis of Three Phase Induction Motor using Written Pole Technology
Theory and Analysis of Three Phase Induction Motor using Written Pole TechnologyTheory and Analysis of Three Phase Induction Motor using Written Pole Technology
Theory and Analysis of Three Phase Induction Motor using Written Pole TechnologyIOSRJEEE
 
Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...
Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...
Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...IJSRD
 
Investigation in Induction Motor Starting and Speed Control with Variable Fre...
Investigation in Induction Motor Starting and Speed Control with Variable Fre...Investigation in Induction Motor Starting and Speed Control with Variable Fre...
Investigation in Induction Motor Starting and Speed Control with Variable Fre...IRJET Journal
 
INTERNSHIP REPORT (FINAL)
INTERNSHIP REPORT (FINAL)INTERNSHIP REPORT (FINAL)
INTERNSHIP REPORT (FINAL)Sindhuja Balaji
 
Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...
Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...
Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...IJERA Editor
 
Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...IAEME Publication
 
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVESA NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVEScscpconf
 
IRJET- Smart Battery Management
IRJET- Smart Battery ManagementIRJET- Smart Battery Management
IRJET- Smart Battery ManagementIRJET Journal
 
Design and development of grid tie inverter with closed loop spwm single stag...
Design and development of grid tie inverter with closed loop spwm single stag...Design and development of grid tie inverter with closed loop spwm single stag...
Design and development of grid tie inverter with closed loop spwm single stag...eSAT Journals
 
IRJET- Speed Control of BLDC Motor using PID Tuned Fuzzy Controller
IRJET-  	  Speed Control of BLDC Motor using PID Tuned Fuzzy ControllerIRJET-  	  Speed Control of BLDC Motor using PID Tuned Fuzzy Controller
IRJET- Speed Control of BLDC Motor using PID Tuned Fuzzy ControllerIRJET Journal
 

What's hot (20)

Analysis and control of four quadrant operation of three phase brushless dc (...
Analysis and control of four quadrant operation of three phase brushless dc (...Analysis and control of four quadrant operation of three phase brushless dc (...
Analysis and control of four quadrant operation of three phase brushless dc (...
 
speed control of three phase induction motor using IOT
speed control of three phase induction motor using IOTspeed control of three phase induction motor using IOT
speed control of three phase induction motor using IOT
 
Brushless DC Motor Speed Controller for Electric Motorbike
Brushless DC Motor Speed Controller for Electric MotorbikeBrushless DC Motor Speed Controller for Electric Motorbike
Brushless DC Motor Speed Controller for Electric Motorbike
 
SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...
SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...
SPEED SYNCHRONIZATION OF MASTER –SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR...
 
IRJET - Renewable Energy based Robotic Grass Cutter using IoT
IRJET - Renewable Energy based Robotic Grass Cutter using IoTIRJET - Renewable Energy based Robotic Grass Cutter using IoT
IRJET - Renewable Energy based Robotic Grass Cutter using IoT
 
Stepper Motor Drive For Position Control in Robotic Applications
Stepper Motor Drive For Position Control in Robotic ApplicationsStepper Motor Drive For Position Control in Robotic Applications
Stepper Motor Drive For Position Control in Robotic Applications
 
Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover
 
Theory and Analysis of Three Phase Induction Motor using Written Pole Technology
Theory and Analysis of Three Phase Induction Motor using Written Pole TechnologyTheory and Analysis of Three Phase Induction Motor using Written Pole Technology
Theory and Analysis of Three Phase Induction Motor using Written Pole Technology
 
Loss minimization DTC electric motor drive system based on adaptive ANN strategy
Loss minimization DTC electric motor drive system based on adaptive ANN strategyLoss minimization DTC electric motor drive system based on adaptive ANN strategy
Loss minimization DTC electric motor drive system based on adaptive ANN strategy
 
Project paper
Project paperProject paper
Project paper
 
Simulation of Automatic speed control DC Drive
Simulation of Automatic speed control DC DriveSimulation of Automatic speed control DC Drive
Simulation of Automatic speed control DC Drive
 
Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...
Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...
Analysis of Induction Motor Speed Control Using SCADA Based Drive Operated Sy...
 
Investigation in Induction Motor Starting and Speed Control with Variable Fre...
Investigation in Induction Motor Starting and Speed Control with Variable Fre...Investigation in Induction Motor Starting and Speed Control with Variable Fre...
Investigation in Induction Motor Starting and Speed Control with Variable Fre...
 
INTERNSHIP REPORT (FINAL)
INTERNSHIP REPORT (FINAL)INTERNSHIP REPORT (FINAL)
INTERNSHIP REPORT (FINAL)
 
Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...
Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...
Speed Synchronization of Multiple Bldcmotors In Textile &Paper Mills Using Mi...
 
Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...Design of embedded based three phase preventor and selector system for indust...
Design of embedded based three phase preventor and selector system for indust...
 
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVESA NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
A NEW APPROACH TO DTC METHOD FOR BLDC MOTOR ADJUSTABLE SPEED DRIVES
 
IRJET- Smart Battery Management
IRJET- Smart Battery ManagementIRJET- Smart Battery Management
IRJET- Smart Battery Management
 
Design and development of grid tie inverter with closed loop spwm single stag...
Design and development of grid tie inverter with closed loop spwm single stag...Design and development of grid tie inverter with closed loop spwm single stag...
Design and development of grid tie inverter with closed loop spwm single stag...
 
IRJET- Speed Control of BLDC Motor using PID Tuned Fuzzy Controller
IRJET-  	  Speed Control of BLDC Motor using PID Tuned Fuzzy ControllerIRJET-  	  Speed Control of BLDC Motor using PID Tuned Fuzzy Controller
IRJET- Speed Control of BLDC Motor using PID Tuned Fuzzy Controller
 

Viewers also liked

Electrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuitElectrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuitRLarivee
 
Programmable Logic Controller(PLC)
Programmable Logic Controller(PLC)Programmable Logic Controller(PLC)
Programmable Logic Controller(PLC)Ahad Hossain
 
Airfield Lighting Introductory
Airfield Lighting IntroductoryAirfield Lighting Introductory
Airfield Lighting IntroductoryMilten Jose
 
airside operation 3
airside operation 3airside operation 3
airside operation 3AiDY
 
Scada and power system automation
Scada and power system automationScada and power system automation
Scada and power system automationShubham Kapoor
 

Viewers also liked (12)

Electrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuitElectrical component at airport for airfield lighting circuit
Electrical component at airport for airfield lighting circuit
 
Project on PLC (SILO)
Project on PLC (SILO)Project on PLC (SILO)
Project on PLC (SILO)
 
Programmable Logic Controller(PLC)
Programmable Logic Controller(PLC)Programmable Logic Controller(PLC)
Programmable Logic Controller(PLC)
 
Airfield Lighting Introductory
Airfield Lighting IntroductoryAirfield Lighting Introductory
Airfield Lighting Introductory
 
Airfield ground lighting (AGL)
Airfield ground lighting (AGL)Airfield ground lighting (AGL)
Airfield ground lighting (AGL)
 
airside operation 3
airside operation 3airside operation 3
airside operation 3
 
Basic runway length
Basic runway lengthBasic runway length
Basic runway length
 
Airport lighting
Airport lightingAirport lighting
Airport lighting
 
Airports presentation
Airports presentationAirports presentation
Airports presentation
 
AGL Engineer
AGL EngineerAGL Engineer
AGL Engineer
 
Scada and power system automation
Scada and power system automationScada and power system automation
Scada and power system automation
 
Airport Layout
Airport LayoutAirport Layout
Airport Layout
 

Similar to Electrical equipment study of AVCTPL coal terminal port

Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Devendra Kumar
 
IRJET- Tap Changing using Solid State Devices for Single Phase Transformer
IRJET- Tap Changing using Solid State Devices for Single Phase TransformerIRJET- Tap Changing using Solid State Devices for Single Phase Transformer
IRJET- Tap Changing using Solid State Devices for Single Phase TransformerIRJET Journal
 
automatic phase changer in three phase supply
automatic phase changer in three phase supplyautomatic phase changer in three phase supply
automatic phase changer in three phase supplyamaljo joju e
 
TAS MRS LAS COLONY.pdf
TAS MRS LAS COLONY.pdfTAS MRS LAS COLONY.pdf
TAS MRS LAS COLONY.pdfpriyanshupal26
 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments Anuj Gupta
 
220 kv Sub- Station By Akshit Jain Majhola Moradabad .docx
220 kv Sub- Station By Akshit Jain Majhola Moradabad .docx220 kv Sub- Station By Akshit Jain Majhola Moradabad .docx
220 kv Sub- Station By Akshit Jain Majhola Moradabad .docxAkshit Jain
 
Dlw summer trainning project electrical branch by shubhang pandey
Dlw summer trainning project electrical branch by shubhang pandeyDlw summer trainning project electrical branch by shubhang pandey
Dlw summer trainning project electrical branch by shubhang pandeyshubhangpandey5
 
IRJET-E-Blood Bank Application using Cloud Computing
IRJET-E-Blood Bank Application using Cloud ComputingIRJET-E-Blood Bank Application using Cloud Computing
IRJET-E-Blood Bank Application using Cloud ComputingIRJET Journal
 
Performance Evaluation of Small Hydro Power Plant
Performance Evaluation of Small Hydro Power PlantPerformance Evaluation of Small Hydro Power Plant
Performance Evaluation of Small Hydro Power PlantGirish Gupta
 
Project report - Industrial applications of PLCs and Drives
Project report - Industrial applications of PLCs and DrivesProject report - Industrial applications of PLCs and Drives
Project report - Industrial applications of PLCs and DrivesRAGHAVENDRA M R
 
Research Internship Report
Research Internship ReportResearch Internship Report
Research Internship ReportArpitSuthar7
 
IRJET- Harnessing the Energy Generated from Staircase using Piezoelectric...
IRJET-  	  Harnessing the Energy Generated from Staircase using Piezoelectric...IRJET-  	  Harnessing the Energy Generated from Staircase using Piezoelectric...
IRJET- Harnessing the Energy Generated from Staircase using Piezoelectric...IRJET Journal
 
Training report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalTraining report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalPiyush Dwivedi
 
TBEA ENERGY (INDIA) PVT LTD
TBEA ENERGY (INDIA) PVT LTDTBEA ENERGY (INDIA) PVT LTD
TBEA ENERGY (INDIA) PVT LTDRaviraj solanki
 
SIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVE
SIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVESIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVE
SIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVEEditor IJMTER
 
IRJET - Single Phase Inverter using MOSFET
IRJET -  	  Single Phase Inverter using MOSFETIRJET -  	  Single Phase Inverter using MOSFET
IRJET - Single Phase Inverter using MOSFETIRJET Journal
 
A review on Design and Fabrication of Frumentum Maskin
A review on Design and Fabrication of Frumentum MaskinA review on Design and Fabrication of Frumentum Maskin
A review on Design and Fabrication of Frumentum MaskinIRJET Journal
 
Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1Kawsar Ahmed
 
C&S Electric Summer Training Report
C&S Electric Summer Training ReportC&S Electric Summer Training Report
C&S Electric Summer Training ReportParas Pratap
 

Similar to Electrical equipment study of AVCTPL coal terminal port (20)

Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
Industrial training report on dlw varanasi for Main Receiving Substation, Tra...
 
IRJET- Tap Changing using Solid State Devices for Single Phase Transformer
IRJET- Tap Changing using Solid State Devices for Single Phase TransformerIRJET- Tap Changing using Solid State Devices for Single Phase Transformer
IRJET- Tap Changing using Solid State Devices for Single Phase Transformer
 
automatic phase changer in three phase supply
automatic phase changer in three phase supplyautomatic phase changer in three phase supply
automatic phase changer in three phase supply
 
TAS MRS LAS COLONY.pdf
TAS MRS LAS COLONY.pdfTAS MRS LAS COLONY.pdf
TAS MRS LAS COLONY.pdf
 
BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments BSES - Maintaince of EHV Equipments
BSES - Maintaince of EHV Equipments
 
220 kv Sub- Station By Akshit Jain Majhola Moradabad .docx
220 kv Sub- Station By Akshit Jain Majhola Moradabad .docx220 kv Sub- Station By Akshit Jain Majhola Moradabad .docx
220 kv Sub- Station By Akshit Jain Majhola Moradabad .docx
 
Dlw summer trainning project electrical branch by shubhang pandey
Dlw summer trainning project electrical branch by shubhang pandeyDlw summer trainning project electrical branch by shubhang pandey
Dlw summer trainning project electrical branch by shubhang pandey
 
IRJET-E-Blood Bank Application using Cloud Computing
IRJET-E-Blood Bank Application using Cloud ComputingIRJET-E-Blood Bank Application using Cloud Computing
IRJET-E-Blood Bank Application using Cloud Computing
 
Performance Evaluation of Small Hydro Power Plant
Performance Evaluation of Small Hydro Power PlantPerformance Evaluation of Small Hydro Power Plant
Performance Evaluation of Small Hydro Power Plant
 
Manoj
ManojManoj
Manoj
 
Project report - Industrial applications of PLCs and Drives
Project report - Industrial applications of PLCs and DrivesProject report - Industrial applications of PLCs and Drives
Project report - Industrial applications of PLCs and Drives
 
Research Internship Report
Research Internship ReportResearch Internship Report
Research Internship Report
 
IRJET- Harnessing the Energy Generated from Staircase using Piezoelectric...
IRJET-  	  Harnessing the Energy Generated from Staircase using Piezoelectric...IRJET-  	  Harnessing the Energy Generated from Staircase using Piezoelectric...
IRJET- Harnessing the Energy Generated from Staircase using Piezoelectric...
 
Training report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electricalTraining report of secl , khairha coal mine , sohagpur area for electrical
Training report of secl , khairha coal mine , sohagpur area for electrical
 
TBEA ENERGY (INDIA) PVT LTD
TBEA ENERGY (INDIA) PVT LTDTBEA ENERGY (INDIA) PVT LTD
TBEA ENERGY (INDIA) PVT LTD
 
SIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVE
SIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVESIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVE
SIMULATION AND ANALYSIS OF TIBC FOR INDUCTION MOTOR DRIVE
 
IRJET - Single Phase Inverter using MOSFET
IRJET -  	  Single Phase Inverter using MOSFETIRJET -  	  Single Phase Inverter using MOSFET
IRJET - Single Phase Inverter using MOSFET
 
A review on Design and Fabrication of Frumentum Maskin
A review on Design and Fabrication of Frumentum MaskinA review on Design and Fabrication of Frumentum Maskin
A review on Design and Fabrication of Frumentum Maskin
 
Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1Presentation on power distribution, operation and maintenance in comilla pbs 1
Presentation on power distribution, operation and maintenance in comilla pbs 1
 
C&S Electric Summer Training Report
C&S Electric Summer Training ReportC&S Electric Summer Training Report
C&S Electric Summer Training Report
 

Electrical equipment study of AVCTPL coal terminal port

  • 1. A study on Electrical equipment used in working modules and power distribution at AVCTPL An Industrial Project Report Submitted In Partial Fulfillment of the requirements for the Award of the Degree of BACHELOR OF TECHNOLOGY IN ELECTRICAL ENGINEERING Submitted by DEEPAK KUMAR DASH Under the Esteemed Guidance of Mr.D.Kiran Kumar (Associate Manager, H.R., AVCTPL) Mr.Siddhant Chatterjee (Head of Engineering Department, AVCTPL) DEPARTMENT OF ELECTRICAL ENGINEERING GANDHI INSTITUTE OF ENGINEERING & TECHNOLOGY GUNUPUR – 765 022, Dist.: Rayagada (Odisha), India (Approved by AICTE, Govt. of Orissa and Affiliated to Biju Patnaik University of Technology) 2015-16
  • 2. DECLARATION I hereby declare that the Industrial project “A study of electrical equipment used in working modules and power distribution at AVCTPL” submitted for the B.Tech Degree is done by me with the association of “Adani Vizag Coal Terminal Port Pvt.ltd, Port Area, Visakhapatnam, Andhra Pradesh 530035, India.” Name & Signature of the Student: SaswatMohapatra Place: AVCTPL, Vizag Date: 15-06-2015
  • 3. ACKNOWLEDGEMENT We would like to express our profound sense of gratitude to all for having helped us in completing this dissertation. We would like to express our deep felt gratitude and sincere thanks to our guide “Mr.B.Pradeep Kumar, H.O.D., electrical” for his skillful guidance, timely suggestions and encouragement in completing this project. We are highly obliged to our project coordinator Mr.Siddhant Chatterjee, Head of the Engineering department, for having extended his affable guidance, constant supervision and encouragement throughout the progress of this project, which helped us to complete it within the stipulated time. We would like to express our sincere thanks to Mr.D.Kiran Kumar, Associate Manager, H.R., AVCTPL, for providing the necessary facilities for the successful completion of this work. Last but not least, we wish to thank our Instructor & Other Staffs, our parents and all our friends for their constant moral support, cooperation and encouragement during this period.
  • 4. CONTENTS ABSTRACT i LIST OF FIGURES & TABLES ii INTRODUCTION 1-2 CHAPTER 1: WORKING MODULES OF AVCTPL 1.1 Introduction 3 1.2 Intermediate transfer tower(ITT) 3 1.2.1 Definition 3 1.2.2 Types 4 1.2.2.0 ITT1 4 1.2.2.1 ITT2 1.2.2.2 ITT3 4 1.2.2.3 ITT4 4 1.2.2.4 ITT5 4 1.2.3 Use of automation 4 1.3 Intermediate Belt Conveyor 5 1.3.1 Definition 5 1.3.2 Types 5 1.3.2.0 IBC1 5 1.3.2.1 IBC2 5 1.3.2.2 IBC3 6 1.3.2.3 IBC3A 6 1.3.2.4 IBC4 6 1.3.3 Use of automation 6 1.4 Stacker and Reclaimer 7 1.4.1 Definition 7 1.4.2 Modes of operation 7 1.4.3 E-house and its function 7 1.4.4 Use of automation 9 1.5 SILO 9 1.5.1 Definition 9 1.5.2 Functional part of SILO 9 1.5.3 Technology of choice and automation 11 1.5.4 Wagon loading 13 1.6 Pump house 13 1.6.1 Need of pump house 13 1.6.2 Main component of pump house 13 CHAPTER 2: CONTROLROOM 2.1 Introduction 15 2.2 Layout view of AVCTPL 15 2.3 Layout view of DS System 16
  • 5. CHAPTER 3: AVCTPL SUBSTATION GRID 3.1 Main objective of Distribution system 17 3.2 Functional parts of substation grid 17 3.3 A Brief lay out of distribution of AVCTPL 22 3.4 New glance of technology in distribution 23 3.5 Case study analysis on distribution system 24 3.6 UPS System 25 3.7 DG Supply 26 3.8 Reactive power compensation 26 3.9 some industrial measurements 27 CHAPTER 4: SAFETY 4.1 Definition 28 4.2 Need of Safety for AVCTPL 28 4.3 Safety equipment and procedure 29 REFERENCE 30
  • 6. ABSTRACT In today's world of power shortages, increasing demand and the energy efficiency debate, how the electricity network is run right through from the power station to consumer end is becoming ever more important. A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A Distribution substation transfers power from the transmission system to the distribution system of an area. It is uneconomical to directly connect electricity consumers to the main transmission network, unless they use large amounts of power, so the distribution station reduces voltage to a level suitable for local distribution. The highest priority in a substation is to detect and isolate failures in the transmission system as hastily as possible. Upholding power quality is one of the main functions of a substation, and it affects operating conditions of the whole transmission and distribution networks. Power quality information is of strategic importance for electricity companies and essential for ensuring competitive operation. In this era, every industry frantically needs both the performance and efficiency simultaneously so as to maintain the performances and efficiencies of different electrical machine is the new challenges for the engineers. The main focus on this project is to scrutinizing the efficient performance of the industry by maintaining the power factor at the acceptable limit and providing healthy performance to the machine used in different modules. So it provides a good economic strength to the industry. The other objective of this project is to analyzing the new technology involved in each working module and the type of electrical equipment used in each module of AVCTPL distribution substation. A careful case study of the project can give an ephemeral idea about the distribution system and the new technology used over here with its future appliances. i
  • 7. LIST OF FIGURES Figure No. Description page no. Fig. 1 BLOCK DIAGRAM OF PLC CONTROL 12 Fig. 2 LAYOUT VIEW OF AVCTPL 15 Fig 3 LAYOUT VIEW OF DS SYSTEM 16 Fig: 4 AVCTPL PANEL 20 Fig. 5 LAYOUT OF DISTRIBUTION OF AVCTPL 22 Fig. 6 LAYOUT OF UPS SYSTEM 25 Fig. 7 DG AND MAIN SUPPLY CONNECTION 26 LIST OF TABLES Table No. Description pageno. Table 1.0 SPECIFICATION OF HT MOTOR 3 Table 1.1 SPECIFICATON OF DRY TANSFORMER[E-HOUSE] 8 Table 1.2 SPECIFICATION OF MOTOR 10 Table 1.3 SPECIFICATION OF MOTOR[PUMP HOUSE] 13 Table 1.4 PANEL POWER SUPPLY 21 Table 1.5 SPECIFICATION OF DRY TRANSFORMER[LIGHTING] 24 Table 1.6 SPECIFICATION OF APFC 27 ii
  • 8. INTRODUCTION The Adani Vizag Coal Terminal Private Ltd (AVCTPL), a subsidiary of APSEZ and also a part of Adani group which is global integrated infrastructure player with interests in resources, logistics, energy and agribusiness. It is an Indian multinational company founded by the former chairman Mr.Goutam Adani. AVCTPL had entered into a concession agreement with Visakhapatnam Port Trust to set up fully mechanized steam coal handling facility with a capacity of 6.4 million tonnes a year in March 2011 with completion deadline of August 2014. The facility is completed eight months ahead of schedule at a cost of Rs400 crore.AVCTPL, being a part of Visakhapatnam Port is strategic for coal imports to feed the local industries and power plants of the states of Andhra Pradesh, Odisha, Chhattisgarh and Maharashtra. AVCTPL occupies a large area of back up yard about 25 Acres. AVCTPL is basically import terminal type to handle the cargo (steam coal) and terminal capacity is 5.0 MMTPA. It is having a Berth of size 280 meters and width of 6.1 meters. It contains maximum vessel size of 80000 DWT. It has a Deck top level of 3.65 meter. Constructional AVCTPL is divided into three different working sites in such a way that failure of any one site can cause a huge amount of loss to the company. So AVCTPL has its own control room from where it invigilates any site easily at any time. AVCTPL has its own substation which is situated inside the operational building. The port site is present in the west side to the operational building. Two Mobile Harbor Crane (MHC) are employed there, which is operated by the operator master. These are mainly running for luffing purpose of cargo which is present inside the vessel. It can be also visualized directly through the control room. AVCTPL has its own storing site used for cargo (i.e. coal) storage purpose. These site mainly contains other working modules namely 2 Stackers, a Pump House and ITT towers. The intermediate transfer tower(ITT) mainly consists of HT Motors(High Tension Motor) and Chutes and all the ITT towers are interconnected by the IBC(intermediate belt conveyor).The Stackers are mainly running in two modes i.e. stacking mode and reclaiming mode depending on the operation to be operated. Pump house at AVCTPL has a reservoir at which it store water and by the help of pump, water is pumped up and supplied to the water sprinklers. Water sprinklers are mainly used for dust separation purpose. In general it is used environment safety 1
  • 9. by preventing the unnecessary air pollution due to blowing of coal dust. AVCTPL has a large cargo storing tank called SILO which is used for storing the cargo in large amount and used for wagon loading. There is an ITT Tower (i.e.ITT5) is present on the SILO. It also has so many parts which can be discussed later. AVCTPL has a substation which is equipped with all the advanced technology. The substation of AVCTPL mainly consists of FEEDERS, UPS ROOM, LIGHTING TRANSFORMER ROOM, INCOMERS, RELAY TRIPS and ALARMS. All the transformers, machines, HT Motor and diesel generators (DG) controls are integrated at the substation with all type of safety has been taking into account. RELAY TRIPS mainly gives protection to the electrically operated modules and DGs are used to give supply instantly for lighting purpose of the plant. DGs are running when there is a failure of main supply encountered. AVCTPL has a control room which is situated on the operational building. This control room is designed in such a way that the total control of the plant can be further possible from this Centre. Control room control equipment are fully based on automation and it is only possible through the application SCADA and PLC. The control room has two big size monitors which are connected with the close circuit cameras. So it may help to invigilate the problem encountered with the working modules easily in short period time. AVCTPL mainly focused on the safety of its labors as well as environments.so for safety of its labor it provides safety helmets, safety jacket, gloves and safety boots to all the labors those who are going to the working field and for environment safety it uses some equipment like DSS (DRY DUST SEPARATION), WATER SPRINKLER etc. 2
  • 10. CHAPTER 1: WORKING MODULES OF AVCTPL 1.1:INTRODUCTION AVCTPL has number of working modules like ITT, IBC, STACKER & RECLAIMER, SILO, PUMP HOUSE, SUBSTATION GRID etc. In this chapter we are predominantly emphasizing on the ITT (Intermediate Transfer Tower) and describing its function which designating the smooth operation of the plant. 1.2:INTERMEDIATETRANSFER TOWER (ITT) 1.2.1:DEFINITION Intermediate transfer tower is one of the foremost functional unit of AVCTPL. It can be demarcated as the tower which has a conveyor system which is again connected by a HT Motor for running the conveyor belt in a particular direction depending on the mode of operation. Further ITT TOWER also contains some mechanical systems like Pulley, scooping system, Drop down system, PCS (Pull cord system), Hooter etc. and some electrical systems like BSS (Belt side system) and metal detector (MD) and a HT Motor (3-ph induction motor). These are the main system which can be found in each and every ITT Towers of AVCTPL. SPECFICATION OF HT MOTOR: [TABLE-1.0] TYPE KW RPM EFFICIENCY VOLTAGE CURRENT DUTY POWER FACTOR 3-PH 720 1492 94.5 6.6kv 77.0Amp S1 0.87 IMS (Inline magnetic Separator) is electromagnetic type which is used for the separation of the ferrous metal. Apart from these equipment AVCTPL uses some PLC and SCADA integrated circuit for automation control at the ITT Towers. There is a CBS (Chute Block Switch) named switch present at all ITT Towers for the detection of any problem encountered in the chute where the cargo is stored. 3
  • 11. 1.2.2:TYPES In AVCTPL the ITT TOWER is broadly divided into 5 different Towers based upon their position and working principle. These are namely as ITT1, ITT2, ITT3, ITT4 and ITT5.The last tower i.e. ITT5 is present on the SILO. 1.2.2.0: ITT1 ITT1 is situated at the port side which provides the connecting medium between IBC1 and IBC2. Its main function is to collect the cargo from hopper through IBC1 and sends it to ITT2. 1.2.2.1: ITT2 ITT2 is having a trichute which has a distinctive of bidirectional flow of cargo with the help of a diverting gate. It mainly decides the flow direction of cargo to ITT3 or IIT4.So ITT2 is present between ITT3 and ITT4.There is an electromechanical actuator is present in this tower. 1.2.2.2: ITT3 ITT3 provides the connecting medium between IBC3 and IBC2.It is not having any diverting gate. It is unidirectional to ITT4.There is no additional electrical equipment is used over here. 1.2.2.3: ITT4 ITT4 receives cargo from ITT2 and ITT3 by means of a gate. The reclaiming process the major factor of ITT4 which cannot be ignored. The cargo is carried out by the reclaiming process is directly connected to the ITT5 present on the SILO. 1.2.2.4: ITT5 ITT5 is the last Tower of the AVCTPL ITT TOWERs which is present on the SILO. So Here the cargo are store in the SILO and finally used for Wagon loading. 1.2.3:USE OF AUTOMATION The use of automation increases safety, efficiency and performance of ITT. The use of PLC and SCADA gives a very good performance on automatic control of the motor as well as in the semiauto mode of operation. The program of plc is done by means of all the control condition of electrical motor before starting. So before writing the program an engineer should focus on 4
  • 12. all the braking and short circuit condition etc. All these mechanisms done so as to provide error free environment and this leads to good performance of ITT. Here we are using SIEMENS PLC device which are integrated with SCADA enable device present at the control room of AVCTPL which is again connected to the other modules where the control is required AVCTPL also provides its WORKERS and ENGINEERS a pulse maker walky-talky for direct contacts of workers with their respective engineers at the control room if any problem encounter at any time. 1.3:INTERMEDIATE BELT CONVEYOR (IBC) 1.3.1: DEFINATION IBC is the important constituent from all the working modules of AVCTPL through which cargo is transferred. So IBC is having the high tensile strength because it is carrying the cargo for the long distance. In AVCTPL working area 1.5km length conveyor belt is present. As the belt is carrying cargo so many protecting switch is present like BSS (Belt Side Switch), ZSS (Zero Speed switch), BRS (Belt Rip Switch) etc. The function of all these parts are described in the use of Automation part. Beside these protecting switch some other systems are connected with IBC such as MD(METAL DETECTOR) is used to separate the ferrous metal from cargo which is toned on the conveyor belt and a DROP DOWN SYSTEM is also used to prevent the initial displacement of the cargo loaded belt which is caused due to sudden power supply to IBC. One end of IBC is always connected to the motor and the other end is connected with the pulley. 1.3.2: TYPES 1.3.2.0: IBC1 IBC1 is related with the belt in which cargo is transferred from MHC (Mobile Harbor Crain) to ITT1. 1.3.2.1: IBC2 The function of IBC2 is to transfer the cargo from ITT1 to ITT2 and from ITT2 to ITT3.Here MD is present and it is used for the detection of the nonferrous metal. 5
  • 13. 1.3.2.2: IBC3 IBC3 is related to transfer of cargo from ITT3 to ITT4 and here two mode of operation is present i.e. stacking mode and reclaiming mode in the respective operation. 1.3.2.3: IBC3A IBC3A deals with the transfer of cargo from ITT2 to ITT4.Here also both stacking mode and reclaiming mode is present. 1.3.2.4: IBC4 The main goal of IBC4 is to transfer the cargo from ITT4 to ITT5.MD is present over here. 1.3.3: USE OF AUTOMATION The use of automation makes more efficient while IBC performing its operation. So in IBC, many protecting switch is present like BSS: It is an electrical device which internally connected with a sensor.It is used to prevent the Cargo carrying belt to be one sided. So here a switch is present which is connected to Belt support in order to sense the exact position of the belt. If belt is encountered any problem with the position then the sensor activated and the related IBC panel is stop working for the solution. ZSS: The function of ZSS is to protect the belt, if the belt is cut in the middle or longitudinally. As the motor is connected through IBC externally, during the cutting of belt in the middle, motor will not stop but pulley will be stopped. A pulse formation mechanism is connected to the pulley. If the pulley is stopped working then pulse formation will also stopped. So we can easily determine by looking the pulse formation. BRS: If the belt is cut vertically then neither motor nor pulley will stop.So in this condition we are having a sensor i.e. transmitter and receiver and it is connected below the belt Conveyor. Transmitter transmits the IR waves and receiver receives. If the belt is cut in the middle then cargo will be wasted at the middle and disturbs the IR wave. After that the sensor will activate and will stop the working of the HT Motor. 6
  • 14. All the protecting switches are programed before the starting of motor accordingly. Apart from these automation there is a manual switch present across the sides of the conveyor known as PCS. This switch is connected through a rope so that any worker can pull the rope from any position so as to stop the running conveyor and find the problem related to the belt then the motor is disconnected from the gearbox. 1.4: STACKER AND RECLAIMER 1.4.1: DEFINATION AVCTPL is having two Stacker and Reclaimer i.e. one is on the running mode and the other one is on the standby mode (namely STACKER1 and STACKER2) .The function of the stacker is to stack or creating the heap of cargo. The function of Reclaimer is to take the cargo from the heap to the SILO. It is shortly designed as SCR (Stacker cum Reclaimer).SCR is having so many functional units like E-house, conveyor and bucket etc. 1.4.2: MODES OF OPERATION SCR is having two modes of operation like (i) STACKING (ii) RECLAIMING In stacking mode, cargo is collected from ITT2 and ITT3 and it is used for creating the heap of 12meter. There is two stack pile is present in AVCTPL campus where heap of cargo is made. In reclaiming mode, the cargo is collected from the heap and allow for transferring the cargo to the ITT4, then ITT5 and finally SILO respectively through the conveyor belt. 1.4.3: E-HOUSE AND ITS FUNCTION The function of E-house is to provide the power supply to the working module present on the SCR. As two SCRs are present so two E-house are available for SR1 and SR2. SCR takes 6.6KV from the substation grid and step down to 0.433 KV/433V by means of DRY TRANSFORMER. 7
  • 15. SPECIFICATION OF DRY TRANSFORMER [E-HOUSE]: The E-house acts as a small substation and used to provide the supply to different working modules. It consists of PLC panel, AOP, MLDB (Main line Distribution Board). [TABLE 1.1] TYPE 3 FREQUENCY 50 HZ AMB. Temperature 45 C IMPEDANCERISE 5.14% CORE ANDWINDING 3420 INSULATION CLASS F NO LOAD VOLTAGE HV 6.6 KV LV O.433 KV CURRENT HV 109.35 AMP LV 1666.72 AMP CONNECTION TYPE - 8
  • 16. 1.4.4: USE OF AUTOMATION The PLC used over here is basically SIEMENS. All the control logic deals with the sensors and performed by means of RELAY which makes the system to be understand easily by every Engineers. 1.5: SILO 1.5.1: DEFINATION It is the most important constituent among all the working module of AVCTPL. The function of SILO can be defined as to collect the cargo from ITT5 and stored at a large amount approximately 3600 tonnes per hour and released it during wagon loading. 1.5.2: FUNCTIONAL PART OF SILO The functional part of SILO is the tank where the cargo is stored and the control mechanism related to the wagon loading. SILO has so many working modules like POWER STACK, ACCUMULATOR and CONTROL ROOM for wagon loading etc. In SILO, so many systems are present like, HYDRAULIC SYSTEM, AIR BLASTING SYSTEM, DFDS(Dry Fog Separation System).SILO is operated at operating pressure of 18000 psi(1psi=0.06895 Bar=0.06895*10^5 Pascal). DFDS is the mixture of water and dust used to settled down the dry dust. This function is similar to DSS. In SILO, POWER STACK is present which consists of (i) MOTOR (ii) PUMP (iii) ACCUMULATOR Motor and Pump are mechanically coupled. The motor having following specification which is on the next page. 9
  • 17. SPECIFICATION OF MOTOR: [TABLE 1.2] TYPE 3-PH IM % EFFICIENCY 93.5% AMB.TEMPERATURE 50 C FRAME 250m DUTY S1 IP 55 FREQUENCY 50hz VOLT 415v KW 55 AMP 97 RPM 1482 POWER FACTOR 0.86 Pump is having a big inlet diameter and a small outlet diameter and one end of the pump (outlet) is connected by means of a FILTER to filter out any raw particle. The inlet of the pump is hydraulic oil filter is having filtered unit of 10 microns. It is having 300hours maintenance period. In the power stack we are having the cooling systemby means of recirculation pump and Heat exchanger by means of fan. Cooling pressure can be measured by cooling system pressure, stand by pressure and pump pressure. Here the circulation type is 1-phase. Air Blasting System is present to blast the compressed the compressed nitrogen cylinder if the cargo remains in the heavy solid form in case of gate removal. So by doing this we are breaking the heavy solid cargo to small pieces. At the top of the tank 4 Gates and 8 Cylinders and at the bottom of the tank 2 Gates and 4 cylinders are present. The blasting of the cylinders is done by means of the solenoid coils and it is operated by 24vDC supply. The operation of the Gate opening and closing is done by means of hydraulic system during wagon loading. 10
  • 18. Why Hydraulic system is preferable then the Electrical system during opening and closing of gate during wagon loading? We can’t use electrical system during the opening and closing of Gate during wagon loading because electrical systems are used on those systems where are needing sudden changes in the operation but here we need a smooth operation. Another reason is this operation is done by means of pressure, as hydraulic system is responsible for creating the pressure but electrical system is not able to create any pressure. .Apart from the step down transformer is also there for stepping down to low voltage and rectifier arrangement is also there for conversion from ac to dc (24dc). 1.5.3: CHOICE OF NEW TECHNOLOGY AND USE OF AUTOMATION SILO is having some new technology like use of sensor and automation in its working unit. In the pump inlet we are having FILTER CLOG SENSOR to sense the filtered particle. We are having proximity sensor like contact type and non-contact type. In contact type manually we have to do and in non-contact type, below 5mm sensor will sense. Three types of proximity sensor are available i.e. (i) fully close (ii) Mid way (iii) Fully open If we consider a new technology, in power stack breather is present to remove the vapor from the hydraulic oil. 3 modes of operation are dealing with the SILO i.e. auto, semiauto, manual mode. For automatic mode of operation, we are having the PLC OF MARIT which is connected through every sensor unit and performed operation by Relay [P.T.O] 11 00 00 0
  • 19. BLOCK DIAGRAM OF PLC CONTROL :( MERIT) [FIGURE- 1] Here the term secondary is referred as the stand by, RB refers to the relay Board. MCB refers as Miniature circuit Breaker. RS 232 is used for communication of data but here technically it is called as command CPU is involved for execution of all the command. So many command is given by control room of SILO i.e. Gate command open/close, Motor command, solenoid command for blasting etc. PRIMARY CPU CPU SECONDARY CPU PRIMARY I/O SECONDARY I/O RB1 RB2 RB3 RB4 RB5 RB6 RB7 MCB1 MCB2 MCB3 MCB4 MCB5 MCB6 MCB7 MCB8 MCB16MCB15MCB14MCB13MCB12MCB11MCB10MCB9 POWER SOCKET MCB17 RS232 RS 232 LAN CONVERTER 24 DC 12 00 00 0
  • 20. 1.5.4:WAGON LOADING It is the final touch of the entire processing system of AVCTPL. Here the wagon is present on the track and the open/close command is given from the control room. According to the command, cargo is put into the respective wagon and wagon loading takes place. There are two sensors relates with the wagon loading i.e. BOXN and BOXNHS. BOXN sensor is present at the height of 1 meter from the ground level. BOXNHS SENSOR is present at the height of 1.2 meter from the ground level which gives the position of wagon. 1.6:PUMP HOUSE 1.6.1:NEED OF PUMP HOUSE Pump house is the very important working module not only for AVCTPL but also for environmental point of view. As AVCTPL is basically a coal port industry so there is occurrence of dust during stacking, reclaiming and wagon loading etc. But the thing is that we can’t compromise for the environmental safety. So any how we have to settle down the dust by using DSS and water sprinkler etc. VPT has made a conditional attachment with AVCTPL that heap should not exceed more then 12meter. The strong wind flow also makes the dust in heavy amount. So the need of pump house becomes more essential for AVCTPL. 1.6.2:MAIN COMPONENTOF PUMP HOUSE The main component of pump house is water sprinkler and pump. The pump used over here is basically (i) CENTRIFUGAL PUMP and (ii) INLINE PUMP. Water is collected from the large reservoir by means of pump and is supplied to sprinkler. The motor in which pump is mechanically coupled is normally 3-ph Induction motor. SPECIFICATION OF MOTOR [PUMP HOUSE] [TABLE-1.3] TYPE 3-Ph FRAME 160 meter VOLTAGE 415V CURRENT 21.0 AMP FEQUENCY 50 Hz EFFICIENCY 88.4% CONNECTION TYPE RPM 1450 INSULATION TYPE F 13 00 00 0
  • 21. Pump is having capacity 360HP, pressure 0.5kg/m^2 and speed1170rpm Here also we are having auto, semiauto and manual mode operation. So we can control the operation of the sprinkler directly from the control room or we can do manually that depends on the choice of the operation. The details layout of the DS SYSTEM is explained in CHAPTER 2. 14 00 00 0
  • 22. CHAPTER 2: CONTROL ROOM 2.1:INTRODUCTION AVCTPL is having a control room in which all the command for every operation, certain instruction and automatic mode of operation is possible. The thing is that here we are having a complete visualization of each and every working site. Here every time engineer scrutinizing the operation of entire working module and giving the required instruction and command. The presence of control room giving very efficient operation of AVCTPL. More over here we can see the wagon loading activity. 2.2:LAYOUT VIEW OF AVCTPL In control room we can see the entire layout of the AVCTPL. So each and every site of working module can be seen with respect to its function in the control room. [FIGURE-2] As we have discussed the entire working modules which are present on the layout in the previous chapter. Here we only focus on the short notation of the variables like, 1. Z- ZSS 2. B- BSS 3.P- PCS 4. MD- METAL DETECTOR 15
  • 23. 2.3:LAYOUT VIEW OF DS SYSTEM As we have discussed the presence of DS system is very much essential for the environmental safety point of view. Here we careful focus on the layout. [ FIGURE-3] In this layout we are having total 55 water sprinkler which are operated by means of side wise like, in STOCK PILE 1 first sprinkler no.1 and sprinkler no.2 will turn on then 2 and 22 respectively. All the sprinklers are operated on the same sequence. 16 00 00
  • 24. CHAPTER 3: AVCTPL SUBSTATION GRID 3.1:MAIN OBJECTIVE OF THE DISTRIBUTION SYSTEM The main planning approach for electrical distribution system to optimize the number of feeders and their roots. It is very much essential for the electrical substation is to maximize the network reliability and minimize the total installation and operational cost. So from generation of electricity to utilization distribution system plays an intermediary operation. So without distribution system the consumers can’t get the electricity from the generation station. Here also AVCTPL is having own substation grid and with a distribution system to each working modules which readily depends on the electricity. 3.2:FUNCTIONALPART OF SUBSTATION GRID The main functional unit of SUBSTATION GRID are (i) Transformer (ii) CT & PT (iii) ACB & VCB (iv) Feeder and distribution panel (v) Reactive power compensation (vi) UPS (vii) DG Supply 1. TRANSFORMER We can say that transformer is the main constituent of the entire sub-station because step up and step down of the voltage can be done by means of transformer. AVCTPL substation Grid receives the 33KV supply from the APEPDCL. This high voltage is stepping down to 6.6 KV and this 6.6 KV is again stepping down to 433 KV. We are using both 6.6 KV for the working of all HT MOTOR and 433KV for the DISTRIBUTION and LIGHTING purpose. 17 00 00 0
  • 25. There are total 4 step down transformer and 1 one to one transformer is there. Out of 4 transformer two transformers are used for 33KV/ 6.6KV and two transformer are used for 6.6KV/433V. The thing is that one is always running and other one is always on the stand by position. Apart from that a single one to one transformer is there used for the lightening purpose, so sudden change in the fluctuation of the voltage can be filtered out. This transformer is dry type transformer. There are two methods are used for transformer tap changing i.e. 1. On load tap changer 2. Off load tap changer During the on load tap changer method the transformer is connected through the load and charged condition and during the off load tap changer method, we have to off the transformer first and change the tap. The changing of tap is required because we can’t get the constant input voltage for the transformer so there is a problem of getting the desired output. 33KV/6.6KV transformer is called as on load tap changer and 6.6KV/0.433KV transformer is called as off load tap changer. 2. CT & PT CT- current Transformer PT- Potential Transformer CT is used for current measurement and PT is used for potential measurement. There are two types of PT used namely LINE PT and BUS PT. 3. ACB & VCB ACB- Air Circuit Breaker VCB- Vaccum Circuit Breaker 18 00 00 0
  • 26. 3. FEEDERAND DISTRIBUTION PANEL We are having two FEEDERS like FEEER1 and FEEDER2 and its main function is to feed the power from VCB (Vaccum Circuit Breaker) to TRANSFORMER for step down of high.voltage. There are two INCOMER are present like INCOMER1 and INCOMER2 which are used for giving the power to all HT MOTOR. Two INCOMERS are connected by means of BUSCOUPLER. BUS PT is used over here to give the information about the INCOMER that which one is running and finally 6.6KV is coming from the INCOMER is stepping down to 0.433KV and used for the distribution [P.T.O] 19 00 00 0
  • 27. AVCTPL is having a panel like [FIGURE-4] PANEL TYPE 1 (MAIN) PANEL TYPE 2(DISTRIBUTION) MVAPFC1 SPARE PH CSS1 SPARE SR1 SPARE MHC1 SPARE IBC1 IBC2 IBC3 SPARE DIST TRAFO1 SPARE BUS APT INCOMER1 BUS COUPLER BUS PT WITH INCOMER2 DISTTRAFO2 SPARE IBC3A IBC4-M1 IBC4-M-2 BUS RISER SPARE MHC2 SPARE SR2 SPARE SILO CSS2 MV APFC SPARE2 PANEL TYPE 3 MLDB- MAIN LINE DISTRIBUTION BOARD PH- PUMP HOUSE PCC- POWER CONTROL CIRCUIT MCC- MOTOR CONTROL CIRCUIT 1 2 3 4 5 6 7 8 161514131211109 2423222120191817 28272625 29 30 31 32 BETTERY CHARGER1 INCOMER3 10KW IN MLDB DG INCOMER BUS COUPLER2 MCC2 PCC INCOMER 2 BUS COUPLER1 PCC INCOMER2 1 FEEDER1 2 INCOMER 3 FEEDER2 20 00 00
  • 28. AMFC- AUTO MAIN FAILURE CONTROLLER: [AMFC provide consistent power supply to the load in the absence of main supply.] The function of AMFC is to maintain the constant power supply to the load in the absence of the main supply. It is having DG set of protection. This panel supplies the power that can be shown below: [TABLE-1.4] PANEL NO. NAME OF THE PANEL POWER 3 PH CSS1 500 KVA 5 SR1 1250 KVA 7 MHC1 1350 KW 9 IBC-1 220 KW 10 IBC-2 450 KW 11 IBC-3 720 KW 12 DIST TRAFO 1.5 MVA 22 IBC 3A 720 KW 23 IBC-4-M-A 450 KW 28 SR2 1250 MVA 31 MV APFC2 1400 KVAR The function of APFC (Automatic power factor control) is to control the power factor that can be discussed in the reactive power compensation part. MCC panel supplies the power to all HT MOTOR present at the ITT. This panel is having THRUSTER BRAKE for all the IBC and all the induction related to the ITT can be seen like, oil circulation trip, radiator pump trip, radiator pump on, radiator pump off, actuator on and actuator off etc. 21 00 00 0
  • 29. 3.3:A BRIEF LAY OUT OF DISTRIBUTION OF AVCTPL [FIGURE-5] LA- lightening arrest NGR- Natural Ground Register ACB- Air Circuit Breaker VCB-Vaccum Circuit Breaker 22 00 00 0
  • 30. 3.4:THE NEW GLANCE OF TECHNOLOGY AVCTPL substation grid is having various new technology like TRAFO FAULT RELAY, MASTER TRIP RELAY, ANNOUCIATOR, MULTIFUNCTIONAL METER, O/C & E/F RELAY and PROTECTIVE RELAY etc. TRAFO FAULT RELAY: The use of TRAFO FAULT RELAY is to protect the transformer from overcurrent. It is of IDMT (Inverse Definite Time Relay Type). MASTER TRIP RELAY: MASTER TRIP RELAY is the main trip relay to which all the protection relays like distance relays, overcurrent relays, earth fault relays and differential relays are connected in parallel. That means master trip relays are providing the type of fault caused in the electrical drives to the user in the display board continuously unless until it is respond by someone. ANNOUCIATOR: An ANNOUCIATOR panel is a centralized warning panel where a group of light used to display the message related to the central industrial purpose. It is very costly to install and it is dedicated to the wiring to the alarm initiating device to the process plant. O/C & E/F RELAY: This relay is used in the transformer winding in terms of CT and PT. Suppose three phase is there having rated current 100A in each phase. If the current flow in one phase is above the 100A then this will go to OVER CURRENT RELAY (O/C) but if the current flow in any one phase is below the rated current i.e. 10-20 AMP then this will go for EARTH FAULT RELAY (E/F). Apart from these there is a presence of MULTIFUNCTIONAL METER in which we can able to see all the current rating like voltage, current, frequency, power factor, kw, KVAR, KVA and %THD(TOTAL HARMONIC DISTRIBUTION) etc. LA (lightening Arrester) is present to protect the cable from high flash over voltage. The rated lightening impulse withstand voltage of each feeder is 170 KV. 23 00 00 0
  • 31. SPECIFICATION OF DRY TRANSFORMER (LIGHTING) In the entire substation the automatic modes of operation is also available by means of PLC and SCADA. We are having the PLC of SIEMENS in all the panel. But practically semi auto mode is used over here. 3.5:CASE STUDY ON THE DISTRIBUTION SYSTEM: We have studied all the working unit of substation and we have seen each and every working performance of each unit. But my point view if there is a presence of SF-6 Circuit Breaker [TABLE-1.5] TYPE 3 FREQUENCY 50 HZ AMB. Temperature 45 C VECTORGROUP Dy11 CORE ANDWINDING 3420 INSULATION CLASS F NO LOAD VOLTAGE PRIMARY 0.415KV SECONDARY 0.415KV CURRENT PRIM 486.92 AMP SEC 486.92 AMP POWER 350 KVA 24 00 00 0
  • 32. instead of ACB and VCB then then the performance may be improved. Otherwise each working module present over here is having very good eye-catching performance. 3.6:UPS SYSTEM The meaning of UPS is uninterrupted power supply. The meaning itself defines its functionalities that the power supply should be continuous. UPS system consists of RECTIFIER, INVERTER, SMPS (Switch Mode Power Supply) and BATTERY. Here ac supply is converted to dc by means of rectifier and stored in battery and in the absence of main supply that stored dc is again converted to ac by means of inverter. LAYOUT OF UPS SYSTEM: [FIGURE-6]: MANUAL BYPASS BYPASS ISOLATOR AC SUPPLY O/P SWITCH MODE INVERTER POWER POWER SUPPLY(SMPS) STSW BATTERY ISOLATOR BATTERY CHARGER BATTERY CHARGER is used to store the DC supply which is converted from AC in terms of RECTIFIER. RECTIFIER INVERTER 25 00 00 0
  • 33. 3.7:DG SUPPLY The function of DG supply is for back up purpose. The DG means DIESEL GENERATOR which is connected by the BUS COUPLER in between two incomer. The performance of AMFC is related to the DG SUPPLY. If the main supply is not present then the DG supply is provided only for the lighting purpose. The DG is connected to the main supply as shown below. LOAD DG SUPPLY KG KM T/F AMF UNIT [FIGURE-7] 3.8:REACTIVE POWER COMPENSATION As all the load used over here is normally inductive load so the lagging power is more .So we have compensate those lagging power. As Substation draws the heavy amount of power from the APEPDCL grid so any how substation is to maintain the constant power factor otherwise current consumption increases. In order to balance both the operation substation is provided with CAPACITOR BANK in which reactive power is compensated and a constant power factor is maintained. In substation we are having the CAPACITOR BANK of rating 1800.55 KVAR. Actually the entire performance of the capacitor bank is known as APFC (Automatic Power factor Control). 26 00 00 0
  • 34. The technical function of APFC is to maintain the constant power factor at a suitable limit. The capacitor bank is connected across the 3-Ph bus line by means of relay. SPECIFICATION OF APFC (AUTOMATIC POWER FACTOR CONTROL): NET O/P KVAR 1800.55 KVAR.7.72 KV RATED KVAR 1400 KVAR,6.6 KV STEP CONFIGURATION 2*250KVAR + 2*450 KVAR RATED CURRENT 122.47AMP NO OF PHASE 3-Ph RATED FREQUENCY 50 Hz TEMP RISE 15 C CONNECTION EXTERNAL [TABLE-1.6] 3.9:SOME INDUSTRIAL MEASUREMENT In AVCTPL we are having so many industrial measurement like MULTIMETRE, MEGGER, CT & PT and TONG TESTER (CLAMP METER) etc. In MULTIMETER we can measure the voltage, current, resistance etc. But now a days we are using the TONG TESTER (CLAMP METER) in which we can measure the voltage (ac/dc), resistance. MEGGER is used for testing the HT motor before running means whether the motor is free from short circuit or not and by using this we can measure the high resistance. If the MEGGER reading is ‘0’ then the motor is unhealthy and if the motor reading is ‘infinite’ then motor is healthy. 27 00 00 0
  • 35. CHAPTER 4: SAFETY 4.1:DEFINITION SAFETY is the state of being “SAFE”, the condition of being protected against physical, social, financial, consequences of failure, damage, error, accidents, harm or any other events which could be considered undesirable. Safety can also be defined to be the control of recognized hazards to achieve an acceptable level of risk. This can take the form of being protected from the event or being protected from the event or from exposure to something that causes health or economical losses. It can include protection of people or of possessions. SAFETY is the foremost thing which is engrossed formerly by any hazardous industries like coal industry. 4.2: NEED OF SAFETYFOR AVCTPL In view of the above discussion AVCTPL is therefore need of the hour. There are some direct costs/effects of an accident but there are certain indirect costs involved in it also e.g. machine down time, damage of machine, ideal time of nearby equipment and horror created among workers, loss of time etc. in aid cost compensation, legal implications and allied costs etc. So safety measures would not only eliminates/avoid above cost but would mean performing their moral responsibility towards workmen/ operators also. More over AVCTPL is a coal industry so more focus on safety is required towards the health of the workers and towards the environment for the smooth running of the industry. An unsafe condition may be present in various forms i.e. in the faulty or defective electrical fittings, use of defective tools, blowing of coal dust on the air etc. so to prevent the occurrence of oath of accidents, unsafe acts have to be avoided or checked properly for the safety purpose at AVCTPL. 28 00 00 0
  • 36. 4.3:SAFETY EQUIPMENTSAND PROCEDURE SAFETY INSTRUCTION AVCTPL provides so many safety instruction like: 1. Use Helmet, Safety reflection jacket and Gloves while entering to the any working site. 2. Don’t touch any machineries without having the proper knowledge and don’t go alone to any working site. 3. Read the instruction of any machine carefully while enter and touch the machine and can take the reading. 4. See the Guard ring and don’t cross the guard ring during running condition. (If the guard ring is not visible by you then tell your instructor to make you confirm about guard ring) 5. Don’t move under the conveyor belt during running. 6. Leave the working site if you hear any alarm sound. 7. Don’t go to heap site during the strong wind flow. 8. Carefully read the instruction guide given below the working module in order to run that working module. SAFETY equipment provided by the AVCTPL are HELMET, SAFETY REFLECTION JACKET and GLOVES. For the Environmental Safety concern AVCTPL provides water sprinkler, DSS and DFDS in the dust producing site. Horticulture is also done in its campus to produce a pollution free environment. 29 00 00 0
  • 37. REFERENCE 1. ELECTRIC MOTOR HAND BOOK, by James L. Kirtley, Jr., H.Wayane Beaty, Nirmal K Ghai, Steven B Leeb, Richard H.Lyon. 2. INDUSTRIAL POWER ENGINEERING AND APPLICATION, by K C Agarwaal. 3. ELECTRICAL GENERATION AND DISTRIBUTION SYSTEMS AND POWER QUALITY, by Rey G.R. 4. POWER SYSTEM-ANALYSIS AND DESIGN, by B.R. Gupta. 30 00 00